You are on page 1of 172

Elan Schaltelemente GmbH & Co.

KG

Safety Relay
Modules
Catalogue SRB-G

S RB-
odules -47
: M -46,
New4, -45,
C.4 L1
OPEN
****
CLOSED
KB
Reset

KA
47 57
C C1 X2 X2.1 S1 X1 S2 13 23 33 (43) (53)

F2 K1 K2
* Trigger K1
F1 circuit
K1 KA
K3 K4 K3
TIMER TIMER

K2
K2 KB
K1 K3 K2 K4 K4

D D1 L62 14 24 34 48 58
(44) (54)

KA KB
e n t all y c o m
o nm p
N
at
r
vi

ib
En

le
p er
m ad

pa
e

ro
f

m le
100% r ec y c

In the interests of a sustainable use


of our world’s resources,
this catalogue has been printed on 100% recycled paper
on the basis of the latest environmental technology.
Catalogue SRB-G

Safety Relay Modules

Contents Page
General 3
1 New products:
– SRB-C.44, -C.45, -C.46, -C.47 6
2 SRB modules 22.5 mm wide
– STOP category 0 25
3 SRB modules 22.5 mm wide
– STOP category 1 47
4 SRB modules 45 mm wide
– Standard version, STOP category 0 53
5 SRB modules 45 mm wide
– Standard version, STOP category 1 67
6 SRB modules 45 mm wide
– Multifunctional version, STOP category 0 73
7 SRB modules 45 mm wide
– Multifunctional version, STOP category 1 87
8 SRB modules 45 mm wide
– Special versions 101
9 SRB modules 90 mm wide
– Standard version 111
10 SRB modules 90 mm wide
– Special versions 117
11 Modules for contact multiplying 143

General technical data 157


Modules for special applications 158
Scope of products 161

We accept no liability for errors. Or as the ancient Greeks already knew: The descriptions, control relationships,
Technical data subject to change without data on external actuators, notes on
The Gods do not reveal everything to installation and operation etc. are
notice. The data quoted in this list are
mortals right at the start. But we find out provided on the best of our knowledge.
typical series values which have been
what is better during the course of time This does not however mean that any
carefully checked.
by searching. warranted characteristics or other claims
Xenophanes (Greek philosopher, born relevant to liability over and above the
570/588 BC) "General Terms and Conditions for
Supply of Goods and Services from the
Electrical Industry" can be deduced from
them. The user is not therefore released
from the obligation to check our data and
recommendations for his own use prior to
operation. We trust this will be under-
stood and this note observed.
1
2
Safety Relay Modules
Guide to Products SRB

3
General

Compact The significant feature of in this Furthermore in housings with Modules which are not listed in this
housings latest issue described Safety Relay 45 mm width modules with addi- guide, in particular older SRB
Modules (or SRB modules) is tional setting and adjustment modules are still on sale. Please ask
highlighting the advantage of advantages are available and also for extra data sheet.
increased functionality, but with modules for some special applica-
reduced space consumption. tions. Some exceptions are realized
in 90 mm housings.
Standard modules, some with
additional technical features are Parallel to these standard housings
offered in housings, 22.5 mm wide also the product family SRBF –
only and 45 mm wide. modules in special housings, 36 mm
wide – will be continued

Advantages Safety Relay Modules in ready-to- Because of the ready-to-install The use of Safety Relay Modules is
install compact housings with snap compact housings Safety Relay saving significantly time for wiring.
on fixing are containing a fail-safe Modules can be placed directly into Furthermore errors in design state
and error tolerant electric circuit, the control cabinet very simple and and errors during wiring are
designed to meet the requirements space saving. eliminated and therefore no extra
of control category 3 and/or 4 time for trouble shooting and repair
(EN 954-1), depending on the needs to be considered.
external wiring.

4
Approvals

ÜFZ
PR
ER
BG-

T.

ÜFZ
PR

ER
BG-

T.
ET

BIA

Certifications of all essential SRB For SRB modules test certificates ● Berufsgenossenschaftliches
basic circuits issued by component from the following authorities have Institut für Arbeitssicherheit
test-authorities provide the user with been issued (for details see technical BIA, St. Augustin,
extra security ensuring that this data):
obligations in respect to product ● Canadian Standard Association
liability are fulfilled. ● Prüfstelle der BG Feinmechanik CSA,
und Elektrotechnik, Cologne,
● Underwriters Laboratories
Inc.UL.

Determination Although all SRB circuits meet the The scope below shall give assis- For better transparency the follow-
specific requirements related to the tance in selecting the appropriate ing illustration and technical data are
protection in case of failures module. filed on the basis of general charac-
(EN 60 204-1 : 1998-11, part 9.4) teristics and functions, but not
the various models differ in some following the historic sequential
important details. number allocation C.XX.

Literature • EN 60 204-1 : 1998-11:


Electrical equipment of machines
• EN 954-1:
Safety related parts
of control systems –
General principles of design
• EN 1050:
Risk assessment
• BIA-Report 6/97:
Kategorien für sicherheits-
bezogene Steuerungen
nach EN 954-1
• VDE-Schriftenreihe:
Buchveröffentlichung
"Absicherung von Maschinen vor
gefahrbringenden Bewegungen"

5
New products:

Safety relay modules


SRB-C.44, -C.46, -C.47

More versatility with 16 terminals in 22.5 mm housing

Owing to a housing 22.5 mm wide with 16 connecting terminals (instead of


12 so far) the new Safety relay modules Type SRB-C.44, -C.46 and -C.47 are now
provided with additional functions which could not be offered till now in such
housings.

Please find below major data:

● SRB-C.44 (data sheet see page 8)


– 3 safety enabling outputs, 1 monitoring contact
– Dual-channel triggering for non-equivalent inputs
– Suitable for reed switches due to current limitation and voltage limitation
at input circuits
– Selectable extras: Trailing edge function, Auto reset, cross-short recognition

● SRB-C.46 (data sheet see page 16)


– 3 safety enabling outputs, 1 monitoring contact
– Single- or dual-channel triggering
– Suitable for signal processing of externally powered inputs

● SRB-C.47 (data sheet see page 20)


– 2 enabling outputs, instantaneous,1 monitoring contact
– 1 enabling output, drop-out-delayed 1 ... 30 sec.
– Single- or dual-channel triggering
– Suitable for signal processing of externally powered inputs
– Selectable extras: Trailing edge function, Auto reset, cross-short recognition

● Safety relay modules SRB-C.46 and -C.47 with hybrid fuse


As a further significant feature the modules SRB-C.46 and -C.47 are fitted
with a so called hybrid fuse. In contrast to a fusible cut-out (glass tube type)
the function will be restored automatically after a short circuit. As distinct
from commercially standard electronic fuses, the hybrid fuse has a latch
function and resets only after power down – power up. This kind of reset
prevents the danger of an unintended restart in mode "Automatic start"
after repairing a short circuit.

6 6
New products: 1

Safety relay module


SRB-C.45 (data sheet see page 12)

With "long-life" feature provided by a complementary electronic circuit


As the result of a complementary electronic circuit comprising photo MOS relays
connected upstream of the safety releases, this new C.45 SRB component possesses
the special feature that the mechanical and the electrical service life of the safety-
orientated relay contacts have become approximately equal. With usual safety relay
components, in contrast, a much shorter electrical service life compared to the
mechanical service life arises from the switch load. This can be a particular
technological disadvantage with applications with a large number of switching cycles,
e.g. for the control of the working cycle of a machine.
The complementary electronic circuit in the C.45 SRB component ensures that during
the switching on or off of the safety releases, the electrical load is exclusively switched
by the photos MOS relay, and that the relay contacts which switch at the same time
remain free of the switch load, i.e. their electrical service life remains unaffected. The
C.45 SRB component is suitable for 1 or 2 channel activation, either trailing edge,
automatic start or cross fault monitoring, it has 2 safety queries available and one
floating contact and one electronic feedback contact. The width of the component is
45 mm.

Functional sequence
Closing release:
1. Release is open 2. Relay contacts close 3. Semi-conductor switches
voltage-free => release is closed
13 13 13

14 14 14

Opening release:
1. Release is kept open 2. Relay contacts are
by the semi-conductor opened voltage-free
13 13

14 14

7
SRB-C.44
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 2-channel triggering ☛ Cross-short recognition
☛ Non-equivalent inputs ☛ 22.5 mm housing
☛ Current limitation at input circuits
☛ Voltage limitation at input circuits
☛ Selectable extras:
– Trailing edge function
– Auto reset
Features – Relay output: 3 NO, 1 NC – Feedback loop – Housing 45 mm, made of
(Auxiliary NC for monitoring thermoplastic in accordance with
must not be used in safety – Input for emergency stop UL-94-V-0, red RAL 3000
enabling circuits!) or door monitoring
– DIN rail mounting
– Input for reset – LED’s for K1, K2, Ui DIN EN 50 022

Approvals
ÜFZ
PR
ER
BG-

T.

01041 Contact manufacturer Contact manufacturer

Front view

13 23 33 L42
A1 X1 X2 X3
K1
Ui
SRB-C.44 K2
A2 S21 S22 S14
14 24 34 S13

Product range Type Enabling outputs Operating voltage Part no.


SRB-C.44 3 NO/1 NC 24 VAC/VDC 600 0101

8
SRB-C.44 (continued) 1

Wiring diagram Example for dual-channel door


monitoring and external reset button.
L1
OPEN RESET
Dual-channel output, suitable for contact
CLOSED
KB
reinforcement or with positively guided
**** contacts.

KA **** = Feedback loop


A1 X2 S13 S14 S21 S22 X3 X1 13 23 33 Wire breakage and earth leakage in the
monitoring circuits are detected.
** Electronic fuse
F1
** (an external leading fuse T 0.5 A
TRIGGER CIRCUIT is recommended)
K1 KA

Ui
K2 KB
K1 K2

A2 14 24 34 L42

KA KB

N
For further examples
refer to page 10/11

Model specific
Operating voltage 24VDC –15%/+20%, residual ripple max. 10%
Technical data
24 VAC –15%/+10%
(refer to page 157
for general data) Frequency 50/60 Hz (for AC operating)
Fuse (power supply) T 0.5 A/250 V (internal electronic fuse, triggering current > 0.6 A,
reset after 1 second)
Power consumption max. 1.8 W; 2.4 VA, plus auxiliary output L42
Switching capacity (enabling contacts) 230 VAC, 4 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 4 A slow blowing
Switching capacity (monitoring contacts) 24 VDC, 100 mA
Current and voltage limitation of input circuits 26 VDC/100 mA
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 120 ms/≤ 30 ms (Auto start, reset button)
Drop-out delay ≤ 20 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.6 qmm, max. 2.5 qmm
Dimensions H/W/D 90 mm/22.5 mm/121 mm
Weight 235 g
Ambient operating temperature –25 °C ... +45 °C (derating curve available)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

9
SRB-C.44 (continued)

Wiring example: Wiring example:


Input level Input level
S21 S13 X1 S21 S13 X1
Dual-channel emergency Dual-channel door
stop switch according to monitoring according to OPEN
EN 60 204-1. EN 1088, one limit switch
CLOSED
Wire breakage and earth with positive opening
leakage in the emergency contact.
EMERGENCY RESET RESET
stop circuits are detected. STOP Wire breakage and earth
Cross-shorts in the leakage in the door
emergency stop circuits are monitoring circuits are
detected. detected.

With external reset button. Cross-shorts in the door


monitoring circuits are
Safety category 3 or 4 detected.
in accordance with
EN 954-1. With external reset button
for increased safety
requirements.

S22 S14 X2
Safety category 3 or 4
S22 S14 X2
in accordance with
EN 954-1.

Wiring example: Wiring example:


Input level Input level
S21 S13 X1 S21 S13 X1
Dual-channel door Dual-channel door
monitoring with reed monitoring with reed switch.
switch. Wire breakage and earth
Wire breakage and earth leakage in the door
leakage in the door monitoring circuits are
monitoring circuits are detected.
detected. Cross-shorts in the door
Cross-shorts in the door monitoring circuits are
monitoring circuits are detected. RESET
detected. With external reset button
Safety category 3 for increased safety
in accordance with requirements.
EN 954-1. Safety category 3
in accordance with
EN 954-1.
S22 S14 X2 S22 S14 X2

Advice:
For "Automatic Reset" X1 X1
connect feed back loop to X1-
X3 or apply jumper X1-X3 if
no feed back loop is used.
When using external reset
button (feed back loop
connected to X1-X2), unit is RESET
triggered by trailing edge
function. KA
KA
Trailing edge function with
"fail-safe" function only by a
DC power supply. KB
KB
After a performed "Emer-
gency Shut Down" an auto-
matic restart of the system
must be prevented by the
higher ranking electric
circuitry when the relay X2 X3
module SRB-C.44/e is been
set into mode "Auto-matic
Start" (refer to EN 60 204-1,
part 9.2.5.4.2 and part 10.8.3).

10
SRB-C.44 (continued) 1

Wiring example: Wiring example:


Power level Power level
Single-channel output L1
L1
Dual-channel output L1
L1
Suitable for contact Suitable for contact
reinforcement or contact KA ** KB reinforcement or contact
**
KA
KA KB
KB
multiplication, using relays XX11 XX22 13
13 multiplication, using relays X1 X2 13 23
X X 13 23
or contactors with or contactors with
KA
KA KB
positively guided contacts. positively guided contacts. KB

14 KB
KB 14
14 24
24 KA
KA

KA
KA KB
KB KA KB

N N
N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

11
SRB-C.45
Safety relay array for emergency stop devices,
interlocking devices and others
☛ "Long life" module ☛ 45 mm housing
☛ 1- or 2-channel triggering ☛ 1 semiconductor output
☛ 3 enabling outputs and ☛ Selectable extras:
1 monitoring output – Trailing edge function
☛ with integrated selective fuse – Auto reset
☛ suitable for signal processing – Cross-short recognition
of externally powered inputs
Features – Relay output: 3 NO, – Input for reset – Housing 45 mm, made of
1 NC with non-equivalence. thermoplastic in accordance with
(Auxiliary NC for monitoring – Feedback loop UL-94-V-0, red RAL 3000
must not be used in safety – Input for emergency stop
enabling circuits!) – DIN rail mounting
or door monitoring DIN EN 50 022-35
– Long life module for application – LED’s for K1, K2, UB and Ui
with high switching frequency.
Electrical life approximate to
mechanical life.

Approvals
ÜFZ
PR
ER
BG-

T.

Pending LR 13571-30 E 54284 (M)

Front view
13 23 33 41 X3
A1 S11 S12 X1 X2
SRB-C.45-24V
UB U i

Fuse K1 K2

A2 S31 S32 S21 S22


14 24 34 42 L52

Product range Type Enabling outputs Operating voltage Part no.


SRB-C.45 3 NO/1 NC 24 VAC/VDC 600 0102

12
SRB-C.45 (continued) 1

Wiring diagram Example for dual-channel door


L1 monitoring and external reset button.
OPEN
**** Dual-channel output, suitable for contact
CLOSED
KB reinforcement or with positively guided
Reset contacts.
KA **** = Feedback loop
A1 S11 X3 X2 S12 X1 S22 S21 13 23 33 41
Wire breakage and earth leakage in the
monitoring circuits are detected.
* Fuse F2 (located in housing lid) 1 A,
F2 K1 K2
Fuse F1 (internal) 1.25 A
* TRIGGER K1
F1 CIRCUIT K1 KA

K2 K2 KB
Ui UB
K1 K2

A2 S31 S32 L52 14 24 34 42

KA KB

N
For further examples
refer to page 14/15

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+10%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) F2: T 1.0 A/250 V (internal F1: T 1.25 A/250 V)
Power consumption max. 3.4 W; 4.4 VA, plus auxiliary output L52
Switching capacity (enabling contacts) 60 VAC/VDC, 3 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 3 A slow blowing
Switching capacity (monitoring contacts) 41/42: 24 V/2 A; L52: max. 100 mA
Fuse (monitoring contacts) 41/42: 2 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 120 ms
Drop-out delay ≤ 20 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/45 mm/140 mm
Weight 460 g
Ambient operating temperature 0 °C ... +45 °C (derating curve available)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

13
SRB-C.45 (continued)

Wiring example: Wiring example:


Input level Input level
S11 S12 X1 S31 S11 S21 X1 S31
Single-channel emergency Dual-channel emergency stop
stop switch according to switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency EMERGENCY RESET leakage in the emergency stop
stop circuits are detected. circuits are detected. EMERGENCY RESET
STOP
STOP
With external reset button. Cross-shorts in the emergency
Safety category 2 stop circuits are not detected.
in accordance with With external reset button.
EN 954-1. Safety category 3 or 4
in accordance with
EN 954-1.

S12 S22 X2 S32 S12 S22 X2 S32

Wiring example: Wiring example:


Input level Input level
S11 S31 X1 S21 S11 S12 X1 S31
Dual-channel emergency Single-channel door
stop switch according to monitoring according to
OPEN
EN 60 204-1. EN 1088 limit switch with
Wire breakage and earth positive opening contact. CLOSED
leakage in the emergency EMERGENCY Wire breakage and earth RESET
RESET
stop circuits are detected. STOP leakage in the emergency
Cross-shorts in the stop circuits are detected.
emergency stop circuits are With external reset button.
detected. Safety category 2
With external reset button. in accordance with
Safety category 3 or 4 EN 954-1.
in accordance with
EN 954-1.

S12 S32 X2 S22 S12 S22 X2 S32

Wiring example: Wiring example:


Input level Input level
S11 S21 X1 S31 S21
S11 S31 X1
Dual-channel door Dual-channel door
monitoring according to OPEN monitoring according to
OPEN
EN 1088, one limit switch CLOSED EN 1088, one limit switch
with positive opening with positive opening CLOSED
contact. contact.
RESET
Wire breakage and earth Wire breakage and earth RESET
leakage in the door leakage in the door
monitoring circuits are monitoring circuits are
detected. detected.
Cross-shorts in the door Cross-shorts in the
monitoring circuits are emergency stop circuits are
not detected. detected.
With external reset button. With external reset button.
Safety category 3 or 4 Safety category 3 or 4
in accordance with in accordance with
EN 954-1. S12 S22 X2 S32 EN 954-1.
S12 S32 X2 S22

14
SRB-C.45 (continued) 1

Wiring example: Wiring example:


Power level Power level
Single-channel output. L1 Dual-channel output.
L1
Suitable for contact Suitable for contact
reinforcement or contact KA * KB reinforcement or contact KA * KB
multiplication, using relays X1 X2 13
multiplication, using relays
X1 X2 13 23
or contactors with or contactors with
positively guided contacts. KA positively guided contacts. KB

14 KB 14 24
KA

KA KB KA KB

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

15
SRB-C.46
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 1- or 2-channel triggering ☛ 22.5 mm housing
☛ 3 enabling outputs and ☛ Selectable extras:
1 monitoring output – Trailing edge function
☛ with electronic short circuit – Auto reset
protection "Hybrid fuse" – Cross-short recognition
☛ suitable for signal processing
of externally powered inputs
Features – Relay output: 3 NO, 1 NC – Feedback loop – Housing 22.5 mm, made of
(Auxiliary NC for monitoring thermoplastic in accordance with
must not be used in safety – Input for emergency stop UL-94-V-0, red RAL 3000
enabling circuits!) or door monitoring
– DIN rail mounting
– Input for reset – LED’s for K1, K2, Ui DIN EN 50 022

Approvals
ÜFZ
PR
ER
BG-

T.

01067 Contact manufacturer Contact manufacturer

Front view

13 23 33 41
A1 S11 X1 X3
K1
Ui
SRB-C.46 K2
A2 S12 S21 S22
14 24 34 42

Product range Type Enabling outputs Operating voltage Part no.


SRB-C.46 3 NO/1 NC 24 VAC/VDC 600 0103

16
SRB-NA-R-C.46 (continued) 1

Wiring diagram Example for dual-channel door


monitoring and external reset button.
L1
Reset
OPEN Dual-channel output, suitable for contact
CLOSED
KB reinforcement with positively guided
**** contacts.

KA **** = Feedback loop


A1 S12 S11 S21 S22 X3 X1 13 23 33 41 Wire breakage and earth leakage in the
monitoring circuits are detected.

F1
** Hybrid fuse
**
Trigger circuit
K1 KA

Ui
K2 KB
K1 K2

A2 14 24 34 42

KA KB

N
For further examples
refer to page 18/19

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+10%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) Internal electronic fuse, triggering current > 0.6 A, reset after power
down
Power consumption max. 2.4 W; 3.3 VA
Switching capacity (enabling contacts) 230 VAC, 4 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 4 A slow blowing
Switching capacity (monitoring contacts) 24 VDC, 2 A
Fuse (monitoring contacts) 2 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 200 ms/≤ 30 ms (Auto start, reset button)
Drop-out delay ≤ 20 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.6 qmm, max. 2.5 qmm
Dimensions H/W/D 90 mm/22.5 mm/121 mm
Weight 235 g
Ambient operating temperature –25 °C ... +45 °C (derating curve available)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

17
SRB-C.46 (continued)

Wiring example: Wiring example:


Input level Input level
S11 S12 S11 S11 S21 S11
Single-channel emergency Dual-channel emergency
stop switch according to stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency leakage in the Emergency
EMERGENCY RESET EMERGENCY RESET
stop circuits are detected. STOP stop circuits are detected. STOP
To deactivate cross-short Cross-shorts in the
monitoring: Set switch emergency stop circuits are
"QS" (bottom of housing) not detected.
to "0". To deactivate cross-short
With external reset button. monitoring: Set switch
Safety category 2 "QS" (bottom of housing)
in accordance with to "0".
EN 954-1. QS With external reset button. QS

0 Safety category 3 or 4 1 0
1
S12 S21 X1 in accordance with S12 S22 X1
EN 954-1.

Wiring example: Wiring example:


Input level Input level
S11 S21 S11 S11 S12 S11
Dual-channel emergency Single-channel door
stop switch according to monitoring according to
OPEN
EN 60 204-1. EN 1088 limit switch with
Wire breakage and earth positive opening contact. CLOSED
leakage in the emergency Wire breakage and earth
EMERGENCY RESET RESET
stop circuits are detected. STOP leakage in the emergency
Cross-shorts in the stop circuits are detected.
emergency stop circuits are To deactivate cross-short
detected. monitoring: Set switch
Activating cross-short "QS" (bottom of housing)
monitoring: Set switch to "0".
"QS" (bottom of housing) With external reset button
to "1". for increased safety
With external reset button. QS requirements. QS

Safety category 3 or 4 Safety category 2


1 0 in accordance with 1 0
in accordance with S12 S22 X1 S12 S21 X1
EN 954-1. EN 954-1.

Wiring example: Wiring example:


Input level Input level
S11 S21 S11 +24V (S11) +24V (S22) S11
Dual-channel door monitoring Dual-channel triggering
according to EN 1088, one OPEN using P-switching
limit switch with positive semiconductors.
CLOSED
opening contact. Wire breakage and earth
Wire breakage and earth leakage in the door RESET
RESET
leakage in the door monitoring circuits are
monitoring circuits are detected.
detected. With external reset button.
Cross-shorts in the door Attention:
monitoring circuits are QS-switch must be set in
detected. position "0".
Activating cross-short WARNING:
monitoring: Set switch "QS" Ignoring may destroy the
(bottom of housing) to "1". QS device. QS
With external reset button for Safety category 3 or 4
increased safety requirements. 1 0 1 0
S12 S22 X1 in accordance with S12 S21 X1
Safety category 3 or 4 EN 954-1.
in accordance with
EN 954-1.

