You are on page 1of 7

Distribution Automation Solutions

 Intelligent platform for future MV


application
 Truly modular design, extensive
hardware options and flexible
adaptation
 Feeder, motor or transformer
protection functionality
 Large customizable HMI with single
line diagram
 Freely configurable alarm LEDs
FXD620 is a series of powerful, and function keys
communication-enabled digital  Large flash memory for logs,
multifunctional relays with up to 12 events and fault recording
measurement inputs. They can be
used in automatic control systems as  Combined optional arc-flash
comprehensive protection devices for detection and high-speed solid
MV bays (incoming, bus coupler, state output relays (SSR), provide
outgoing, transformer, engine, fast tripping and security
measurement, etc.), and small
 Comprehensive set of
generators. They offer comprehensive
communication protocols, including
and cost effective solution for
IEC 61850
protection, control, measuring and
supervision of utility and industrial  Digital technology ensuring high
distribution substations. stability, accuracy and reliability of
operation
FXD620 series is a universal platform
which developed on the latest  Compact and designed for
technology, the power of multi- reliability in harsh environments
processor architecture takes the  Operating temperature range from -
accuracy of protection and 25°C to +70°C
measurement to a new level.
Eaton’s 620 Series protection and Fully modular hardware construction gives a high level of flexibility; additional I/O
control IEDs relays offer reliable, or communication modules can be simply plugged in according to application.
secure and complete protection and
control of power distribution systems.
The hardware and software Slot A: Communication module
commonality across the 620-Series
IEDs platform makes it easy for users
to program simple to complex settings Slot B: Input/Output module
or schemes for each of their unique
applications. 620 Series IEDs have a
multiple microprocessor design. The Slot C: Extension Input/Output module
microprocessors perform software
functions such as signal processing,
protection algorithms, scheme logic, Slot D: CT/VT module
output control and intuitive user
interface.
Slot E: Power supply module
Common features include:

Protection

 Truly modular design, extensive


hardware options and flexible Wide range of communication
adaptation protocols:
 Feeder, motor or transformer
protection functionality Two Ethernet Ports,
Ethernet-based communication:
Control IEC61850;
IEC60870-5-104;
 Programmable digital inputs and DNP3.0 TCP;
outputs Modbus TCP
Two RS485/232 Ports,
 Digital inputs with adjustable
Serial communication:
thresholds
DNP3.0;
 Eight common pushbuttons IEC60870-5-101/103;
MODBUS
 Programmable logic elements Time Synchronization Port,
 Wide AC/DC power supply range IRIG-B
Information

 Device setting and waveform


software
 RS-232 front access port
 High-contrast, illuminated HMI 5 x Function LEDs
 Programmable LEDs
8 x Programmable alarm LEDs
 Cause-of-Trip indication
128x64 dot matrix LCD display
Engineering tool

All 620-Series relays use the same 6 x Navigation push buttons


software interface for easy access to
information and programming of 4 x Control push buttons
settings.
Whether you are using the front panel
or the external software, the interface Local Port, Ethernet Interface
is the same on all models.

2 EATON 620 series Protection IED


The 620 series is characterized by fast, versatile and Setting group change control
dependable protection functions with uniquely wide
operating frequency band making it perfect choice for the Change between up to 4 setting groups by any digital
most demanding feeder protection applications including signal including virtual inputs signal or force change
rotating machines. overrule of local controls either from setting tool, HMI or
SCADA.
Overcurrent and earth-fault protection (ANSI 50/51,
50/51N) Object control

Up to three stages of overcurrent and earth fault Up to 4 locally or remotely controllable objects and status
protection functions, Definite time, IEC or ANSI inverse indications. Visualize and control objects locally by
time curves with settable reset delays to coordinate with means of large graphic HMI display.
electromechanical relays.
Auto-reclose (ANSI 79)
Thermal protection (ANSI 49)
Up to 4 independent or scheme controlled shots with
Thermal protection for cable overloading based on cable possibility to set parallel signals in each request. Request
time constants used for heating and cooling calculation of inputs may be digital inputs, virtual inputs.
the thermal image. Provides maximum allowed load
current, one alarm stage and tripping stage. Cold-load pick-up function

Arc protection (50ARC/50NARC) Programmable cold-load pick-up function for blocking


protection functions based on cold-loads.
Optional fast arc protection is available in selected
models. Stage can be set to operate on any combination Circuit breaker failure protection (ANSI 50BF)
of arc light, residual current or phase current conditions.
Typical operation time is 10ms. User settable function initiation based on overcurrent or
digital input or digital output status alone or in any
Voltage protection (ANSI 59/27/59N/47) combination. Two separate levels for Re-Trip and CBFP.

Under and overvoltage and residual overvoltage and


positive/negative sequence voltage stages with DT or
IDMT characteristics and settable voltage thresholds.
CT supervision
Frequency protection (ANSI 81U/81O/81R)
Alarms or blocks in case of lose wiring by constantly
monitoring phase current instant values as well as key
Under and overfrequency and rate of change of
calculated magnitudes of the phase currents.
frequency with DT characteristics. May be applied for
extensive load shedding logic or simple Underfrequency
Fuse failure (VT supervision)
protection.
Alarm or block in case of lose wiring or blown fuse by
Power protection (ANSI 32/37/32R)
constantly monitoring connected instant values and
calculated magnitudes.
Over power, under power and reverse power protection
may be applied for overload, loss-of-load and generator
Recording
turbine protection with DT characteristics and settable 3
phase active power thresholds.
Alarms and events (1024 records) can be recorded with
1ms resolution.

