Professional Documents
Culture Documents
INDEX
1.3 Nameplate…………………………………………………………………………………………………
1
Schneider®
2
Schneider®
Output power(KVA) 11 14 21 26 31
Output power consumption(A) 14 18 27 34 41
(A) 15 20 30 40 50
Wave filter
(mH) 1.42 1.06 0.7 0.53 0.42
Figure1.1 capacity 400V model Specification
3
Schneider®
4
Schneider®
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure
that the temperature inside the enclosure remains below 45℃。
5
Schneider®
6
Schneider®
‐ A large number of interfering current may earth connecting when using noise filte, so the PE earthing
cable need to have a Min. 10mm2 cross section.
‐ Follow the instruction, use differenct wire for heavy or weak current, otherwise it would effect on the
EMC.
‐ Use copper wire to shield the cabinet and the motor, cannot use steel wire
‐ Shield the main cable and brake resistor from the terMinal cover to the control cabinet cable.
‐ The tachometer shielding line must be erthing with both sides and wiring from the the side face to
outer covering (PE).
‐ If electric relay and contactor are in the same integrate circuit, anti‐spark component and overvoltage
protection component must be installed. All the contactor and ouside the cabinet, the R‐C filter must
be installed
‐ Contril wire and tachometer wire must be set in separate casing.
‐ Same potential cables in the cabinet should be wiring together to avoid the interference
‐ When connect the metal part, should keep Max. Interface and good conductibility. Mind the anodizing
oxygenation layer and dyeing layer(such as guide rail, screw, bolt ect. ) . As they will be in high
resistance value, better to use Al panel inside cabinet.
‐ The system designer must Mind the high frequency noise and noise sensibility, and consider available
protection .
‐ Note: Good shield make good antijamMing, at the same time can protect the system itself.
7
Schneider®
8
Schneider®
internal public
9
Schneider®
input signal
X02 Power failure emergency level NO X16 The upper limit ( without ) NC
UPS
deceleration
deceleration
deceleration
M2 The input signal of the (+) X26 The security module the Open
door
internal public feedback signal
common
+24‐CPU internal CPU power supply positive CAN1 outbound / select interface
GND‐CPU nternal CPU power supply cathode CAN2 outbound / select interface
+24‐CAN external serial bus power supply cathode CAN3 operator interface
10
Schneider®
Note: call boards used as selected show all address code needs to be set in the OFF state.
2.8 Car Call Model I/O Spec.
Input/Output Signal
IN01‐IN16 1F‐16F Car Call Button VCC Com of Car Call Model
LED01‐LED16 1‐16F Car call Light GND Car Call Board Power Negative
11
Schneider®
NO
COM1 The input signal of the internal public A12 Side door screen input
A00 The main door to open the door in A13 The door zone input signal
12
Schneider®
place
A01 The main door is closed in place P24 + 24V power output
A03 Side door closing in place COM2 Open the output signal of the public
A04 Overload input signal B00 The main doors open output
A05 Full load bypass signal B01 The main door closes the output
A06 Half of the input signal B02 Side door open output
A07 The main door touch panel input B03 Side door closes the output
A10 Side door touch panel input COM3 The station clock public
A11 The main door screen input B04 The station clock output
In accordance with the drawings connected control circuit, system electricity operation screen to display
an initial interface. Press ENTER to enter the main menu of the cabinet; in the main menu interface by UP
/ DOWN keys can be in the main menu / page down; in selected main menu page click on the ENTER
button to enter the next level menu in the menu, press UP / DOWN button will be in the menu. / page
down;
13
Schneider®
Cabinet in the original interface, click the confirmation button ENTER can enter the main menu, press
the ESC key to exit to the main menu to return to initial interface; such as a press UP / DN button in the
main menu, press ENTER circular turning selected menu enter the next level sub menu submenu;
according to UP / DOWN keys can be circular turning press the ENTER key can enter and modify data.
The OP menu system operating parameters; A menu for quick debug menu, we in order to facilitate the
debugging and the different motor parameters or elevator main protection of data integration in a menu.
Press ENTER
14
Schneider®
Press ENTER
Key
Press ESC
15
Schneider®
When power ON or password confirmed, in 15 minutes without operation, need to confirmed again the
menu
rs 1: impedance learning
2: asynchronous rotary
Synchronous Static
3: synchronous motor to
rotate the 1
4: synchronous motor to
rotate the 2
5 : automatic
16
Schneider®
initialization initiation
1: drive asynchronous
initialization
2: system initialization
3: asynchronous system
initialization
System read
4: system.
1: English
menu (PM/IM)
control
vector control
17
Schneider®
1: ABZUVW increment
2: SIN / COS
3: rotary transformer
6: magnetic encoder
encoder
electromotive force
B14
nameplate )
nameplate )
18
Schneider®
reverse
dock
elevator
learning
speed limit
speed limit
value
(PM/IM)
19
Schneider®
( do not change )
angle
acquisition
coefficient acquisition
20
Schneider®
direction
direction
value
(PM/IM)
Can time
Line time
C07 self learning speed Intelligent self learning speed of S curve 00.300m/s
speed
Speed Control D02 multistage speed and Multistage velocity deceleration time 2.5s
D04 accelerated the end Multistage speed start time end corner 0.8s
21
Schneider®
corner of time
D09 self learning speed Multistage speed curve self learning 8/4.00HZ
speed
speed
D14 highest multi speed Multi speed, single and multi floor 1
setting setting
value s
(PM/IM)
Play selection
Dynamic E02 zero velocity Motor zero velocity position locking gain 01.2 33
Set frequency
22
Schneider®
time
compensation
compensation ( standby)
direction
proportional gain
proportional gain
proportional gain
integration time
time
frequency
23
Schneider®
limit
overheat protection
protection time
temperature
2: deceleration stop
24
Schneider®
protection threshold
time
2: deceleration stop
threshold frequency
time
2: deceleration stop
frequency
protection time
disconnection
protection
25
Schneider®
The F20 output phase Output phase loss protection universal set OFF 35
protection enable
is set to F22
enable
protection time
protect time
protection time
protection time
number
26
Schneider®
speed limit
speed limit
speed
speed
speed
distance distance
distance distance
distance distance
ence ence
value page
(PM/I
M)
Electric delay
27
Schneider®
That ʹs ok G04 parking DC lock time Stop when the DC lock time 0.50s 36
When the The G05 outputs a stop over time Output stop over time 0.00s 36
Sequence G06 Direction enable release time Direction Enables releasetime 3.0S 37
G08 stop 0 speed brake delay 0 Speed brake delay when stop 0.15S 37
The G09 output curve of time Starting curve of output time 0.5/1.2 37
G10 delay time to open the door Into the portal area delay time to 2.0S 37
Off delay time G11 crawling Off delay time crawling 0.9S 37
G12 maintenance fault direction enable Maintenance fault direction enable 0.0S 37
G15 returned to the base station time Return to the base station time 0S 37
The G16 energy saving lighting start Illumination power‐saving mode 3min 37
Transmissio ally
n open
In / lose H02 band‐type brake feedback X13 Normally open / close Norm 37
Out ally
Set ally
Meaning of open
ally
open
28
Schneider®
ally
open
ally
open
Quasi I02 called light load voltage Car light load analog voltage 00.0V 38
Transmiss I03 weighing half load Car half load analog voltage 00.0V 38
ion voltage
Set I04 weighing load voltage Car load analog voltage 00.0V 38
voltage
( analog input )
Electric J01 group mode ON/OFF OFF 38
29
Schneider®
close
1: display of fire
2: F
3: display pi
4: alternate
1: Hongkong
2: Russia
3: Singapore
4: alternate
mode
detection
detection
J14 standby power operation 0: return to the base station after the 0 39
continue
30
Schneider®
function
control
open
to maintain
detection
base station
31
Schneider®
correction floor
2: manual door
correction
elimination
page
c
K02 magnetic separation sheet Magnetic separation sheet length setting 00240mm 40
Ladder
length ( the governor on the encoder to use )
Adjust
K03 magnetic separation sheet ( well self learning acquisition ) 0 40
able
pulse
Test
K04 well self learning ON / OFF ( self learning ) OFF 40
32
Schneider®
The main entrance door set K12 The main entrance door set 40
K13 side access door set K13 side access door set 40
value
display
runs
state
33
Schneider®
change
number
distance acquiration
distance acquiration
acquiration
distance acquiration
menu value
acquiration
acquiration
34
Schneider®
value
monitoring
Flat adjustment
Adjust adjustment
ment M03 floor level set 1‐63 upstairs level adjustment +/‐ 0 41
adjustment
N The N01 call floor instruction Call instruction given on the floor 41
Call
instruc N02 call floor instruction Call instructions given under floor 41
instruction
35
Schneider®
menu
others
User password settings for 000000000 is the use of a 9 password protection. Users in the power system or
the password confirmation after 15 minutes to re‐type the user password to change all user data, but the
access fault records or data set can be directly operated; such as change user password to confirm the
factory value and then change password change password for the new user, users need to bear in mind
The system password for manufacturer dedicated, the user can not change the.