18
SRB-C.46 (continued) 1

Wiring example: Wiring example:


Power level Power level
Single-channel output L1
L1
Dual-channel output L1
L1
Suitable for contact Suitable for contact
reinforcement or contact KA
KA
** KB
KB reinforcement or contact **
KA
KA KB
KB
multiplication, using relays XD1 S11
X2 13
13
multiplication, using relays
XD
1 S11
X2 1313 2323
or contactors with or contactors with
positively guided contacts. KA
KA positively guided contacts. KB
KB

14 KB
KB
14 1414 2424 KA
KA

KA
KA KB
KB KA KB
KA KB

NN N
N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

Advice
For "Automatic Reset" S11 X1
connect feed back loop to X1-
X3 or apply jumper X1-X3 if
no feed back loop is used.
When using external reset
button (feed back loop
connected to S11-X1), unit is RESET
triggered by trailing edge
function. KA
KA
Trailing edge function with
"fail-safe" function only by a
DC power supply. KB
KB
After a performed "Emer-
gency Shut Down" an auto-
matic restart of the system
must be prevented by the
higher ranking electric
circuitry when the relay X1 X3
module SRB-C.46/e is been
set into mode "Automatic
Start" (refer to EN 60 204-1,
part 9.2.5.4.2 and part 10.8.3).

19
SRB-C.47
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 1- or 2-channel triggering ☛ 22.5 mm housing
☛ 3 enabling outputs, instant and ☛ Selectable extras:
1 enabling output, drop-out delayed – Trailing edge function
☛ with "Hybrid fuse" – Auto reset
☛ suitable for processing of – Cross-short recognition
externally powered input signals

Features – Relay output: – Feedback loop – Housing 22.5 mm, made of


2 NO, instantaneous; thermoplastic in accordance with
1 NO, drop-out delayed – Input for emergency stop UL-94-V-0, red RAL 3000
or door monitoring
– 1 semi-conductor output – DIN rail mounting
– LED’s for K1, K2, K3/k4 and Ui DIN EN 50 022
– Input for reset

Approvals
ÜFZ
PR
ER
BG-

T.

01069 Contact manufacturer Contact manufacturer

Front view

13 23 37 X2
A1 S11 X1 X3

SRB-C.47 Ui K1
K2 K3/4
t: s
A2 S12 S21 S22
14 24 38 L42

Product range Type Enabling outputs Operating voltage Part no.


SRB-C.47 2 NO/1 NO /1 NC 24 VAC/VDC 600 0104

20
SRB-C.47 (continued) 1

Wiring diagram Example for dual-channel door


monitoring and external reset button.
L1
OPEN
RESET
Dual-channel output, suitable for contact
CLOSED
KB reinforcement with positively guided
**** contacts.
KA **** = Feedback loop
A1 S12 S11 S21 S22 X1 X2 X3 13 23 37 Wire breakage and earth leakage in the
monitoring circuits are detected.

F1
** Hybrid fuse
**
TRIGGER CIRCUIT
K1 KA
K3

Ui
K2 KB
K1 K2 K3 K4 K4

A2 L42 14 24 38

KA KB

N
For further examples
refer to page 22/23

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) Internal electronic fuse, triggering current < 0.6 A, reset after power
down
Power consumption max. 4 W; 5.5 VA, plus auxiliary output L42
Switching capacity (enabling contacts) 230 VAC, 4 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 4 A slow blowing
Switching capacity (monitoring contacts) L42: 24 VDC, 100 mA
Application category AC 15/DC 13, DIN VDE 0660 Part 200
13/14, 23/24: AC 15: 250 V/1.5 A; DC 13: 24 V/1.2 A
37/38: AC 15: 250 V/3 A; DC 13: 24 V/2 A
Pick-up delay ≤ 120 ms/≤ 30 ms (Auto start, reset button)
Drop-out delay ≤ 20 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 90 mm/22.5 mm/121 mm
Weight 235 g
Ambient operating temperature –25 °C ... +45 °C (derating curve available)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

21
SRB-C.47 (continued)

Wiring example: Wiring example:


Input level Input level
S11 S12 X1 S11 S21 X1
Single-channel emergency Dual-channel emergency stop
stop switch according to switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency leakage in the emergency stop
EMERGENCY RESET EMERGENCY RESET
stop circuits are detected. STOP circuits are detected. STOP
To deactivate Cross-short Cross-shorts in the emergency
monitoring: Set switch stop circuits are not detected.
"QS" (bottom of housing) To deactivate cross-short
to "0". monitoring: set switch "QS"
With external reset button. (bottom of housing) to "0".
Safety category 2 With external reset button.
in accordance with Safety category 3 or 4
EN 954-1. QS QS
in accordance with
1 0 EN 954-1. 1 0
S12 S21 X2 S12 S22 X2

Wiring example: Wiring example:


Input level Input level
S11 S21 X1 S11 S21 X1
Dual-channel emergency Single-channel door
stop switch according to monitoring according to OPEN
EN 60 204-1. EN 1088 limit switch with
Wire breakage and earth positive opening contact. CLOSED
leakage in the emergency Wire breakage and earth
EMERGENCY RESET RESET
stop circuits are detected. STOP leakage in the door
Activating cross-short monitoring circuits are
monitoring: Set switch detected.
"QS" (bottom of housing) To deactivate cross-short
to "1". monitoring: set switch
With external reset button. "QS" (bottom of housing)
to "0".
Safety category 3 or 4
in accordance with With external reset button
EN 954-1. QS for increased safety QS
requirements.
1 0 Safety category 2 1 0
S12 S22 X2 S12 S22 X2
in accordance with
EN 954-1.

Wiring example: Wiring example:


Input level Input level
S11 S21 X1 +24V (S11) +24V (S22) X1
Dual-channel door Dual-channel triggering
monitoring according to OPEN using P-switching semi-
EN 1088, one limit switch CLOSED conductors.
with positive opening Wire breakage and earth
contact. leakage in the door RESET
RESET
Wire breakage and earth monitoring circuits are
leakage in the door detected.
monitoring circuits are With external reset button.
detected.
Attention:
Activating cross-short QS-switch must be set in
monitoring: Set switch position "0".
"QS" (bottom of housing)
to "1". WARNING:
Ignoring may destroy the
With external reset button. QS QS
device.
Safety category 3 or 4 Safety category 3 or 4 in
1 0 1 0
in accordance with S12 S22 X2 accordance with EN 954-1. S12 S21 X2
EN 954-1.

22
SRB-NA-R-C.47 (continued) 1

Wiring example: Wiring example:


Power level Power level
Single-channel output L1
Dual-channel output
L1
Suitable for contact Suitable for contact
reinforcement or contact KA * KB reinforcement or contact *
KA KB
multiplication, using relays multiplication, using relays
X1 X2 13 X1 X2 13 23
or contactors with or contactors with
positively guided contacts. KA positively guided contacts. KB

14 KB 14 24 KA

KA KB KA KB

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

Advice
For "Automatic Reset"
connect feed back loop to X1 X1
X1-X3 or apply jumper
X1-X3 if no feed back
loop is used.
When using external reset
button (feed back loop
connected to X1-X2), unit RESET
is triggered by trailing
edge function. KA
KA
Trailing edge function with
"fail-safe" function only by
a DC power supply. KB
KB
After a performed
"Emergency Shut Down"
an automatic restart of the
system must be prevented
by the higher ranking
electric circuitry when the X2 X3
relay module SRB-C.46/e
is been set into mode
"Automatic Start" (refer to
EN 60 204-1, part 9.2.5.4.2
and part 10.8.3).

23
24
SRB modules 22.5 mm wide,
STOP category 0

☛ max. 3 enabling outputs and 1 monitoring output


☛ max. load current: 6 Ampere
☛ max. safety category: 4
☛ 1- or 2-channel triggering
☛ Trailing edge function selectable
☛ Cross-short recognition selectable
☛ Semiconductor monitoring outputs selectable
☛ 24 VDC/VAC-version
☛ Approvals: BG, CSA, UL

Options

0 .1
t. t 2
ca ca A) ) 1/ g ts
P P ( ts (A el i o n e r i n n
T O T O n t u n t r y a n n
i t g t i o inpu
S s S r r e t p r r e g o ch g n t r i g n c d
ts u
pu tpu ad c C o ad c ca w ∞ r e c n e l ge f wer t e s C
t u u te o u e t
t l al l
o u u
o lo y N l y
o e t nd o o r t
h a n e d p o
a r t VA
/ o va rov ova
g
in in
g x. ar x . s a f wi s h - c g al st C C AC AC pr pp pr
a b l a b l m a x i l i m a x . me- o s s - n g l e a i l i n t e r n i t i a l V D V A 5 V 0 V a p A a a p
u a
Type E n E n = > A = > m Ti C r S i Tr Ex I n 24 48 11 23 BG CS UL
SRB-NA-R-C.14 2 6 4 ✚ ✚ ● ● ✔ ✔ ✔ refer to page 26
SRB-NA-R-C.15 3 6 1 2 3 ✚ ✚ ● ● ✔ ✔ ✔ refer to page 30
SRB-NA-R-C.17 2 4 4 ✚ ✚ ● ●* ✔ ✔ ✔ refer to page 34
SRB-NA-R-C.18 2 6 4 ✚ ● ● ● ✔ ✔ ✔ refer to page 38
SRB-NA-R-C.36 2 6 4 ✚ ● ● ● ●* ✔ ✔ ✔ refer to page 42
✚ = fixed; ● = selectable; ● = selectable feature; * = available in 24 VDC only; ✔ = approved

25
SRB-NA-R-C.14
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 2 enabling outputs
☛ Cross-short recognition

Features – Relay output: 2 NO – Input for emergency stop – Housing 22.5 mm, made of
or door monitoring thermoplastic in accordance with
– Reset, feedback loop UL-94-V-0, red RAL 3000
– LED’s for K1, K2, Ui
– DIN rail mounting
DIN EN 50 022

Approvals
ÜFZ
PR
ER
BG-

T.

96147 LR 13571-30 E 54284 (M)

Front view

C C1 23
13 S1 24
K1
SRB- UB
NA-R
-C.14 K2
X2 S2 X1
14 D1 D

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.14-24VDC 2 NO 24 VDC 600 0025
SRB-NA-R-C.14-24VAC 2 NO 24 VAC 600 0047
SRB-NA-R-C.14/UC 2 NO 24 VDC/VAC On request

26
SRB-NA-R-C.14 (continued)

Wiring diagram L1
Example for dual-channel door
monitoring using two limit switches
Open ****
(one with positive opening contacts) and
Closed
KB external reset button.
Reset
Dual-channel output, suitable for contact
KA reinforcement or contact multiplication,
using relays or contactors with positively
C C1 S1 X1 X2 13 23
guided contacts.
**** = Feedback loop
F1** Wire breakage and earth leakage in the
K2 K1 K1 K2 Monitoring circuits are detected.
K1 KA
** Fuse M 0.5 A
(an external leading fuse M 0.25 A
is recommended)
K2 KB
K1 K2

D D1 S2 14 24

KA KB

For further examples N


refer to page 28/29

Model specific
Operating voltage 24VDC –15%/+20%, residual ripple max. 10%
Technical data
24 VAC –15%/+6%
(refer to page 157
for general data) Frequency 50/60 Hz (for AC operating)
Fuse (power supply) M 0.25 A/250 V (internal M 0.5 A/250 V)
Power consumption max. 2.5 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 10 ms
Drop-out delay ≤ 30 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.6 qmm, max. 2.5 qmm
Dimensions H/W/D 82 mm/22.5 mm/98.8 mm
Weight 190 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

27
SRB-NA-R-C.14 (continued)

Wiring example: Wiring example:


Input level Input level
L+(A1) C1 D1 X1 L+(A1) L-(A2) C1 D1 X1
Single-channel emergency Dual-channel emergency
stop switch according to stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency stop Emergency Reset
stop circuits are detected. switch off circuits are detected. switch off
With external reset button. Earth leakage at input A2 is
Safety category 2 detected in non grounded
in accordance with mains only!
EN 954-1. Cross-shorts in the emergency
stop circuits are detected.
With external reset button.
Safety category 3
in accordance with
EN 954-1.
C S1 S2 X2 C D S1 S2 X2

Wiring example: Wiring example:


Input level Input level
C1 D1 X1 L+(A1) C1 D1 X1
Dual-channel emergency Single-channel door
stop switch according to monitoring according to
Open
EN 60 204-1. EN 1088 limit switch with
positive opening contact. Closed
Wire breakage and earth
leakage in the emergency Reset Wire breakage and earth Reset
stop circuits are detected. Emergency leakage in the door
switch off
Cross-shorts in the monitoring circuits are
emergency stop circuits are detected.
detected. With external reset button
With external reset button. for increased safety
requirements.
Safety category 3 or 4
in accordance with Safety category 2
EN 954-1. in accordance with
EN 954-1.

S1 S2 X2 C S1 S2 X2

Wiring example:
Input level
C1 D1 X1
Dual-channel door
monitoring according to Open
EN 1088, one limit switch
Closed
with positive opening
contact.
Reset
Wire breakage and earth
leakage in the door
monitoring circuits are
detected.
Cross-shorts in the
emergency stop circuits are
detected.
With external reset button
for increased safety
requirements.
Safety category 3 or 4 S1 S2 X2
in accordance with
EN 954-1.

28
SRB-NA-R-C.14 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output Dual-channel output
L1 L1
Suitable for contact Suitable for contact
reinforcement or contact KA * KB reinforcement or contact KA * KB
multiplication, using relays X1 X2 13
multiplication, using relays
X1 X2 13 23
or contactors with or contactors with
positively guided contacts. KA positively guided contacts. KB

14 KB 14 24 KA

KA KB KA KB

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

29
SRB-NA-R-C.15, ...-C.15/1
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 3 enabling outputs and 1 monitoring output
☛ Cross-short recognition

Features – Relay output: 3 NO, 1 NC – NC contacts for monitoring – Housing 22.5 mm, made of
(Auxiliary NC for monitoring (SRB-NA-R-C.15/1: in series) thermoplastic in accordance with
must not be used in Safety (SRB-NA-R-C.15: in parallel) UL-94-V-0, red RAL 3000
Enabling Circuits!)
– Input for emergency stop – DIN rail mounting
– Reset, feedback loop or door monitoring DIN EN 50 022
– LED’s for K1, K2, Ui

Approvals
(SRB-NA-R-C.15) PR
ÜFZ
ER
BG-

T.

96201 LR 13571-30 E 54284 (M)

Front view

13 23 33
14 24 34
K2
UB SRB-
NA-R
K1 -C.15
41 X1 C
42 X2 D

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.15-24VDC 3 NO/1 NC 24 VDC 600 0032
SRB-NA-R-C.15-24VAC 3 NO/1 NC 24 VAC 600 0044
SRB-NA-R-C.15/1-24VDC 3 NO/1 NC 24 VDC 600 0046
SRB-NA-R-C.15/UC 3 NO/1 NC 24 VDC/VAC On request

30
SRB-NA-R-C.15, ...-C.15/1 (continued)

Wiring diagram L-(A2) L+(A1) L1


Example for dual-channel door
monitoring using two limit switches
Open (one with positive opening contacts) and
Closed
KB
external reset button.
Reset
**** Dual-channel output, suitable for contact
KA
reinforcement or contact multiplication,
using relays or contactors with positively
C X1 X2 13 23 33 41 41* guided contacts.
**** = Feedback loop
F1** Wire breakage and earth leakage in the
K2 K1 K1 K2 Monitoring circuits are detected.
K1 KA
Earth leakage at input D is detected only
in mains with insulation leakage
monitoring.
K2 KB
K1 K2 * Monitoring contacts in series at
SRB-NA-R-C.15/1
D 14 24 34 42 42
** Fuse M 0.5 A
KA KB (an external leading fuse M 0.25 A
is recommended)
For further examples N
refer to page 32/33

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) M 0.25 A/250 V (internal M 0.5 A/250 V)
Power consumption max. 2.5 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Switching capacity (monitoring contacts) 24 V, 2 A ohmic (inductive with suitable suppression)
Fuse (monitoring contacts) 2 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 10 ms
Drop-out delay ≤ 30 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.6 qmm, max. 2.5 qmm
Dimensions H/W/D 82 mm/22.5 mm/98.8 mm
Weight 190 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

31
SRB-NA-R-C.15, ...-C.15/1 (continued)

Wiring example: Wiring example:


Input level Input level
L+(A1) L-(A2) X1 L+(A1) L-(A2) X1
Single-channel emergency Dual-channel emergency stop
stop switch according to switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency leakage in the emergency stop
Emergency Reset Emergency Reset
stop circuits are detected. circuits are detected.
switch off switch off
With external reset button. Cross-shorts in the emergency
Safety category 2 stop circuits are detected.
in accordance with With external reset button.
EN 954-1. Safety category 3
in accordance with
EN 954-1.

C D X2 C D X2

Wiring example: Wiring example:


Input level Input level
L+(A1) L-(A2) X1 L+(A1) L-(A2) X1
Single-channel door Dual-channel door
monitoring according to monitoring according to
Open ON
EN 1088 limit switch with EN 1088, one limit switch
positive opening contact. Closed with positive opening OFF

Wire breakage and earth contact.


Reset Reset
leakage in the door Wire breakage and earth
monitoring circuits are leakage in the door
detected. monitoring circuits are
With external reset button detected.
for increased safety Cross-shorts in the
requirements. emergency stop circuits are
Safety category 2 detected.
in accordance with With external reset button
EN 954-1. for increased safety
requirements.
C D X2 Safety category 3 C D X2
in accordance with
EN 954-1.

32
SRB-NA-R-C.15, ...-C.15/1 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output. L1 Dual-channel output.
L1
Suitable for contact Suitable for contact
reinforcement or contact KA * KB reinforcement or contact KA * KB
multiplication, using relays X1 X2 13
multiplication, using relays
X1 X2 13 23
or contactors with or contactors with
positively guided contacts. KA positively guided contacts. KB

14 KB 14 24
KA

KA KB KA KB

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

33
SRB-NA-R-C.17
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 2 enabling outputs
☛ Selectable extras:
– Trailing edge function
– Auto reset
☛ Cross-short recognition

Features – Relay output: 2 NO – Reset, feedback loop – DIN rail mounting


DIN EN 50 022
– Input for emergency stop – LED’s for K1, K2
or door monitoring
– Housing 22.5 mm, made of
thermoplastic in accordance with
UL-94-V-0, red RAL 3000

Approvals
ÜFZ
PR
ER
BG-

T.

98186 LR 13571-30 E 54284 (M)

Front view

13 23 X1
14 24 X2
K1
SRB-
NA-R
-C.17 K2
S1 S2 C
S11 S21 D

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.17-24VDC 2 NO 24 VDC 600 0045

34
SRB-NA-R-C.17 (continued)

Wiring diagram L1
Example for dual-channel door
monitoring using two limit switches
Open
Closed **** (one with positive opening contacts) and
KB external reset button.
Reset
Dual-channel output, suitable for contact
KA reinforcement or contact multiplication,
using relays or contactors with positively
C S2 S1 S11 S21 X1 X2 13 23
guided contacts.
**** = Feedback loop

F1** Wire breakage and earth leakage in the


monitoring circuits are detected.
Trigger K1 KA
circuit ** Internal electronic fuse

K2 KB
K1 K2

D 14 24

KA KB

For further examples N


refer to page 36/37

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data
Fuse (power supply) internal electronic fuse, breaking current > 0.6 A, reset time approx. 1 sec.
(refer to page 157
for general data) Power consumption max. 2.5 W
Switching capacity (enabling contacts) 230 VAC, 4 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 4 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 50 ms
Drop-out delay ≤ 20 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.6 qmm, max. 2.5 qmm
Dimensions H/W/D 82 mm/22.5 mm/98.8 mm
Weight 190 g
Ambient operating temperature 0 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

35
SRB-NA-R-C.17 (continued)

Wiring example: Wiring example:


Input level Input level
S1 S2 C D S1 S2 C D
Dual-channel emergency Dual-channel door monitoring
stop switch according to according to EN 1088, one
Open
EN 60 204-1. limit switch with positive
opening contact. Closed
Wire breakage and earth
leakage in the emergency Emergency Reset Wire breakage and earth Reset
stop circuits are detected. switch off leakage in the door monitoring
Cross-shorts in the circuits are detected.
emergency stop circuits Cross-shorts in the emergency
are detected. stop circuits are detected.
With external reset button. With external reset button for
Safety category 3 or 4 increased safety requirements.
in accordance with Safety category 3 or 4
EN 954-1. in accordance with
EN 954-1.

S11 S21 X1 X2 S11 S21 X1 X2

Advice:
Change over from mode
"External reset with
trailing edge" to mode A1 (+) A2 (-) A1 (+) A2 (-)
"Automatic reset" is
achieved by altering the
polarity of the supply
voltage.
In "Automatic reset" the
reset button is eliminated.

C D D C

Trailing edge Automatic reset

36
SRB-NA-R-C.17 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output. L1
Dual-channel output.
L1
Suitable for contact Suitable for contact
reinforcement or contact KA * KB reinforcement or contact *
KA KB
multiplication, using relays D X2 13
multiplication, using relays
D X2 13 23
or contactors with or contactors with
positively guided contacts. KA positively guided contacts. KB

14 KB 14 24 KA

KA KB KA KB

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

37
SRB-NA-R-C.18
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 2 enabling outputs
☛ Suitable for semiconductor monitoring outputs

Features – Relay output: 2 NO – Input for emergency stop – Housing 22.5 mm, made of
or door monitoring thermoplastic in accordance with
– Reset, feedback loop UL-94-V-0, red RAL 3000
– LED’s for K1, K2, UB
– No cross-short recognition – DIN rail mounting
DIN EN 50 022

Approvals
ÜFZ
PR
ER
BG-

T.

98135 LR 13571-30 E 54284 (M)

Front view

C C1 23
13 S1 24
K1
SRB- UB
NA-R
-C.18 K2
X2 S2 X1
14 C1.1 D

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.18-24VDC 2 NO 24 VDC 600 0090
SRB-NA-R-C.18-24VAC 2 NO 24 VAC On request

38
SRB-NA-R-C.18 (continued)

Wiring diagram L1
Example for dual-channel door
Open
****
Reset
monitoring using two limit switches
Closed
(one with positive opening contacts) and
KB external reset button.
Dual-channel output, suitable for contact
KA reinforcement or contact multiplication,
using relays or contactors with positively
C C1.1 C1 S1 X1 X2 S2 13 23
guided contacts.
**** = Feedback loop
F1** Wire breakage and earth leakage in the
K2 K1 K2
K1 monitoring circuits are detected.
K1 KA
** Fuse M 0.5 A
(an external leading fuse M 0.25 A
is recommended)
K2 KB
K1 K2

D 14 24

KA KB

For further examples N


refer to page 40/41

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) M 0.25 A/250 V (internal M 0.5 A/250 V)
Power consumtion max. 2.5 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 10 ms
Drop-out delay ≤ 30 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.6 qmm, max. 2.5 qmm
Dimensions H/W/D 82 mm/22.5 mm/98.8 mm
Weight 190 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

39
SRB-NA-R-C.18 (continued)

Wiring example: Wiring example:


Input level Input level
L+(A1) C1 C1.1 X1 L+(A1) L-(A2) C1 C1.1 X1
Single-channel emergency Dual-channel emergency stop
stop switch according to switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency stop Emergency Reset
stop circuits are detected. switch off circuits are detected. switch off

With external reset button. Earth leakage at input A2 is


Safety category 2 detected in non grounded
in accordance with mains only.
EN 954-1. Cross-shorts in the emergency
stop circuits are detected.
With external reset button.
Safety category 3
in accordance with
EN 954-1.
C S1 S2 X2 C D S1 S2 X2

Wiring example: Wiring example:


Input level Input level
C1 C1.1 X1 L+(A1) C1 C1.1 X1
Dual-channel emergency Single-channel door
stop switch according to monitoring according to
EN 60 204-1. EN 1088 limit switch with ON

Wire breakage and earth positive opening contact. OFF


leakage in the emergency Emergency Reset Wire breakage and earth Reset
stop circuits are detected. switch off leakage in the door
Cross-shorts in the monitoring circuits are
emergency stop circuits are detected.
not detected. With external reset button
With external reset button. for increased safety
requirements.
Safety category 3 or 4
in accordance with Safety category 2
EN 954-1. in accordance with
EN 954-1.

