BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 1
LOAD DESCRIPTION: 9- 12 WATTS ROUND DOWNLIGHT
2- 12 WATTS ROUND DOWNLIGHT

NO. OF LUMINAIRES: 11
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (11) x (100W)
= 1100 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (1100 VA) / (230V)
= 4.78 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 2
LOAD DESCRIPTION: 9- 12 WATTS ROUND DOWNLIGHT
2- 12 WATTS ROUND DOWNLIGHT

NO. OF LUMINAIRES: 11
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (11) x (100W)
= 1100 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (1100 VA) / (230V)
= 4.78 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 3
LOAD DESCRIPTION: 4- 12 WATTS ROUND DOWNLIGHT
6- 32 WATTS RECESSED BACKLIT PANEL

NO. OF LUMINAIRES: 10
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (10) x (100W)
= 1000 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (1000 VA) / (230V)
= 4.35 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 4
LOAD DESCRIPTION: 5- 12 WATTS ROUND DOWNLIGHT
6- 32 WATTS RECESSED BACKLIT PANEL

NO. OF LUMINAIRES: 11
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (11) x (100W)
= 1100 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (1100 VA) / (230V)
= 4.78 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 5
LOAD DESCRIPTION: 9- 12 WATTS ROUND DOWNLIGHT

NO. OF LUMINAIRES: 9
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (9) x (100W)
= 900 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (900 VA) / (230V)
= 3.91 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)


Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 6
LOAD DESCRIPTION: 5- 12 WATTS ROUND DOWNLIGHT
1- 12 WATTS ROUND DOWNLIGHT

NO. OF LUMINAIRES: 6
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (6) x (100W)
= 600 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (600 VA) / (230V)
= 2.61 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 7
LOAD DESCRIPTION: 7- 12 WATTS ROUND DOWNLIGHT
2- 6 WATTS WALL LIGHT

NO. OF LUMINAIRES: 9
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (9) x (100W)
= 900 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (900 VA) / (230V)
= 3.91 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 8
LOAD DESCRIPTION: 5- RECEPTACLE OUTLETS

NO. OF CONVENIENCE OUTLETS: 5


OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Receptacle Outlets) × (180 VA per Convenience Outlet)


= (5) x (180 VA)
= 900 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (900 VA) ÷ (230V)
= 3.91 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 9
LOAD DESCRIPTION: 5- RECEPTACLE OUTLETS

NO. OF CONVENIENCE OUTLETS: 5


OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Receptacle Outlets) × (180 VA per Convenience Outlet)


= (5) x (180 VA)
= 900 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (900 VA) / (230V)
= 3.91 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 10
LOAD DESCRIPTION: 7- RECEPTACLE OUTLETS

NO. OF CONVENIENCE OUTLETS: 7


OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Receptacle Outlets) × (180 VA per Convenience Outlet)


= (7) x (180 VA)
= 1260 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (1260 VA) / (230V)
= 5.48 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 11
LOAD DESCRIPTION: 3- RECEPTACLE OUTLETS

NO. OF CONVENIENCE OUTLETS: 3


OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Receptacle Outlets) × (180 VA per Convenience Outlet)


= (3) x (180 VA)
= 540 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (540 VA) / (230V)
= 2.35 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 12
LOAD DESCRIPTION: 3- RECEPTACLE OUTLETS

NO. OF CONVENIENCE OUTLETS: 3


OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Receptacle Outlets) × (180 VA per Convenience Outlet)


= (3) x (180 VA)
= 540 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (540 VA) / (230V)
= 2.35 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 13
LOAD DESCRIPTION: 3-HP TREADMILL
NO. OF PHASE: SINGLE-PHASE
FULL LOAD CURRENT: 17 A (FROM TABLE 4.30.14.2, PAGE 370)
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR


(From Table 3.10.2.6(B)(16), page 174)
IBF = (125%) × (IFL) = (1.25) × (17 A) = 21.25 A
Use: 2-8.0 mm2, + 1-5.5 mm2, THHN Copper Wire