Motor parameter self learning before first in the simple menu set the corresponding parameters ( B04,
B05, B06, B08, B10, B11, B12, B13, B14, B15, B16 ).
36
Schneider®
(5) Automatic
System data can be matched with the initial / asynchronous motor to drive or initialization of system
(0) Read ‐ drive set parameter is read to the hand‐held device and save.
(1) Write ‐ to save the hand‐held operator within a few written to the drive.
(2) Correction ‐ for read / write operation after the collation operation device and the drive between the
data consistency.
(3) System read ‐ set the system parameter is read to the hand‐held device and save.
(4) System write ‐ the preserved in hand‐held device within a few written to the register.
(5) System write correction – Use to check if the data is same after copied
37
Schneider®
menu.
B Drive menu
B01: Motor capacity: 11KW,machine capacity display can not change.
B02 power supply voltage level: 380V set voltage level until.
B03 carrier frequency: 8.0KHZ set frequency carrier frequency, if the motor operation of a higher
resonant resonate tone or please reduce the carrier frequency converter.
B04 motor control mode
(0) V / F : V / F control mode is only suitable for three‐phase asynchronous motor without speed sensor
feedback control mode of poor control precision.
(1) No sensor vector control: the control mode does not require the use of feedback signals from the
motor, torque can be rapid response, so that the motor at low speed can also obtain greater torque.
(2) Magnetic flux vector control: magnetic flux vector control model can be adapted to lift all universal
asynchronous ( IM ) motor, need to receive the motor encoder feedback signal, to achieve high
performance of torque control of all variable speed control, so that the lift to get better comfort
torque response than the current vector control slow.
(3) The current vector control: current vector control mode needs to meet the motor encoder feedback
signal to achieve high performance of torque control of all variable speed control, torque response
fast adjustable electrical characteristics of variable frequency motor for better.
(4)Synchronous current vector control synchronous current vector control mode is used for driving a
three‐phase permanent magnet synchronous motor ( PM ), the use of SIN / COS encoder feedback to
achieve high performance of torque control of all variable speed control, torque response faster
better adaptable dynamic characteristics of permanent magnet synchronous motor ( PM ).
(5) Synchronous magnetic flux vector control synchronous current vector control mode is used for
driving a three‐phase permanent magnet synchronous motor ( PM ), the use of SIN / COS encoder
feedback to achieve high performance of torque control of all variable speed control, torque
response slower adaptation can be good general‐purpose three‐phase permanent magnet
synchronous motor ( PM ).
B06 Encoder pulse: encoder pulses can be applied to 300‐‐‐10000 output pulse encoder.
B07 Encoder filter: encoder signal input filter usually defaults to 3.0ms, increase this value can be
enhanced encoder signal to jamming capability.
38
Schneider®
B08 E ncoder sequence: the encoder input signal sequence, set to OFF A phase lead ( A‐B ), set to ON B
phase lead ( B‐A ). When the encoder input signal inversion can set this value commutation without
the need to change the encoder connection.
B09 Encoder deviation angle encoder: deviating from the electrical angle parameters for the permanent
magnet synchronous motor ( PM ) special, when debugging through OP3 = 3 self learning gain.
B10 Motor rated power: according to the motor nameplate set the motor rated power.
B11 motor pole number: according to the motor nameplate setting pole number, must be properly
set the motor pole number or not running.
B12 motor rated current according to the motor nameplate: set the motor rated current value.
B13 motor rated voltage: according to the motor nameplate set motor rated voltage.
Motor rated frequency B14: according to the motor nameplate rated motor frequency value set.
B15 The rated speed of the motor according to the motor nameplate rated motor frequency value set.
B16 No‐load current according to the motor nameplate set motor no‐load current value, the value of
general asynchronous motor is set to 40% of the rated current, synchronous motor should be set to
0
B17 Motor rated slip: through the OP3 parameter self ‐ learning to obtain this value.
B18 Motor a resistance: through the OP3 parameter self ‐ learning to obtain this value.
B19 Motor leakage reactance: through the OP3 parameter self ‐ learning to obtain this value.
B20 Motor saturation coefficient 1: through the OP3 parameter self ‐ learning to obtain this value.
B21 Motor saturation coefficient 2: through the OP3 parameter self ‐ learning to obtain this value.
B22 The direction of motor rotation: elevator running direction and system given in opposite directions
when can put this value is set to ON change the motor running direction.
B23 system: system internal high‐speed counting input direction, monitor L18 elevator current position
display parameters, when the elevator is slow when the numerical increment, the elevator when the
value delivery speed slow. Otherwise there will be set to ON internal counting reversed input.
39
Schneider®
( Note: all the smart S curve setting characteristics, J04 = 0 / 1 set effective )
C05 crawling speed: this value is usually set value should be < 0.1M / s to ensure the comfort of the
elevator stops at,
This parameter is only J04 docked mode when set to 1, setting the other is invalid.
C06 inspection speed: set the overhaul of elevator running speed.
C07 self learning speed: set elevator hoistway data when learning speed.
C08 self‐help flat layer speed: set when the elevator is not in level position for automatic level position of
speed.
C09 leveling speed: set elevator parking due to load changes caused by uneven layer of wire rope tension,
then automatic level setting velocity.
C10 elevator actual speed: set of elevator running speed.
C11 rated speed: set the nominal speed of the elevator.
40
Schneider®
( Note: S curve characteristics of multistage speed setting, J04 = 2 when setting the valid )
DO7 crawling speed: elevator gear reducer crawling after induced portal zone speed, and can be used to
adjust the level the elevator, elevator owe usually increase this value, super flat layer to reduce some
value.
D08 inspection speed: Elevator maintenance operating speed.
D09 self learning speed: elevator shaft self‐learning when the operation speed.
D10 self‐help leveling speed: the elevator is not in door zone automatic back flat layer velocity.
D11 leveling speed: set elevator parking due to load changes caused by uneven layer of wire rope tension,
then automatic level setting velocity.
D12 single speed: set the single speed elevator.
D13 multilayer speed: set of middle speed elevator.
D14 maximum speed period settings: set elevator multistage speed set run single multilayer speed
number. J04 is usually set to 0 / 1 when D14 is set to 1, J04 = 2 D14 can be set to 1 / 2 / 3 that is the
most can be divided into three sections speed operation.
41
Schneider®
E11 high speed proportional gain: This is the adjustment of high speed control ( ASR ) response gain.
Increasing the set value response will improve. Typically a load greater set value is larger, but the
setting will cause the vibration of.
E12 low speed proportional gain: This is to adjust the low speed speed control ( ASR ) response gain.
Increasing the set value response will improve. Typically a load greater set value is larger, but the
setting will cause the vibration of.
E13 starting proportional gain : This is to adjust the starting speed control ( ASR ) response gain.
Increasing the set value response will improve. Typically a load greater set value is larger, but the
setting will cause the vibration of.
E14 high speed integration time: high speed control ( ASR ) integral time fine‐tuning, integral time
response characteristics can be reduced, the relative force counterforce also worse; but the
integration time is too small will cause vibration.
E15 low‐speed integral time: low speed control ( ASR ) integral time fine‐tuning, integral time response
characteristics can be reduced, the relative force counterforce also worse; but the integration time is
too small will cause vibration.
E16 starting integral time: starting speed control ( ASR ) integral time fine‐tuning, integral time response
characteristics can be reduced, the relative force counterforce also worse; but the integration time is
too small will cause vibration.
