ANSI/IEC61850 Code of Generator Protection

S.no Name of Protection ANSI CODE IEC 61850


Code
1 Definite-Time Overcorrect Protection I>, 50 PH4PIOC
2 Thermal Overload Protection 49 TRPTTR
3 Unbalanced Load (Negative Sequence) 46 NS2PTOC
Protection
4 Differential Protection 87G GENPDIF
5 Under excitation (Loss-of-Field) Protection 40 LEXPDIS
6 Reverse Power Protection 32R/32 GOPPDOP
7 Low Forward Active Power 32F/37 GUPPDUP
8 Impedance Protection 21 ZMHPDIS /ZDMRDIR
9 Out-of-Step Protection 78 OOSPPAM
10 Under voltage Protection 27 UV2PTOV
11 Overvoltage Protection 59 OV2PTOV
12 Frequency Protection 81 SAPTOF/ SAPTUF
13 Over excitation (Volt/Hertz) Protection 24 OEXPVPH
14 95-%-Stator Earth Fault Protection 59N, 64G, STEFPHIZ
67G
15 100-%-Stator Earth Fault Protection with 64G STEFPHIZ
20 Hz Voltage Injection
16 Sensitive Rotor Earth Fault Protection with 64R ROTIPHIZ
1 to 3 Hz Square Wave Voltage Injection
17 Inadvertent Energization or Dead machine 50/27 AEGPVOC
protection
18 Inter turn Fault Protection 59 ROVPTOV

64- Current based Ground Protective Relay


59-Under voltage based Ground Protective Relay
67-Directional based Ground Protective Relay

ANSI/IEC61850 Code of Protection


S.no Name of Protection ANSI CODE IEC 61850 Remarks
Code

1 Instantaneous & Definite-Time Over 50 PHPIOC I


Current Protection
2  Inverse time over current Protection 51 OCPTOC Ip
3 Definite-Time Earth fault Current 50N EFPIOC IE
Protection
4 Inverse time current Earth fault 51N EFPTOC IEp
Protection
5 Stand by E/F Protection 50N/51N EFPIOC/
EFPTOC
6 Inverse time Residual current Earth fault 51 EFLPTOC I0=calculate
Protection
7 Transformer REF Protection 64R,50Ns HZPDIF
8 Local Breaker Backup 50Z
9 Over Flux Protection 99 OEXPVPH
10 Differential Protection 87T T3WPDIF
11
12
13