SIZE OF CONDUIT (NON-METALLIC):


(From Table C.11, page 1027)
Use: 25 mm Ø PVC CONDUIT

MOTOR OVERLOAD PROTECTION:


(Refer to 4.30.3.2 (1) (Separate Over Load Protection) (Page 351)
I (OVERLOAD DEVICE) = (1.25) × (17 A) = 21.25 A
Overload Device no more than 21.25 A

MOTOR SHORT CIRCUIT PROTECTION (MSCP):


(From Table 4.30.4.2, page 356)
MSCP = (250%) × (IFL) = (2.50) × (17 A) = 42.5 A
Use: 2P – 50 AT, 100 AF, MCCB, 230 V, 60 HZ
MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 14 | 15 | 16
LOAD DESCRIPTION: 2-HP AIR CONDITIONING UNIT (INVERTER)
TYPE OF MOTOR: HERMETIC MOTOR
NO. OF PHASE: SINGLE-PHASE
FULL LOAD CURRENT: 12 A (FROM TABLE 4.30.14.2, PAGE 370)
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR


(From Table 3.10.2.6(B)(16), page 174)
IBF = (125%) × (IFL) = (1.25) × (12 A) = 15 A
Use: 2-5.5 mm2, + 1-5.5 mm2, THHN Copper Wire

SIZE OF CONDUIT (NON-METALLIC)


(From Table C.11, page 1027)
Use: 20 mm Ø PVC CONDUIT

MOTOR OVERLOAD PROTECTION:


(Refer to 4.30.3.2 (1) (Separate Over Load Protection) (Page 351)
I (OVERLOAD DEVICE) = (1.25) × (12 A) = 15 A
Overload Device no more than 15 A

MOTOR SHORT CIRCUIT PROTECTION (MSCP):


(From Article 4.40.3.2(A), page 377)
MSCP = (175%) × (IFL) = (1.75) × (12 A) = 21 A
Use: 2P – 30 AT, 100 AF, MCCB, 230 V, 60 HZ
BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB1


CIRCUIT NUMBER: 17 | 18
LOAD DESCRIPTION: SPARE
NO. OF SPECIAL PURPOSE OUTLET: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Special Outlets) × (Load)


= (1) x (1500)
= 1500 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (1500 VA) / (230V)
= 6.52 A

SIZING OF CONDUCTOR

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB2


CIRCUIT NUMBER: 1
LOAD DESCRIPTION: 3- 12 WATTS ROUND DOWNLIGHT
1- 6 WATTS WALL LIGHT
3- 12 WATTS ROUND DOWNLIGHT
2- 60 WATTS BEDSIDE LAMP
1- 7.9 WATTS ROUND DOWNLIGHT
1-24 WATTS WALL LIGHT
1- 15 WATTS CEILING LIGHT
1- 4 WATTS TRACKING LIGHT
1- 80 WATTS RECTANGULAR CHANDELIER

NO. OF LUMINAIRES: 14
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (14) x (100W)
= 1400 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (1400 VA) / (230V)
= 6.09 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB2


CIRCUIT NUMBER: 2
LOAD DESCRIPTION: 2- 12 WATTS ROUND DOWNLIGHT
2- 6 WATTS WALL LIGHT
4- 12 WATTS ROUND DOWNLIGHT
1- 20 WATTS CEILING LIGHT
1- 90 WATTS ROUND CHANDELIER
2- 4 WATTS TRACKING LIGHT

NO. OF LUMINAIRES: 12
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (12) x (100W)
= 1200 VA

LOAD CURRENT, IL:

IL = (VA/CKT) x (Operating Voltage)


= (1200 VA) ÷ (230V)
= 5.22 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB2


CIRCUIT NUMBER: 3
LOAD DESCRIPTION: 1- 12 WATTS ROUND DOWNLIGHT
1- 6 WATTS WALL LIGHT
3- 12 WATTS ROUND DOWNLIGHT
1- 15 WATTS CEILING LIGHT
1- 80 WATTS RECTANGULAR CHANDELIER
2- 4 WATTS TRACKING LIGHT
1- 7.9 WATTS ROUND DOWNLIGHT
1- 24 WATTS WALL LIGHT