S1 S2 X2 C S1 S2 X2

Wiring example: Wiring example:


Input level Input level
C1.1 X1 C1 C1.1 X1
C1
Dual-channel door Dual-channel triggering
monitoring according to using P-switching
Open
EN 1088, one limit switch semiconductors.
with positive opening Closed
Wire breakage and earth
contact. leakage in the monitoring Reset
Reset
Wire breakage and earth circuits are detected.
leakage in the door With external reset button.
monitoring circuits are
detected. Safety category 3 or 4
in accordance with
Cross-shorts in the EN 954-1.
emergency stop circuits are
not detected.
With external reset button
for increased safety
requirements.
Safety category 3 or 4 S1 S2 X2 S1 S2 X2
in accordance with
EN 954-1.

40
SRB-NA-R-C.18 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1
Dual-channel output
L1
Suitable for contact Suitable for contact
reinforcement or contact KA * KB reinforcement or contact KA
* KB
multiplication, using relays X1 X2 13
multiplication, using relays
X1 X2 13 23
or contactors with or contactors with
positively guided contacts. KA positively guided contacts. KB

14 KB 14 24
KA

KA KB KA KB

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

41
SRB-NA-R-C.36
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 2 enabling outputs
☛ Selectable extras:
– Trailing edge function
– Auto reset
☛ Suitable for semiconductor monitoring outputs

Features – Relay output: 2 NO – Input for emergency stop – Housing 22.5 mm, made of
or door monitoring thermoplastic in accordance with
– Reset, feedback loop UL-94-V-0, red RAL 3000
– LED’s for K1, K2
– No cross-short recognition – DIN rail mounting
DIN EN 50 022

Approvals
ÜFZ
PR
ER
BG-

T.

99103 LR 13571-30 E 54284 (M)

Front view

13 23 X1
14 24 X2
K2
SRB-
NA-R-
K1 C.36
S1 S2 C
C1 X3 D

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.36-24VDC 2 NO 24 VDC 600 0067

42
SRB-NA-R-C.36 (continued)

Wiring diagram L1
Example for dual-channel door
monitoring using two limit switches
Open
Closed
**** (one with positive opening contacts) and
external reset button.
KB
Reset Dual-channel output, suitable for contact
KA reinforcement or contact multiplication,
using relays or contactors with positively
C C1 S1 S2 X1 X2 X3 13 23
guided contacts.
**** = Feedback loop
F1
**
Wire breakage and earth leakage in the
K1 K2 monitoring circuits are detected.
K1
KA ** Internal electronic fuse
Trigger circuit

K2
K1 K2 KB

D 14 24

KA KB

For further examples N


refer to page 44/45

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data
Fuse (power supply) internal electronic fuse, breaking current > 0.6 A, reset time approx. 1 sec.
(refer to page 157
for general data) Power consumption max. 2.5 W
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 330 ms/720 ms (Reset /Auto Reset)
Drop-out delay ≤ 20 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.6 qmm, max. 2.5 qmm
Dimensions H/W/D 82 mm/22.5 mm/98.8 mm
Weight 190 g
Ambient operating temperature 0 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

43
SRB-NA-R-C.36 (continued)

Wiring example: Wiring example:


Input level Input level
C1 S1 X1 C1 C1 X1
Single-channel emergency Dual-channel emergency
stop switch according to stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency Emergency Reset
stop circuits are detected. switch off stop circuits are detected. switch off

With external reset button. Cross-shorts in the


Safety category 2 emergency stop circuits are
in accordance with not detected.
EN 954-1. With external reset button.
Safety category 3 or 4
in accordance with
EN 954-1.

S1 S2 X2 S1 S2 X2

Wiring example: Wiring example:


Input level Input level
C1 S1 X1 C1 C1 X1
Single-channel door Dual-channel door
monitoring according to monitoring according to
Open Open
EN 1088 one limit switch EN 1088 one limit switch
with positive opening Closed with positive opening Closed
contact. contact.
Reset Reset
Wire breakage and earth Wire breakage and earth
leakage in the door leakage in the door
monitoring circuits are monitoring circuits are
detected. detected.
With external reset button Cross-shorts in the door
for increased safety monitoring circuits are not
requirements. detected.
Safety category 2 With external reset button
in accordance with for increased safety
EN 954-1. requirements.

S1 S2 X2 Safety category 3 or 4
S1 S2 X2
in accordance with
EN 954-1.

Wiring example: Advice:


Input level
C1 C1 X1 For "Automatic Reset" X1 X1
Dual-channel triggering apply jumper X1-X3.
using P-switching
semiconductors. When using external reset
button (connected to X1-
Wire breakage and earth X2), unit is triggered by
leakage in the door Reset trailling edge function. Reset
monitoring circuits are
detected. Reset button wired in
series to feedback loop.
With external reset. KA KA
Safety category 3 or 4
in accordance with
EN 954-1.
KB KB

S1 S2 X2 X2 X3

44
SRB-NA-R-C.36 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1
Dual-channel output
L1
Suitable for contact Suitable for contact
reinforcement or contact KA * KB reinforcement or contact KA
* KB
multiplication, using relays X1 X3 13
multiplication, using relays
X1 X3 13 23
or contactors with or contactors with
positively guided contacts. KA positively guided contacts. KB

14 KB 14 24 KA

KA KB KA KB

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

45
46
SRB modules 22.5 wide,
STOP category 1

3
☛ Enabling outputs drop-out delayed: 1 sec.
☛ 3 enabling outputs and 1 monitoring output
☛ max. load current: 6 Ampere
☛ max. safety category: 4
☛ 1- or 2-channel triggering
☛ Cross-short recognition
☛ 24 VDC/VAC-Version
☛ Approvals: BG, CSA, UL

Options

0 . 1*
t. t /2
ca ca A) A ) e l1 n ng ts
P P
T O TO nt ( uts nt ( ry a nn itio geri ion npu
S S r e p r e o c h n i g c t i
s s ur out ur teg ∞ g r un red
ut ut co l t t
u tp utp ad c C ad c y ca ow t re nne ge f owe t tes AC l
al ova val
o o l o y N l o et nd or ha ed p ar / V o v r
g
in in
g x. ar x. af wi sh -c g al st C C AC AC pr pp pro
a bl abl ma xili ma x. s me oss- ngle ailin tern itial VD VA 5 V 0 V ap A a ap
u a
Type En En => A => m Ti C r Si Tr Ex In 24 48 11 23 BG CS UL
SRB-NA-R-C.16 3 6 1 2 3 ✚ ✚ ● ● ✔ ✔ ✔ refer to page 48
* = drop-out delay: 1 sec.; ✚ = fixed; ● = selectable; ✔ = approved

47
47
SRB-NA-R-C.16, ...-C.16/1
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 3 enabling outputs and 1 monitoring output
☛ Drop-out delayed (1 sec.) enabling outputs
☛ STOP category 1
☛ Cross-short recognition

Features – Relay output: 3 NO, 1NC – NC contacts for monitoring – LED’s for K1, K2, UB
(Auxiliary NC for monitoring (SRB-NA-R-C.16/1: in series)
must not be used in safety (SRB-NA-R-C.16: in parallel) – Housing 22.5 mm, made of
enabling circuits!) thermoplastic in accordance with
– Input for emergency stop UL-94-V-0, red RAL 3000
– Reset, feedback loop or door monitoring
– DIN rail mounting
DIN EN 50 022

Approvals
ÜFZ
PR
ER
BG-

T.

97203 LR 13571-30 E 54284 (M)

Front view

13 23 33
14 24 34
K2
UB SRB-
NA-R
K1 -C.16
41 X1 C
42 X2 D

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.16-24VDC 3 NO /1 NC 24 VDC 600 0035
SRB-NA-R-C.16/1-24VDC 3 NO /1 NC 24 VDC 600 0034
SRB-NA-R-C.16-24VAC 3 NO /1 NC 24 VAC On request

48
SRB-NA-R-C.16, ...-C.16/1 (continued)

Wiring diagram Example for dual-channel door


3
L-(A2) L+(A1) L1
monitoring using two limit switches
Open (one with positive opening contacts) and
Closed
KB
external reset button.
Reset Dual-channel output, suitable for contact
****
KA
reinforcement or contact multiplication,
using relays or contactors with positively
C X1 X2 13 23 33 41 41* guided contacts.
**** = Feedback loop
Wire breakage and earth leakage in the
K2 K1 K1 K2 monitoring circuits are detected.
KA
Earth leakage at input D is detected only
K1
in mains with insulation leakage
monitoring.
KB
K1 K2 K2 An external leading fuse 0.5 A is
recommended.
D 14 24 34 42 42
* Monitoring contacts in series at
KA KB SRB-NA-R-C.16/1

For further examples N


refer to page 50/51

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) M 0.5 A/250 V
Power consumption max. 2.5 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Switching capacity (monitoring contacts) 24 V, 2 A ohmic (inductive with suitable suppression)
Fuse (monitoring contacts) 2 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 50 ms
Drop-out delay 1.1 s –20%/+20% (for UB = 24 VDC)
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.6 qmm, max. 2.5 qmm
Dimensions H/W/D 82 mm/22.5 mm/98.8 mm
Weight 190 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

49
SRB-NA-R-C.16, ...-C.16/1 (continued)

Wiring example: Wiring example:


Input level Input level
L+(A1) L-(A2) X1 L+(A1) L-(A2) X1
Single-channel emergency Dual-channel emergency
stop switch according to stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency Emergency Reset
stop circuits are detected. switch off stop circuits are detected. switch off
With external reset button. Cross-shorts in the
Safety category 2 emergency stop circuits are
in accordance with detected.
EN 954-1. With external reset button.
Safety category 3
in accordance with
EN 954-1.

C D X2 C D X2

Wiring example: Wiring example:


Input level Input level
Single-channel door L+(A1) L-(A2) X1 Dual-channel door L+(A1) L-(A2) X1
monitoring according to monitoring according to
EN 1088 limit switch with Open EN 1088, one limit switch Open
positive opening contact. with positive opening Closed
Closed contact.
Wire breakage and earth
leakage in the door Reset Wire breakage and earth Reset
monitoring circuits are leakage in the door
detected. monitoring circuits are
With external reset button detected.
for increased safety Cross-shorts in the door
requirements. monitoring circuits are
Safety category 2 detected.
in accordance with With external reset button
EN 954-1. for increased safety
requirements.
Safety category 3
C D X2 in accordance with C D X2
EN 954-1.

Safety relevant advice!


The drop-out delay features in the
SRB-NA-R-C.16 24 VDC refers to control
category 1 "tried and testet components
and principles" according to EN 954-1.

50
SRB-NA-R-C.16, ...-C.16/1 (continued)

Wiring example: Wiring example:


3
Power level Power level
Single-channel output L1
Dual-channel output
L1
Suitable for contact Suitable for contact
reinforcement or contact KA * KB reinforcement or contact KA * KB
multiplication, using relays X1 X2 13
multiplication, using relays
X1 X2 13 23
or contactors with or contactors with
positively guided contacts. KA positively guided contacts. KB

Drop-out delay: Drop-out delay:


Safety category 1 Safety category 1
in accordance with in accordance with
EN 954-1. EN 954-1.
14 KB 14 24 KA

KA KB KA KB

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

51
52
SRB modules 45 mm wide,
standard version,
STOP category 0

☛ max. 3 enabling outputs and 2 monitoring outputs


☛ max. load current: 6 Ampere
☛ max. safety category: 4
☛ 1- or 2-channel triggering
☛ Trailing edge function selectable 4
☛ Cross-short recognition selectable
☛ Semiconductor monitoring outputs selectable
☛ 24 VDC/VAC, 48 VAC, 115 VAC and 230 VAC versions
☛ Approvals: BG, CSA, UL

Options

0 .1
t. t /2
ca ca A) uts A) l1 n g
OP P
O nt ( utp nt ( ry n n io erin on puts
e
a t
S T S T e o e o h n i g g cti in
u ts uts curr /NO curr teg ∞ c cog l tri fun red t
tp tp d C d ca w re ne e we tes C l al l
ou g ou loa y N loa ety ndo ort han edg l po art /VA C C o va rov ova
g . r . a f i h c g a s t C C A r p p pr
in in x a x w s - A p
a bl abl ma xili ma x. s me oss- ngle ailin tern itial VD VA 5 V 0 V ap A a ap
u a L
Type En En => A => m Ti Cr Si Tr Ex In 24 48 11 23 BG CS U
SRB-NA-R-C.12 3 6 3 ✚ ✚ ● ● ✚ ✚ ✚ ✔ ✔ ✔ refer to page 54
SRB-NA-R-C.33 3 6 1 2 4 ✚ ● ● ● ✚ ✚ ✚ ✔ ✔ ✔ refer to page 58
SRB-NA-R-C.34 3 6 1/1 2 4 ✚ ● ● ● ● ✔ ✔ ✔ refer to page 62
✚ = fixed; ● = selectable; ● = selectable feature; ✔ = approved; ✔ = in preparation

53
SRB-NA-R-C.12
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 3 enabling outputs
☛ 3-channel triggering
☛ Different operating voltage
☛ Cross-short recognition

Features – Relay output: 3 NO – LED’s for K1, K2, UB – DIN rail mounting
DIN EN 50 022
– Reset, feedback loop – Housing 45 mm, made of
thermoplastic in accordance with
– Input for emergency stop UL-94-V-0, red RAL 3000
or door monitoring

Approvals
ÜFZ
PR
ER
BG-

T.

96158 LR 13571-30 E 54284 (M)

Front view
C S1.1 13 23 33
K1
UB
K2

SRB-NA-
R-C.12

D S2.1 14 24 34

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.12-24VDC 3 NO 24 VDC 600 0023
SRB-NA-R-C.12-48VAC 3 NO 48 VAC 600 0059
SRB-NA-R-C.12-115VAC 3 NO 115 VAC 600 0052
SRB-NA-R-C.12-230VAC 3 NO 230 VAC 600 0050

54
SRB-NA-R-C.12 (continued)

Wiring diagram L-(A2) L+(A1) L1


Example for dual-channel door
monitoring using two limit switches
Open
(one with positive opening contacts) and
Closed
KB external reset button.
Reset Dual-channel output, suitable for contact
****
KA
reinforcement or contact multiplication,
C S1.1 S2.1 13 23 33
using relays or contactors with positively
guided contacts. 4
F1** **** = Feedback loop
Wire breakage and earth leakage in the
K2 K1 K1 K2 monitoring circuits are detected.
K1 KA
Earth leakage at input D is detected only
in mains with insulation leakage
monitoring.
K2 KB
K1 K2 ** Fuse M 0.5 A
(an external leading fuse M 0.25 A
D 14 24 34 is recommended)

KA KB

For further examples N


refer to page 56/57

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 48 VAC, 115 VAC, 230 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) M 0.25 A/250 V (internal M 0.5 A/250 V)
Power consumption max. 2.5 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 30 ms
Drop-out delay ≤ 50 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.6 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/45 mm/127 mm
Weight 280 g (360 g at 48 VAC, 115 VAC and 230 VAC versions)
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

55
SRB-NA-R-C.12 (continued)

Wiring example: Wiring example:


Input level Input level
L+(A1) L-(A2) S1.1 L+(A1) L-(A2) S1.1
Single-channel emergency Dual-channel emergency stop
stop switch according to switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency stop Emergency Reset
stop circuits are detected. switch off circuits are detected. switch off
With external reset button. Earth leakage at input A2 is
Safety category 2 detected in non grounded
in accordance with mains only!
EN 954-1. Cross-shorts in the emergency
stop circuits are detected.
With external reset button.
Safety category 3
in accordance with
EN 954-1.
C D S2.1 C D S2.1

Wiring example: Wiring example:


Input level Input level
L+(A1) L-(A2) S1.1 L+(A1) L-(A2) S1.1
Single-channel door Dual-channel door
monitoring according to monitoring according to Open
Open
EN 1088 limit switch with EN 1088, one limit switch
Closed Closed
positive opening contact. with positive opening
Wire breakage and earth contact.
Reset Reset
EIN
leakage in the door Wire breakage and earth
monitoring circuits are leakage in the door
detected. monitoring circuits are
With external reset button detected.
for increased safety Cross-shorts in the door
requirements. monitoring circuits are
Safety category 2 detected.
in accordance with With external reset button
EN 954-1. for increased safety
requirements.
C D S2.1 Safety category 3 C D S2.1
in accordance with
EN 954-1.

56
SRB-NA-R-C.12 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1
Dual-channel output
L1
Suitable for contact Suitable for contact
reinforcement or contact KA * KB reinforcement or contact *
KA KB
multiplication, using relays 13
multiplication, using relays
S1.1 S2.1 S1.1 S2.1 13 23
or contactors with
positively guided contacts. KA
or contactors with
positively guided contacts. KB 4

14 KB 14 24 KA

KA KB KA KB

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

57
SRB-NA-R-C.33
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 2 enabling outputs and 1 monitoring output
☛ Different operating voltage

Features – Relay output: 3 NO, 1 NC – Input for emergency stop – DIN rail mounting
(Auxiliary NC for monitoring or door monitoring DIN EN 50 022
must not be used in safety
enabling circuits!) – LED’s for K1, K2, UB, UI

– Reset, feedback loop – Housing 45 mm, made of


thermoplastic in accordance with
UL-94-V-0, red RAL 3000

Approvals
ÜFZ
PR
ER
BG-

T.

Pending LR 13571-30 E 54284 (M)

Front view
41 33 23 13 A1
T11 T12 T12 T22
SRB-NA-R-
C.33 UB U i

Fuse K1 K2

T33 T34 PE X1 X2
42 34 24 14 A2

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.33-24V 3 NO/1 NC 24 VDC/VAC 600 0001
SRB-NA-R-C.33-48VAC 3 NO/1 NC 48 VAC On request
SRB-NA-R-C.33-115VAC 3 NO/1 NC 115 VAC 600 0006
SRB-NA-R-C.33-230VAC 3 NO/1 NC 230 VAC 600 0002

58
SRB-NA-R-C.33 (continued)

Wiring diagram L1
Example for dual-channel door
monitoring using two limit switches
OPEN
(one with positive opening contacts) and
CLOSED
KB external reset button.

**** Reset
Dual-channel output, suitable for contact
KA reinforcement or contact multiplication,

A1 T11 X2 X1 T34 T33 T12 T12 T22 13 23 33 41


using relays or contactors with positively
guided contacts. 4
F1 **** = Feedback loop
F2 Wire breakage and earth leakage in the
Trigger
circuit monitoring circuits are detected.
K1 K2 K1 KA

K1 K2
K2 KB

A2 PE 14 24 34 42

KA KB

N
For further examples
refer to page 60/61

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC, 48 VAC, 115 VAC, 230 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) F2: T 0.125 A/250 V (internal F1: TM 0.25 A/250 V)
Power consumption max. 2.5 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Switching capacity (monitoring contacts) 24 V, 2 A ohmic (inductive with suitable suppression)
Fuse (monitoring contacts) 2 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 20 ms
Drop-out delay ≤ 50 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/B/T 83 mm/45 mm/140 mm
Weight 190 g (280 g at 48 VAC, 115 VAC and 230 VAC versions)
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

59
SRB-NA-R-C.33 (continued)

Wiring example: Wiring example:


Input level Input level
T11 T12 T33 X1 T11 T11 T33 X1
Single-channel emergency Dual-channel emergency stop
stop switch according to switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency stop Emergency Reset
stop circuits are detected. switch off circuits are detected. switch off

With external reset button. Cross-shorts in the emergency


Safety category 2 stop circuits are not detected.
in accordance with With external reset button.
EN 954-1. Safety category 3 or 4
in accordance with
EN 954-1.

T12 T22 T34 X2 T12 T22 T34 X2

Wiring example: Wiring example:


Input level Input level
T11 T12 T33 X1 T11 T11 T33 X1
Single-channel door Dual-channel door
monitoring according to monitoring according to
Open Open
EN 1088 limit switch with EN 1088, one limit switch
positive opening contact. Closed with positive opening Closed

Wire breakage and earth contact.


Reset Reset
leakage in the door Wire breakage and earth
monitoring circuits are leakage in the door
detected. monitoring circuits are
With external reset button detected.
for increased safety Cross-shorts in the door
requirements. monitoring circuits are not
Safety category 2 detected.
in accordance with With external reset button
EN 954-1. for increased safety
requirements.
Safety category 3 or 4
T12 T22 T34 X2 in accordance with T12 T22 T34 X2
EN 954-1.

60
SRB-NA-R-C.33 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1 Dual-channel output L1

Suitable for contact


KA
* KB
Suitable for contact *
reinforcement or contact reinforcement or contact KA KB
multiplication, using relays X1 X2 13 multiplication, using relays X1 X2 13 23
or contactors with
positively guided contacts.
KA or contactors with
positively guided contacts.
KB
4
14 KB 14 24 KA

KA KB
KA KB

N N

* Feedback loop * Feedback loop

61
SRB-NA-R-C.34
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 3 enabling outputs and 2 monitoring outputs
☛ Selectable extras:
– Trailing edge function
– Auto reset

Features – Relay output: 3 NO, 2 NO/NC – Input for emergency stop – DIN rail mounting
(Auxiliary NO/NC for monitoring or door monitoring DIN EN 50 022
must not be used in safety
enabling circuits!) – LED’s for K1, K2, UB, UI

– Reset, feedback loop – Housing 90 mm, made of


thermoplastic in accordance with
UL-94-V-0, red RAL 3000

Approvals
ÜFZ
PR
ER
BG-

T.

00063 LR 13571-30 E 54284 (M)

Front view
13 23 33 41 53
A1 T11 T12 T22 X5
SRB-NA-R-
C.34-24V UB U i

Fuse K2 K3

T33 T34 X3 X4 A2
14 24 34 42 54

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.34-24V 3 NO/1 NC/1 NO 24 VDC/VAC 600 0087

62
SRB-NA-R-C.34 (continued)

Wiring diagram L1 Example for dual-channel door


Open
monitoring using two limit switches
Closed
(one with positive opening contacts) and
external reset button.
Reset
**** Dual-channel output, suitable for contact
KA KB reinforcement or contact multiplication,
A1 T11 T33 X4 X5 X3 T34 T12 T22 13 23 33 41 53
using relays or contactors with positively
guided contacts. 4
F1 **** = Feedback loop
F2 K3 K2 K2 K3 Wire breakage and earth leakage in the
monitoring circuits are detected.
K2 KA
K2A
Trigger circuit
K3 K2 K3

K3 KB
K1 K2 K2A K3 K3A K3A

A2 14 24 34 42 54

KA KB

N
For further examples
refer to page 64/65

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) F2: T 0.25 A/250 V (internal F1: T 0.5 A/250 V)
Power consumption max. 4 W; 4.3 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
DC 13: 24 V/2 A; AC 15: 230 VAC/3 A
Fuse (enabling contacts) 6 A slow blowing
Switching capacity (monitoring contacts) max. 24 VDC/2 A ohmic (inductive with suitable suppression)
Fuse (monitoring contacts) 2 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 20 ms
Drop-out delay ≤ 30 ms
Contact material / contacts AgCdO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/45 mm/140 mm
Weight 200 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

63
SRB-NA-R-C.34 (continued)

Wiring example: Wiring example:


Input level Input level
T11 T12 T33 X3 T11 T11 T33 X3
Single-channel emergency Dual-channel emergency stop
stop switch according to switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency stop Emergency Reset
stop circuits are detected. switch off circuits are detected. switch off
With external reset button. Cross-shorts in the emergency
Safety category 2 stop circuits are not detected.
in accordance with With external reset button.
EN 954-1. Safety category 3 or 4
in accordance with
EN 954-1.

