You are on page 1of 1

Article 310 ● Conductors for General Wiring 310.

10

(G) Corrosive Conditions. Conductors exposed to oils, to indicating instruments, contactors, relays, solenoids, and
greases, vapors, gases, fumes, liquids, or other substances hav- similar control devices, or for frequencies of 360 Hz and higher,
ing a deleterious effect on the conductor or insulation shall be provided all of the following apply:
of a type suitable for the application. (a) They are contained within the same raceway or cable.
Nylon-jacketed conductors, such as Type THWN, are suitable for use (b) The ampacity of each individual conductor is sufficient
where exposed to gasoline. The UL Guide Information for Electrical to carry the entire load current shared by the parallel
Equipment — The White Book states in the category for Thermoplastic- conductors.
Insulated Wire (ZLGR) in part: (c) The overcurrent protection is such that the ampacity of
THWN — wire that is suitable for exposure to mineral oil, and to liq- each individual conductor will not be exceeded if one or
uid gasoline and gasoline vapors at ordinary ambient temperature, is more of the parallel conductors become inadvertently
marked “Gasoline and Oil Resistant I” if suitable for exposure to min- disconnected.
eral oil at 60°C, or “Gasoline and Oil Resistant II” if the compound is In control wiring and circuits that operate at frequencies greater than
suitable for exposure to mineral oil at 75°C. Gasoline-resistant wire 360 Hz, a reduction of cable capacitance or voltage drop in long lengths
has been tested at 23°C when immersed in gasoline and is consid- of wire may be necessary. A 14 AWG conductor might have more than
ered inherently resistant to gasoline vapors within the limits of the sufficient capacity to carry the load, but by installing two conductors in
temperature rating of the wire type. parallel, the voltage drop can be reduced to acceptable limits. The pres-
Before using a wire-pulling compound, it should first be investi- ence of the word polarity in 310.10(H)(1) specifically allows the inclusion
gated to determine compliance with 310.10(G). of dc circuits.
(H) Conductors in Parallel. Exception No. 2: Under engineering supervision, 2 AWG and
(1) General. Aluminum, copper-clad aluminum, or copper con- 1 AWG grounded neutral conductors shall be permitted to be
ductors, for each phase, polarity, neutral, or grounded circuit shall installed in parallel for existing installations.
be permitted to be connected in parallel (electrically joined at Informational Note to Exception No. 2: Exception No. 2 can be
both ends) only in sizes 1/0 AWG and larger where installed in used to alleviate overheating of neutral conductors in existing
accordance with 310.10(H)(2) through (H)(6). installations due to high content of triplen harmonic currents.
Conductors connected in parallel are treated by the NEC® as a single The word triplen refers to a third-order harmonic current, such as the third,
conductor with a total cross-sectional area of all conductors in parallel. sixth, ninth, and so on. The concern is limited to odd-number triplen har-
The use of parallel conductors is a practical and cost-effective means of monic currents, such as the third, ninth, and fifteenth, since these are
installing large-capacity feeders or services. Using conductors larger additive currents in the neutral conductor and they do not cancel.
than 1000 kcmil in raceways is neither economical nor practical unless
E7D60B35 B2F4 4C42
the conductor size is governed by vo tage drop. The ampacity of larger
sizes of conductors would increase very little in proportion to the
F
See also
Chapter 10 of NFPA 70B, Recommended Practice for Electrical Equip-
increase in the size of the conductor. Where the cross-sectional area of a ment Maintenance, for additional information on power quality and
harmonics
conductor increases 50 percent (e.g., from 1000 to 1500 kcmil), a Type
THW conductor ampacity increases only 80 amperes (less than 15 per- (2) Conductor and Installation Characteristics. The paral-
cent). A 100-percent increase (from 1000 to 2000 kcmil) causes an leled conductors in each phase, polarity, neutral, grounded circuit
increase of only 120 amperes (approximately 22 percent). Generally, conductor, equipment grounding conductor, or equipment bond-
where cost is a factor, installation of two (or more) paralleled conductors ing jumper shall comply with all of the following:
per phase may be beneficial.
The parallel connection of two or more conductors in place of (1) Be the same length.
using one large conductor depends on compliance with 310.10(H)(2) to (2) Consist of the same conductor material.
ensure equal current division in order to prevent overloading any of the (3) Be the same size in circular mil area.
individual paralleled conductors. (4) Have the same insulation type.
Where individual conductors are tapped from conductors in paral- (5) Be terminated in the same manner.
lel, the tap connection must include all the conductors in parallel for that
In order to avoid excessive voltage drop and also to ensure equal divi-
particular phase. Tapping into only one of the parallel conductors would
sion of current, different phase conductors must be located close
result in unbalanced distribution of tap load current between parallel
together. Each phase conductor, grounded conductor, and the ground-
conductors, resulting in one of the conductors carrying more than its
ing conductor (if used) must also be grouped together in each raceway
share of the load, which could cause overheating and conductor insula-
or cable. However, isolated phase installations are permitted under-
tion failure. For example, if a 250-kcmil conductor is tapped from a set of
ground where the phase conductors are run in nonmetallic raceways
two 500-kcmil conductors in parallel, the splicing device must include
that are in close proximity.
both 500-kcmil conductors and the single 250-kcmil tap conductor.
All conductors of the same phase or neutral are required by
Exception No. 1: Conductors in sizes smaller than 1/0 AWG 310.10(H)(2) to be of the same conductor material. For example, if
shall be permitted to be run in parallel to supply control power 12 conductors are paralleled for a 3-phase, 4-wire, 480Y/277volt ac

National Electrical Code Handbook   2017 255

You might also like