NO. OF LUMINAIRES: 11
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (11) x (100W)
= 1100 VA

LOAD CURRENT, IL:

IL = (VA/CKT) x (Operating Voltage)


= (1100 VA) ÷ (230V)
= 4.78 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)


Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB2


CIRCUIT NUMBER: 4
LOAD DESCRIPTION: 9- RECEPTACLE OUTLETS

NO. OF CONVENIENCE OUTLETS: 9


OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Receptacle Outlets) × (180 VA per Convenience Outlet)


= (9) x (180 VA)
= 1620 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (1620 VA) / (230V)
= 7.04 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB2


CIRCUIT NUMBER: 5
LOAD DESCRIPTION: 6- RECEPTACLE OUTLETS

NO. OF CONVENIENCE OUTLETS: 6


OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Receptacle Outlets) × (180 VA per Convenience Outlet)


= (6) x (180 VA)
= 1080 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (1080 VA) / (230V)
= 4.70 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB2


CIRCUIT NUMBER: 6
LOAD DESCRIPTION: 5- RECEPTACLE OUTLETS

NO. OF CONVENIENCE OUTLETS: 5


OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Receptacle Outlets) × (180 VA per Convenience Outlet)


= (5) x (180 VA)
= 900 VA

LOAD CURRENT, IL:

IL = (VA/CKT) x (Operating Voltage)


= (900 VA) ÷ (230V)
= 3.91 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB2


CIRCUIT NUMBER: 7 | 12
LOAD DESCRIPTION: 2-HP AIR CONDITIONING UNIT (INVERTER)
TYPE OF MOTOR: HERMETIC MOTOR
NO. OF PHASE: SINGLE-PHASE
FULL LOAD CURRENT: 12 A (FROM TABLE 4.30.14.2, PAGE 370)
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR


(From Table 3.10.2.6(B)(16), page 174)
IBF = (125%) × (IFL) = (1.25) × (12 A) = 15 A
Use: 2-5.5 mm2, + 1-5.5 mm2, THHN Copper Wire

SIZE OF CONDUIT (NON-METALLIC)


(From Table C.11, page 1027)
Use: 20 mm Ø PVC CONDUIT

MOTOR OVERLOAD PROTECTION:


(Refer to 4.30.3.2 (1) (Separate Over Load Protection) (Page 351)
I (OVERLOAD DEVICE) = (1.25) × (12 A) = 15 A
Overload Device no more than 15 A

MOTOR SHORT CIRCUIT PROTECTION (MSCP):


(From Article 4.40.3.2(A), page 377)
MSCP = (175%) × (IFL) = (1.75) × (12 A) = 21 A
Use: 2P – 30 AT, 100 AF, MCCB, 230 V, 60 HZ
MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB2


CIRCUIT NUMBER: 9
LOAD DESCRIPTION: RANGE HOOD EXHAUST FAN
NO. OF PHASE: SINGLE-PHASE
FULL LOAD CURRENT: 0.43 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR


(From Table 3.10.2.6(B)(16), page 174)
IBF = (125%) × (IFL) = (1.25) × (0.43 A) = 0.5375 A
Use: 2-3.5 mm2, + 1-3.5 mm2, THHN Copper Wire

SIZE OF CONDUIT (NON-METALLIC)


(From Table C.11, page 1027)
Use: 20 mm Ø PVC CONDUIT

MOTOR OVERLOAD PROTECTION:


(Refer to 4.30.3.2 (1) (Separate Over Load Protection) (Page 351)
I (OVERLOAD DEVICE) = (1.25) × (0.43 A) = 0.5375 A
Overload Device no more than 0.5375 A

MOTOR SHORT CIRCUIT PROTECTION (MSCP):


(From Table 4.30.4.2, page 356)
MSCP = (250%) × (IFL) = (2.50) × (0.43A) = 1.075 A
Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 HZ
BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB2