E17 ASR switching frequency speed control ( ASR ): high and low velocity gain switching point.
E18 torque filter time: the output torque of the filtering time.
E19 drag torque limit: drag torque upper limit setting, increase this value can increase the drag torque
protection cap, if the load is increased with increasing in this setting value.
E20 braking torque limit: braking torque upper limit setting, increase this value can increase the braking
torque of the protective cap, if the load is increased with increasing in this setting value.
E21 current gain: current control loop proportional gain, this value may be within the scope of
20%‐‐‐150% regulation, increase this value can be increased by current control response
characteristics, if set too large will cause vibration.
42
Schneider®
43
Schneider®
F17 encoder disconnection protection: set the encoder signal phase failure protection function, when the
lift operation in the encoder signal abnormalities or phase interruption, stop running.
The F18 input signal phase protection enable
(0) does not protect: one input phase when the elevator does not protect continue to run.
(1) free slide stop: one input phase when the elevator free slide stop.
(2) a deceleration stop: one input phase when the elevator free slide stop.
(3): one machine is stopping input phase when the elevator emergency stop.
F19 input open‐phase protection threshold: one machine input open‐phase protection threshold.
The F20 output phase loss protection enable: one machine output phase loss protection enable, some
value is set to ON output phase loss effectively, when set to OFF, the elevator output phase loss
protection.
F21 electric leakage protection enable: one machine detects the electric leakage, if this value is set to ON
elevator protection output closed, set to OFF when the elevator does not protect continue to run.
Low voltage F22 run enable: when one power supply phase or the use of lower level power supply
If this value is set to ON, one machine not to implement low voltage protection can continue to run. Set to
OFF when the elevator low voltage protection does not continue to operate.
F23 low voltage operation terminal enable: this value is set to 28 when power failure while the elevator is
not in the flat position, one of the X02 input low voltage input can be detected when the shielding low
voltage detection and the use of UPS on the electric cabinet power supply automatic leveling layer
release.
F24 elevator running protection time: set of elevator running overtime protection time for preventing
elevator skid. After starting to lift in the setting time to stop running; when the elevator in a single run
detection to the gate area signal change when the timer resets.
F25 level changes protect time: set the lift operation in the two adjacent floor leveling signal changes
allowed the most long time, prevent the elevator slip function. Usually the factory value of 13S, users can
according to the velocity of the elevator or the floor height of reasonable setting this value.
F26 shielding safety contact plate of time: setting the safe contact plate or screen was blocked buzzer
alarm time.
F27 elevator door protection time: when the elevator door to door if the layer door is blocked or
abnormal signals in the protection of the time.
F28 elevator door protection time: elevator closed if the layer door is blocked or to the gate signal is
abnormal protection time.
F29 fault door allowed number: set of elevator fault or not to open the door when the allow the times of
opening.
F30 elevator zero speed detection value: elevators set zero speed detection threshold, set this value
crosses congress to affect parking comfort.
F31 high speed change strong velocity speed limit: set the lift operation to end station high speed
reduction position when the maximum permitted speed. If it exceeds the set value of elevator emergency
parking brake.
F32 low speed changing speed limits: strong set of elevator running to the end station speed strong
reducing position when the maximum permitted speed. If it exceeds the set value of elevator emergency
parking brake.
F33 S4 to S3 average speed: high speed elevator set from the detection switch S4 to S3 average speed.
44
Schneider®
F34 S3 to S2 average speed: high speed elevator set from the detection switch S3 to S2 average speed.
F35 S2 to S1 average speed: high speed elevator set from the detection switch S2 to S1 average speed.
F36 terminal S4 distance to S3: high‐speed elevators set from S4 to S3 distance detection switch.
F37 terminal S3 distance to S2: high‐speed elevators set from S3 to S2 distance detection switch.
F38 terminal S2 distance to S1: high‐speed elevators set from S2 to S1 distance detection switch.
G elevator operation timing
G01 contactor disconnect delay: set elevator parking time release main loop contactor time.
G02 starting DC lock time: set elevator starting opening when the motor DC lock time,
J04 is set to 0, this value should be set with the G09 parameter setting values.
Opening G03 starting delay: set the output opening command delay output speed instruction time.
G04 parking lock time: DC elevator running to the zero speed output zero speed brake lock time.
The G05 output stop transition time:
Note: the operating sequence is as follows:
G06 direction to release time: set elevator after stopping the release direction signal time.
G07 brake open time: setting one engine when starting up open brake delay time ( J04 was 0 / 1 when,
should let G07 = 0 ).
G08 parking zero speed delay contracting: set elevator parking brake release zero speed delay.
The G09 output curve of time: the elevator starts up the output rise curve time, this value should be
with G02, To get better starting comfort.
G10 delay opening hours: Elevator parking brake delay time to open the door after the zero speed.
G11 off delay time crawling speed: this value as the elevator stops at mode ( J04 ) set 2 using a multistage
speed curve when effective, when the elevator reaches the target floor reduction after receiving the
gate area signal start delay cut‐off crawling speed time.
G12 maintenance fault direction enable: set elevator maintenance operation stop when drive direction
delay time, usually asynchronous motor this value is set to 0S, the synchronous motor can be set to
1S or so can be increased when parking locking torque at zero speed, prevent the elevator slip.
G13 buzzer ringing frequency: setting the buzzer resounds time interval.
G14 arrival bell duration: setting the arrival bell signal output duration.
G15 returned to the base station time: elevator without operation instruction still according to the set
time automatically returns the setting base station waiting. In seconds, setting time, setting 0 does
not automatically return to the base station.
The G16 energy saving lighting start time: Elevator self‐closing no operation instruction after delay
45
Schneider®
46
Schneider®
efficiency.
( 1) the S curve directly crawling docked: set using built in full intelligent S curve crawling of docking
methods, debugging easier with large amounts of data automatic calculation, to a destination floor
distance calculation of reasonable running speed, forward vehicle principle more scientific and high
efficiency. Parking time can be set to crawl time leveling precision.
( 2) the digital quantity with crawl call: the use of multistage speed curve operation, need to set
corresponding to the running speed, acceleration and deceleration time and deceleration S curve.
The J05 driver to operate the directional pattern
( 0) driver directional: elevator in the driver mode by the elevator operator in a compartment within the
selected button selected decide the elevator running direction.
( 1): Elevator call directed in the driver mode by the calling signal determines the elevator running
direction.
J06 driver operation closed mode
(0 ) according to the close button and close the door: elevator in the driver mode by the elevator operator
selected target layer according to the close button to close the line ladder.
( 1) to move the door close button and close the door: elevator in the driver mode by the elevator operator
selected target layer after moving a door close button close bank ladder.
J07 anti‐nuisance function: set to ON when the elevator anti‐nuisance functions to open, when the system
detects the light signal input set by J08 plies running after the completion of its elimination. When
set to OFF is invalid.
J08 anti‐nuisance layers : setting the anti‐nuisance function after initiation of adjacent layers allow floor
movement.
J09 fire back display
( 0) do not show: elevator into the fire mode return fire station fire information after the show.
( 1) display fire elevator into fire mode return fire station in the floor display display fire indication
information.
( 2) showed F: elevator into the fire mode return fire station in the floor display display on F words
information.
( 3) showed PI: elevator into the fire mode return fire station in the floor display display ‐ʺ information
( Russian elevator special way ).
( 4) ( 5) ( 6) ( 7) ( 8) ( 9) spare
J10 fire mode
( 0 ): China according to the Chinese GB7588‐2003 standard mode to execute the fire operation mode.
( 1) Hongkong: according to the Hongkong electrical and Mechanical Services Department provides fire
operation mode of execution.
( 2 ): Russia by the Russian fire operation mode of execution.
( 3): Singapore by Singapore fire operation mode of execution.
( 4) ( 5) ( 6) ( 7) ( 8) ( 9) spare
J11 firefighters dedicated mode: set the ON executable firefighters dedicated mode, OFF only performed
when fire emergency landing automatically return fire station.
47
Schneider®
J12 Russian Deputy lock detection: set to OFF when this function is invalid, the Russian domestic use
must be set for each layer of outbound board X01 detection point shall be connected to the
corresponding hall door lock detection point.