T12 T22 T34 X4 T12 T22 T34 X4

Wiring example: Wiring example:


Input level Input level
T11 T12 T33 X3 T11 T11 T33 X3
Single-channel door Dual-channel door
monitoring according to Open
monitoring according to Open
EN 1088 limit switch with EN 1088, one limit switch
Closed Closed
positive opening contact. with positive opening
Wire breakage and earth contact.
Reset Reset
leakage in the door Wire breakage and earth
monitoring circuits are leakage in the door
detected. monitoring circuits are
With external reset button detected.
for increased safety Cross-shorts in the
requirements. emergency stop circuits are
Safety category 2 not detected.
in accordance with With external reset button
EN 954-1. for increased safety
requirements.
Safety category 3 or 4
T12 T22 T34 X4 T12 T22 T34 X4
in accordance with
EN 954-1.

Advice: Wiring example:


Input level
Time window infinite
T 33 X3 T 33 X3
channel 1 and channel 2 Start with trailing edge
via cable link between function.
X3/X4 and T33/T34.
Module is activated after
For external reset connect release of the reset button.
reset button to X3/X4.
This prevents tampering of Reset
the reset button which
could lead to an automatic
reset.

T 34 X4 T 34 X5 X4

64
SRB-NA-R-C.34 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1 Dual-channel output L1
Suitable for contact * Suitable for contact
reinforcement or contact
KA KB
reinforcement or contact KA
* KB
multiplication, using relays X3 X4 13 multiplication, using relays X3 X4 13 23
or contactors with
positively guided contacts.
KA
or contactors with
positively guided contacts. KB
4
14 KB 14 24
KA

KA KB KA KB

N N

* Feedback loop * Feedback loop

65
66
SRB modules 45 mm wide,
standard versions,
STOP category 1

☛ 4 enabling outputs and 1 monitoring output


☛ 1 enabling output drop-out delayed: 0 ... 30 sec.
☛ max. load current: 6 Ampere
☛ max. safety category: 4
☛ 1- or 2-channel triggering
☛ Trailing edge function selectable
☛ Cross-short recognition selectable
☛ Semiconductor monitoring outputs selectable
☛ 24 VDC/VAC version
☛ Approvals: BG, CSA, UL 5

Options

0 1* 2
a t. at. 1/
c c A) A ) el on ring n
P P ( ( n
O O t ts t n ti e o ts
s ST s ST rren tpu rren gory cha gni rigg ncti inpu
t
pu pu
t cu ou cu te ∞ eco el t fu er st C
a
ut out oad NC oad ty c dow rt r ann dge pow rt te VA l al l
o l ry . l fe in ho ch e a / C C o va rov ova
g g . a g a l s t C C A r p p pr
in in x a x w s - A p
a bl abl ma xili ma x. s me oss- ngle ailin tern itial VD VA 5 V 0 V ap A a ap
a
Type En En => Au => m Ti Cr Si Tr Ex In 24 48 11 23 BG CS UL
SRB-NA-R-C.35/WE 3 1 6 1 2 4 ● ● ● ● ✔ ✔ ✔ refer to page 68
SRB-NA-R-C.35/KE 3 1 6 1 2 4 ● ● ● ● ✔ ✔ ✔ refer to page 68
SRB-NA-R-C.35/
WE.QS 3 1 6 1 2 4 ✚ ● ● ● ✔ ✔ ✔ refer to page 68
SRB-NA-R-C.35/
KE.QS 3 1 6 1 2 4 ✚ ● ● ● ✔ ✔ ✔ refer to page 68
* = drop-out delay: 0 ... 30 sec.: setting by manufacturer (WE)/setting by customer (KE);
✚ = fixed; ● = selectable; ● = selectable feature; ✔ = in preparation

67
SRB-NA-R-C.35
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 4 enabling outputs and 1 monitoring output
☛ 1 enabling output drop-out delayed: 0 ... 30 seconds
☛ Selectable extras:
– Trailing edge function
– Auto reset

Features – Relay output: 4 NO, 1 NC – Reset, feedback loop – Housing 45 mm, made of
1 NO drop out delayed thermoplastic in accordance with
(Auxiliary NC for monitoring – Input for emergency stop UL-94-V-0, red RAL 3000
must not be used in safety or door monitoring
enabling circuits!) – DIN rail mounting
– LED’s for K2, K3, K4, K5, UB, Ui DIN EN 50 022

Approvals
ÜFZ
PR
ER
BG-

T.

Pending LR 13571-30 E 54284 (M)

Front view
13 23 33 47 51
A1 T11 T12 T22 X5
SRB-NA-R-
C.35 t ...... s
UB U i

Fuse K2 K3

K4 K5
A2 A2.1 T33 T34 UT
14 24 34 48 52

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.35/WE-24V 3 NO/1 NO/1 NC 24 VDC/VAC 600 0763
SRB-NA-R-C.35/KE-24V 3 NO/1 NO/1 NC 24 VDC/VAC 600 0762
SRB-NA-R-C.35/WE-QS-24V 3 NO/1 NO/1 NC 24 VDC/VAC On request
SRB-NA-R-C.35/KE.QS-24V 3 NO/1 NO/1 NC 24 VDC/VAC On request

68
SRB-NA-R-C.35 (continued)

Wiring diagram L1 Example for dual channel door


Open
monitoring using two limit switches
**** Closed
(one with positive opening contacts) and
external reset button.
KB
Reset Dual-channel output, suitable for contact
KA
reinforcement or contact multiplication,
using relays or contactors with positively
A1 T11 T33 T34 X5 T12 T22 UT 13 23 33 47 51 guided contacts.
**** = Feedback loop
F1 K2 K1
trailing
F2 edge Wire breakage and earth leakage in the
K3 K1 K2 K1 K4
monitoring circuits are detected.
K2
K4 K2
KA
K3
K5 TIMER TIMER

K1 K2 K3 K4 K5
K4
K5
K4

KB
5
A2 A2.1 14 24 34 48 52

KA KB

For further examples N


refer to page 70/71

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) F2: T 0.25 A/250 V (internal F1: T 0.5 A/250 V)
Power consumption max. 3.5 W; 4.7 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
DC 13: 24 V/2 A; AC 15: 230 VAC/3 A
Fuse (enabling contacts) 6 A slow blowing
Switching capacity (monitoring contacts) max. 24 V/2 A ohmic (inductive with suitable suppression)
Fuse (monitoring contacts) 2 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 200 ms
Drop-out delay ≤ 30 ms
Contact material / contacts AgCdO self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/45 mm/140 mm
Weight 280 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

69
SRB-NA-R-C.35 (continued)

Wiring example: Wiring example:


Input level Input level
T11 T12 T33 T33 T11 T11 T33 T33
Single-channel emergency Dual-channel emergency
stop switch according to stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency Emergency Reset
stop circuits are detected. switch off stop circuits are detected. switch off

With external reset button. Cross-shorts in the


Safety category 2 emergency stop circuits are
in accordance with not detected.
EN 954-1. With external reset button.
Safety category 3 or 4
in accordance with
EN 954-1.

T12 T22 T34 UT T12 T22 T34 UT

Wiring example: Wiring example:


Input level Input level
T11 T12 T 33 T33 T11 T11 T33 T33
Single-channel door Dual-channel door
Open Open
monitoring according to monitoring according to
EN 1088 limit switch with Closed EN 1088 one limit switch Closed
positive opening contact. with positive opening
Reset contact. Reset
Wire breakage and earth
leakage in the door Wire breakage and earth
monitoring circuits are leakage in the door
detected. monitoring circuits are
With external reset button detected.
for increased safety Cross-shorts in the door
requirements. monitoring circuits are
Safety category 2 not detected.
in accordance with With external reset button
EN 954-1. for increased safety
requirements.
Safety category 3 or 4
T12 T22 T34 UT T12 T22 T34 UT
in accordance with
EN 954-1.

Wiring example: Wiring example:


Input level Input level
T11 A2.1 T33 T33 T11 A2.1 T 33 T33
(Type QS) (Typ QS)
Open
Dual-channel emergency Dual-channel door
Closed
stop switch according to monitoring according to
EN 60 204-1. EN 1088, one limit switch
Reset
Wire breakage and earth Emergency Reset with positive opening
leakage in the emergency switch off contact.
stop circuits are detected. Wire breakage and earth
Cross-shorts in the leakage in the door
emergency stop circuits are monitoring circuits are
detected. detected.

With external reset button. Cross-shorts in the door


monitoring circuits are
Safety category 3 or 4 detected.
in accordance with
EN 954-1. With external reset button
for increased safety
T12 T22 T34 UT
requirements.
T12 T22 T34 UT
Safety category 3 or 4
in accordance with
EN 954-1.

70
SRB-NA-R-C.35 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1 Dual-channel output L1
Suitable for contact KB Suitable for contact KB
reinforcement or contact KA KC reinforcement or contact KA KC
multiplication, using relays * multiplication, using relays *
13 47 13 23 47
or contactors with or contactors with
positively guided contacts. T33 T34 KB positively guided contacts. T33 T34 KB

14 48 KA 14 24 48 KA

KA KB KC KA KB KC

N N
5
* Reset button wired in * Reset button wired in
series to feedback loop. series to feedback loop.

Advice: Wiring example:


Input level
The supply for the T33
electronic timers of the T33
Start with trailing edge
delayed enabeling output function.
47/48 is on terminal UT.
Module is activated after
For a controled operation release of the reset button.
in case of power lost,
This prevents tampering of Reset
supply external power to
the reset button which
terminal UT.
could lead to an automatic
Warning: reset.
If external voltage
(24 VDC, no ripple) is
applied on terminal UT, a
fuse 0.1 A quick blow shall
be provided.

UT T34 X5

Advice:
Drop-out delay of the 47
enabling output 47/48
adjustable 0 ... 30 sec.
Enabling output 47/48
corresponds to Stop-
category 1 in accordance
with EN 60 204-1.
Enabling output 13/14,
23/24 and 33/34
corresponds to Stop-
category 0 in accordance
with EN 60 204-1.

48

71
72
SRB modules 45 mm wide,
multifunctional version,
STOP category 0

☛ max. 5 enabling outputs and 1 monitoring output


☛ 2 semiconductor outputs
☛ max. load current: 6 Ampere
☛ max. safety category: 4
☛ 1- or 2-channel triggering
☛ Trailing edge function selectable
☛ Cross-short recognition selectable
☛ Semiconductor monitoring outputs selectable
☛ Initial start test selectable
☛ 24 VDC/VAC version
☛ Approvals: BG, CSA, UL

Options

0 .1 2
t. t 1/
ca ca A) uts A) el on ring n s
P P ( t p ( n ut
S TO STO ent ou ent ory han niti igge ctio inp
s s urr NO ur
r c
teg ∞ co l t
g r un red
ut ut t
u tp utp ad c C/ ad c y ca ow t re nne ge f owe t tes AC al
l
va al
o o o
l ry N l o t d r a d
e in ho ch g e al p sta C/V C r ov pro rov
g g . . f C C r
A pp ap pp
lin lin ax lia ax sa w s-s e- in n l D A A
n ab nab > m uxi > m ax. ime ros ingl rail xter itia 4 V 8 V 15 V 30 V G a SA L a
Type E E = A = m T C S T E I n 2 4 1 2 B C U
SRB-NA-R-C.20 5 4 1 0,5 4 ✚ ● ● ● ✔ ✔ ✔ refer to page 74
SRB-NA-R-C.22 3 4 1 0,5 4 ✚ ● ● ● ✔ ✔ ✔ refer to page 78
SRB-NA-R-C.27 3 6 1/2 2/0,1 4 ✚ ● ● ● ● ● ✔ ✔ ✔ refer to page 82
✚ = fixed; = DIP switch setting; ● = selectable; ● = selectable feature; ✔ = approved; ✔ = in preparation

73
SRB-NA-R-C.20
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 5 enabling outputs and 1 monitoring output
☛ Selectable extras:
– Trailing edge function
– Auto reset
– Cross-short recognition

Features – Relay output: 5 NO, 1 NC – Input for emergency stop – DIN rail mounting
(Auxiliary NC for monitoring or door monitoring DIN EN 50 022
must not be used in safety
enabling circuits!) – LED’s for K1, K2, K3, K4, UB, Ui

– Reset, feedback loop – Housing 45 mm, made of


thermoplastic in accordance with
UL-94-V-0, red RAL 3000

Approvals
ÜFZ
PR
ER
BG-

T.

98107 LR 13571-30 E 54284 (M)

Front view
13 23 33 43 53
C C1 S1 X1 X2
SRB-NA-R-
C.20-24V UB U i

Fuse K1 K3

K2 K4
D D1 S2 X2.1 L62
14 24 34 44 54

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.20-24V 5 NO/1 NC 24 VAC/VDC 600 0048

74
SRB-NA-R-C.20 (continued)

Wiring diagram Example for dual-channel door


L1 monitoring using two limit switches
Open
**** (one with positive opening contacts) and
Closed
external reset button.
KB
Reset Dual-channel output, suitable for contact
KA
reinforcement or contact multiplication,
using relays or contactors with positively
C C1 X2 X2.1 S1 X1 S2 13 23 33 43 53
guided contacts.
**** = Feedback loop

F2 K1 K2 Wire breakage and earth leakage in the


* Trigger K1 monitoring circuits are detected.
F1 circuit
K1 KA
K3 K4 K3 * Fuse F2 (front cover) 1 A, Fuse F1
(internal) 1.25 A
K2
K2 KB
K1 K3 K2 K4 K4

D D1 L62 14 24 34 44 54

KA KB
For further examples
N
refer to page 76/77

6
Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical Data 24 VAC –15%/+6%
(Refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) T 1.0 A/250 V (internal T 1.25 A/250 V)
Power consumption max. 3.6 VA, plus monitoring output L62
Switching capacity (enabling contacts) 230 VAC, 4 A ohmic (inductive with suitable suppression)
NO 43/44, 53/54: DC 13: 24 VDC/2 A; AC 15: 230 VAC/3 A
Fuse (enabling contacts) 4 A slow blowing
Switching capacity (monitoring contacts) L62: max. 500 mA
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 30 ms
Drop-out delay ≤ 60 ms
Contact material / contacts AgSnO, AgNi self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/45 mm/140 mm
Weight 460 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

75
SRB-NA-R-C.20 (continued)

Wiring example: Wiring example:


Input level Input level
C1 S1 X1 C1 C1 X1
Single-channel emergency Dual-channel emergency stop
stop switch according to switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency stop Emergency Reset
stop circuits are detected. switch off circuits are detected. switch off

With external reset button. Cross-shorts in the emergency


Safety category 2 stop circuits are not detected.
in accordance with With external reset button.
EN 954-1. Safety category 3 or 4
in accordance with
EN 954-1.
QS QS
1 0 1 0

S1 S2 X2 S1 S2 X2

Wiring example: Wiring example:


Input level Input level
C1 D1 X1 C1 S1 X1
Dual-channel emergency stop Single-channel door
switch according to monitoring according to
Open
EN 60 204-1. EN 1088 limit switch with
Wire breakage and earth positive opening contact. Closed

leakage in the emergency stop Emergency Reset Wire breakage and earth Reset
circuits are detected. switch off leakage in the door
Cross-shorts in the emergency monitoring circuits are
stop circuits are detected. detected.

To enable cross-short With external reset button


monitoring: Set switch QS for increased safety
(bottom of housing) to 1. requirements.

With external reset button. Safety category 2 or 4


QS in accordance with QS
Safety category 3 or 4 EN 954-1.
in accordance with 1 0 1 0
EN 954-1.
S1 S2 X2 S1 S2 X2

Wiring example: Wiring example:


Input level Input level
C1 D1 X1 C1 C1 X1
Dual-channel door monitoring Dual-channel door monitoring
according to EN 1088, one Open
according to EN 1088, one Open
limit switch with positive limit switch with positive
Closed Closed
opening contact. opening contact.
Wire breakage and earth Reset Wire breakage and earth Reset
leakage in the door monitoring leakage in the door monitoring
circuits are detected. circuits are detected.
Cross-shorts in the door Cross-shorts in the door
monitoring circuits are monitoring circuits are
detected. not detected.
To enable cross-short With external reset button for
monitoring: Set switch QS increased safety requirements.
(bottom of housing) to 1. QS Safety category 3 or 4 QS
With external reset button for 1 0 in accordance with 1 0
increased safety requirements. EN 954-1.
Safety category 3 or 4 S1 S2 X2 S1 S2 X2
in accordance with
EN 954-1.

76
SRB-NA-R-C.20 (continued)

Advice:
For "Automatic Reset" X1
apply jumper X1-X2.
When using external Reset
button (connect to X1-
X2.1), unit is triggered by
trailing edge function. Reset
Reset button wired in
series to feedback loop.

X2.1

Wiring example: Wiring example:


Power level Power level
Single-channel output L1
L1
Dual-channel output L1
L1
6
Suitable for contact Suitable for contact
KA
KA ** KB
KB **
reinforcement or contact reinforcement or contact KA
KA KB
KB
multiplication, using relays X1
X1 X2
X2 13
13
multiplication, using relays X1 X2 13 23
X1 X2 13 23
or contactors with or contactors with
KA
KA KB
positively guided contacts. positively guided contacts. KB

14
14 KB 14
14 24
24
KB KA
KA

KA
KA KB
KB KA KB
KA KB

N
N N
N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

77
SRB-NA-R-C.22
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 3 enabling outputs and 1 monitoring output
☛ Selectable extras:
– Trailing edge function
– Auto reset
– Cross-short recognition

Features – Relay output: 3 NO, 1 NC – Input for emergency stop – DIN rail mounting
(Auxiliary NC for monitoring or door monitoring DIN EN 50 022
must not be used in safety
enabling circuits!) – LED’s for K1, K2, UB, Ui

– Reset, feedback loop – Housing 45 mm, made of


thermoplastic in accordance with
UL-94-V-0, red RAL 3000

Approvals
ÜFZ
PR
ER
BG-

T.

98107 LR 13571-30 E 54284 (M)

Front view
13 23 33
C C1 S1 X1 X2
SRB-NA-R-
C.22-24V UB U i

Fuse K1

K2
D D1 S2 X2.1 L62
14 24 34

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.22-24V 3 NO/1 NC 24 VAC/VDC 600 0049

78
SRB-NA-R-C.22 (continued)

Wiring diagram L1
Example for dual-channel door
monitoring using two limit switches
Open
**** (one with positive opening contacts) and
Closed
KB external reset button.
Reset
Dual-channel output, suitable for contact
KA reinforcement or contact multiplication,
using relays or contactors with positively
C C1 X2 X2.1 S1 X1 S2 13 23 33
guided contacts.
**** = Feedback loop
F2 K1 K2 Wire breakage and earth leakage in the
* Trigger K1 monitoring circuits are detected.
F1 circuit K1 KA
* Fuse F2 (front cover) 1 A, Fuse F1
(internal) 1.25 A
K2
K2 KB
K1 K2

D D1 L62 14 24 34

KA KB
For further examples
refer to page 80/81 N

6
Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) T 1.0 A/250 V (internal T 1.25 A/250 V)
Power consumption max. 2.0 VA, plus monitoring output L62
Switching capacity (enabling contacts) 230 VAC, 4 A ohmic (inductive with suitable suppression)
NO 43/44, 53/54: DC 13: 24 VDC/2 A; AC 15: 230 VAC/3 A
Fuse (enabling contacts) 4 A slow blowing
Switching capacity (monitoring contacts) L62: max. 500 mA
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 30 ms
Drop-out delay ≤ 60 ms
Contact material / contacts AgSnO, AgNi self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/45 mm/140 mm
Weight 460 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

79
SRB-NA-R-C.22 (continued)

Wiring example: Wiring example:


Input level Input level
C1 S1 X1 C1 C1 X1
Single-channel emergency Dual-channel emergency stop
stop switch according to switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency stop Emergency Reset
stop circuits are detected. switch off circuits are detected. switch off

With external reset button. Cross-shorts in the emergency


Safety category 2 stop circuits are not detected.
in accordance with With external reset button.
EN 954-1. Safety category 3 or 4
in accordance with
EN 954-1.
QS QS
1 0 1 0

S1 S2 X2 S1 S2 X2

Wiring example: Wiring example:


Input level Input level
C1 D1 X1 C1 S1 X1
Dual-channel emergency stop Single-channel door
switch according to monitoring according to
Open
EN 60 204-1. EN 1088 limit switch with
Wire breakage and earth positive opening contact. Closed

leakage in the emergency stop Emergency Reset Wire breakage and earth Reset
circuits are detected. switch off leakage in the door
Cross-shorts in the emergency monitoring circuits are
stop circuits are detected. detected.

To enable cross-short With external reset button


monitoring: Set switch QS for increased safety
(bottom of housing) to 1. requirements.

With external reset button. Safety category 2


QS in accordance with QS
Safety category 3 or 4 EN 954-1.
in accordance with 1 0 1 0
EN 954-1.
S1 S2 X2 S1 S2 X2

Wiring example: Wiring example:-


input level input level
C1 D1 X1 C1 C1 X1
Dual-channel door monitoring Dual-channel door monitoring
according to EN 1088, one Open according to EN 1088, one Open
limit switch with positive limit switch with positive
Closed Closed
opening contact. opening contact.
Wire breakage and earth Reset Wire breakage and earth Reset
leakage in the door monitoring leakage in the door monitoring
circuits are detected. circuits are detected.
Cross-shorts in the door Cross-shorts in the door
monitoring circuits are monitoring circuits are not
detected. detected.
To enable cross-short With external reset button for
monitoring: Set switch QS increased safety requirements.
(bottom of housing) to 1. QS Safety category 3 or 4 QS
With external reset button for 1 0 in accordance with 1 0
increased safety requirements. EN 954-1.
Safety category 3 or 4 S1 S2 X2 S1 S2 X2
in accordance with
EN 954-1.

80
SRB-NA-R-C.22 (continued)

Advice:
For "Automatic reset" X1
apply jumper X1-X2.
When using external
reset button (connect to
X1-X2.1), unit is triggered
by trailing edge function. Reset
Reset button wired in
series to feedback loop.

X2.1

Wiring example: Wiring example:


Power level Power level
Single-channel output. L1 Dual-channel output. L1 6
Suitable for contact * Suitable for contact *
KA KB KA KB
reinforcement or contact reinforcement or contact
multiplication, using relays X1 X2 13 multiplication, using relays X1 X2 13 23
or contactors with KA or contactors with
KB
positively guided contacts. positively guided contacts.

14 KB 14 24
KA

KA KB KA KB

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

81
SRB-NA-R-C.27
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 3 enabling outputs and 1 monitoring output
☛ 2 semiconductor outputs
☛ Selectable extras:
– Auto reset
– Trailing edge function
– Initial start test

Features – Relay output: 3 NO, 1 NC – Reset, feedback loop – Housing 45 mm, made of
(Auxiliary NC for monitoring thermoplastic in accordance with
must not be used in safety – Input for emergency stop UL-94-V-0, red RAL 3000
enabling circuits!) or door monitoring
– DIN rail mounting
– Monitoring outputs for K1, – LED’s for K1, K2, K3, Qs, UB, Ui DIN EN 50 022
K2/K3

Approvals
ÜFZ
PR
ER
BG-

T.

