Professional Documents
Culture Documents
FMDS0159
FMDS0159
Table of Contents
Page
List of Figures
Fig. 1. Typical roll of fabric showing warp (machine) and fill (cross or weft) directions. ............................. 12
Fig. 2. Typical fabric yarns showing warp and fill (weft) orientation. ........................................................... 12
Fig. 3. Membrane covered structure under construction. ............................................................................. 13
©2013 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.
1-59 Fabric and Membrane Structures
Page 2 FM Global Property Loss Prevention Data Sheets
List of Tables
Table 1. Load Combinations and Safety Factors for Fabric or Membrane Tension at the Start
of Service Life .................................................................................................................................... 5
Table 2. Load Combinations and Safety Factors for Fabric or Membrane Tension During Service Life ...... 6
Table 3. Mechanical Test Sampling Frequency for Fabric or Membrane ....................................................... 7
1.0 SCOPE
This data sheet is applicable to fabric and membrane structures, which include tensioned fabric or tensioned
membrane structures (tensile surface structures), tensegrity structures, fabric- or membrane-covered (-clad)
structures, cable-supported structures with fabric or membrane covering, and air-supported structures.
1.1 Changes
October 2014. Interim revision to Section 2.3, Fire Protection Systems and Section 3.10, Fire, Fire Protection,
and Exterior Fire Exposure.
2.1 General
Use fabric and membrane structures, including air-supported structures, only for temporary structures or
where building contents are of low value, easily replaceable, or not easily damaged.
Do not use fabric or membrane structures for occupancies with combustible storage or ignitable liquids. Refer
to Section 2.3, Fire Protection Systems, for additional guidance.
2.2.1 Wind
Wind-related recommendations apply only to cladding (fabric or membrane covering) and components
(structural members that directly support the fabric or membrane). For loads on primary structural framing
and main lateral force resisting systems, use ASCE 7 or another nationally recognized standard or code
applicable to the jurisdiction.
Avoid the use of fabric and membrane structures, including air-supported structures, in hurricane-prone
regions (which include tropical cyclone-prone and typhoon-prone regions). Refer to Data Sheet 1-28, Wind
Design, for the definition of hurricane-prone regions.
2.2.2 Roof Gravity Loads (Snow, Ice, Rain, and Roof Live Load)
2.2.2.1 Do not use flat or low-sloped roofs. Refer to Appendix A for definitions of flat and low-sloped roofs.
2.2.2.2 Where snow or icing can occur, situate fabric or membrane structures so they will not be exposed to
sliding or drifting snow load, or falling or sliding ice. This includes snow drifts at low roofs, roof projections
and parapets, roof valleys, or snow drifts due to adjacent structures or terrain features; as well as snow or ice
from an adjacent high roof, rooftop equipment, exterior cables, or other overhanging support members. (This
recommendation includes all types of sliding and drifting snow load, but does not include unbalanced snow
load on hip, gable, curved, and dome roofs as described in Data Sheet 1-54.)
2.2.2.3 Refer to Data Sheet 1-54 to determine the design snow, ice, rain, rain-on-snow, and roof live loads
for the appropriate building shapes. For all fabric and membrane structures, including air-supported structures,
use the recommendations in Data Sheet 1-54 but with the following changes:
A. Use a Roof Slope Factor (Cs) for “Cold Roof” for all structures.
B. Use a Roof Slope Factor (Cs) for “All Other Surfaces” (not “Unobstructed Slippery Surface”) for all
structures.
C. When determining the sliding snow load on a lower roof from an upper fabric or membrane roof, consider
the upper fabric or membrane roof surface to be “slippery.”
2.2.2.4 If the standard roof shapes in Data Sheet 1-54 are not representative of the building under
consideration, then use snow loads from an appropriate boundary layer wind tunnel test, water flume model,
or other appropriate test or model to determine the design snow loads.
2.2.2.5 Do not reduce the design snow loads based on any type of snow or ice melting systems or removal
system.
2.2.2.6 For pneumatic membrane systems where multilayer membrane panels or cushions are inflated by
a mechanical air pressure system, base the snow, rain, or ice loading on the assumption that the membrane
panels or cushions are inflated as designed, and deflated to atmospheric pressure. Ensure the shapes of
the inflated and deflated panels or cushions are accounted for when determining loads, including any increase
or concentration of loading due to snow sliding or drifting, or ponding rainwater.