J13 Russian security window detection: Russia mode, other regions of the user must be set to OFF.
J15 elevator function: when set to ON and leveling function effectively, but must detect security module
can start to the flat layer, is set to OFF is invalid.
J16 elevator open door function: when set to ON to open early function effectively, but must detect
security module to open early, when set to OFF is invalid.
J18 signal output to maintain open: set ON when the door in place signal moves continue to maintain the
door open signal output, until the execution instruction when the instruction is maintained open
close cancel. Let OFF when the door is opened to maintain output invalid.
J19 door close signal output remains: setting ON in‐place close signal moves to maintain close door
signal output, until the execution instruction when the instruction is maintained closed door to
cancel. Let OFF closed at output remains invalid.
J20 closed signal detection: setting ON elevator detection close to signal moves to allow starting express
operation, set the OFF closed signal detection of invalid.
J21 opens the door waiting: setting ON elevator in the elevator floor door waiting, set the OFF when the
function is invalid.
48
Schneider®
J23 cell / remote monitoring: ON / OFF setting cell / remote monitoring function is open.
J26 automatic test run: ON / OFF setting elevator test run automatically when opened.
J27 automatic test run times: setting the J26 automatic test pneumatic stop limit value.
J28 motor thermal testing: ON / OFF X00 set point input for motor overheating nearby flat layer to open
the door to the temperature of the motor recovery after to continue.
J29 parking brake feedback detection: ON / OFF elevators set zero speed brake after the brake is released.
J30 pulse error correction: base station ON / OFF setting elevator midrib count mistake back lower station
correction.
J31 outbound signal periodically refresh: ON / OFF settings from time to time to refresh the outbound
signal.
J32 terminal position correction floor: ON / OFF setting the elevator to reach the end station after the
automatic correction of floor.
J34 Gate location counting correction: ON / OFF elevator running through a door area automatic
correction lift position.
J35 floor fault display: ON / OFF setting elevator fault information in the floor display panel display.
J36 Elevator reversing elimination: ON / OFF set elevator reversing car instruction elimination.
K elevator tune parameters
49
Schneider®
K03 magnetic separation sheet pulse number: Elevator leveling pulse elevator learning acquisition
display value of 5MM magnetic separation sheet length pulse number.
K04 well self learning: elevator shaft signal and system data set after the completion of the installation to
the elevator stopped at the lower station level position, the elevator switch to automatic elevator
door after self‐test, the K04 menu settings for ON confirmation, the elevator will be self learning
speed automatically run the first end station to meet strong reducing signal when X22 began to
decelerate, arrived at the upper station door zone after stop running automatically completed well
self learning.
K05 base station setting: set the lift lock staircase or automatic waiting station.
K06 first fire layer set: set elevator first fire station.
K08 top station: Elevator top station to set values for the shaft self‐learning automatically wins, does not
need to be set up.
K09 the first elevator floor: Elevator no operation instruction automatically returns the elevator floor.
K12 main access door set: set elevator main entrance door floor.
K13 side access door set: set elevator side access door floor.
K14 floor display settings: setting the absolute floor corresponding display content.
L monitoring menu
L05 output current: monitoring the operation of the motor output current.
50
Schneider®
L09 intermediate loop DC voltage monitor machine: the value of DC voltage intermediate circuit.
L12 cumulative running time: monitor machine from the first power began to calculate the total usage
time.
L13 cumulative running time: monitor machine operation records the total number of times each.
L16 encoder pulse rate of change: monitor machine work encoder pulse rate monitoring encoder signal
interference.
L18 elevator current position : displays the current location of the pulse number of elevator.
L19 RUN‐IN distance: display elevator automatic leveling layer when the distance, if the J04 is set to zero
the value is automatically set to zero.
L20 V1 deceleration distance: display multiple speed curve of V1 speed deceleration distance pulse.
L21 V2 deceleration distance: display multiple speed curve of V2 speed deceleration distance pulse.
L22 V3 deceleration distance: display multiple speed curve of V3 speed deceleration distance pulse.
L23 V2 allows the deceleration distance: multistage speed V2 speed allows the deceleration distance
pulse.
L24 V3 allows the deceleration distance: multistage speed V3 speed allows the deceleration distance
pulse.
51
Schneider®
L25 start V2 speed distance: multistage fast when starting V2 speed required distance pulse.
L26 start V3 speed distance: multistage fast when starting V3 speed required distance pulse.
L27 self‐learning floor distance: display elevator self learning 1 buildings to 64 Buildings ( F01‐F64 )
floor pulse number.
L28 pulse correction times: display elevator running pulse automatic correction times record.
L29 pulse error maximum: demonstration elevator running pulse in the maximal error.
L30 arrived at high speed change rate: display elevator express running at high speed in running speed
record high.
L31 arrived at low speed high speed elevator operation display change: express to low‐speed strong
change speed record.
L32 B104 internal parameters: B104 internal parameters, the factory value of 2 could not be changed.
L33 B105 internal parameters: B105 internal parameters, the factory value of 5 could not be changed.
L34 D201 internal parameters: D201 internal parameters for the system automatically calculates
machine input with the highest frequency value.
L35 angle deviation correction component: display machine running angle deviation correction
component.
L36 voltage deviation correction component: display machine running voltage deviation correction
component.
M leveling adjustment
M01 eveling adjustment: if the elevator up records of each floor level deviation value is consistent, just
put the M01 leveling adjustment ( the value defaults to the magnetic separation sheet half the
length of the home district ) level position adjustment is good (no need to enter M03 parameter
layer adjusting each floor level location value).
M02 eveling adjustment: if the elevator running down records of each floor level deviation values, only
the M02 leveling adjustment ( the value defaults to the magnetic separation sheet half the length of
the gate area ) under a flat layer position adjustment is good (no need to enter M04 parameter
adjustment of each floor flat layer by layer layer position value ).
M03 foor level setting: enter M03 floor level settings menu, the value defaults to 0, ( F02 ) from the first
floor to mm as a unit to adjust each floor on the floor. Elevator up ( high ) super flat layer is set
52
Schneider®
when the value is negative ( ‐ ) number; the uplink ( low ) less flat layer set to positive ( + ); setting
principle for more than the value, not to owe a flat layer, increase the value of.
M04 foor level setting: enter M04 floor level settings menu, the value defaults to 0, ( F01 ) from the first
floor to mm as a unit to adjust each floor under the flat layer. Elevator down ( low ) super flat layer
is set when the value is negative ( ‐ ) number; the uplink ( high ) less flat layer set what is positive
( +); setting principle for more than the value, not to owe a flat layer, increase the value of,
N call instruction
N01 call floor instruction: in one machine operation screen given 1 to 63 floor of the call instruction on
floor.
N02 call floor instruction: in one machine operation screen given 2 to 64 floor of the call instruction on
floor.
N03 within selected floors instruction: in one machine operation screen given 1 to 64 buildings within
the selected floor instruction.
O I / O monitoring
O01 controller input monitoring: one input signal monitoring points of an input signal, a white.
O02 controller outputs: one machine output signal monitoring, total output signal point.
O03 expansion board monitoring: car top board (PM709 ) and select board (OCAL‐08C ) input signal
monitoring.
P fault record
P01 drive current fault record: one machine drive current fault recorder can record 6 fault current. Each
fault recording information for classification:
N: for fault recording serial numbers;
C: number of repetitions for fault;
T: the first fault occurs when the cumulative running time.
P02 drive current fault: drive current fault information only for the fault status information, when the
drive is a new fault occurs, the fault will be refreshed. Fault state information:
Supplementary information: a segmentation fault information;
Frequency command: fault system given frequency command;
Output frequency: fault occurs when the machine output frequency;
Feedback frequency: fault occurs when the system detects that the feedback frequency;
Output current: fault occurs when the machine output current;
Instruction: the instruction torque breakdown torque;
Output voltage: fault occurs when the machine output voltage;
53
Schneider®
P03 Elevator fault record: elevator operation due to the external input signal abnormalities or function
timeout fault condition.
E3: Can ʹ t Find the Leveling Point ( elevator gear reducer after more than 10 seconds is not detected
signal gate area )
Original: door zone due to damage, flat plate insertion depth of less
Solution: replace the door zone, flat plate at least insertion switch 2 / 3
Recovery: floor display, microcomputer recording fault, maintenance reduction.