Pending LR 13571-30 E 54284 (M)

Front view
41 13 23 33 L11
C C1 S11 S12 L13
SRB-NA-R-
C.27-24V UB U i

Fuse K1 K3

K2 Qs
D S13 S21 S41 L14
42 14 24 34 D2

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.27-24V 3 NO/1 NC 24 VAC/VDC 600 0063

82
SRB-NA-R-C.27 (continued)

Wiring diagram Example for dual-channel door


monitoring using two limit switches
L1 (one with positive opening contacts) and
Open
external reset button.
Closed ****
KB
Reset
Dual-channel output, suitable for contact
reinforcement or contact multiplication,
KA using relays or contactors with positively
C C1 S11 S12 S13 S21 S41 13 23 33 41 guided contacts.

F2 S5
**** = Feedback loop
K1
F1
S1 K2 K1 K1 K2 K1 K3
Wire breakage and earth leakage in the
monitoring circuits are detected.
K1 K2 KA
Cross-short
recognition
K3 K2 K3 S4

K3 KB
K1 K2 K3

D L13 L11 D2 L14 14 24 34 42

KA KB

For further examples


refer to page 84/85
6
Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) T 1.0 A/250 V (internal T 1.25 A/250 V)
Power consumption max. 7 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Switching capacity (monitoring contacts) 41/42: 24 VDC, 2 A; L11, L14: max. 100 mA
Fuse (monitoring contacts) 41/42: 2 A slow blowing; L11, L14: 100 mA slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 200 ms
Drop-out delay ≤ 30 ms
Contact material / contacts AgSnO self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/45 mm/140 mm
Weight 460 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

83
SRB-NA-R-C.27 (continued)

Wiring example: Wiring example:


Input level Input level
C1 S21 C1 S11
Single-channel emergency Dual-channel emergency stop C1 C1 S41 S11
stop switch according to switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency stop
stop circuits are detected. switch off circuits are detected. Emergency Reset
switch off
With external reset button. Cross-shorts in the emergency
Safety category 2 stop circuits are not detected.
in accordance with With external reset button.
EN 954-1. Safety category 3 or 4
in accordance with
EN 954-1.
S4
1 S4
0
1 0
S21 S41 S13 S12
S21 S41 S13 S12

Wiring example: Wiring example:


Input level Input level
C1 D C1 S11 C1 S21 C1 S11
Dual-channel emergency stop Single-channel door
switch according to monitoring according to
Open
EN 60 204-1. EN 1088 limit switch with
Wire breakage and earth positive opening contact. Closed
leakage in the emergency stop Emergency Reset Wire breakage and earth Reset
circuits are detected. switch off leakage in the door
Cross-shorts in the emergency monitoring circuits are
stop circuits are detected. detected.

To enable cross-short With external reset button


monitoring: Set switch QS for increased safety
(bottom of housing) to 0. requirements.

With external reset button. Safety category 2


S4 in accordance with S4
Safety category 3 or 4 EN 954-1.
in accordance with 1 0 1 0
EN 954-1.
S21 S41 S13 S12 S21 S41 S13 S12

Wiring example: Wiring example:


Input level Input level
C1 D C1 S11 C1 D C1 S11
Dual-channel door monitoring Dual-channel door monitoring
according to EN 1088, one Open according to EN 1088, one Open
limit switch with positive Closed
limit switch with positive Closed
opening contact. opening contact.
Wire breakage and earth Reset Wire breakage and earth Reset
leakage in the door monitoring leakage in the door monitoring
circuits are detected. circuits are detected.
Cross-shorts in the door Cross-shorts in the door
monitoring circuits are monitoring circuits are not
detected. detected.
To enable cross-short With external reset button for
monitoring: Set switch QS increased safety requirements.
(bottom of housing) to 0. S4 S4
Safety category 3 or 4
With external reset button for 1 0 in accordance with 1 0
increased safety requirements. EN 954-1.
S21 S41 S13 S12 S21 S41 S13 S12
Safety category 3 or 4
in accordance with
EN 954-1.

84
SRB-NA-R-C.27 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1 Dual-channel output L1
Suitable for contact * Suitable for contact
reinforcement or contact KA KB
reinforcement or contact KA
* KB
multiplication, using relays S11 S12 13 multiplication, using relays S11 S12 13 23
or contactors with or contactors with
KA KB
positively guided contacts. positively guided contacts.

14 KB 14 24 KA

KA KB KA KB

N N

* Feedback loop * Feedback loop

Advice: Advice:

6
For "Automatic reset" apply C1 Semiconductor outputs 24 VDC 0V
jumper C1-S13. L11 and L14 are
When using external reset galvanically separated
button (switch S1 is set to from the other sections of
"1"), unit is triggered by the SRB-NA-R-C.27.
trailing edge function. Reset Provide power supply
If the time difference between through inputs L13 and
input channel 1 and 2 of the D2.
safety relay exceeds ca. Semiconductor output L11
100 msec. when connecting a is linked to relay K1
safety limit switch or (reset), semiconductor
interlocking device, a self- output L14 is linked to
locking function can be relays K2 and K3.
achieved by setting switch S5
to "1". The time difference is
then extended to infinite.

S13 L13 D2

Rear view

Setting:
S1 ON = Trailing edge function on OFF = Trailing edge function off
1 0 S5
S4 ON = Cross-short recognition off OFF = Cross-short recognition on
1 0 S4 S5 ON = Time delay between input OFF = Time delay between input
1 0 S1
channel 1 and 2 infinite channel 1 and 2 ca. 100 msec.

85
86
SRB modules 45 mm wide,
multifunctional version,
STOP category 1

☛ max. 5 enabling outputs and 1 monitoring output


☛ max. 3 enabling outputs drop-out delayed: 0 ... 30 sec.
☛ max. load current: 4 Ampere
☛ max. safety category: 4
☛ 1- or 2-channel triggering
☛ Trailing edge function selectable
☛ Cross-short recognition selectable
☛ Semiconductor monitoring outputs selectable
☛ 24 VDC/VAC version
☛ Approvals: BG, CSA, UL

7
Options

0 . 1* 2
t. t 1/
ca ca A) ) el on ring n s
P P ( ( A n ut
S TO STO ent puts ent ory han niti igge ctio inp
s s urr out urr teg ∞ c og l tr un red t
ut ut c
tp utp ad c C ad c y ca ow t re nne ge f owe t tes AC l al l
o u o l o y N lo et nd or ha ed p ar / V C C o va rov ova
g g . r . a f i h -c g a l s t C C A r p p pr
in in x a x w s A p
a bl abl ma xili ma x. s me oss- ngle ailin tern itial VD VA 5 V 0 V ap A a ap
a
Type En En => Au => m Ti Cr Si Tr Ex In 24 48 11 23 BG CS UL
SRB-NA-R-C.19 3 4 4 ✚ ● ● ● ✔ ✔ ✔ refer to page 88
SRB-NA-R-C.21 3 2 4 1 0,5 4 ✚ ● ● ● ✔ ✔ ✔ refer to page 92
SRB-NA-R-C.38 3 2 4 4 ✚ ● ● ● ✔ ✔ ✔ refer to page 96
* = Drop-out delay time 0 ... 30 sec. (0 ... 5.3 sec.) external setting; ✚ = fixed; = DIP switch setting;
● = selectable; ● = selectable feature; ✔ = in preparation; ✔ = approved

87
SRB-NA-R-C.19
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 3 safety enabling outputs drop-out delayed: 0 ... 5.3 sec.
☛ Selectable extras:
– Trailing edge function
– Auto reset
☛ Possibility to shorten the drop-out delay

Features – Relay output: 3 NO – LED’s for K2, K3, K4, Ui – DIN rail mounting
DIN EN 50 022
– Reset, feedback loop – Housing 45 mm, made of
thermoplastic in accordance with
– Input for emergency stop UL-94-V-0, red RAL 3000
or door monitoring

Approvals

LR 13571-30 E 54284 (M)

Front view
13 23 33
A1 T11 Y2 Y1 S11
SRB-NA-R-
C.19-24V Ui

Fuse K2 K3

K4
A2 S1 S2 S22 V1
14 24 34

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.19-24VDC 3 NO 24 VDC 600 0058
SRB-NA-R-C.19-24VAC 3 NO 24 VAC On request

88
SRB-NA-R-C.19 (continued)

Wiring diagram Example for dual-channel door


L1 monitoring using two limit switches
****
Open (one with positive opening contacts) and
Closed KB external reset button.
Dual-channel output, suitable for contact
reinforcement or contact multiplication,
Reset K A
using relays or contactors with positively
A1 T11 Y1 Y2 S1 S11 S2 S22 V1 13 23 33 guided contacts.
F2 F1 F3 F1 **** = Feedback loop
K2 K1
K2 K1 K3
K1
K1 Wire breakage and earth leakage in the
K2 monitoring circuits are detected.
KA
K3 K4 K4 Cross-shorts in the door monitoring
circuits are not detected.
K1 K2 K3 K4 K3
KB With external reset button.

A2 14 24 34

KA KB

N
For further examples
refer to page 90/91

Model specific
Technical data
Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
(refer to page 157 24 VAC –15%/+6%
for general data)
Frequency 50/60 Hz (for AC operating)
7
Fuse (power supply) F2: M 0.25 A/250 V (internal M 0.5 A/250 V; F3: T 0.1 A/250 V)
Power consumption max. 3 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 100 ms
Drop-out delay Refer to page 91
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/45 mm/140 mm
Weight 390 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

89
SRB-NA-R-C.19 (continued)

Wiring example: Wiring example:


Input level Input level
T11 S1 S11 T11 T11 S11
Single-channel emergency Dual-channel emergency
stop switch according to stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency Emergency Reset
stop circuits are detected. switch off stop circuits are detected. switch off
With external reset button. Earth leakage at input A2 is
Safety category 2 detected in non grounded
in accordance with mains only!
EN 954-1. Cross-shorts in the
emergency stop circuits are
not detected.
With external reset button.
Safety category 3 or 4
in accordance with
S1 S2 Y1 EN 954-1. S1 S2 Y1

Wiring example: Wiring example:


Input level Input level
T11 S1 S11 T11 T11 S11
Single-channel door Dual-channel door
monitoring according to monitoring according to Open
Open
EN 1088 limit switch with EN 1088, one limit switch
Closed Closed
positive opening contact. with positive opening
Wire breakage and earth contact.
Reset Reset
leakage in the door Wire breakage and earth
monitoring circuits are leakage in the door
detected. monitoring circuits are
With external reset button. detected.

Safety category 2 Cross-shorts in the door


in accordance with monitoring circuits are
EN 954-1. not detected.
With external reset button
for increased safety
requirements.
S1 S2 Y1 Safety category 3 or 4 S1 S2 Y1
in accordance with
EN 954-1.

Advice:
For "Automatic reset" apply S11
jumper S11-Y1.
When using external reset
button (S11-Y2) and jumper
Y1-Y2, unit is triggered by
trailing edge function. Reset
Reset button wired in series to
feedback loop.
If the time between channel 1
and 2 exceeds ca. 20 msec.
when connecting a safety limit
switch or interlocking device,
a lock function can be
achieved by triggering channel
2 (T11-S2) prior to channel 1
(T11-S1). The time difference
is then extended to infinite.
Y2 Y1

90
SRB-NA-R-C.19 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output. L1 Dual-channel output. L1
Suitable for contact KA * KB
Suitable for contact *
reinforcement or contact reinforcement or contact KA KB
multiplication, using relays S11 Y1 13 multiplication, using relays S11 Y1 13 23
or contactors with KA
or contactors with
KB
positively guided contacts. positively guided contacts.

14 KB 14 24
KA

KA KB KA KB

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

Advice: Advice:
Enabling outputs 23/24 A1 14 It is possible to shorten the A1 14
and 33/34 correspond drop-out delay time via an
to STOP category 1 external NC between
in accordance with terminals 14 and V1.
EN 60 204-1.
S1
The safety relay module
has no safety function if
connector V1 is triggered
external.

13 V1 13 V1

Set to ON Time in seconds


Rear view S1, S4 ca. 0,7
S2, S5 ca. 1,4
S1, S2, S4, S5 ca. 2,1
S6
S5
S4
S3, S6 ca. 3,2
S3
S2
S1
S1, S3, S4, S6 ca. 3,9
S2, S3, S5, S6 ca. 4,6
S1, S2, S3, S4, S5, S6 ca. 5,3
Tolerance: ± 30%

91
SRB-NA-R-C.21
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 5 enabling outputs and 1 monitoring output
☛ 2 enabling outputs drop-out delayed: 0 ... 30 sec.
☛ Selectable extras:
– Trailing edge function
– Auto reset
– Cross-short recognition
☛ Time set in 24 stages (at bottom of housing)
Features – Relay output: 3 NO, 2 NO time – Input for emergency stop – DIN rail mounting
delayed, 1 NC or door monitoring DIN EN 50 022
(Auxiliary NC for monitoring
must not be used in safety – LED’s for K1, K2, K3, K4, UB, Ui
enabling circuits!) – Housing 45 mm, made of
– Reset, feedback loop thermoplastic in accordance with
UL-94-V-0, red RAL 3000

Approvals
ÜFZ
PR
ER
BG-

T.

98107 LR 13571-30 E 54284 (M)

Front view 47 57
13 23 33 (43) (53)
C C1 S1 X1 X2
SRB-NA-R- t ...... s
C.21-24V UB U i

Fuse K1 K3

K2 K4
D D1 S2 X2.1 L62
48 58
14 24 34 (44) (54)

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.21-24V 3 NO/2 NO /1 NC 24 VAC/VDC 600 0790

92
SRB-NA-R-C.21 (continued)

Wiring diagram Example for dual-channel door


L1 monitoring using two limit switches
Open
**** (one with positive opening contacts) and
Closed
KB
external reset button.
Reset Dual-channel output, suitable for contact
KA
reinforcement or contact multiplication,
47 57 using relays or contactors with positively
C C1 X2 X2.1 S1 X1 S2 13 23 33 (43) (53)
guided contacts.
**** = Feedback loop
F2 K1 K2 Wire breakage and earth leakage in the
* Trigger K1 monitoring circuits are detected.
F1 circuit
K1 KA
K3 K4 K3
TIMER TIMER
* Fuse F2 (front cover) 1 A,
K2 fuse F1 (internal) 1.25 A
K2 KB
K1 K3 K2 K4 K4

D D1 L62 14 24 34 48 58
(44) (54)

KA KB

N
For further examples
refer to page 94/95

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) T 1.0 A/250 V (internal T 1.25 A/250 V) 7
Power consumption max. 4.0 VA, plus monitoring output L62
Switching capacity (enabling contacts) 230 VAC, 4 A ohmic (inductive with suitable suppression)
NO 43/44, 53/54: DC 13: 24 VDC/2 A; AC 15: 230 VAC/3 A
Fuse (enabling contacts) 4 A slow blowing
Switching capacity (monitoring contacts) L62: max. 500 mA
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 30 ms
Drop-out delay ≤ 60 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/45 mm/140 mm
Weight 480 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

93
SRB-NA-R-C.21 (continued)

Wiring example: Wiring example:


Input level Input level
C1 S1 X1 C1 C1 X1
Single-channel emergency Dual-channel emergency
stop switch according to stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency Emergency Reset
stop circuits are detected. switch off stop circuits are detected. switch off

With external reset button. Cross-shorts in the


Safety category 2 emergency stop circuits are
in accordance with not detected.
EN 954-1. With external reset button.
Safety category 3 or 4
in accordance with
QS QS
EN 954-1.
1 0 1 0

S1 S2 X2 S1 S2 X2

Wiring example: Wiring example:


Input level Input level
C1 D1 X1 C1 S1 X1
Dual-channel emergency Single-channel door
stop switch according to monitoring according to
EN 60 204-1. EN 1088 limit switch with Open

Wire breakage and earth positive opening contact. Closed


leakage in the emergency Emergency Reset Wire breakage and earth
Reset
stop circuits are detected. switch off leakage in the door
Cross-shorts in the monitoring circuits are
emergency stop circuits are detected.
detected. With external reset button
To enable cross-short for increased safety
monitoring: Set switch requirements.
"QS" (bottom of housing) Safety category 2
to 1. QS in accordance with QS
With external reset button. EN 954-1.
1 0 1 0
Safety category 3 or 4
in accordance with S1 S2 X2 S1 S2 X2
EN 954-1.

Wiring example: Wiring example:


Input level Input level
C1 D1 X1 C1 C1 X1
Dual-channel door monitoring Dual-channel door
according to EN 1088, one Open monitoring according to Open
limit switch with positive EN 1088, one limit switch
Closed Closed
opening contact. with positive opening
Wire breakage and earth contact.
Reset Reset
leakage in the door Wire breakage and earth
monitoring circuits are leakage in the door
detected. monitoring circuits are
Cross-shorts in the detected.
emergency stop circuits are Cross-shorts in the
detected. emergency stop circuits are
To enable cross-short not detected.
monitoring: Set switch "QS" QS With external reset button QS
(bottom of housing) to 1. for increased safety
1 0 requirements. 1 0
With external reset button
for increased safety S2 X2
Safety category 3 or 4 S2 X2
S1 S1
requirements. in accordance with
Safety category 3 or 4 EN 954-1.
in accordance with
EN 954-1.

94
SRB-NA-R-C.21 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1 Dual-channel output L1
Suitable for contact KB Suitable for contact KB
reinforcement or contact KA KC reinforcement or contact KA KC
* * 47
multiplication, using relays 13 43 multiplication, using relays 13 23 (43)
or contactors with KA
or contactors with
X1 X2 X1 X2 KA
positively guided contacts. positively guided contacts.

14 44 KB 14 24 48 KB
(44)

KA KB KC KA KB KC

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

Advice: Advice:
47 57
For "Automatic reset" X1 Drop-out delay of the (43) (53)
apply jumper X1-X2. enabling outputs 47/48
When using external reset and 57/58 adjustable from
button (X1-X2.1), unit is 0–30 sec.
triggered by trailing edge Enabling outputs 43/44
function. Reset and 53/54 correspond
Reset button wired in to STOP category 1
series to feedback loop. in accordance with
EN 60 204-1.
Enabling outputs 47/48
and 57/58 correspond
to STOP category 1
7
in accordance with
EN 60 204-1.

X2.1 (44) (54)


48 58

Time S1 = 1, S1 = 0, S1 = 1, S1 = 0,
in seconds S2 = 1, S2 = 1, S2 = 0, S2 = 0,
Rear view S3 = 1, S3 = 0, S3 = 1, S3 = 0,
S4 = 1 S4 = 1 S4 = 0 S4 = 0
IV V

II
III
VI Max I 0.44 2.30 3.5 18
Min I

1 0
II 0.62 2.45 5.0 20
QS S4
1 0 S3
S2
III 0.87 2.70 7.0 22
S1
IV 1.05 2.85 8.5 23
V 1.27 3.05 10.2 25
VI 1.77 3.55 14.2 29
Tolerance: ± 5%

95
SRB-NA-R-C.38
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 5 enabling outputs
☛ 2 enabling outputs drop-out delayed: 0 ... 30 seconds
☛ Selectable extras:
– Trailing edge function, – Auto reset, – Cross-short recognition
☛ Time set in 24 stages (at bottom of housing)
☛ Possibility to shorten the drop-out delay

Features – Relay output: 3 NO, 2 NO drop- – LED’s for K1, K2, K3, K4, UB – DIN rail mounting
out delayed and Ui DIN EN 50 022
– Reset, feedback loop – Housing 90 mm, made of
thermoplastic in accordance with
– Input for emergency stop UL-94-V-0, red RAL 3000
or door monitoring

Approvals
ÜFZ
PR
ER
BG-

T.

in preparation LR 13571-30 E 54284 (M)

Front view
13 23 33 47 57
A1 T11 T12 T33 T34
SRB-NA-R- t: .... s
C.38-24V UB Ui

Fuse K1 K3

K2 K4
A2 T21 T22 T35 RT
14 24 34 48 58

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.38-24V 3 NO/2 NO 24 VAC/VDC On request

96
SRB-NA-R-C.38 (continued)

Wiring diagram L1
Example for dual-channel door
monitoring using two limit switches
Open
(one with positive opening contacts) and
Closed **** external reset button.
KB
Reset
Dual-channel output, suitable for contact
KA reinforcement or contact multiplication,
using relays or contactors with positively
A1 T11 T34 T35 T33 T12 RT T22 13 23 33 47 57 guided contacts.
**** = Feedback loop

F2 K1 K2 Wire breakage and earth leakage in the


Trigger
monitoring circuits are detected.
F1 circuit K1 KA
K3 K4 K3 * Fuse F2 (front cover) 1 A,
TIMER TIMER
fuse F1 (internal) 1.25 A
K2 KB
K1 K3 K2 K4 K4

A2 T21 14 24 34 48 58

KA KB

N
For further examples
refer to page 98/99

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) T 1.0 A/250 V (internal T 1.25 A/250 V) 7
Power consumption max. 4.0 VA
Switching capacity (enabling contacts) 230 VAC, 4 A ohmic (inductive with suitable suppression)
NO 43/44, 53/54: DC 13: 24 VDC/2 A; AC 15: 230 VAC/3 A
Fuse (enabling contacts) 4 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 30 ms
Drop-out delay ≤ 60 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/45 mm/140 mm
Weight 480 g
Ambient operating temperaturer –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

97
SRB-NA-R-C.38 (continued)

Wiring example: Wiring example:


Input level Input level
T11 T12 T33 T11 T11 T33
Single-channel emergency Dual-channel emergency
stop switch according to stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency Emergency Reset
stop circuits are detected. switch off stop circuits are detected. switch off

With external reset button. Cross-shorts in the


Safety category 2 emergency stop circuits are
in accordance with not detected.
EN 954-1. With external reset button.
Safety category 3 or 4
in accordance with
QS QS
EN 954-1.
1 0 1 0

T12 T22 T34 T12 T22 T34

Wiring example: Wiring example:


Input level Input level
T11 T21 T33 T11 T12 T33
Dual-channel door moni- Single-channel door
toring according to EN 1088, monitoring according to
Open
one limit switch with EN 1088 limit switch with
positive opening contact. positive opening contact. Closed

Wire breakage and earth Emergency Reset Wire breakage and earth Reset
leakage in the door switch off leakage in the door
monitoring circuits are monitoring circuits are
detected. detected.
Cross-shorts in the With external reset button
emergency stop circuits are for increased safety
detected. requirements.
To enable cross-short Safety category 2
monitoring: Set switch "QS" QS in accordance with QS
(bottom of housing) to 1. EN 954-1.
1 0 1 0
With external reset button.
Safety category 3 or 4 T12 T22 T34 T12 T22 T34
in accordance with
EN 954-1.

Wiring example: Wiring example:


Input level Input level
T11 T21 T33 T11 T11 T33
Dual-channel door monitoring Dual-channel door
according to EN 1088, one Open monitoring according to Open
limit switch with positive EN 1088, one limit switch
Closed Closed
opening contact. with positive opening
Wire breakage and earth contact.
Reset Reset
leakage in the door monitoring Wire breakage and earth
circuits are detected. leakage in the door
Cross-shorts in the emergency monitoring circuits are
stop circuits are detected. detected.