CIRCUIT NUMBER: 10
LOAD DESCRIPTION: ELECTRICAL COOKING RANGE
NO. OF SPECIAL PURPOSE OUTLET: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Special Outlets) × (Load)


= (1) x (4500)
= 4500 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (4500 VA) / (230V)
= 19.57 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

IBF = (125%) × (IFL) = (1.25) × (19.57 A) = 24.4625 A


Use: 2-5.5 mm2, + 1-5.5 mm2, THHN Copper Wire

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 30 AT, 100 AF, MCCB, 230 V, 60 Hz


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB2


CIRCUIT NUMBER: 11
LOAD DESCRIPTION: REFRIGERATOR
TYPE OF MOTOR: HERMETIC MOTOR
NO. OF PHASE: SINGLE-PHASE
FULL LOAD CURRENT: 0.65 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR


(From Table 3.10.2.6(B)(16), page 174)
IBF = (125%) × (IFL) = (1.25) × (0.65 A) = 0.8125 A
Use: 2-3.5 mm2, + 1-3.5 mm2, THHN Copper Wire

SIZE OF CONDUIT (NON-METALLIC)


(From Table C.11, page 1027)
Use: 20 mm Ø PVC CONDUIT

MOTOR OVERLOAD PROTECTION:


(Refer to 4.30.3.2 (1) (Separate Over Load Protection) (Page 351)
I (OVERLOAD DEVICE) = (1.25) × (0.65 A) = 0.8125 A
Overload Device no more than 0.8125 A

MOTOR SHORT CIRCUIT PROTECTION (MSCP):


(From Article 4.40.3.2(A), page 377)
MSCP = (225%) × (IFL) = (2.25) × (0.65 A) = 1.4625 A
Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 HZ
BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB2


CIRCUIT NUMBER: 13 | 14
LOAD DESCRIPTION: WATER HEATER
NO. OF SPECIAL PURPOSE OUTLET: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Special Outlets) × (Load)


= (1) x (3500)
= 3500 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (3500 VA) / (230V)
= 15.22 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

IBF = (125%) × (IFL) = (1.25) × (15.22 A) = 19.025 A


Use: 2-3.5 mm2, + 1-3.5 mm2, THHN Copper Wire

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB2


CIRCUIT NUMBER: 15 | 16
LOAD DESCRIPTION: SPARE
NO. OF SPECIAL PURPOSE OUTLET: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Special Outlets) × (Load)


= (1) x (1500)
= 1500 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (1500 VA) / (230V)
= 6.52 A

SIZING OF CONDUCTOR

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 1
LOAD DESCRIPTION: 4- 12 WATTS ROUND DOWNLIGHT
4- 32 WATTS RECESSED BACKLIT PANEL

NO. OF LUMINAIRES: 8
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (8) x (100W)
= 800 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (800 VA) / (230V)
= 3.48 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 2
LOAD DESCRIPTION: 2- 6 WATTS WALL LIGHT

NO. OF LUMINAIRES: 2
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (2) x (100W)
= 200 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (200 VA) / (230V)
= 0.87 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 3
LOAD DESCRIPTION: 3- 7.9 WATTS ROUND DOWNLIGHT
1- 6 WATTS WALL LIGHT
1- 24 WATTS WALL LIGHT
1- 15 WATTS CEILING LIGHT

NO. OF LUMINAIRES: 6
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (6) x (100W)
= 600 VA

LOAD CURRENT, IL:

IL = (VA/CKT) x (Operating Voltage)


= (600 VA) ÷ (230V)
= 2.61 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 4
LOAD DESCRIPTION: 7- 12 WATTS ROUND DOWNLIGHT
7- 32 WATTS RECESSED BACKLIT PANEL

NO. OF LUMINAIRES: 14
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (14) x (100W)
= 1400 VA

LOAD CURRENT, IL:

IL = (VA/CKT) x (Operating Voltage)


= (1400 VA) ÷ (230V)
= 6.09 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 4
LOAD DESCRIPTION: 3- 12 WATTS ROUND DOWNLIGHT