E4: Can ʹ t Find the Deceleration Point ( not detected deceleration point )
The original for each: ( bistable ) switch fault, each magnet position error; frequency divider card output
pulse error or interference, the parameter F25 setting error;
Solution: check for speed switch, through the main controller display interface effect of pulse signal
changes is normal, adjusting the F25 settings ( default 13S )
Recovery: the floor indicator can display, microcomputer recording fault, this failure may be
accompanied by E14, electric
Ladder to the end station to correction recovery after operation.
E5: Up Limited Switch Opened ( a disconnect, uplink downlink uplink emergency stop, can, canʹt start)
Original: Elevator encounter because of limit
Solution: theʺ TESTʺ run down
Recovery: the floor indicator can display, microcomputer recording fault
E6: Down Limited Switch Opened ( lower limit disconnect downlink, uplink downlink emergency stop,
54
Schneider®
E7: Deceleration Switch Error ( when the lift starts multilayer speed, if the short station Shun to strong
change is disconnected, the elevator
Emergency stop, this fault is generally strong switch misoperation caused by )
The original for each speed changing switch: switch fault location error
Solution: check the speed control switch, and the replacement of
Recovery: floor display does not show, the microcomputer fault, elevator emergency stop will slow flat
layer
E10: Brake Error ( band‐type brake feedback fault; elevator running brake not open, the elevator to
deceleration level, cannot start)
Original: brake detection switch damage. Check whether the normal line. The error of parameter setting
( without this function and the parameter is set )
Solution: replacement of damaged components. Reset the controller parameters
Recovery: floor display and record the fault, maintenance or recovery after power cut.
E11: Run Time Error ( operation timeout, elevator running over F25 menu restrictions, or layer sensor
signal does not change. )
Original: changes due to floor protection time F25 is too short or broken crawling G11 time is too long;
canʹt find the door zone or zone signal loss; flat plate is inserted into the door zone is not deep enough,
the switch can act reliably; the deceleration point action is not normal
Solution: adjust the floor protection time F25&G11 value; check the door zone and line; inspection flat
plate is inserted into the door zone deep enough; check for speed signal and switch is normal
Recovery: the floor indicator can display, microcomputer recording fault, maintenance or recovery after
power cut.
55
Schneider®
E13: Door Contact not Release (opens the door for more than 3 seconds, the door open, the elevator can
not start)
The original because of: door machine without electricity or manual door machine wiring error, open /
close the door controlled relay malfunction, check the PM709 gate control signal
Solution: open the door machine, a power switch and a bit automatic status; check the door machine
wiring; check relay ( PM709 )
Recovery: the floor indicator can display, microcomputer recording fault, lock off or hit recovery after
overhaul.
E14: counting error, the elevator floor and calculating pulse error than shorter station Decal distance
The original due to: (1) counting error, may be disturbed, the elevator can not normally docked in a level
position, sometimes E2, E4, E9 fault may cause the alarm.
( 2) the gate area sensor interference (usually a photoelectric switch )
( 3) the car skid
When the E14 fault occur may appear at the same time, E20, E15, E22 fault, the counting error is caused,
first deal with the counting error can solve the fault.
Solution: ( 1) examining the inverter grounding, microcomputer pulse check whether the wiring is
correct, shielding line should be single end is connected with the grounding end are frequency converter.
( 2) examining the inverter PG output is normal.
( 3) in the region of the door sensor and filter.
( 4) processing the car skid
If it can not solve the problem, please self learning
Recovery: floor display does not show, the microcomputer fault, elevator flat layer will be single speed
regression lower station.
E16: in E22 fault, the elevator at the limit but end station signal is not correct, the limit signal when
disconnected, the end station for speed switch to disconnect
Original: short for speed changing switch station due to damage or installation does not reach the
designated position
Solution: replace the switch; check installation relative size is correct
56
Schneider®
E17: not
E18: the direction of output signal for 4 seconds after the detected signal converter
Original: inverter parameter settings for error; terminal or terminal loose; elevator running a main
contactor shake off
Solution: examining the inverter and parameter; check the wiring and the terminal; observation elevator
running a main contactor jitter is disconnected, such as inspection safety loop or whether the door lock is
instantaneously disconnect condition
E19: not
E20: floor records to strong switch inconsistencies, the elevator is not in the end station and switches off
Original: speed control switch for damage; speed control switch is not installed properly; door zone
switch malfunction; counting error
Solution: check for speed switch, modelled on the E14 fault examination counting error
Recovery: floor display does not show, the microcomputer fault
E21: mechanical brake feedback set point adhesion test, if the mechanical brake feedback point adhesion
times this fault.
Solution: check switch,
Recovery: the floor indicator can display, microcomputer recording fault, feedback not adhesion failure
recovery.
E22: floor records to strong switch inconsistent, elevator in the end station and change ceaselessly open
Reason: speed control switch damage; counting error
Solution: check or speed control switch, modelled on the E14 fault examination counting error fault
display and restoring method; the fault is not in the layer of display, but the microcomputer fault.
E24: when the door lock is switched on for more than 3 seconds, close spacing without disconnecting the
computer will record the fault, then E24, and in layer showing the
Fault signal, and reverse the door, if there is no no. 2 door machine, door machine No. 2 closed limit
input must be in place.
State.
Original: threshold for damaged switch; limit switch adjustment is not in place; frequency door machine
parameter setting error.
Solution: to check or replace the switch switch position; adjust; check frequency door machine
parameters.
Recovery: to repair or lock off for more than 2 seconds or close spacing after disconnection can reset the
57
Schneider®
fault.
E25: advance the function of opening the door, not detectedʺ safety zoneʺ input point
Original: loose wiring or error; the security module is damaged
Solution: check the wiring; examination security module
Recovery: the fault in the layer of display, the computer records fault; signal recovery to reset the fault.
E26: not
E27: advance the function of opening the door, not detectedʺ contactsʺ input
Original: loose wiring or error; the gate area signal fault; the security module fault
Solution: check the door zone action is accurate, whether the installation in place; check whether the
normal work of the security module
Recovery: the fault in the layer of display, the computer records fault; signal recovery to reset the fault.
E28: advance the function of opening the door, not detected frequency converter speed input
The original cause: inverter parameter error or the damage of components
Solution: check the parameters of converter and speed monitoring signal
Recovery: the fault in the layer of display, the computer records fault; signal recovery to reset the fault.
E29: not
E30: in Russia mode safety window is opened, the elevator cannot take the car, security window is closed
to maintenance position
Original: safety window switch due to damage or wiring problems; artificial operation after forgetting to
reset
Solution: check the wiring or replace the switch; overhaul reset
Recovery: the fault in the layer of display, the computer records fault; in the maintenance state can reset
the fault.
E31: level switch signal adhesion fault, shows the running signal 3S Zhong Ping layer signal without
action.
Original: level switch level switch movement is not accurate; damage; wrong wiring, short circuit
phenomenon
Solution: flat plate at least insertion switch 2 / 3, please read theʺ Handbook of electrical installation
practiceʺ. Replacement switch circuit check;
Recovery: the floor indicator can display, microcomputer recording fault, only after maintenance can
reset the fault.
E32: motor overheating, the elevator to keep the doors open is not running
Original: motor overheating; detection switch or circuit problem
Solution: in this fault please contact with the manufacturers
Recovery: floor display does not show, the microcomputer fault, the motor cooling recovery after the
58
Schneider®
fault.
E34: use the open door function security module signal does not release the door zone.