To enable cross-short Cross-shorts in the


monitoring: Set switch "QS" emergency stop circuits are
(bottom of housing) to 1. not detected.
QS With external reset button. QS
With external reset button.
Safety category 3 or 4 1 0 Safety category 3 or 4 1 0
in accordance with in accordance with
EN 954-1. T12 T22 T34 EN 954-1. T12 T22 T34

98
SRB-NA-R-C.38 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output Dual-channel output
L1 L1
Suitable for contact KB Suitable for contact KB
reinforcement or contact KA reinforcement or contact
multiplication, using relays
* KC multiplication, using relays
KA
* KC
13 47 13 23 47
or contactors with or contactors with
positively guided contacts. T33 T34 KB positively guided contacts. T33 T34 KA

14 48 KA 14 24 48 KB

KA KB KC KA KB KC

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

Advice: Advice:
For "Automatic reset" Drop-out delay of the 47 57
T33
apply jumper X1-X2. enabling outputs 47/48
When using external reset and 53/54 adjustable from
button (X1-X2.1), unit is 0–30 sec.
triggered by trailing edge Enabling outputs 57/58
function. Reset and 53/54 correspond
Reset button wired in to STOP category 1
series to feedback loop. in accordance with
EN 60 204-1.
Enabling outputs 47/48
and 57/58 correspond
to STOP category 1
7
in accordance with
EN 60 204-1.

T35 48 58

Time S1 = 1, S1 = 0, S1 = 1, S1 = 0,
in seconds S2 = 1, S2 = 1, S2 = 0, S2 = 0,
Rear view S3 = 1, S3 = 0, S3 = 1, S3 = 0,
S4 = 1 S4 = 1 S4 = 0 S4 = 0
IV V
III
II
VI Max I 0.44 2.30 3.5 18
Min I

1 0
II 0.62 2.45 5.0 20
QS S4
1 0 S3 III 0.87 2.70 7.0 22
S2
S1
IV 1.05 2.85 8.5 23
V 1.27 3.05 10.2 25
VI 1.77 3.55 14.2 29
Tolerance: ± 5%

99
100
SRB modules 45 mm wide,
special versions

☛ Suitable for battery powered networks


☛ Suitable for humid environments, non-equivalent input circuits
☛ max. 3 enabling outputs and 1 monitoring output
☛ max. load current: 6 Ampere
☛ max. safety category: 3
☛ 1- or 2-channel triggering
☛ Cross-short recognition
☛ 12 VDC, 24 VDC/VAC, 48 VAC, 115 VAC and 230 VAC versions
☛ Approvals: CSA, UL

Options

0 .1
t. t /2
ca ca A) A ) e l1 n ng ts
OP P
O nt ( uts nt ( ry nn itio geri ion npu
s S
ut ut
T S T
r e
s ur out ur teg ∞ p r e o
tp utp ad c C ad c y ca ow t re nne ge f owe t tes AC
c h a
g n
co l t
i g
r un red c t i
t
l al l
8
o u o l o y N l o et nd or ha ed p ar /V C C C o va rov ova
g g . r . a f i h c g a l s t C r p p pr
in in x a x w s - A A p
a bl abl ma xili ma x. s me oss- ngle ailin tern itial VD VA 5 V 0 V ap A a ap
u a L
Type En En => A => m Ti Cr Si Tr Ex In 24 48 11 23 BG CS U
SRB-NA-NF 3 6 3 ✚ ✚ ● ●* refer to page 102
Special feature(s): operated by battery powered networks, * = voltage 12 VDC, refer to page 159
SRB-NA-R-C.26 3 6 1 2 3 ✚ ✚ ● ✚ ✚ ✚ ✔ ✔ ✔ refer to page 106
Special feature(s): dual channel non-equivalent input circuits for humid environments, refer to page 159
✚ = fixed; ● = selectable; ✔ = in preparation; ✔ = approved

101
8
SRB-NA-NF
E-Stop module for vehicles
☛ Suitable for battery powered networks
☛ 3 safety enabling outputs
☛ Cross-short recognition

Features – Relay output: 3 NO – LED’s for K1, K2, UB – DIN rail mounting
DIN EN 50 022
– Reset, feedback loop – Housing 45 mm, made of
thermoplastic in accordance with
– Input for emergency stop UL-94-V-0, red RAL 3000
or door monitoring

Approvals
ÜFZ
PR
ER
BG-

T.

98107 LR 13571-30 E 54284 (M)

Front view
C S1.1 13 23 33
K1
UB
K2

SRB-NA-NF

D S2.1 14 24 34

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-NF-24V 3 NO 24 VDC 600 0758
SRB-NA-NF-12VDC 3 NO 12 VDC On request

102
SRB-NA-NF (continued)

Wiring diagram L-(A2) L+(A1) L1


Example for dual-channel door
monitoring using two limit switches
Open
(one with positive opening contacts) and
Closed
KB
external reset button.
Reset Dual-channel output, suitable for contact
****
KA
reinforcement or contact multiplication,
using relays or contactors with positively
C S1.1 S2.1 13 23 33
guided contacts.
F1** **** = Feedback loop
Wire breakage and earth leakage in the
K2 K1 K1 K2 monitoring circuits are detected.
Power
supply K1 KA
Earth leakage at input D is detected only
in mains with insulation leakage
monitoring.
K2 KB
K1 K2
** Fuse M 0.5 A
D 14 24 34
(an external leading fuse
M 0.25 A is recommendedd)
KA KB

N
For further examples
refer to page 104/105

Model specific Operating voltage 24 VDC, 12 VDC –25%/+35%, residual ripple 10%
Technical data
Fuse (power supply) M 0.25 A/250 V (internal M 0.5 A/250 V)
(refer to page 157
for general data) Power consumption max. 2.5 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 30 ms
≤ 50 ms
Drop-out delay
Contact material / contacts AgSnO, self cleaning, positively driven
8
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/45 mm/127 mm
Weight 280 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

103
8
SRB-NA-NF (continued)

Wiring example: Wiring example:


Input level Input level
L+(A1) L-(A2) S1.1 L+(A1) L-(A2) S1.1
Single-channel emergency Dual-channel emergency
stop switch according to Stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency Emergency Reset
stop circuits are detected. switch off stop circuits are detected. switch off
With external reset button. Earth leakage at input A2 is
Safety category 2 detected in non grounded
in accordance with mains only!
EN 954-1. Cross-shorts in the
emergency stop circuits are
detected.
With external reset button.
Safety category 3
in accordance with
C D S2.1 EN 954-1. C D S2.1

104
SRB-NA-NF (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1 Dual-channel output
L1
Suitable for contact Suitable for contact
KA * KB *
reinforcement or contact reinforcement or contact KA KB
multiplication, using relays S1.1 S2.1 13 multiplication, using relays S1.1 S2.1 13 23
or contactors with or contactors with
KA KB
positively guided contacts. positively guided contacts.

14 KB 14 24 KA

KA KB KA KB

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

105
8
SRB-NA-R-C.26
Safety relay array for emergency stop devices,
interlocking devices and others
☛ Suitable for humid environments
☛ 3 enabling outputs and 1 monitoring output
☛ Non-equivalent input
☛ Cross-short recognition

Features – Relay output: 3 NO, 1 NO time – Reset, feedback loop – Housing 45 mm, made of
delayed, 1 NC thermoplastic in accordance with
(Auxiliary NC for monitoring – Input for emergency stop UL-94-V-0, red RAL 3000
must not be used in safety or door monitoring
enabling circuits!) – DIN rail mounting
– LED’s for K2, K3, UB, Ui DIN EN 50 022

Approvals
ÜFZ
PR
ER
BG-

T.

Pending LR 13571-30 E 54284 (M)

Front view
A1 13 23 33 41
T11 T23 T24 T12
SRB-NA-R-C.26
UB U i

Fuse K2 K3

T33 T34 X1 X2
A2 14 24 34 42

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.26-24V 3 NO/1 NC 24 VDC/VAC On request
SRB-NA-R-C.26-115VAC 3 NO/1 NC 115 VAC 600 0091
SRB-NA-R-C.26-230VAC 3 NO/1 NC 230 VAC On request

106
SRB-NA-R-C.26 (continued)

Wiring diagram Example for dual channel door


L1 monitoring using two limit switches
Open (one with positive opening contacts) and
Closed
external reset button.
KB
**** Dual-channel output, suitable for contact
Reset
reinforcement or contact multiplication,
KA
using relays or contactors with positively
A1 T23 T11 T24 T33 T12 X2 X1 T34 13 23 33 41
guided contacts.

K1
**** = Feedback loop
F2
K1Trigger
K2 circuit
K1 K3 Wire breakage and earth leakage in the
F1
monitoring circuits are detected.
K2 KA

K3 KB
K1 K2 K3

A2 14 24 34 42

KA KB

N
For further examples
refer to page 108/109

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC, 46 VAC, 115 VAC, 230 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) F2: T 0.125 A/250 V (internal F1: T 0.25 A/250 V)
Power consumption max. 1.8 W, 5.5 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Switching capacity (monitoring contacts) 24 VDC, 2 A
Fuse (monitoring) 2 A slow blowing 8
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 50 ms
Drop-out delay ≤ 60 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/90 mm/127 mm
Weight 460 g (600 g at 230 V and 115 V version)
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

107
8
SRB-NA-R-C.26 (continued)

Wiring example: Wiring example:


Input level Input level
T11 T23 T33 X1 T11 T23 T33 X1
Dual-channel emergency Dual-channel door
stop switch according to monitoring according to Open
EN 60 204-1. EN 1088, one limit switch Closed
Wire breakage and earth with positive opening
leakage in the emergency Emergency Reset contact. Reset
stop circuits are detected. switch off Wire breakage and earth
Cross-shorts in the leakage in the door
emergency stop circuits are monitoring circuits are
detected. detected.

With external reset button. Cross-shorts in the door


monitoring circuits are
Safety category 3 detected.
in accordance with
EN 954-1. With external reset button
for increased safety
requirements.
T12 T24 T34 X2 Safety category 3 T12 T24 T34 X2
in accordance with
EN 954-1.

108
SRB-NA-R-C.26 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1
Dual-channel output
L1
Suitable for contact Suitable for contact
reinforcement or contact KA * KB reinforcement or contact *
KA KB
multiplication, using relays X1 X2 13
multiplication, using relays
X1 X2 13 23
or contactors with or contactors with
positively guided contacts. KA positively guided contacts. KB

14 KB 14 24 KA

KA KB KA KB

N N

* Feedback loop * Feedback loop

109
8
110
SRB modules 90 mm wide,
standard version

☛ 3 enabling outputs and 1 monitoring output


☛ max. load current: 6 Ampere
☛ max. safety category: 4
☛ 1- or 2-channel triggering
☛ Trailing edge function selectable
☛ Semiconductor monitoring outputs selectable
☛ Initial start test selectable
☛ 24 VDC/VAC version
☛ Approvals: BG, CSA, UL

Options

0 .1

OP
t.
P
t
ca ca A) uts A)
O nt ( utp nt ( ry
l1 n
/2
g
n io erin on puts
e 9
a n t
S T S T e o e o h n i g g cti in
u ts uts curr /NO curr teg ∞ c cog l tri fun red t
tp tp d C d ca w re ne e we tes C l al l
ou g ou loa y N loa ety ndo ort han edg l po art /VA C C o va rov ova
g . r . a f i h c g a s t C C A r p p pr
in in x a x w s - A p
a bl abl ma xili ma x. s me oss- ngle ailin tern itial VD VA 5 V 0 V ap A a ap
a
Type En En => Au => m Ti Cr Si Tr Ex In 24 48 11 23 BG CS UL
SRB-NA-R-C.8/97 3 6 1/1 2 4 ✚ ● ● ● ● ● ✔ ✔ ✔ refer to page 112
✚ = fixed; ● = selectable; ● = selectable feature; ✔ = approved

111
SRB-NA-R-C.8/97
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 3 enabling outputs and 2 monitoring outputs
☛ Selectable extras:
– Trailing edge function
– Auto reset

Features – Relay output: 3 NO, 2 NO/NC – Input for emergency stop – DIN rail mounting
(Auxiliary NO/NC for monitoring or door monitoring DIN EN 50 022
must not be used in safety
enabling circuits!) – LED’s for K1, K2, UB und Ui

– Reset, feedback loop – Housing 90 mm, made of


thermoplastic in accordance with
UL-94-V-0, red RAL 3000

Approvals
ÜFZ
PR
ER
BG-

T.

97273 LR 13571-30 E 54284 (M)

Front view T11 T12 T22


A1 (S11) (S12) (S22) 13 23 33 41 53 X5
SRB-NA-R-C.8/97 (C.8,C.8F)
24V

UB Ui

K2 K3

T33 T34
(S33) (S34) X3 X4 14 24 34 42 54 A2

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.8/97-24V 3 NO/1 NC/1 NO 24 VDC/VAC 600 0040

112
SRB-NA-R-C.8/97 (continued)

Wiring diagram L1
Example for dual channel door
monitoring using two limit switches
Open
(one with positive opening contacts) and
Closed
external reset button.
Reset
**** Dual-channel output, suitable for contact
KA KB reinforcement or contact multiplication,
using relays or contactors with positively
A1 T11 T33 X4 X3 T34 T12 T22 X5 13 23 33 41 53
guided contacts.
F2
K1
**** = Feedback loop
F1
K2 K1 K1 K2 K1 K3 K1
Wire breakage and earth leakage in the
monitoring circuits are detected.
K2 KA
K2A
K3 K2 K3

K3 KB
K1 K2 K2A K3 K3A K3A

A2 14 24 34 42 54

KA KB

N
For further examples
refer to page 114/115

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) F2: M 0.25 A/250 V (internal F1: M 0.5 A/250 V)
Power consumption max. 2.4 W, 4.6 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Switching capacity (monitoring contacts) max. 24 VDC/2 A ohmic (inductive with suitable suppression)
Fuse (monitoring contacts) 2 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 200 ms
Drop-out delay ≤ 20 ms
Contact material / contacts
Contact resistance
AgSnO, self cleaning, positively driven
max. 100 mOhm when new
9
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.6 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/90 mm/127 mm
Weight 500 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

113
SRB-NA-R-C.8/97 (continued)

Wiring example: Wiring example:


Input level Input level
T11 T12 T33 X3 T11 T11 T33 X3
Single-channel emergency Dual-channel emergency
stop switch according to stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency Emergency Reset
stop circuits are detected. switch off stop circuits are detected. switch off
With external reset button. Cross-shorts in the emergency
Safety category 2 stop circuits are not detected.
in accordance with With external reset button.
EN 954-1. Safety category 3
in accordance with
EN 954-1.

T12 T22 T34 X4 T12 T22 T34 X4

Wiring example: Wiring example:


Input level Input level
T11 T12 T33 X3 T11 T12 X3 T33
Single-channel door Dual-channel door
monitoring according to monitoring according to
Open Open
EN 1088 limit switch with EN 1088, one limit switch
positive opening contact. Closed with positive opening Closed

Wire breakage and earth contact.


Reset
leakage in the door Wire breakage and earth
monitoring circuits are leakage in the door
detected. monitoring circuits are
With external reset button detected.
for increased safety WARNING: Auto reset
requirements. after closing door.
Safety category 2 Safety category 2
in accordance with in accordance with
EN 954-1. EN 954-1.

T12 T22 T34 X4 T12 T22 X4 T34

Wiring example: Wiring example:


Input level Input level
T11 T11 T33 X3 T11 T11 X3 T33
Dual-channel door Dual-channel door
monitoring according to monitoring according to
Open Open
EN 1088, one limit switch EN 1088, one limit switch
with positive opening Closed with positive opening Closed
contact. contact and automatic
Wire breakage and earth
Reset initial start test.
leakage in the door Wire breakage and earth
monitoring circuits are leakage in the door
detected. monitoring circuits are
Cross-shorts in the detected.
emergency stop circuits are Cross-shorts in the
not detected. emergency stop circuits are
With external reset button not detected.
for increased safety WARNING: Auto reset
requirements. after closing door.
Safety category 3 or 4 Safety category 3 or 4
T12 T22 T34 X4 T12 T22 X4 T34
in accordance with in accordance with
EN 954-1. EN 954-1.

114
SRB-NA-R-C.8/97 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1
Dual-channel output
L1
Suitable for contact Suitable for contact
reinforcement or contact KA * KB reinforcement or contact KA * KB
multiplication, using relays X3 X4 13
multiplication, using relays
X3 X4 13 23
or contactors with or contactors with
positively guided contacts. KA positively guided contacts. KB

14 KB 14 24 KA

KA KB KA KB

N N

* Feedback loop * Feedback loop

Advice: Wiring example:


Input level
Time window infinite T 33 X3
T33 X3
between channel 1 and Start with trailing edge
channel 2 via jumper function.
between X3/X4 and
Module is activated after
T33/T34.
release of the reset button.
For external reset connect Reset
This prevents tampering of
reset button to X3/X4.
the reset button which
could lead to an automatic
reset.

T34 X4 T34 X5 X4

115
116
SRB modules 90 mm wide,
special versions

☛ Distinct restart
☛ Monitored contact multiplication
☛ 2-voltage version
☛ With separate output to operate solenoids
☛ max. 3 enabling outputs and 1 monitoring output
☛ max. 8 enabling outputs
☛ max. load current: 6 Ampere
☛ max. safety category: 4
☛ 1- or 2-channel triggering
☛ Trailing edge function selectable
☛ Semiconductor monitoring outputs selectable
☛ Initial start test selectable
☛ 24 VDC/VAC, 48 VAC, 115 VAC and 230 VAC versions
☛ Approvals: BG, CSA, UL

Options

0 .1 2
t. t 1/
ca ca A) uts A) el on ring n s
OP O P ( t p ( n ut
S T ST ent ou ent ory han niti igge ctio inp
s s urr NO urr teg ∞ c og l tr un red t
ut ut c
tp utp ad c C/ ad c y ca ow t re nne ge f owe t tes AC l al l
o u o l o y N lo et nd or ha ed p ar / V C C o va rov ova
g g . r . a f i h c g a l s t C C A r p p pr
in in x a x w s - A p
a bl abl ma xili ma x. s me oss- ngle ailin tern itial VD VA 5 V 0 V ap A a ap
a
Type En En => Au => m Ti Cr Si Tr Ex In 24 48 11 23 BG CS UL
SRB-NA-R-C.25 3 6 1 2 4 ● ● ✚ ● ● ● ● ● ✔ ✔ ✔ refer to page 118
Special feature(s): distinct restart, refer to page 158 8
SRB-2NA-R-E 3 6 4 ✚ ● ● ● ✚ ✚ ✚ ✚ ✔ ✔ refer to page 122
SRB-FE-R 5 6 ✚ ✚ ✚ ✚ ✚ ✔ ✔ refer to page 126
Special feature(s): monitored contact multiplication (using ribbon cable) , refer to page 160
SRB-QS.1/QS.2 3 6 1/1 2 4 ✚ ✚ ● ● ● ✚ ✚ ✚ ✔ ✔ ✔ refer to page 130
Special feature(s): 2-voltage-version: selectable 24 VDC/115 VAC or 24 VDC/230 VAC 1
SRB-TF-R 3 6 1 4 ✚ ● ● ● ● ✚ ✚ ✚ ✔ ✔ refer to page 134 0
SRB-TM-R 3 6 1 4 ✚ ● ● ● ● ✚ ✚ ✚ ✔ ✔ ✔ refer to page 138
Special feature(s): With separat output to operate solenoids, refer to page 161
✚ = fixed; ● = selectable; ● = selectable feature; ✔ = in preparation; ✔ = approved

117
SRB-NA-R-C.25
Safety relay array for emergency stop devices,
interlocking devices and others
☛ Distinct restart
☛ 3 safety enabling outputs and 1 monitoring output
☛ Selectable extra:
– Cross-short recognition

Features – Relay output: 3 NO, 1 NC – Input for emergency stop – DIN rail mounting
(Auxiliary NC for monitoring or door monitoring DIN EN 50 022
must not be used in safety
enabling circuits!) – LED’s for K2, K3, UB und Ui

– Reset, feedback loop – Housing 90 mm, made of


thermoplastic in accordance with
UL-94-V-0, red RAL 3000

Approvals
ÜFZ
PR
ER
BG-

T.

in preparation LR 13571-30 E 54284 (M)

Front view
A1 T11 T12 T22 T21 13 23 33 41 PE

SRB-NA-R-C.25

UB Ui

K2 K3

X1 X2 T33 T34 T23 14 24 34 42 A2

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.25-24V 3 NO/1 NC 24 VDC/VAC 600 0092
SRB-NA-R-C.25-115VAC 3 NO/1 NC 115 VAC On request
SRB-NA-R-C.25-230VAC 3 NO/1 NC 230 VAC On request

118
SRB-NA-R-C.25 (continued)

Wiring diagram Example for dual-channel door


L1 monitoring using two limit switches
Open (one with positive opening contacts) and
Closed
Reset external reset button.
KB
Dual-channel output, suitable for contact
****
reinforcement or contact multiplication,
KA
using relays or contactors with positively
A1 T11 T33 T34 X1 X2 T12 T22 13 23 33 41 guided contacts.

K1
**** = Feedback loop
F2
Trigger
circuit K1 K2 K1 K3 Wire breakage and earth leakage in the
F1 K2
monitoring circuits are detected.
K2 KA

K3

K3 KB
K1 K2 K3

A2 T21 PE T23 14 24 34 42

KA KB

For further examples


refer to page 120/121

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC, 115 VAC, 230 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) F2: T 0.25 A/250 V (internal F1: T 0.5 A/250 V)
Power consumption max. 2.4 W, 4.6 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Switching capacity (monitoring contacts) 24 VDC, 2 A
Fuse (monitoring contacts) 2 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 200 ms (Start button), < 450 ms (Auto-Start)
Drop-out delay ≤ 20 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions
Weight
H/W/D 83 mm/90 mm/127 mm
450 g (600 g at 230 V and 115 V version)
1
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
0
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

119
SRB-NA-R-C.25 (continued)

Wiring example: Wiring example:


Input level Input level
T11 T12 T33 X1 T21 T11 T11 T33 X1 T21
Single-channel emergency Dual-channel emergency
stop switch according to stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency Emergency Reset
stop circuits are detected. switch off stop circuits are detected. switch off

With external reset button. Cross-shorts in the


Safety category 2 emergency stop circuits are
in accordance with not detected.
EN 954-1. With external reset button.
Safety category 3 or 4
in accordance with
EN 954-1.

T12 T22 T34 X2 T23 T12 T22 T34 X2 T23

Wiring example: Advice:


Input level
This module is equipped
T11 T21 T33 X1 T11 T33
Dual-channel emergency with a particular restart
stop switch according to circuit. Automatic restart is
EN 60 204-1. provided after a previous
power down situation, whilst
Wire breakage and earth
a restart after operating a
leakage in the emergency
Emergency Reset protective device needs an Reset
stop circuits are detected.
switch off extra restart signal.
Cross-shorts in the
emergency stop circuits are
detected.
With external reset button.
Safety category 3 or 4
in accordance with
EN 954-1.

T12 T23 T34 X2 T22 T34

120
SRB-NA-R-C.25 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1
Dual-channel output
L1
Suitable for contact Suitable for contact
reinforcement or contact KA
* KB reinforcement or contact *
KA KB
multiplication, using relays X1 X2 13
multiplication, using relays
X1 X2 13 23
or contactors with or contactors with
positively guided contacts. KA positively guided contacts. KB

14 KB 14 24
KA

KA KB KA KB

N N

* Feedback loop * Feedback loop

1
0

121
SRB-2NA-R-E
Safety relay array for emergency stop devices,
interlocking devices and others
☛ Monitored contact multiplication
☛ 3 safety enabling outputs
☛ 8 safety enabling outputs with extension module SRB-FE-R

Features – Relay output: 3 NO – LED’s for K2, K3 – DIN rail mounting


DIN EN 50 022
– Reset, feedback loop – Housing 90 mm, made of
thermoplastic in accordance with
– Input for emergency stop UL-94-V-0, red RAL 3000
or door monitoring

Approvals
ÜFZ
PR
ER
BG-

T.

89046/89047 E 54284 (M)

Front view
A1
(+) 1 2 13 23 33 43
SRB-2NA-R-E

K2 K3

A2
5 6 7 8 PE 14 24 34 44 (–)

Product range Type Enabling outputs Operating voltage Part no.