NO. OF LUMINAIRES: 3
NO. OF LAMPS PER LUMINAIRE: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) × (Watts)


= (3) x (100W)
= 300 VA

LOAD CURRENT, IL:

IL = (VA/CKT) x (Operating Voltage)


= (300 VA) ÷ (230V)
= 1.3 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 6
LOAD DESCRIPTION: 5- RECEPTACLE OUTLETS

NO. OF CONVENIENCE OUTLETS: 5


OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Receptacle Outlets) × (180 VA per Convenience Outlet)


= (5) x (180 VA)
= 900 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (900 VA) / (230V)
= 3.91 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 7
LOAD DESCRIPTION: 2- RECEPTACLE OUTLETS

NO. OF CONVENIENCE OUTLETS: 2


OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Receptacle Outlets) × (180 VA per Convenience Outlet)


= (2) x (180 VA)
= 360 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (360 VA) / (230V)
= 1.57 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 8
LOAD DESCRIPTION: 5- RECEPTACLE OUTLETS

NO. OF CONVENIENCE OUTLETS: 5


OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Receptacle Outlets) × (180 VA per Convenience Outlet)


= (5) x (180 VA)
= 900 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (900 VA) / (230V)
= 3.91 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 9
LOAD DESCRIPTION: 2-HP AIR CONDITIONING UNIT (INVERTER)
TYPE OF MOTOR: HERMETIC MOTOR
NO. OF PHASE: SINGLE-PHASE
FULL LOAD CURRENT: 12 A (FROM TABLE 4.30.14.2, PAGE 370)
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR


(From Table 3.10.2.6(B)(16), page 174)
IBF = (125%) × (IFL) = (1.25) × (12 A) = 15 A
Use: 2-5.5 mm2, + 1-5.5 mm2, THHN Copper Wire

SIZE OF CONDUIT (NON-METALLIC)


(From Table C.11, page 1027)
Use: 20 mm Ø PVC CONDUIT

MOTOR OVERLOAD PROTECTION:


(Refer to 4.30.3.2 (1) (Separate Over Load Protection) (Page 351)
I (OVERLOAD DEVICE) = (1.25) × (12 A) = 15 A
Overload Device no more than 15 A

MOTOR SHORT CIRCUIT PROTECTION (MSCP):


(From Article 4.40.3.2(A), page 377)
MSCP = (175%) × (IFL) = (1.75) × (12 A) = 21 A
Use: 2P – 30 AT, 100 AF, MCCB, 230 V, 60 HZ
MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 10
LOAD DESCRIPTION: WASHING MACHINE
NO. OF PHASE: SINGLE-PHASE
FULL LOAD CURRENT: 6.52 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR


(From Table 3.10.2.6(B)(16), page 174)
IBF = (125%) × (IFL) = (1.25) × (6.52 A) = 8.15 A
Use: 2-3.5 mm2, + 1-3.5 mm2, THHN Copper Wire

SIZE OF CONDUIT (NON-METALLIC):


(From Table C.11, page 1027)
Use: 20 mm Ø PVC CONDUIT

MOTOR OVERLOAD PROTECTION:


(Refer to 4.30.3.2 (1) (Separate Over Load Protection) (Page 351)
I (OVERLOAD DEVICE) = (1.25) × (6.52 A) = 8.15 A
Overload Device no more than 8.15 A

MOTOR SHORT CIRCUIT PROTECTION (MSCP):


(From Article 4.40.3.2(A), page 377)
MSCP = (225%) × (IFL) = (2.25) × (6.52 A) = 14.67 A
USE: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 HZ
MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 11
LOAD DESCRIPTION: POWER SPRAYER
NO. OF PHASE: SINGLE-PHASE
FULL LOAD CURRENT: 6.09 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR


(From Table 3.10.2.6(B)(16), page 174)
IBF = (125%) × (IFL) = (1.25) × (6.09 A) = 7.6125 A
Use: 2-3.5 mm2, + 1-3.5 mm2, THHN Copper Wire

SIZE OF CONDUIT (NON-METALLIC):