E38: screen action time beyond the menu F26 setting time
E100 OC1 / speed of flow in acceleration and deceleration process, drives the output current exceeds the
threshold (about 200% of the rated current load excessive ), deceleration time is too short, the use of
special motor or the maximum power above the motor, drive the output side short circuit, grounding
E101 OC2 / steady velocity of flow in steady speed process, drive the output current exceeds a threshold
(about 200% of the rated current ) load is too large, the use of special motor or the maximum power
above the motor, drive the output side short circuit, grounding
E102 OV1 / deceleration of overvoltage reducer, OV or DV > OV threshold speed too fast, braking resistor
is too large or not connected, a brake module failure
59
Schneider®
E103 OV2 / a deceleration of overvoltage not slowing down, OV or DV > OV threshold high input voltage,
inverted overload, braking resistor is too large or not connected, a brake module failure
E104 OC3 / instantaneous overcurrent module overcurrent and thermal accelerated too, overload, motor
and inverter does not match
E105 UV1 / DV < LV threshold low voltage low voltage power supply, a contactor disconnection, or input
phase
E106 OC4 / module over current module detected excessive output current overload or parameter setting
bad
E107 OV3 / power supply voltage abnormal power supply voltage high power supply voltage exceeds
the Braking threshold
E108 GF / on leakage average leakage current > threshold motor of low impedance
E109 OL3 / overload of the transducer reaches the output current limit lasts more than 10S overload,
motor and inverter does not match
E110 OH2 / other overheated OT small radiating fan failure, a charging resistor overheating, overheating
( external motor, brake resistor ), a main contactor disconnecting or bad contact
E111 BER1 / internal brake unit abnormal running before the open or not open brake braking unit and its
driving circuit fault
E112 BD / motherboard failure occurred in 1 timeout reset ( crash ) subject to strong interference or
motherboard adverse
E113 BER1 / motherboard failure 2 EEPROM data read / write fault check error
E114 BER2 / motherboard failure 3 PG card communication fault / absolute type encoder communication
fault
E117 CE / current transformer checking fault initial current is not zero under strong interference or
motherboard adverse
60
Schneider®
E121 EF / reverse at the same time input forward instruction (X1 ) and reversal instruction (X2) input at
the same time 0.5 seconds
E122 LE / self learning failure code display to alarm when the auxiliary drive, or auxiliary information in
detail, with reference to the auxiliary code table
E126
E127 BER3 / motherboard failure 2 EEPROM data anomalies ( word is not correct. )
E128
E129
E131 OPE1 / parameters exceed the range EEPROM data read out the scope of illegal EEPROM write or
motherboard version of the software is more variable
E132 OPE2 / parameters unreasonable (P02 ) auxiliary code displayed on the driver when the alarm, or
auxiliary information in detail, with reference to the auxiliary code table
E133 OPE3 / parameter settings conflict or repeat ( P02 ) auxiliary code displayed on the driver when the
alarm, or auxiliary information in detail, with reference to the auxiliary code table
E134 OPE4 / ( V / F ) the error of parameter setting did not press D2.01 > E1.01 > E1.03 > E1.05,
E136 OPE6 / multifunctional terminal function set conflict did not follow the multifunctional terminal
61
Schneider®
E137 OPE7 / simulation terminal function set conflict an analog input quantity is a function reference
E150 OH1 / module overheating RTH > threshold radiator temperature, cooling fan failure
E151 PF1 / input phase average DC voltage fluctuation value > threshold load is too large, motor and
inverter mismatch, input phase, the power capacity of small, instantaneous power interruption
E152 PF2 / output phase loss after excitation time motor feedback current can not reach the set value of
the 50% motor broken or wrong type motor
E153 OS1 / speed motor speed exceeds the overspeed protection threshold setting value and maintains
the overspeed protection time over time command speed is too high, the speed control of big deviation,
setting value is not appropriate
E154 OS2 / stall motor speed deviation exceeds a speed deviation protection threshold value set and
maintained the excessive speed deviation protection time over time. The load is too large, the
acceleration time is too short, the load is in a locking state setting value is not appropriate
E155 PGO / encoder disconnected average torque command over monitoring threshold pulse number
changes less than 2 encoder disconnected
E156 PGE / phase error average torque command over monitoring threshold torque command and
feedback frequency reverse phase and phase of the motor encoder instead
E157 OL2 / torque average torque command exceeds the threshold overload, or parameter is not set
correctly
E158 OL3 / maximum current output current reaches the maximum value and the maintain time
overload, motor
E159 OL1 / motor overload motor thermal overload overload, motor and inverter does not match
62
Schneider®
E161 torque fluctuation average torque command fluctuation value exceeds the threshold
E163
E164 encoder pulse fluctuation speed per 10ms changes of pulse number difference larger than the value
encoder interference or poor installation
E165 JE / Z phase correction failure no Z signal, Z signal interference, encoder line number or pole
number setting error
E166 zero servo fault zero servo but position deviates from the overload, zero servo parameter setting is
not suitable
The E167 terminal signal error illegal load switch combination
E200
E201 cannot reach the test current electrical disconnection or motor parameter setting error
E203 cannot achieve the testing speed motor axle load is too large, the motor error of parameter setting,
the encoder lines are positive solution.
E204 encoder phase correct encoder signal abnormalities, abnormal encoder connection, PG card
anomaly
63
Schneider®
E212 pole position learning not learning when the current is too small, the encoder to slip, axial load is
too large or negative inconsistent
The E213 pole static learning encoder is not correct
4.3 P02 driver fault current corresponding to the auxiliary code and state table
E132
1 the upper frequency limit of % less than the lower frequency limit %
2 undefined capacity code
3 no‐load current B16 is greater than or equal to the motor rated current B12
4 no‐load current larger than 60% B16 inverter maximum output current
5 motor a line resistance B18 is much smaller than the reasonable value
6 motor a line resistance B18 setting unreasonable ‐ motor rated current B12 * motor a phase resistance >
motor rated voltage B13
7 motor power factor calculation is not reasonable. Related parameters: the motor rated power rated
current
B12 B10, motor, motor a line resistance B18, torque compensation of motor iron loss
8 no‐load current is too small
9 parameter is not reasonable, rated torque current instruction 0
10 resistance by the no‐load current is greater than the rated voltage
11 format error code 1 ( speed )
12 format error code 2 ( position instruction )
13 format error code 3 (PID directive )
14 stage is not properly defined electronic cam
15 communication port definition error
16 Encoder line number does not conform to Z phase correction request / /
17 Pulse input can be used as a PID bias input
18 Escalator mode automatic lubrication stop time is longer than the cycle
64
Schneider®
E122 1 Can not achieve the testing current motor disconnection, motor parameters setting error
2 The test results are not reasonable
3 Can not achieve the testing speed of motor shaft, motor overload error of parameter setting, coder line
numberwrong
65
Schneider®
66
Schneider®
off)
E126
EEPROM Data
E127 BER3/Main Board Error 2
Error(rection failed)
E128
E129
E130 UV/ Low control power
EEPROM data reading Unleagal EEPROM write in or main board
E131 OPE1/Parameter out of range
out of range version changed
( P02 ) Assist code display on driver
E132 OPE2/ Parameter not rigt board, or in assist information, please
reference assist code form
E133 OPE3/parameter conflict or ( P02 ) Assist code display on driver
67
Schneider®
68
Schneider®
value, torque
instructions and
feedback frquency
reverse
Average torque
E157 OL2/ Over torque instruction over rated Overload, or data setting not right
value
Reach maximum
output current and
E158 OL3/Max current Overload, motor rotation track
maintain a period of
time
E159 OL1/Motor overload Motor over heated Overload, motor and inverter not match
External fault terminal
E160 EE/Outer Error
effective
Average torque
E161 Torque wave normal fluctuation more than
rated value
E162 CCE/communication cable cut
E163
Steady speed every 10
ms pulse changing
E164 Encoder pulse faulty Encoder interference or installation bad
different bigger than
rated value
No Z phase signal, Z phase signal
E165 JE/Z phase rectify failed interferenced, encoder line number or
motor pole setting error
Zero servo but Bear is overweight, zero servo parameter
E166 Server Faulty deviation from the setting not appropriate
position
Illegal weighing switch
E167 Terminal Signal Faulty
combination
E168 POE1/position not exact
E169 POE2/position rectify failed
E170 PID1/PID feedback lose
Self‐Learning Error (Note: Self‐learning has Error pleae reference to E100‐E199)
E200
Motor wire cut, or motor parameter
E201 Can not reach test current
setting wrong
E202 Test Wrong
69
Schneider®
70
Schneider®
71
Schneider®
72
Schneider®
Methods: integration is in an operating state, has not set parameters, please run enable undo integration
after setting.
Integration of startup password, OP1 / OP2 has set the encryption or decryption decryption errors but
not when, the corresponding parameters of the system will not be changed, please enter the correct
password to decrypt. Note: forget the password, please contact the supplier.