SRB-2NA-R-E-24V 3 NO 24 VDC/VAC 600 0105
SRB-2NA-R-E-115VAC 3 NO 115 VAC 600 0173
SRB-2NA-R-E-230VAC 3 NO 230 VAC 600 0175

122
SRB-2NA-R-E (continued)

Wiring diagram Example for dual-channel door


L1 monitoring using two limit switches
Open (one with positive opening contacts) and
Closed external reset button.
KB
Dual-channel output, suitable for contact
Reset **** reinforcement or contact multiplication,
KA using relays or contactors with positively
A1(+) 1 5 2 6 7 8 23 33 43 13 guided contacts.

F1 K2 **** = Feedback loop


** K1
Wire breakage and earth leakage in the
K1 K2 K1 K3
monitoring circuits are detected.
K3 K2 K3
K2
KA

K1 K2 K3

K3
KB
3 4 8 9 6 7 10

A2(–) PE 24 34 44

KA KB

N
For further examples
refer to page 124/125

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC, 115 VAC, 230 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) M 0.25 A/250 V (internal M 0.5 A/250 V)
Power consumption max. 2.4 W, 4.6 VA
Switching capacity (enabling contacts) 230 VAC, ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Switching capacity (monitoring contacts) 13/14 24 VDC/2 A (only together with SRB-FE-R)
Fuse (monitoring contacts) 13/14 2 low blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 200 ms
Drop-out delay ≤ 20 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions
Weight
H/W/D 83 mm/90 mm/127 mm
600 g (850 g at 230 V and 115 V version)
1
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
0
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

123
SRB-2NA-R-E (continued)

Wiring example: Wiring example:


Input level Input level
1 7 1 1 1
Single-channel emergency Dual-channel emergency
stop switch according to stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency Emergency Reset
stop circuits are detected. switch off stop circuits are detected. switch off
With external reset button. Cross-shorts in the
Safety category 2 emergency stop circuits are
in accordance with not detected.
EN 954-1. With external reset button.
Safety category 3 or 4
in accordance with
EN 954-1.

7 8 2 7 8 2

Wiring example: Wiring example:


Input level Input level
1 7 1 1 7 1
Single-channel door Single-channel door
monitoring according to Open monitoring according to Open
EN 1088 limit switch with EN 1088 limit switch with
Closed Closed
positive opening contact. positive opening contact
Wire breakage and earth and automatic initial start
Reset test.
leakage in the door
monitoring circuits are Wire breakage and earth
detected. leakage in the door
With external reset button monitoring circuits are
for increased safety detected.
requirements. WARNING: Auto reset
Safety category 2 after closing door.
in accordance with With external reset button.
EN 954-1.
Safety category 2
in accordance with
7 8 2 EN 954-1. 7 8 2

Wiring example:
Input level
1 1
Dual-channel door
monitoring according to Open
EN 1088, one limit switch Closed
with positive opening
contact.
Reset
Wire breakage and earth
leakage in the door
monitoring circuits are
detected.
Cross-shorts in the door
monitoring circuits are
not detected.
With external reset button
for increased safety
requirements.
Safety category 3 or 4 7 8 2
in accordance with
EN 954-1.

124
SRB-2NA-R-E (continued)

Advice: Advice:
Module can be used as a The max. load of safety
basic safety relay module enabling output 13/14 is
or as a combination limited to 2 A/24 VDC, 13
module with the extension due to technical reasons of
SRB-2NA-R-E
module SRB-FE-R. the ribbon cable. Refer to
The contact multiplication technical data.
must be done via a ribbon
SRB-2NA-R-E
cable.
The end connector of the
base module will be
exchanged in this case with SRB-FE-R
the ribbon cable.
The safety enabling output
13/14 can only be used in SRB-FE-R
combination with the
extension module. 14

Wiring example: Wiring example:


Power level Power level
Single-channel output L1 Dual-channel output L1
Suitable for contact * Suitable for contact
reinforcement or contact KA KB reinforcement or contact
*
KA KB
multiplication, using relays 1 2 13 multiplication, using relays 1 2 13 23
or contactors with or contactors with
KA KB
positively guided contacts. positively guided contacts.

14 KB 14 24
KA

1
0
KA KB KA KB

N N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

125
SRB-FE-R
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 8 safety enabling outputs with basic module SRB-2NA-R-E

Features – Relay output: 5 NO – LED’s for K2A, K3A – DIN rail mounting
DIN EN 50 022
– Input for emergency stop – Housing 90 mm, made of
or door monitoring thermoplastic in accordance with
UL-94-V-0, red RAL 3000

Approvals
ÜFZ
PR
ER
BG-

T.

89047 LR 13571-30 E 54284 (M)

Front view A1
(+) 53 63 73 83

SRB-FE-R

K2A K3A

A2
PE 14 54 64 74 84 (–)

Product range Type Enabling outputs Operating voltage Part no.


SRB-FE-R-24V 5 NO 24 VDC/VAC 600 0500
SRB-FE-R-230VAC 5 NO 230 VAC 600 0570

126
SRB-FE-R (continued)

Wiring diagram ???

A1(+) 53 63 73 83

10
3 8 9 4 6 7
K1

K2 K3 K1
K2
K2
K3
K3 K2
K3
K1 K2 K3

A2(–) PE 54 64 74 84 14

For further examples


refer to page 128/129

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC, 230 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) M 0.25 A/250 V (internal M 0.5 A/250 V)
Power consumtion max. 1.2 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Switching capacity (monitoring contacts) 13/14 24 VDC, 2 A (only together with SRB-2NA-R-E)
Fuse (monitoring contacts) 13/14 2 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 200 ms
Drop-out delay ≤ 20 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions
Weight
H/W/D 83 mm/90 mm/127 mm
710 g (850 g at 230 V version)
1
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
0
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

127
SRB-FE-R (continued)

Advice: Advice:
Module SRB-2NA-R-E The max. load of safety
can be used as a basic enabling output 13/14 is
safety relay module or as limited to 2 A/24 VDC, 13
a combination module due to technical reasons of
SRB-2NA-R-E
with the extension module the ribbon cable. Refer to
SRB-FE-R. technical data.
The contact multiplication
SRB-2NA-R-E
must be done via a ribbon
cable.
The end connector of the
base module will be SRB-FE-R
exchanged in this case with
the ribbon cable.
The safety enabling output SRB-FE-R
13/14 can only be used in
combination with the 14
extension module.

128
Notes

1
0

129
SRB-QS.1/SRB-QS.2
Safety relay array for emergency stop devices,
interlocking devices and others
☛ 2-voltage version
☛ 3 safety enabling outputs and 1 monitoring output
☛ Cross-short recognition
☛ Wipe contact

Features – Relay output: 3 NO, 1 NO, – Input for emergency stop – DIN rail mounting
1 wipe contact or door monitoring DIN EN 50 022
(Auxiliary NC for monitoring
must not be used in safety – LED for UN
enabling circuits!) – Housing 90 mm, made of
– Reset, feedback loop thermoplastic in accordance with
UL-94-V-0, red RAL 3000

Approvals
ÜFZ
PR
ER
BG-

T.

99121 LR 13571-30 E 54284 (M)

Front view
13 23 33
A1 E11 E21 43 51
24V B1 X5 E12 E22
UN

SRB-QS.x
E34 X1 X2
A2 0V PE 44 52

14 24 34

Product range Type Enabling outputs Operating voltage Part no.


SRB-QS.1 3 NO/1 NO/1 NC 24 VDC/VAC, 115 VAC 600 0590
SRB-QS.2 3 NO/1 NO/1 NC 24 VDC/VAC, 230 VAC 600 0600

130
SRB-QS.1/SRB-QS.2 (continued)

Wiring diagram Example for dual-channel door


monitoring using two limit switches
L1
(one with positive opening contacts) and
Open
Closed
external reset button.
KB
Reset
Dual-channel output, suitable for contact
**** reinforcement or contact multiplication,
KA using relays or contactors with positively
A1 B1 24V E11 X5 X2 X1 E34 E12 E22 13 23 33 51 43
guided contacts.
**** = Feedback loop
K3
F1
** Wire breakage and earth leakage in the
K1 K3 K2 K3 K1
monitoring circuits are detected.
K2
KA
K2

K1
K3 K2 K1 KB

A2 PE 0 V E21 14 24 34 52 44

KA KB

N
For further examples
refer to page 132/133

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 115 VAC –15%/+6% (SRB-QS.1), 230 VAC –15%/+6% (SRB-QS.2)
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) M 0.25 A/250 V (internal M 0.5 A/250 V)
Power consumption max. 3.9 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Switching capacity (monitoring contacts) 24 VDC, 2 A ohmic (inductive with suitable suppression)
Fuse (monitoring contacts) 2 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 200 ms
Drop-out delay ≤ 30 ms
Contact material / contacts AgCdO self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions
Weight
H/W/D 83 mm/90 mm/140 mm
700 g
1
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
0
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

131
SRB-QS.1/SRB-QS.2 (continued)

Wiring example: Advice:


Input level
E11 E21 E11 X1 Time window between E11 52 43
Dual-channel emergency channel 1 and channel 2
stop switch according to infinite.
EN 60 204-1. WARNING: Auto reset
Wire breakage and earth after closing door.
leakage in the emergency Emergency Reset
stop circuits are detected. switch off

Cross-shorts in the
emergency stop circuits are
detected.
With external reset button.
Safety category 3 or 4
in accordance with
EN 954-1.

E12 E22 E34 X2 51 44 X5

Wiring example: Wiring example:


Input level Input level
E11 E21 E11 X1
Dual-channel door 2-voltage-versions
monitoring according to selectable: Standard Trafo
Open
230 VAC/115 VAC 24 V
EN 1088, one limit switch Closed 115 VAC/24 V:
with positive opening version SRB-QS.1 L1 N B1 L+ L–
contact.
Reset 230 VAC/24 V:
Wire breakage and earth version SRB-QS.2
leakage in the door
monitoring circuits are
detected.
Cross-shorts in the door
monitoring circuits are
detected.
With external reset button
for increased safety
requirements. A1 A2 24 V 24 V 0V

Safety category 3 or 4 E12 E22 E34 X2


in accordance with
EN 954-1.

Wiring example:
Input level
E11 44 X1 Advice:
Start with trailing edge
function. LED (UN) is only ON if triggering circuits are
activated.
Module is activated after
release of the reset button. Reset
This prevents tampering of
the reset button which
could lead to an automatic
reset.

E34 43 X5 X2

132
SRB-QS.1/SRB-QS.2 (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1
Dual-channel output
L1
Suitable for contact Suitable for contact
reinforcement or contact KA
* KB reinforcement or contact
*
KA KB
multiplication, using relays X1 X2 13
multiplication, using relays
X1 X2 13 23
or contactors with or contactors with
positively guided contacts. KA positively guided contacts. KB

14 KB 14 24 KA

KA KB KA KB

N N

* Feedback loop * Feedback loop

1
0

133
SRB-TF-R
Safety relay array for emergency stop devices,
interlocking devices and others
☛ With separate output to operate solenoids
suitable for spring forced interlocking devices
☛ 3 safety enabling outputs

Features – Relay output: 3 NO – LED’s for K1, K2 – DIN rail mounting


DIN EN 50 022
– Reset, feedback loop – Housing 90 mm, made of
thermoplastic in accordance with
– Input for emergency stop UL-94-V-0, red RAL 3000
or door monitoring

Approvals
ÜFZ
PR
ER
BG-

T.

93112 LR 13571-30 E 54284 (M)

Front view A1
(+) 1 2 3 PE 13 23 33
SRB-TF-R

K2 K3

A2
5 6 8 8.1 14 24 34 (–)

Product range Type Enabling outputs Operating voltage Part no.


SRB-TF-R-24V 3 NO 24 VDC/VAC 610 0300
SRB-TF-R-115VAC 3 NO 115 VAC 610 0350
SRB-TF-R-230VAC 3 NO 230 VAC 610 0370

134
SRB-TF-R (continued)

Wiring diagram L1 Example for dual-channel door


ON
monitoring using two limit switches
KB
OFF
(one with positive opening contacts) and
**** external reset button.
KA
Dual-channel output, suitable for contact
Reset reinforcement or contact multiplication,
using relays or contactors with positively
A1 5 3 6 1 2 8 8.1 13 23 33
guided contacts.
F1 **** = Feedback loop
** K1

K3 K1 K2 K1 K2 K1 K3
Wire breakage and earth leakage in the
monitoring circuits are detected.
K2 KA
** Fuse M 0.5 A
K3 K2 K3 (an external leading fuse
M 0.25 A is recommended)
K3 KB
K1 K2 K3

A2 PE 14 24 34

KA KB

For further examples N


refer to page 136/137

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC, 115 VAC, 230 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) F2: T 0.25 A/250 V (internal F1: T 0.5 A/250 V)
Power consumption max. 3.6 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 200 ms
Drop-out delay ≤ 20 ms
Contact material / contacts AgCdO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/90 mm/127 mm
Weight 580 g (830 g at 230 V and 115 V version)
–25 °C ... +45 °C (derating curve page 157)
Ambient operating temperature
Mechanical life 107 switching cycles
1
Terminal labeling DIN EN 50 005/DIN 50 013
0

135
SRB-TF-R (continued)

Wiring example: Wiring example:


Input level Input level
5 8 5 5 5
Single-channel emergency Dual-channel emergency
stop switch according to stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency Emergency Reset
stop circuits are detected. switch off stop circuits are detected. switch off

With external reset button. Cross-shorts in the


Safety category 2 emergency stop circuits are
in accordance with not detected.
EN 954-1. With external reset button.
Safety category 3 or 4
in accordance with
EN 954-1.

8 8.1 2 8 8.1 2

Wiring example: Wiring example:


Input level Input level
5 8 5 5 8 1 5
Single-channel door Single-channel door
monitoring according to Open monitoring according to Open
EN 1088 limit switch with EN 1088 limit switch with
Closed Closed
positive opening contact. positive opening contact and
automatic initial start test.
Wire breakage and earth Reset
leakage in the door Wire breakage and earth
monitoring circuits are leakage in the door
detected. monitoring circuits are
detected.
With external reset button
for increased safety WARNING: Auto Reset after
requirements. closing door.
Safety category 2 Safety category 2
in accordance with in accordance with
EN 954-1. EN 954-1.

8 8.1 2 8 8.1 2 1

Wiring example: Wiring example:


Input level Input level
5 5 5 1 5
Dual-channel door Dual-channel door
monitoring according to Open monitoring according to Open
EN 1088, one limit switch Closed EN 1088, one limit switch Closed
with positive opening with positive opening
contact. contact and automatic
Reset
Wire breakage and earth initial start test.
leakage in the door Wire breakage and earth
monitoring circuits are leakage in the door
detected. monitoring circuits are
Cross-shorts in the door detected.
monitoring circuits are Cross-shorts in the door
not detected. monitoring circuits are
With external reset button not detected.
for increased safety WARNING: Auto reset
requirements. after closing door.
Safety category 3 or 4 8 8.1 2
Safety category 3 or 4 8 8.1 2 1
in accordance with in accordance with
EN 954-1. EN 954-1.

136
SRB-TF-R (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1
Dual-channel output
L1
Suitable for contact Suitable for contact
reinforcement or contact KA * KB reinforcement or contact *
KA KB
multiplication, using relays 5 2 13
multiplication, using relays
5 2 13 23
or contactors with or contactors with
positively guided contacts. KA positively guided contacts. KB

14 KB 14 24
KA

KA KB KA KB

N
N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

1
0

137
SRB-TM-R
Safety relay array for emergency stop devices,
interlocking devices and others
☛ With separate output to operate solenoids
suitable for electro-magnetic forced interlocking devices
☛ 3 safety enabling outputs

Features – Relay output: 3 NO – LED’s for K1, K2 – DIN rail mounting


DIN EN 50 022
– Reset, feedback loop – Housing 90 mm, made of
thermoplastic in accordance with
– Input for emergency stop UL-94-V-0, red RAL 3000
or door monitoring

Approvals
ÜFZ
PR
ER
BG-

T.

93113 LR 13571-30 E 54284 (M)

Front view
A1
(+) 1 2 3 13 23 33
SRB-TM-R

K2 K3

A2
5 7 8 8.1 14 24 34 (–)

Product range Type Enabling outputs Operating voltage Part no.


SRB-TM-R-24V 3 NO 24 VDC/VAC 610 0200
SRB-TM-R-115V 3 NO 115 VAC 610 0250
SRB-TM-R-230V 3 NO 230 VAC 610 0270

138
SRB-TM-R (continued)

Wiring diagram L1
Example for dual-channel door
monitoring using two limit switches
Open
KB Closed
(one with positive opening contacts) and
**** external reset button.
KA
Dual-channel output, suitable for contact
Reset reinforcement or contact multiplication,
using relays or contactors with positively
A1 5 3 7 1 2 8 8.1 13 23 33 guided contacts.
**
F1 **** = Feedback loop
K1

K3 K1 K2 K1 K2 K1 K3
Wire breakage and earth leakage in the
monitoring circuits are detected.
K2 KA
** Fuse M 0.5 A
K3 K2 K3 (an external leading fuse
M 0.25 A is recommended)
K3 KB
K1 K2 K3

A2 PE 14 24 34

KA KB

For further examples N


refer to page 140/141

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC, 115 VAC, 230 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) M 0.25 A/250 V (internal M 0.5 A/250 V)
Power consumption max. 3.6 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 200 ms
Drop-out delay ≤ 20 ms
Contact material / contacts AgCdO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/90 mm/127 mm
Weight 580 g (830 g at 230 V and 115 V version)
–25 °C ... +45 °C (derating curve page 157)
Ambient operating temperature
Mechanical life 107 switching cycles
1
Terminal labeling DIN EN 50 005/DIN 50 013
0

139
SRB-TM-R (continued)

Wiring example: Wiring example:


Input level Input level
5 8 5 5 5
Single-channel emergency Dual-channel emergency
stop switch according to stop switch according to
EN 60 204-1. EN 60 204-1.
Wire breakage and earth Wire breakage and earth
leakage in the emergency Emergency Reset leakage in the emergency Emergency Reset
stop circuits are detected. switch off stop circuits are detected. switch off

With external reset button. Cross-shorts in the


Safety category 2 emergency stop circuits are
in accordance with not detected.
EN 954-1. With external reset button.
Safety category 3 or 4
in accordance with
EN 954-1.

8 8.1 2 8 8.1 2

Wiring example: Wiring example:


Input level Input level
5 8 5 5 8 1 5
Single-channel door Single-channel door
monitoring according to monitoring according to Open
Open
EN 1088 limit switch with EN 1088 limit switch with
Closed Closed
positive opening contact. positive opening contact
and automatic initial start
Wire breakage and earth Reset test.
leakage in the door
monitoring circuits are Wire breakage and earth
detected. leakage in the door
monitoring circuits are
With external reset button
detected.
for increased safety
requirements. WARNING: Auto reset
after closing door.
Safety category 2
in accordance with Safety category 2
EN 954-1. in accordance with
EN 954-1.

8 8.1 2 8 8.1 2 1

Wiring example: Wiring example:


input level Input level
5 5 5 1 5
Dual-channel door Dual-channel door
monitoring according to Open monitoring according to Open
EN 1088, one limit switch Closed EN 1088, one limit switch Closed
with positive opening with positive opening
contact. contact and automatic
Reset
initial start test.
Wire breakage and earth
leakage in the door Wire breakage and earth
monitoring circuits are leakage in the door
detected. monitoring circuits are
detected.
Cross-shorts in the door
monitoring circuits are Cross-shorts in the door
not detected. monitoring circuits are
not detected.
With external reset button
for increased safety WARNING: Auto reset
requirements. after closing door.
Safety category 3 or 4 8 8.1 2
Safety category 3 or 4 8 8.1 2 1
in accordance with in accordance with
EN 954-1. EN 954-1.

140
SRB-TM-R (continued)

Wiring example: Wiring example:


Power level Power level
Single-channel output L1 Dual-channel output L1
Suitable for contact Suitable for contact
reinforcement or contact KA * KB *
reinforcement or contact KA KB
multiplication, using relays 5 2 13 multiplication, using relays 5 2 13 23
or contactors with or contactors with
positively guided contacts. KA KB
positively guided contacts.

14 KB 14 24
KA

KA KB KA KB

N
N

* Reset button wired in * Reset button wired in


series to feedback loop. series to feedback loop.

1
0

141
142
Modules for contact multiplying

☛ max. 6 enabling outputs or max. 4 enabling outputs


and 1 monitoring output
☛ max. load current: 6 Ampere
☛ 22.5 mm and 90 mm wide
☛ 1- or 2-channel triggering
☛ 24 VDC/VAC, 48 VAC, 115 VAC and 230 VAC versions
☛ Approvals: CSA, UL

0 .1 2
t. t 1/
ca ca A) el on ring n ts
P P ( n
T O TO ) u t n t ry a n iti ge io npu
S s S (A tp rre go ch ogn trig nc ed t i
ts
pu tpu ren C o d c cat w ∞ rec nel ge f wer test AC
t t u u e u
t l al l
o u o u
c u r
y N l o a
e t y n d o
o r t
h a n
e d p o rt /V
a C C o va rov ova
g g
lin lin ad lia ax sa
r . f wi h
s-s e- in
c g nal l st DC AC A A ppr app ppr
n ab nab > lo uxi > m ax. ime ros ingl rail xter itia 4 V 8 V 15 V 30 V G a SA L a
Type E E = A = m T C S T E In 2 4 1 2 B C U
SRB-NA-R-C.EW 4 6 ● ✔ ✔ refer to page 144
SRB-ZB-Mo 6 6 ● ✔ ✔ refer to page 148
SRB-LV 4 6 1 2 ● ● ● ● ✔ ✔ refer to page 152
● = selectable; ✔ = approved

1
143
1
SRB-NA-R-C.EW
Output expansion module for additional enabling outputs
☛ 4 enabling outputs
☛ 22.5 mm housing

Features – Relay output: 4 NO – Housing 22.5 mm, made of – DIN rail mounting
thermoplastic in accordance with DIN EN 50 022
– LED’s for K1, K2 UL-94-V-0, red RAL 3000
– Feedback circuit X1, X2

Approvals

LR 13571-30 E 54284 (M)

Front view

13 23 33
X2 X1 A1
K2
SRB-NA
-R-C.EW
K1
14 24 34
A2 43 44

Product range Type Enabling outputs Operating voltage Part no.


SRB-NA-R-C.EW-24V 4 NO 24 VDC/VAC 610 0405

144
SRB-NA-R-C.EW (continued)

Wiring diagram

A1 X1 13 23 33 43

K1

K1

K1
K2

K2 K2
K1 K2

A2 X2 14 24 34 44
For further examples
refer to page 146/147

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) M 0.25 A/250 V
Power consumption max. 1.2 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 20 ms
Drop-out delay ≤ 35 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.6 qmm, max. 2.5 qmm
Dimensions H/W/D 82 mm/22.5 mm/98 mm
Weight 190 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

1
145
1
SRB-NA-R-C.EW (continued)

Wiring example:
Input level 24 V

Single-channel control of
the expansion module
SRB-NA-R-C.EW via one
enabling output of the base
module.
A fault in the expansion
module is not detected by X1 X2 13 23 A1 X1 X2
the base module. Base module Expansion module
Connect terminals X1 and SRB-NA-... SRB-NA-R-C.EW
X2 to the feedback loop of 14 24 A2
the base module.

0V

Advice:
Warning !
The expansion module
must be installed according
to the example since the
device is not fitted with its
own safety circuits.