2.2.3 Hail
Provide fabric or membrane that adequately resists hail damage. Refer to Data Sheet 1-34, Hail Damage,
for specific recommendations related to hail damage. Provide building fenestrations and any exposed
equipment, such as rooftop equipment, that adequately resists hail damage or has adequate hail damage
protection (e.g., hail screens or hail guards) in accordance with the recommendations in Data Sheet 1-34.
Table 1. Load Combinations and Safety Factors for Fabric or Membrane Tension at the Start of Service Life
No. Load Combination Minimum Safety Factor*
1 P+D 8.0
2 P + D + (L, S, or R) 5.0
3 P+D+W 5.0
4 P+D+T 5.0
Key:
P = pre-stress load for fabric or membrane
D = dead load (including collateral load)
L = live load
S = snow load (including ice load)
R = rain load
W = wind load (including 1.15 importance factor)
T = thermal expansion or contraction effects on self-restraining loads
*Safety factors do not include a life-cycle factor, but are based on the condition that at least 75% of the initial strength will be retained
over the service life of the structure.
2.2.6.2 The life-cycle factor accounts for the loss of initial material strength over the service life of the structure
due to the effects of exposure, aging, weathering, handling, and folding.
Use a life-cycle factor based on test data from the manufacturer and the judgment of the design engineer,
but not greater than 0.60 for fabric or membrane that will be subjected to repeated handling or folding (as with
a deployable or seasonal structure) or 0.75 for all other fabric or membrane.
The following equation describes the relationship between life-cycle factor and safety factors for fabric or
membrane:
2.2.6.3 Refer to Table 2 for the recommended minimum safety factors for fabric or membrane strength over
the service life of the structure (i.e., aged, exposed and weathered fabric or membrane). These minimum
safety factors include all life-cycle factors and are not intended to be reduced further for any reason.
Table 2. Load Combinations and Safety Factors for Fabric or Membrane Tension During Service Life
No. Load Combination Minimum Safety Factor*
1 P+D 6.0
2 P + D + (L, S, or R) 3.7
3 P+D+W 3.7
4 P+D+T 3.7
Key:
P = pre-stress load for fabric or membrane
D = dead load (including collateral load)
L = live load
S = snow load (including ice load)
R = rain load
W = wind load (including 1.15 importance factor)
T = thermal expansion or contraction effects on self-restraining loads
*Safety factors represent the minimum values that are acceptable over the service life of the structure.
2.2.6.4 Refer to Sections 2.2.7 and 2.2.8 for recommendations related to material tensile tests and mock-up
panels to determine life-cycle factors.
Refer to Section 3.6 for additional information regarding safety factors.
D. Use a uniaxial or biaxial tensile test to determine the strength of the fabric or membrane material
subjected to ultra-violet (UV) weathering representative of the design life of the structure. Compare the
test results of the UV weathered material to the new material. Use a life-cycle factor based on the ratio of
weathered to new tensile strength, but not to exceed 0.75. If UV weathering tests are not performed,
assume a life-cycle factor of not more than 0.6.
E. Perform tensile strength tests in conformance with ASTM D4851 or another nationally recognized test
standard specific to fabric or membrane structures.
F. Provide the total number of tensile tests based on the recommended sampling frequency in Table 3,
and on a minimum of 10 test strips (5 in the warp direction, 5 in the fill direction) per roll sample.
B. Fabric or membrane construction that has undergone full-scale fire testing with automatic sprinklers,
where test results demonstrate that the proposed sprinklers (including sprinkler orientation, temperature
rating, and K-factor) will perform satisfactorily and sprinkler actuation will not be delayed or otherwise
adversely affected. Automatic sprinkler systems for full-scale fire testing do not necessarily have to be
connected to a water source, but must demonstrate that sprinkler actuation (e.g., fusing) will occur prior
to failure (creation of any holes or openings) in the fabric or membrane that could vent heat. For dry-pipe
sprinkler systems, account for the expected delay between sprinkler actuation and initial water flow from
the sprinkler by ensuring the sprinklers will actuate at least 1 minute before the fabric or membrane fails.
Submit test results to FM Global for review.
C. Fabric or membrane that has been determined to be noncombustible, or to not self-propagate fire,
based on the recommendations in Section 2.2.10 Fire Resistance.
D. Check that fabric or membrane roof slopes or ceiling slopes do not exceed the recommended slopes
for the automatic sprinkler system. Refer to Data Sheet 2-0, Installation Guidelines for Automatic
Sprinklers.