(From Table C.11, page 1027)
Use: 20 mm Ø PVC CONDUIT

MOTOR OVERLOAD PROTECTION:


(Refer to 4.30.3.2 (1) (Separate Over Load Protection) (Page 351)
I (OVERLOAD DEVICE) = (1.25) × (6.09 A) = 7.6125 A
Overload Device no more than 7.6125 A

MOTOR SHORT CIRCUIT PROTECTION (MSCP):


(From Table 4.30.4.2, page 356)
MSCP = (250%) × (IFL) = (2.50) × (6.09 A) = 15.225 A
USE: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 HZ
MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 12
LOAD DESCRIPTION: WATER PUMP
NO. OF PHASE: SINGLE-PHASE
FULL LOAD CURRENT: 10 A (FROM TABLE 4.30.14.2, PAGE 370)
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR


(From Table 3.10.2.6(B)(16), page 174)
IBF = (125%) × (IFL) = (1.25) × (10 A) = 12.5 A
Use: 2-5.5 mm2, + 1-5.5 mm2, THHN Copper Wire

SIZE OF CONDUIT (NON-METALLIC):


(From Table C.11, page 1027)
Use: 20 mm Ø PVC CONDUIT

MOTOR OVERLOAD PROTECTION:


(Refer to 4.30.3.2 (1) (Separate Over Load Protection) (Page 351)
I (OVERLOAD DEVICE) = (1.25) × (10 A) = 12.5 A
Overload Device no more than 12.5 A

MOTOR SHORT CIRCUIT PROTECTION (MSCP):


(From Table 4.30.4.2, page 356)
MSCP = (250%) × (IFL) = (2.50) × (10 A) = 25 A
USE: 2P – 30 AT, 100 AF, MCCB, 230 V, 60 HZ
MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 13
LOAD DESCRIPTION: RANGE HOOD EXHAUST FAN
NO. OF PHASE: SINGLE-PHASE
FULL LOAD CURRENT: 0.43 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR


(From Table 3.10.2.6(B)(16), page 174)
IBF = (125%) × (IFL) = (1.25) × (0.43 A) = 0.5375 A
Use: 2-3.5 mm2, + 1-3.5 mm2, THHN Copper Wire

SIZE OF CONDUIT (NON-METALLIC)


(From Table C.11, page 1027)
Use: 20 mm Ø PVC CONDUIT

MOTOR OVERLOAD PROTECTION:


(Refer to 4.30.3.2 (1) (Separate Over Load Protection) (Page 351)
I (OVERLOAD DEVICE) = (1.25) × (0.43 A) = 0.5375 A
Overload Device no more than 0.5375 A

MOTOR SHORT CIRCUIT PROTECTION (MSCP):


(From Table 4.30.4.2, page 356)
MSCP = (250%) × (IFL) = (2.50) × (0.43A) = 1.075 A
Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 HZ
BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 14
LOAD DESCRIPTION: ELECTRICAL COOKING RANGE
NO. OF SPECIAL PURPOSE OUTLET: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Special Outlets) × (Load)


= (1) x (4500)
= 4500 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (4500 VA) / (230V)
= 19.57 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

IBF = (125%) × (IFL) = (1.25) × (19.57 A) = 24.4625 A


Use: 2-5.5 mm2, + 1-5.5 mm2, THHN Copper Wire

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 30 AT, 100 AF, MCCB, 230 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: PB3


CIRCUIT NUMBER: 15 | 16
LOAD DESCRIPTION: SPARE
NO. OF SPECIAL PURPOSE OUTLET: 1
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Special Outlets) × (Load)


= (1) x (1500)
= 1500 VA

LOAD CURRENT, IL:

IL = (VA/CKT) / (Operating Voltage)


= (1500 VA) / (230V)
= 6.52 A

SIZING OF CONDUCTOR

SIZE OF CONDUIT (NON-METALLIC): (From Table C.11, page 1027)

Use: 20 mm Ø PVC Conduit

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 20 AT, 100 AF, MCCB, 230 V, 60 Hz