The 8 most recent time-tagged fault records including


The 620 series IEDs offers extensive metering pre-fault and fault values for currents and voltages in text
capabilities, including: format.
 Instantaneous Volt, Amp, Watt, VARS, pf and
frequency Disturbance record acquired using sampled data from all
analog inputs and binary signals selected with
 Energy metering
COMTRADE format.
 Harmonics metering through the 15th harmonic.

EATON 620 series Protection IED 3


Different with opto-electronic sensor, the Eaton’s
eSensor is optical sensor that captures the light, then
guided to the optical receiver through an optical fiber.
Arc flashes can cause great harm. They may occur in the
The eSensor is special plastic optical fiber that allows the
switchgears of the electrical power grid, causing damage
system engineer to avoid any galvanic contact between
in critical and expensive equipment and severe injuries to
the arc flash area and the detection electronics.
humans. Arc flash detectors have become a very
successful means to reduce, or even avoid, the extensive
The eSensor may implement a heartbeat capability as
damage caused by arc flashes. 620 series has
self-supervision functionality. In arc flash detection
developed a high-performance cost-effective arc flash
system, the heartbeat signal consists of an optical pulse
detection board and arc sensor, based on the latest
that is periodically sent from the transmitter to the
technology, and may be applied to the detection of arc
receiver. The heartbeat signal checks whether sensor is
flash events.
unplugged, broken wire, or damaged, consequently,
whether the arc flash detection system keeps enabled or
Application
not.
The 620 series protection relays with arc-flash detection
There are two types of optical sensors used in arc flash
board and sensors for MV/LV switchgear applications,
detection system: the point sensor and the loop sensor.
suitable for new and existing retrofit applications, to
You can choose from point sensors, loop sensors, or a
improve sustainability and life of electrical equipment.
combination to protect a wide variety of switchgear
configurations. The point sensor captures light only in a
relatively small area around its location. The loop sensors
Features detect light from the arc flash over the entire length of the
fiber loop. The loop sensor can also be distributed along
 Combine arc flash sensing technology with fast to cover all horizontal and vertical bus bars, breaker
overcurrent protection to provide high speed tripping compartments, drawers, and anywhere that there is
 Provide 100 percent coverage of the possible arc fault potential for an arc-fault.
locations with a combination of loop-fiber sensors and
point sensors
 Three solid state output relays for fast trip
 Up to four arc flash sensors channels for detection in
multiple locations in MV/LV switchgear
 Continuous self-supervision/health monitoring of
sensors, and arc flash relay with trouble indication
 Easily installed without changes to existing layout
 Flexible sensor configuration for any application
 No additional software is required
 Full self-supervision of all system components and
interconnections

4 EATON 620 series Protection IED


Protection and Control IEC ANSI FXD620-51 FXD620-52
Current Protection
Overcurrent I>,I>>, I>>> 50/51 x x
Earth-fault I0>, I0>>, I0>>> 50N/51N x x
Negative sequence overcurrent I2>, I2>>, I2>>> 46 x x
Thermal overload T> 49 x x
Inrush detection and blocking I2f> 68 x x
Voltage Protection
Overvoltage U>, U>>, U>>> 59 x x
Undervoltage U<, U<<, U<<< 27 x x
Residual overvoltage U0>, U0>>, U0>>> 59N x
Negative sequence overvoltage U2> 47O x
Positive sequence undervoltage U1< 27D x
Frequency Protection
Over Frequency f>, f>> 81O x
Under Frequency f<, f<< 81U x
Rate of change (ROCOF) df/dt 81R x
Automation and diagnostic
Auto-reclose 0->1 79 x x
VT supervision VTS 60 x
CT supervision CTS x x
Cold load pick-up CLP 68 x x
Switch on to fault SOTF x x
Breaker failure protection CBFP 50BF x x
Arc protection IL> 50ARC Option Option
Metering and monitoring
Phase, sequence and residual currents x x
Phase, sequence and residual voltage and frequency x x
Power (P, Q, S, pf) and Energy (E+, E-, Eq+, Eq-) x
Hardware
Current inputs(CT) 4 4
Voltage inputs(VT) 1 4
CT expansion 4
Digital inputs/outputs standard 8/5 8/5
Digital inputs/outputs expansion 8/5 8/5
Event recording
Disturbance recorder 10 10
Event records 1024 1024
Communication interface
RJ45 Ethernet 2 2
RS485/232 serial ports 2 2
Communication protocols
IEC60870-5-103, Modbus RTU&TCP/IP, DNP3 x x
IEC61850 Option Option

EATON 620 series Protection IED 5


Unit: mm

6 EATON 620 series Protection IED


Eaton Corporation
No.3, Lane 280, Linhong Road,
Changning District,
Shanghai, China 200335

Cooper Power Systems


No. 955 Shengli Road,
Zhangjiang East High-Tech Zone,
Shanghai, China 201201
www.eaton.com.cn/das
© 2016 Eaton Corporation
All Rights Reserved
Eaton is a registered trademark of
Printed in China
Eaton Corporation.
Publication No.: CA600012EN All trademarks are property of their
May 2017 respective owners.