E. Do not use fabric or membrane structures for occupancies with combustible storage or ignitable liquids.
2.3.2.2 Ensure the maximum ambient temperature at the sprinkler level will not exceed the recommended
maximum value based on the nominal temperature rating of the installed sprinklers as indicated in Table 1 of
DS 2-0.
2.3.3 Provide smoke or heat detection that, when activated, will shut down the air-handling system. Refer
to Data Sheet 5-48, Automatic Fire Detection.
2.4.1 Inflation Systems for Air-Supported Structures and Pneumatic Membrane Systems
2.4.1.1 Provide two inflation systems: a primary inflation system and an emergency backup inflation system,
with each system alone having the capacity to adequately maintain design inflation pressure with normal
air loss (leakage), including the air loss associated with the operation of the building’s entrances and exits
(including emergency exits) for air-supported structures.
2.4.1.2 Provide the emergency backup inflation system with an independent self-contained power source
that is not reliant on the power grid.
2.4.1.3 Provide an electrical interlock so the emergency backup inflation system will operate automatically
if the primary inflation system fails to operate.
2.4.1.4 For air-supported structures, base the assumed normal air loss (leakage) on the provisions of Annex
G of CSA S367-09, another nationally recognized standard, or calculations made by the design engineer.
C. Heat and smoke detector systems: Follow the manufacturer’s recommendations in maintaining,
inspecting, and testing the equipment.
2.6.2 Maintain an up-to-date list of control valves, by type and location, for building automatic sprinkler piping
systems.
2.8 Electrical
See Section 2.4 for recommendations regarding emergency backup power for inflation systems for pneumatic
membrane systems (e.g., ETFE panels or cushions) and air-supported structures.
3.4 Roof Gravity Loads (Snow, Ice, Rain, and Roof Live Load)
A Roof Slope Factor (Cs) for “Cold Roof” is recommended because the loss of heating for a building, due
to either the loss of electrical power or the loss of heated internal air from an opening (e.g., tearing or
breaching) in the membrane covering, would negate the potential reduction in snow loads that could be
applicable to a warm roof.
A Roof Slope Factor (Cs) for “All Other Surfaces” (not “Unobstructed Slippery Surface”) is recommended to
account for the effects of aging (including roughening of the membrane surface or fabric fraying), local
fabric/membrane deflection, actual roof shape (including valleys or other distortions created by support cables
for example), or obstructions.
The recommendation to consider the membrane roof surface slippery when determining sliding snow loads
(on a lower roof) is intended to account for conditions where the membrane is relatively new and has not
been substantially roughened or frayed, and the membrane has not deformed due to loss of tension or creep
deformation.
For fabric or membrane structures with two layers of membrane or fabric, the air space between the inner
and outer layers is sometimes used as a plenum for heated air, which is intended to heat the outer layer of
membrane to melt snow. This type of snow melting system is an example of a snow melting system that
should not be used to reduce snow or ice loads.
ASCE 55 does not allow design snow loads to be reduced by using snow melting or removal methods for
permanent structures.
For pneumatic membrane systems (e.g., pressurized multilayer ETFE panels), the inflated panels or cushions
can deflate due to a malfunction or loss of power to the inflation systems, or from physical damage to the
inflated panel or cushion (e.g., a cut, tear, or puncture of the membrane). Therefore, it is recommended that
two scenarios be evaluated to determine the more demanding (least favorable) condition: snow, ice, or rain
loads with the panels inflated as designed, and with the panels deflated. The deflated panel scenario in
particular could allow for increased or concentrated loading, for example from sliding snow or ponding
rainwater.
properties of the fabric. The fabric is generally stronger in the warp direction than in the fill direction, and
the % elongation in the fill direction is generally greater than in the warp direction.
Refer to Figure 1 for a schematic view of the typical warp and fill yarn orientation on a fabric roll.
Refer to Figure 2 for a detailed view of the warp and fill yarns in a typical woven fabric.
Fill Fabric
roll
Warp
Fig. 1. Typical roll of fabric showing warp (machine) and fill (cross or weft) directions.
See Figure 3 for a typical large membrane-covered structure under construction. Note that the membrane
has not been installed at the near-side gable end wall, exposing the steel trust frame and the end wall steel
posts and girts. Also note the inner layer (liner) of fabric, which is often used as an acoustical barrier or to
create a space for mecanical, electrical, and/or pluming systems.
See Figures 4 through 7 for representations of some common shapes of tensioned membrane structures.
therefore reduce the level of tension and tautness in the material. For this reason, many types of fabric or
membrane need to be re-tensioned over the service life of the structure.