Setting value of a parameter is abnormal, please refer to the inverter parameters menu P02
( supplementary information ) values for display, queryʺ failures corresponding auxiliary code tableʺIn 3,
The motor is not rotated, please carry out the following processing steps.Reason 1, motor parameter
setting error
73
Schneider®
Motor parameters are incorrect or PG wrong equal causes motor does not rotate. Please correct
connection, set the basic motor parameters, and according to the actual conditions of the corresponding
Frequency command than F30 ( zero speed threshold frequency ) set the frequency value is low, the
motor can not rotate. According to the actual need to change the parameters of a given zero speed
The load is too large. Integration of preventing a stall function and automatic torque increasing function.
Acceleration or the load is too large, will exceed the motor in response to the limit, please extend the
acceleration time ( C02 / D01 ), reduce the load. In addition, please also consider increasing motor and
machine capacity.
The motor rotates in the opposite direction is wrong wiring of motor output line. If the integration of the
power phase sequence U, V, W and motor power supply phase sequence U, V, W connected correctly, it
is to command the motor forward. Forward direction by a motor manufacturers and models decision. So
please confirm the motor specifications, rotation direction selection instead, please switch U, V, W / B22
Motor output torque, acceleration time is too long, please carry out the following processing steps.
Set parameter E19 / E20 ( torque limit), due to failure of output torque of the torque upper limit above,
74
Schneider®
will lead to insufficient torque, acceleration time. Please confirm whether the appropriate torque limit.
The parameter F12 ( operation stall prevention threshold % ) setting too low a value, will cause the
output torque prior speed reduce. Please confirm whether the appropriate setting value.
Not the implementation of self learning, can not achieve the vector control performance, please carry out
The rotation of the motor exceeds frequency instruction, please carry out the following processing steps.
In 1 J04 set to 2 digital quantity with crawl docked curve when the frequency command terminal input
signal is abnormal
7, use no sensor vector control mode, high rotation speed control precision is too low, the motor rated
voltage high.
The integration of the output voltage of the maximum value is determined by an input voltage. When the
vector control calculation results of the output voltage instruction value higher than the integration of the
output voltage when the maximum of speed control accuracy, reduce. Please use the rated voltage value
of the motor ( motor vector control special ).In 8, the motor speed is slow
Motor speed slow, please carry out the following processing steps.
Phenomenon: if connected with the braking resistance deceleration time is too long
Please confirm the parameter C04 / D02 ( deceleration time ) setting is appropriate.
75
Schneider®
The normal parameters, also did not have fault alarm, said motor power limit has been reached. Please
Set parameter E19 / E20 ( torque limit), due to failure of output torque of the torque upper limit above,
will lead to insufficient torque, acceleration time. Please confirm whether the appropriate torque limit.
Due to the order to bad. One machine in the reduction after the end of 0.5 seconds for the DC braking
state (the factory settings). In order to keep the brake, the parameter F30 frequency detection value,
setting the output frequency to frequency detection value above OFF, reach detection value for ON. The
value is set larger leads to stop when the slip, please change within 0.5Hz.In 9, motor overheating
The motor is overheated, please carry out the following processing steps.
Motor load is too large, the actual torque in exceed the motor rated torque under long time operation, the
motor will cause overheating. In the motor parameters in the table, have documented continuous rated
project beyond the short time overload project. Please reduce the load or extension acceleration time. In
Motor rated value is in the rated ambient temperature within the decision. In exceeding the rated
ambient temperature, continue to maintain the rated torque operation, will lead to the damage of the
motor. Please send the motor environmental temperature was reduced to a rated value.
In the integrated output terminal is connected on the motor, integrated switch and a motor winding can
produce impulse voltage. Usually, the maximum output voltage is about 3 times the input supply
76
Schneider®
Using phase impulse withstand voltage than the largest impact high voltage motor. 400V integration, use
Are 4 reasons, in vector control mode, not the implementation of self learning
Not the implementation of self learning, can not achieve the vector control performance, please carry out
self learning or calculated according to the setting of motor parameters.10 to start the machine will
By integration of the harmonic interference, please carry out the following processing steps.
L downregulation of parameter B03 ( carrier frequency ) of the set value. Because of reducing the internal
2 in one machine power input side set the input side noise filter.
3 in one machine power output side to set the output side noise filter.
4 because the waves can be made of metal shielding, please cable sheathed on the metal pipe, and one
5 please make sure the machine body and a motor good grounding.
6 please send the main circuit and control circuit wiring separation line.11 operating one machine
leakage breaker
Due to the switch motion is in the integration of interior, it causes the leakage current. Excessive leakage
current will cause the leakage breaker and cut off the power supply. Please change the leakage current
detecting value higher breaker ( sensitivity current more than 200mA, the action time of more than 0.1
Downregulation of parameter B03 ( carrier frequency ) of the set value in some extent effect.
In addition, if extended the length of the wire, it will lead to the increase of a leakage current.
12 mechanical vibration
Mechanical vibration, please carry out the following processing method.
1 mechanical system inherent frequency and carrier frequency resonance
A separate motor movements when no problem, but the connection machine after mechanical screeching,
said mechanical system inherent frequency and the integration of the carrier frequency to produce a
resonance. Please adjust the parameters of B03 ( carrier frequency ) of the setting value, avoid resonance
frequency.
77
Schneider®
Not the implementation of self learning, can not achieve the vector control performance, please carry out
self learning or calculated according to the setting of motor parameters.
Elevator traffic operation need to mechanical parts installed, to ensure that each layer door installed in
the locking device is working properly, the electrical part installed in place to meet the system operating
( 1) connected to the control cabinet main power supply, motor power line, connects the encoder, brake
78
Schneider®
( 2) arranged the car top junction box and cable, upper and lower hoistway cables and the corresponding
junction box. Ensure the safety of system circuit of normal and each part of the emergency stop button
function, a hall door / car door lock loop is switched on and the function of the normal upper limit and
the lower limit, the signal is switched on. ( refer to control cabinet drawings attached )
( 3) with a multimeter and an insulating sheet detecting the electrical properties and insulation resistance
of normal.
( 4) the system parameter settings: set A simple menu table under the corresponding parameter values
B04 motor control mode B05 encoder type B06 encoder pulse B10 motor rated power
B11 pole number B12 motor rated current B13 motor rated voltage Motor rated frequency B14
B15 motor rated rpm B16 no‐load current B22 motor rotation J04 docking methods
direction
Learning OP3 = 1 confirmed after the system will automatically close output contactor is used for self
learning, is completed automatically save parameters and release contactor. Motor parameters upon
79
Schneider®
completion of study can enter the idle running, if the motor output in opposite directions to get B22
motor rotation direction is set to ON; if the motor does not rotate or low motor speed not to set the
parameters and the operating current is too big to check the encoder signal / input sequence, and the B08
encoder sequence set to ON test whether can be the normal operation of traffic.
Note: if the drive parameters adjustable parameter adjust unreasonable or overrun confused when the
OP4 is set to 1 drive asynchronous initialization, after power failure automatic parameter set according to
the parameters of asynchronous motor complex restoring factory settings. Repeat 4.1.1 and 4.1.2
If it is a permanent magnet synchronous motor in addition to 4.1.2 must satisfy even the encoder angle
self learning can take the car. In the OP3 self learning menu can choose OP3 = 5 can be automatically
completed all the parameters of electric static self learning; or can be set to OP3 = 1 to study electrical
resistance between the wires and the leakage reactance %, to set the OP3 = 3 motor learning pole position.
Learning OP3 = 5 confirmed after the system will automatically close output contactor is used for self
learning, is completed automatically save parameters and release contactor. Motor parameters upon
completion of study can enter the idle running, if the motor output in opposite directions to get B22
80
Schneider®
motor rotation direction is set to ON; if the motor does not rotate or low motor speed not to set the
parameters and the operating current is too big to check the encoder signal / input sequence, and the B08
encoder sequence is set to ON. Off system power, to self‐study process test whether the normal operation
of traffic.
Note: if the drive parameters adjustable parameter adjust unreasonable or overrun confused when the
OP4 is set to 0 drive synchronous initialization, after power failure automatic parameter set according to
the synchronous motor parameter complex restoring factory settings. Repeat 4.1.1 and 4.1.3 operation is
good.
