You are on page 1of 2

1 2 3 4 5 6

44.5(1 3/4")
23 40 40 1 Cable inlet see fig.
4 60 100 R50 1

22.5
44.5
D=14(13x) 2 Terminal of aluminium.

44.5 28
2

60
40
3 Terminal of aluminium.

292
40

40
4 Holes for earthing clamp

28
D=14(7x)

33.5
5 Centre of gravity
A A
6 Hole for bolt M24

7 Break chamber insulator


Polymeric insulator
4174
8 Post insulator
1750 1750 255 2 3 Polymeric insulator
510
267
9 Open/closed indicator.
7
10 Density switch
5

20
8 11 Cubicle

1157

1324
4
B 2 B

20
184
13 Locking mechansim (inside cubicle)
15 4
14 Padlock device

850
690
R9
185

39
9 15 Earthing switch NVA

4654
10 16 Operating Mechanism SM800

3287
9
9

2497
2205
2065

C 16 C
1046

4 D=14(5x)
60

40

44
1 11

28
300
890
127
4

182
158
866

10

25
6

10
2530
420 1
320 1

D CO2 DISCONNECTING CIRCUIT BREAKER LTA 72.5D1 D


WITH OPERATING MECHANISM TYPE MSD1
Comments Order Scale Units Format

mm A3
Prepared Based on

2016-10-03 A Parling
Reviewed Responsible department Language

2016-10-03 A Parling PGHV/SE/TC/LTB SF6 CIRCUIT BREAKER en


320 1 Approved Document kind Page
6 2016-10-03 A Claesson Customer drawing LTA 72.5D1 1 of 2
420 1 We reserve all rights in this document and in the information contained
therein.It is Document id. Revision
provided for information only and ABB assumes no liability whatsoever.
Reproduction,
use or disclosure to third parties without express authority is forbidden.
strictly
NOTE! ABB AB is working continuously to improve the products. We therefore
reserve

ABB AB
the right to change designs, dimensions
and data without prior notice. Copyright 2016 ABB 1HSBDG00005-124 A
1 2 3 4 5 6
1 2 3 4 5 6

Mass in kg Loads on foundation and foundation bolts


Breaker Frame/polebeam Operating mechanism Total mass (gas excluded)
Foundation Foundation bolt

3x114 160x2++59 230 +194 1146 Load definition Horizontal forces Bending moments Vertical force Vertical force

Fx [kN] Fy [kN] Mx [kNm] My [kNm] Fz [kN] Fbz [kN]

Weight --- --- --- --- 5,6 1,4


Static terminal load 1,1 0,8 3,5 5,5 1,1 7,2
A A
Short circuit 31,5 kA --- 0,6 0,4 --- --- 0,6
Wind 34 m/s 1,7 1,5 3,6 4,3 --- 5,4
Upwards --- --- 12,1 3,9
Operation --- ---
Downwards --- --- 8,3 4,4

B B

X
C C
X
Y
Y
Z
Z

CO2 DISCONNECTING CIRCUIT BREAKER LTA 72.5D1


D D
WITH OPERATING MECHANISM TYPE MSD1
Comments Order Scale Units Format

mm A3
Prepared Based on

2016-10-03 A Parling
Reviewed Responsible department Language

2016-10-03 A Parling PGHV/SE/TC/LTB SF6 CIRCUIT BREAKER en


Approved Document kind Page

2016-10-03 A Claesson Customer drawing LTA 72.5D1 2 of 2


We reserve all rights in this document and in the information contained
therein.It is Document id. Revision
provided for information only and ABB assumes no liability whatsoever.
Reproduction,
use or disclosure to third parties without express authority is forbidden.
strictly
NOTE! ABB AB is working continuously to improve the products. We therefore
reserve

ABB AB
the right to change designs, dimensions
and data without prior notice. Copyright 2016 ABB 1HSBDG00005-124 A
1 2 3 4 5 6