Solar transmission through some fabrics and membranes can contribute to increased ambient air
temperatures at ceiling levels. If the effects of solar transmission are not properly accounted for by the
building’s mechanical (HVAC) engineer, and coordinated with the fire protection engineer, it is possible that
ambient air temperatures could exceed the maximum recommended values in DS 2-0 for the specified
nominal temperature rating of the sprinklers, which could result in unintended sprinkler actuation.
Solar transmission could also affect flame detectors that are not properly arranged and shielded. The potential
hazard is that false alarms may be triggered. This hazard is addressed in DS 5-48.
ASTM E108 is composed of several types of tests, including the intermittent flame test, spread of flame test,
and burning brand test, and is generally intended for typical roof covers (e.g., simply-ply roofing membrane
on an insulated steel deck), not fabric or membrane structures. The ASTM E108 intermittent flame test and
spread of flame test are of limited value for fabric and membrane structures and difficult to use for comparisons
to traditional roof covers. However, the burning brand test is useful when determining whether or not the
contents of a fabric/membrane building are susceptible to exterior fire exposure - such as from an adjacent
building, yard storage, or brush fire.
Fabric / membrane
skirt
Revolving doors
Transport doors
Emergency exit
Inflation unit
Anchorage / foundation
Emergency back-up
inflation unit
4.0 REFERENCES
4.1 FM Global
Data Sheet 1-12, Ceiling and Concealed Spaces
Data Sheet 1-20, Protection Against Exterior Fire Exposure
Data Sheet 1-28, Wind Design
Data Sheet 1-34, Hail Damage
Data Sheet 1-54, Roof Loads for New Construction
4.2 Others
American Society of Civil Engineers (ASCE). Air-Supported Structures. ASCE 17-96.
American Society of Civil Engineers (ASCE). Minimum Design Loads for Buildings and Other Structures.
ASCE 7-05.
American Society of Civil Engineers (ASCE). Structural Applications of Steel Cable for Buildings. ASCE/SEI
19-10.
American Society of Civil Engineers (ASCE). Tensile Membrane Structures. ASCE 55-10.
American Society of Civil Engineers (ASCE). Wind Tunnel Studies of Buildings and Structures. ASCE Manual
No. 67.
American Society for Testing and Materials (ASTM). Standard Test Method for Behavior of Materials in a
Tube Furnace with a Cone-shaped Airflow Stabilizer. ASTM E2652.
American Society for Testing and Materials (ASTM). Standard Test Method for Behavior of Materials in a
Vertical Tube Furnace at 750°C. ASTM E136
American Society for Testing and Materials (ASTM). Standard Test Methods for Fire Tests of Roof Coverings.
ASTM E108.
American Society for Testing and Materials (ASTM). Standard Test Methods for Surface Burning
Characteristics of Building Materials. ASTM E84.
Canadian Standards Association (CSA). Air-, Cable-, and Frame-Supported Membrane Structures. CSA
S367-09.
Forster, B., and M. Mollaert. European Design Guide for Tensile Surface Structures. TensiNet, 2004.
National Fire Protection Association (NFPA). Standard for Grandstands, Folding and Telescoping Seating,
Tents, and Membrane Structures. NFPA 102.
National Fire Protection Association (NFPA). Standard Methods of Fire Tests for Flame Propagation of Textiles
and Films. NFPA 701 (Method 2).
Shaeffer, R. E. (ed.). Tensioned Fabric Structures: A Practical Introduction. Task Committee on Tensioned
Fabric Structures. ASCE, 1996.
Service Life: The life span of a structure over which adequate performance is provided. The service life should
not exceed the intended design life.
Synclastic: A membrane shaped with positive curvature in both directions (i.e., a bubble or dome-shaped
surface).
Unbalanced Snow Loading: The snow load due to wind-driven snow distribution on the windward (upwind)
and leeward (downwind) roof areas of hip, gable, curved, and dome roofs. The unbalanced snow loading on
the windward roof area will be less than the uniform snow load on the same area, while the unbalanced
snow loading on the leeward roof area will be greater than the uniform snow load on the same area. Refer
to Data Sheet 1-54 for additional details.
Warp: The fabric yarns that are initially straight or near straight (not crimped) when not tensioned, but bend
or warp when tensioned; usually oriented at right angles to the fill (weft) yarns. Also known as the machine
direction of a roll of fabric.
Weft: See Fill.