At idle normal, well signal installation, wiring is completed, further check switch is correct and can be
self learning
The elevator to overhaul and operation to the two end station hit pressure under the strong change / limit
check switch signal action is normal. And monitoring system of O01 menu monitor limit X15 / X16 ( such
as the system does not install the upper limit and lower limit of price signals do not need ), strong for the
X20 / X22, X17 / X21 under strong for the normal movements.
Shaft switch confirm good, again confirm L18 elevator current location display pulse is normal ( elevator
maintenance when the number of increments, descending numerical decline ), otherwise the elevator
traffic to run when E9 fault display, this time as long as the B23 system direction is set to ON system
Elevator maintenance operation returns a floor level position, and the elevator to automatic state into the
81
Schneider®
K elevator debugging parameters to set K04 to ON after confirmation. Elevator with self learning speed
automatic uplink, collision to the low‐speed strong switch ( X22 off signal ) when elevator gear reducer,
reaching the top door zone ( X14 level signals are switched on ) when elevator automatic parking
complete self learning system will automatically record all floors of the hoistway information.5.2.3 Flat
Leveling adjustment:
1. first lift upward or downward to a certain fixed floor, such as the 5 floor, the elevator upward or
downward arrives at the floor, parking position with repeatability, and from the leveling error no more
than 3cm. If the car does not have the repetitive, for adjusting the frequency converter gain, if the leveling
error exceeds 3cm, need to move the layer separated from the magnetic plate and the flat layer position,
2 new self learning. When the elevator reaches a fixed layer, parking has the duplication and the error is
The elevator from the lower station began to express run each layer are sequentially to the top and
Enter the M03 floor level settings menu, the value defaults to 0, ( F02 ) from the first floor to mm as a unit
to adjust each floor on the floor. Elevator up ( high ) super flat layer is set when the value is negative ( ‐ )
number; the uplink ( low ) less flat layer set what is the number of ( + ).
Example: two upstairs flat layer ( high ) super flat layer 5mm, two floor level to set up F02 : ‐ 0005
On the second floor level ( low level ) in 7mm, is on the third floor level to set F03: + 0007
Setting principle for more than the value of reduction, not to owe a flat layer, increase the value of.
Example: to reach the 5 floor, more than 5mm ( high ), then the value is set to 5, the second is still more
than 2mm ( high ), this value is set to 5‐2 = ‐ 7, if not second ( low ) to 1mm, then the value is set to 5+1 = ‐
82
Schneider®
4.
The elevator from the upper station began to express run each layer are sequentially reach the first layer
Enter the M04 floor level settings menu, the value defaults to 0, ( F01 ) from the first floor to mm as a unit
to adjust each floor under the flat layer. Elevator down ( low ) super flat layer is set when the value is
negative ( ‐ ) number; the uplink ( high ) less flat layer set what is positive ( + ) number.
Example: a downstairs flat layer ( low ) super flat layer of 5mm, a floor level to set up F01 : ‐ 0005
Four downstairs flat layer ( high level ) in 7mm, four floor level to set F04: + 0007
Setting principle for more than the value of reduction, not to owe a flat layer, increase the value of,
Example: downward to reach the 5 floor, more than 5mm ( low ), then the value is set to 5, the second is
still more than 2mm ( low ), this value is set to 5‐2 = ‐ 7, if second times before ( high ) 1mm, then the
If the elevator up records of each floor level deviation value is consistent, just put the M01 leveling
adjustment ( the value defaults to the magnetic separation sheet half the length of the home district )
level position adjustment is good (no need to enter M03 parameter layer adjusting each floor level
position value ).
Example 1: as a 8 layer station electrical building from the 2 floor to the 8 floor of each layer of the upper
flat layer ( high ) super flat layer 20mm, with mm as unit to reduce 20 M01 flat layer parameters.
Example 2: as a 8 layer station electrical building from the 2 floor to the 8 floor of each layer of the upper
flat layer ( low ) owe a flat layer of 15mm, with mm as unit to a flat layer to adjust the parameter M01
increases by 15.
83
Schneider®
If the elevator running down records of each floor level deviation values, only the M02 leveling
adjustment ( the value defaults to the magnetic separation sheet half the length of the gate area ) under a
flat layer position adjustment is good (no need to enter M04 parameter layer adjusting each floor level
position value ).
Example 1: as a 8 layer station electrical building from the 1 floor to the 7 floor of each layer of the lower
flat layer ( high ) less flat layer 20mm, with mm as unit to adjust the parameter M02 increases in level 20.
Example 1: as a 8 layer station electrical building from the 1 floor to the 7 floor of each layer of the lower
flat layer ( low ) super flat layer 15mm, with mm as unit to a flat layer of adjust the parameter M02 by 15.
Flat layer after adjustment, the microcomputer can be saved if changing parameters, microcomputer
when parameter can be saved to another computer, without the need for well self learning, only the lift
Reasonable adjust control system timing and driving part of ASR control performance can obtain better
The elevator high speed vibration: E11 speed proportional gain is increased, E14 high speed integration
The lift at low speed vibration: E12 low speed proportional gain is increased, E15 low‐speed integral time
constant or small.
The elevator starts up a vibration: E13 starting proportional gain integral time constant is increased, E16
starting up or down.
But the proportion gain adjustment is too large, the response characteristics of ultra sharp vibration
caused by the elevator when the corresponding proportional gain reduction, or increase the
corresponding integral time to improve the operation of the elevator. If the motor to run when a ringing,
the elevator car a low‐frequency vibration, please B03 carrier frequency is reduced to accommodate the
84
Schneider®
motor characteristics can reduce motor noise and vibration of the car.
High speed E14 integral time 100100 ~ 500 ( generally not adjustable )
E15 low velocity integral time 10050 ~ 300 ( generally not adjustable )
The elevator start / stop when the slide car ( permanent magnet synchronous motor )
A starting position locking ring E01 parameter should be set to ON motor on electric operation prior to
B zero velocity position to lock the gain of E02 parameters increase ( range 1 ~ 3 ) can improve the zero
speed lock when the response characteristics to prevent starting when the slide car.
C adjusts starting DC lock time G02 / G09 ( range 0.5 ~ 1.5 ) can improve the starting from setting
characteristics.
D G04 ( DC adjust parking lock time regulation range 0.5 ~ 1 ) can prevent the elevator parking slip.
The lift starts / deceleration when the sensation of weightlessness significantly too.
85
Schneider®
A starting DC lock time G02 and output curve time G09 set inconsistent values.
B using a smart S curve acceleration and acceleration time of C01 C02 / deceleration deceleration time
Small; the use of multistage speed S curve acceleration D01 and time D03 / D04 degree corner or
C to adjust the current gain value of the E21 parameter can change the current loop control characteristics,
Sex.
86
Schneider®
18 LCD keypad
19 Communicate with Computer
20 Record Error History
21 Hositway Parameter Self‐learning
22 Service Floor Setting
23 Floor Indicator Signs Easy Setting
24 Manual Operation
Car Button Flash with Hall button flashing when Manual
25 Operation
26 Car Call answer and Car call cancel
27 Hall Call Answer And Slow Down Cancel
28 Independence Running
29 Dot‐matrix Floor Indicator
30 Arrow Running of Indicator
31 Auto Amend of floor position signal
32 Lock Lift Service
33 Emergency Return Under Fire Station Function for Non‐Firemen Lift
34 Fireman Operator Optional Function for firemen lift
35 Voice Announcement Optional Function
36 Safety edge protection
37 Overload Alarm and protection
38 Anti‐Nuisance of light‐load Optional Function
39 Protection when Reverse Running
40 Sliding Protection
Reverse direction hall call answer when the lift in farthest
41 position
42 Force Slow Down At End Side
43 Auto Door re‐open when door close error
44 Protection when inverter error
45 WDT Protection of Main CPU
46 Area(Building) Monitoring Optional Function
Optional Function, by MODEM and Telephone
47 Remote Monitoring wire
48 Duplex Running Optional Function
49 Group Control Optional Function
50 Rush Hour Service Optional when using group control
51 Parking Separated Only for group control
Need to match with speed measure encoder,
52 Elevator Running Curve Optional Function
87
Schneider®
88
Schneider®
89