146
Notes

1
147
1
SRB-ZB-Mo
Output expansion module for additional enabling outputs
☛ 6 enabling outputs
☛ 90 mm housing

Features – Relay outputs: 2 x 3 NO – Housing 90 mm, made of – DIN rail mounting


thermoplastic in accordance with DIN EN 50 022
– LED’s for B1, B2, B10, B20 UL-94-V-0, red RAL 3000
– Feedback circuit X1, X2
and X11, X12

Approvals

LR 13571-30 E 54284 (M)

Front view
B1 B2 X1 X11 13 23 33 43 53 63

B1 B2

SRB-ZB-Mo

B10 B20

A B12 X2 X12 14 24 34 44 54 64

Product range Type Enabling outputs Operating voltage Part no.


SRB-ZB-Mo-24VDC 2 x 3 NO 24 VDC 610 0620

148
SRB-ZB-Mo (continued)

Wiring diagram

B1 B2 B12 X1 X11 13 23 33 43 53 63

B1 B10

B1 B10

B2 B20 B2 B20
B1 B2 B10 B20

A X2 X12 14 24 34 44 54 64

For further examples


refer to page 150/151

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data
Fuse (power supply) M 0.25 A/250 V
(refer to page 157
for general data) Power consumption max. 2.4 W
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 30 ms
Drop-out delay ≤ 20 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.5 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/90 mm/127 mm
Weight 470 g
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 50 005/DIN 50 013

1
149
1
SRB-ZB-Mo (continued)

Wiring example:
Input level
L (L+)
Single-channel control of
the expansion module
SRB-NA-R-C.EW via one
enabling output of the base
module.
A fault in the expansion
module is not detected by X1 X2 13 23 X1 X2 X11 X12
the base module. Base module Expansion module
SRB-NA-... A SRB-ZB-Mo
Connect terminals X1 and
X2 to the feedback loop of 14 24 B1 B2 B12
the base module.

N (L–)

Wiring example:
Input level
Dual-channel control of L (L+)
the expansion module
SRB-NA-R-C.EW via two
enabling output of the base
module.
A fault in the expansion
module is not detected by X1 X2 13 23 X1 X2 X11 X12
the base module. Base module Expansion module
Connect terminals X1, X2 SRB-NA-... A SRB-ZB-Mo
and X11, X12 to the 14 24 B1 B2 B12
feedback loop of the base
module.

N (L–)

Advice:
WARNING: The expansion
module must be installed
according to the example
shown since the device is
not fitted with its own
safety monitoring.

150
Notes

1
151
1
SRB-LV
Output expansion module for additional enabling outputs
☛ 4 enabling outputs and 1 monitoring output
☛ 90 mm housing

Features – Relay output: 4 NO, 1 NC – LED’s for K1, K2 – Housing 90 mm, made of
(Auxiliary NC for monitoring thermoplastic in accordance with
must not be used in safety – Feedback circuit X1, X2 UL-94-V-0, red RAL 3000
enabling circuits!)
– DIN rail mounting
DIN EN 50 022

Approvals

LR 13571-30 E 54284 (M)

Front view A1
(+) U K1 X1 13 23 33 43 51
SRB-LV

K1 K2

A2
(–) U PE K2 X2 14 24 34 44 52

Product range Type Enabling outputs Operating voltage Part no.


SRB-LV-24V 4 NO/1 NC 24 VDC/VAC 610 0400
SRB-LV-115V 4 NO/1 NC 115 VAC 610 0450
SRB-LV-230V 4 NO/1 NC 230 VAC 610 0470

152
SRB-LV (continued)

Wiring diagram

A1 U U K1 K2 X1 13 23 33 43 51

K1

K1

K1
K2

K2 K2
K1 K2

A2 PE X2 14 24 34 44 52

For further examples


refer to page 154/155

Model specific Operating voltage 24 VDC –15%/+20%, residual ripple max. 10%
Technical data 24 VAC, 115 VAC, 230 VAC –15%/+6%
(refer to page 157 Frequency 50/60 Hz (for AC operating)
for general data)
Fuse (power supply) M 0.25 A/250 V
Power consumption max. 1.2 VA
Switching capacity (enabling contacts) 230 VAC, 6 A ohmic (inductive with suitable suppression)
Fuse (enabling contacts) 6 A slow blowing
Switching capacity (monitoring contacts) 24 VDC/2 A
Fuse (monitoring contacts) 2 A slow blowing
Application category AC 15/DC 13, DIN VDE 0660 Part 200
Pick-up delay ≤ 20 ms
Drop-out delay ≤ 20 ms
Contact material / contacts AgSnO, self cleaning, positively driven
Contact resistance max. 100 mOhm when new
Air and creeping distances DIN VDE 0110-1 (04.97), 4 kV/2
Connections Self lifting screw terminals min. 0.6 qmm, max. 2.5 qmm
Dimensions H/W/D 83 mm/90 mm/127 mm
Weight 410 g (500 g at 115 V and 230 V version)
Ambient operating temperature –25 °C ... +45 °C (derating curve page 157)
Mechanical life 107 switching cycles
Terminal labeling DIN EN 60 445/DIN 40 719 Part 2

1
153
1
SRB-LV (continued)

Wiring example:
Input level
Single-channel control of L (L+)
the expansion module
SRB-LV via one enabling
output of the base module.
A fault in the expansion
module is not detected by
the base module. X1 X2 13 23 U U X1 X2
A1
Connect terminals X1 and Base module Expansion module
X2 to the feedback loop of SRB-NA-... A2 SRB-LV
the base module. 14 24 K1 K2

N (L-)

Wiring example:
Input level
L (L+)
Dual-channel control of
the expansion module
SRB-LV via one enabling
output of the base module.
A fault in the expansion
module is not detected by
the base module. X1 X2 13 23 U U X1 X2
A1
Connect terminals X1 and Base module Expansion module
X2 to the feedback loop of SRB-NA-... A2 SRB-LV
the base module. 14 24 K1 K2

N (L-)

Advice:
Warning !
The expansion module
must be installed according
to the example since the
device is not fitted with its
own safety circuits.

154
Notes

1
155
1
156
General technical data

Design Housing material Fibre glass reinforced thermoplastic, self-extinguishing in accordance


with UL-94-V-0
Colour Red RAL 3000
Protection class Built-in device
Enclosure protection IP 40
Terminal protection IP 20
Indicator lights LED’s

Mechanical data Mounting Top hat rail DIN EN 50 022


Warning: Modules must be assembled with a distance of 10 mm, if the
operating voltage or the ambient operating temperature exceeds.
Mechanical stability VDE 0435
Mounting position optional
Air and creepage distance DIN VDE 0110 Part 1

Electrical data Running time 100% ED


Additional data Refer to device descriptions

EMC Interference suppression Integrated suppressor, electronic EMC suppressor circuit if necessary

Approvals BG, CSA, UL Refer to product ranges (copies available upon request)

Derating curve
SRB-... Ampere
6.0

5.0
Safety enabling outputs with switching
4.0 capacity of 6 A

3.0
Safety enabling outputs with switching
2.0 capacity of 4 A

1.0

0
40 45 50 55 60
Ambient operating temperature
1
157
1
Modules for special applications

Modules for
contact multi-
plying

▲ Examples of SRB modules for contact multiplying

Modules SRB-NA-R-C.EW, However, the availability is different inputs are interrupted. Also after
SRB-LV and SRB-ZB-MO are compared to the SRB combination restart only the enabling outputs of
designed for multiplying of SRB-2NA-R-E/SRB-FE-R for 8 the basic module will be activated,
enabling outputs of other SRB enabling outputs. In case of a broken but not those of the contact multi-
modules. wire between the basic module and plying module.
the contact multiplying module just
Due to a feed back loop to the SRB the additional enabling outputs of
module also in the contact multiply- the contact multiplying module will
ing module the same safety level disconnect at once. The enabling
(category 3 or category 4) is outputs of the basic module will
achieved as in the corresponding disconnect only when the safety
basic module.

Distinct restart SRB module C.25 is equipped with This feature for SRB module C.25
a particular restart circuit. The was developed for applications in
module itself determines which which a restart via Reset button
event has caused the drop out of the would require an unreasonable lot of
enabling outputs. If for instance a performance, i.e. in large installa-
loss in power or because a protective tions with decentralized locations of
device was operated. E-Stops and protective devices
where only short time supply
Automatic restart is provided after a failures may cause a drop out of the
previous power down situation, relay circuit. In situations however,
whilst a restart after operating a when a safety device was operated a
protective device needs an extra manual restart is essential. The
restart signal. function of “distinct restart” needs a
special risk assessment by the user
in order to make sure, that the ▲ Example of SRB module with
automatic restart function does not distinct restart
involve a risk for personal protection
function.

158
Dual channel Customarily dual channel inputs for contact is provided. The monitoring
antivalent input SRB modules have the same of these distinct input circuits
circuits for operating principle, normally based enables for instance to detect the
humid environ- on two NC contacts, one of these at ingress of a conductive liquid into an
least with positive opening function. external safety device.
ments
For SRB module C.26 in particular
an antivalent input circuit, one
consisting of a positively opening
NC contact and the other of a NO

▲ Example of SRB module with


dual channel antivalent input
circuits for humid environments

SRB modules The typical inconstancy of the –25% to +35% of the supply
operated by voltage in battery powered ship and voltage. Furthermore the voltage
battery powered vehicle networks makes it critical to regulator is designed to cope with
networks in use standard safety relay circuits in typical situations in such networks
such a supply system. i.e. the critical interference caused
vehicles and
by "load" and "dump".
others The characteristics of the SRB
modules SRB-NA-NF is an extra
integrated voltage regulator which
can accomodate tolerances from

▲ Example of SRB module for


battery powered safety circuits in


vehicles a. o.

SRB modules The specific feature of this SRB or as a selfholding contact via the
with output module is an extra output to drive guard monitoring contact in case of
to operate the solenoids in interlocking devices automatic interlocking.
solenoids with guard-locking function, either
for devices interlocked by spring
force or interlocked by electro
magnetic force. This additional
contact serves as a selfholding
contact for the interlock pushbutton

Example of SRB module


with output to operate solenoids

159
Modules for special applications (continued)

SRB combi- This module combination consists of A broken wire in hard wired contact
nation modules the basic module SRB-2NA-R-E multiplying circuits would shut
for 8 enabling (with termination plug = 3 enabling down the enabling outputs in the
outputs outputs) and the extension module extension module only and the
SRB-FE-R (with ribbon cable = 8 failure detection via a process
enabling outputs). interrupt is not guaranteed.
Therefore wiring errors can be
excluded.


Example of SRB modules
for 8 enabling outputs

SRBF modules The housing SRBF is designed for Further special features of the SRBF
relay circuits with high complexity housings:
and therefore more space consuming
because of the number of relays and • connection via quick disconnect
other components. strips, alternatively with screw
terminals or with cage clamps,
In all situations where modules with
45 mm, 90 mm and more are an • convenient setting for mode,
obstacle because of the dimension, delay time etc. via DIP switches.
the circuits might be redesigned into
a shape fitting into the SRBF
housing. The described SRBF are
only representative examples.

Muting controls
refer to catalogue
SRB-MS

Two-hand relay
modules
refer to customer
information or
catalogue ZHS

160
Scope of products

Control catego- The internal circuits of the SRB Structure of a safety circuit

ries according modules are designed to correspond Open

EN 954-1 generally with control category 4, in Emergency


Closed

exemptions with category 3. Sensor e.g. stop, inter-


locking devices

The final achieved control category


of the complete safety circuit and
SRB-
therefore the achieved level of safety Precontrol e.g.
Modules
depends however mainly on the
structure of the input and output
Power
circuits. Main
e.g. contactor, SRB module
control
main valve
In the view of control categories
those SRB modules allowing the
loop-in of input channels only into Drive for
hazardous e.g.
Drive motor,
lift cylinder
the power supply are predetermined movements

to control category 3. No practical


B33
input circuits are existing which
could eliminate such kind of errors
leading to a possible accumulation
of failures as described in the
requirements of control category 4.

Categorie Summary of requirements System behaviour Principles


B Safety related parts of machine control systems and/or their When a fault occurs it can lead to the
protective equipment as well as their components shall be loss of the safety function.
designed, constructed, selected, assembled and combined in
accordance with relevant standards so that they can withstand Mainly cha-
the expected influences. racterized by
1 Requirements of B shall apply. As described for Category B, but with selection of
higher safety related reliability of the components
Use well-tried components and well-tried safety principles. safety function.
2 Requirements of B and the use of well-tried safety The occurrence of a fault can lead to
principles shall apply. the loss of the safety function between
the checking intervals.
Safety function shall be checked at suitable intervals by
the machine control system. The loss of safety functions is detected
by.
3 Requirements of B and the use of well-tried safety Some but not all fault will be detected.
principles shall apply.
Accumulation of undetected faults can Mainly
Control systems shall be designed so that: lead to the loss of the safety function. characterized
1. a single fault in the control does not lead to the loss of by structure
the safety function,
2. whenever reasonably practicable, a single fault is detected.
4 Requirements of B and the use of well-tried safety When the faults occur the safety function
principles shall apply. is always performed.

Safety related parts shall be designed so that: Faults will be detected in time to prevent
1. a single fault in any of these parts does not lead to the loss the loss of the safety function.
of the safety function,
2. the single fault is detected at or before the next demand
on the safety function or, if this is not possible, an accu-
mulation of faults shall not lead to a loss of safety functions.

161
Scope of products (continued)

Circuit layout Depending on the utilization purpose


the internal circuits of the SRB
modules are carried out in so-called
2-relay or 3-relay technique.
3-relay technique represents a circuit
with own start relay (K1) which is
set into operation separately by the
start signal and then consecutively
triggers the channel relays K2 and
K3.
Unlike to the above the circuit in
2-relay technique is not triggered by
an own start relay. The initial start
test and setting into operation is
achieved by setting the channel
relays into latch state in one step.
Resulting from the different
operations of relay modules in
2-relay or in 3-relay technique
various functional possibilities are
on disposition. ▲ Example circuit of a SRB module with three safety relays in power off
The advantages of the 2-relay state.
technique are quite obvious:
• Primarily is the space saving in
the control cabinet since the
modules for 24 V generally are
22.5 mm wide only.
• The second important advantage
is the cost saving.
From the safety point of view there
is no difference between these two
circuit techniques. But certain
functional characteristics i.e.
performing of initial start test as
required in control categories 2 and
4 (see par. "Initial Start Test" on
page 163) or start procedures in
connection with feed-back signals
are practically realized only with
circuits using 3 (internal) safety
relays. ▲ Example circuit of a SRB module with two safety relays in power off state.
In all circuits only safety relays with
positively guided contacts are
applied. The majority of the circuits
is equipped with pivoting armature
relays, some others with cutout
blade relays.

162
Input circuitry Input circuits as proposed below are
sufficient in standard situations:
Control category 1:
single channel input without initial
start test.
Control category 2:
Single channel input with initial start
test.
Control category 3:
Dual channel input without initial
start test.
Control category 4:
Dual channel input with initial start
test. ▲ Examples of SRB modules with option "Initial start test"
A dual channel safety circuit is not
necessarily the answer to the
question if a moveable protective Initial start test means the complete contact safety devices (i.e. light
gate needs to be monitored by one or safety circuit needs to perform a test curtains) relay circuits may be
by two Safety Limit Switches. This run on power up prior to be set into needed to perform such a test
is to be found either in the corre- the determined function in order to independently from intention. This
sponding product standards (C- detect possible hidden defects. means in the case of a door inter-
standards) or is resulting of a risk locking that the protective door must
If such an initial start test is not part be opened and closed to initialize
assessment as per EN 1050. of the safety device itself like in non the safety circuit, proper result
provided.

Enabling Enabling
Open output
output
Open
S1
Protective guard

Protective S1
guard
K1
K1
S2
S2
Closed
Closed

K2 K2 K1
K2

K2 K1 K1 K2 K3 K2 K3 K1 K2 K1 K3

K3

K1 K2 K1 K2 K3

e.g. Safety
e.g. Safety relay module
relay module

▲ Example of graded protective measures, Category 3 ▲ Example of graded protective measures, Category 4
Execution: Execution:
1. Two contacts of which at least one contact is positive opening 1. Requirements of Category 3
2. Enclosure for contactor/relay to IP 54 2. Wiring of protective devices in separate jacketed cables or
3. Jacketed cables conforming to relevant standards sequentially with short and cross detection or "special shielded
4. Contactor/relay coils with common connection to ground of cable"
control current circuit. 3. Initial start test

163
Scope of products (continued)

Peculiarities Additional to the initial start test in


of control category 4 it is required to ensure a
category 4 cross short proof installation at the
input channels. This is to be
achieved either by using a separate
multi-core cable ("shielded cable")
for each channel or by fitting a
Safety Relay with cross short
recognition.

▲▲ Examples of SRB modules with



cross-short recognition

SRB modules Relay circuits are generally designed


capable for for inputs from safety devices fitted
external with mechanical contacts. For safety
powered inputs reasons the operating voltage for the
safety devices is sourced from the
SRB modules.
Connection of safety devices with
non isolated contacts i.e. light
barriers with semi-conductor outputs
or from safety devices with outputs
powered from own power supply
needs suitable circuits (refer to
appropriate data sheet).
Connection of safety devices with
isolated contacts is of course still
practical.
▲ Examples of SRB modules for externally powered inputs from electronic
devices. Connection of safety devices with potential free contacts is of course
still practical.

164
"Reset button" : The purpose of using a reset button with trailing edge function (slope monitoring accessible chambers in
Automatic or start button in the input circuitry detection) to prevent unexpected machines and in manufacturing
restart of a relay circuit is under safety restart in case of a faulty start systems. In some cases it is even
aspects persuading the operator to button. required by regulations i.e. when
observe a danger free restart. A using safety mats or optical safety
typical example are E-stop circuits. Trailing edge function means the devices. It must be ensured if a
Any restart needs always a separate relay circuit does not process the regulation requires a trailing edge
Reset button. rising slope from an operated start function resp. a slope detection, the
button, but the trailing slope after involved control part is carried out
Sometimes optional, sometimes it is releasing the button. in fail safe technique, too.
mandatory to provide a dynamic
Start signal from the Start button Signal processing based on trailing
edge function is recommended when

Output circuitry SRB modules are available with 2 Stop category 0 or to Stop category In Stop category 1 (= controlled
and with 3 enabling outputs (plus 1 (see EN 60 204-1 : 1998-11, Part stopping) the enabling outputs will
feedback contact) for standard 9.5.4). drop out time delayed. Purpose is to
applications and for more complex maintain the power supply to the
applications with 4 or 5 enabling In Stop category 0 (= uncontrolled motors etc. to complete a controlled
outputs (plus feedback contact). stopping) the enabling outputs will stop. After run out of delay time the
Furthermore the enabling outputs drop out immediately in order to power will then be cut off.
can be selected in correspondence to interrupt the power supply for the
motors etc. as quickly as possible.

Time delayed An immediate shut down of the • Drop out delay time is either fix • If convenient and adequate in
enabling out- power supply to the motors of or is preset in the factory respect to the process the set
puts hazardous motions etc. does not according to customers request delay time may be reduced by an
always lead to the endeavored quick and/or adjusted on site by the external control signal given to a
stop. user. separate input terminal.
A typical example are motors which
can be slowed down to stand still by
generatoric brake mode more rapidly
rather than by immediate shut down
of the energy. In this case drift to
stand still will take more time and is
therefore more dangerous. Time
delayed enabling outputs are also
taking care that fuses in intermediate
circuits of closed loop drives and
also the drives itself are not being
destroyed.
The delayed shut down of energy,
adapted to the maximum breaking
time of the drive serves as a
protection in the case of failure and
protects against unintended restart.
Depending on the application SRB ▲ Examples of SRB modules with time delayed enabling outputs
modules with time delayed enabling
outputs – some up to 30 seconds –
are available.

165
Scope of products (continued)

Scheme of The delay function of drop out


time delayed delayed enabling outputs in SRB
enabling modules is carried out by using
outputs 2 independent time channels each
triggering 2 independent safety
relays (does not apply for SRB type
C.16).The circuit also corresponds to
EN 60 204 : 1998-11 for E-stop
signals.
Errors in the time modules due to
component defects do not affect the
safety related function of the
delayed enabling outputs. The
protection in case of fault corre-
sponds with control cagegory 4
(EN 954-1).
▲ Further SRB modules with time delayed enabling outputs
In time delayed enabling outputs it
is state of the art to disregard
multiple errors based on component Not considered in the error analyses Application of time delayed
up drifts leading to increased time. of time delayed enabling outputs is enabling contacts is up to the risk
The Berufsgenossenschaft, however, "Power down" and component down and responsibility of the user.
is setting a time limit to max. 30 sec. drift which are reducing (already
if human protection is involved. also as first error) the delay time
accordingly.

Power outputs/ Instructions regarding the power


Contact multi- output circuitry of SRB modules can
plying be concluded normally out of the
C-standards. Regulator
enable
input
In many cases a single over rated On Emergency
power relay (contactor) with stop
positively guided contacts and a NC-
contact wired into the feedback loop
for safety check routines is suffi-
Function course E-
cient. Standard On Stop Time
release 13/14,
23/24, 33/34
When using redundant power relays Time delayed
release 43/44
(contactors) one NC-contact of each
Contactors
must be looped in (in series). For
safety reasons also in this case Motor

contactors with positively guided


contacts shall be preferred. The
regulations for the feedback loop
applies also for further relays used
for contact multiplying.

▲ Controlled shut-down of STOP category I in accordance with


EN 60 204-1 : 1998-11. In this example the controller enable was shut down
immediately after a stop signal from an emergency stop device and the power
contactor K1 only after the operational brake time of the motor.

166
Another good opportunity to A sophisticated combination of
perform dual channel on the power positively guided contacts ensures
side without doubling contactors is maximum only one safety contact
to include the enabling input of the could be affected in case of failure.
closed loop regulator as a second For SUVA dual channel outputs on
channel in the shut down system of a the power side are essential.
dangerous motion (see fig.).
This would also avoid dangerous
situations at the power side caused
by a welded contact of the contactor.
In this case the interrupted enabling
input would stop the dangerous
motion or vice versa.
Should the enabling of the regulator
not work properly it can be assumed
the contactor works correctly and
brings the dangerous motion to stop. In case of dual channel control on
the power level the use of SRB
If the regulator provides also a
modules providing SUVA circuitry
feedback signal an error detection is recommended. The term SUVA
also of this channel is possible. circuitry is rooted back to require-
In practice after a given Stop signal ments from the Swiss occupational
the enabling input of the regulator safety organization SUVA. This
circuit is covering also the simulta- ▲ Examples of SRB modules with
would interrupt at once and the SUVA circuitry
contactor K1 after the preset slow neous welding of contacts in the
down time of the motor. channel relays.

Fuses Generally all SRB modules are On request the outputs are provided In the SRB module C.17 a special
equipped with internal fuses (glass with an automatic unlatched short electronic overload protection is
tube type). In 45 mm wide modules circuit protection. Please note: In performed. In case of overload reset
– excluding exceptions – for free application without Reset button an is achieved by power down followed
access an additional second fuse unintentional restart is to be by power up. So no exchange of
with lower rated current is located expected. The consideration of this blown fuses is necessary and on the
on the front lid for a simplified fuse warning is on the users side. other hand the danger of unintended
exchange. Otherwise it is recom- restart is eliminated.
mended to furnish an additional fuse
with lower rated current in the
power supply circuit.

167
Notes

168
Sales organisation

Europe Overseas
Austria Australia
Belgium Brazil
Czech Republic Canada
Denmark Chile
Finland China
France Hong Kong
Hungary India
Iceland Israel
Italy Japan
Luxembourg Malaysia
Norway Singapore
Poland Taiwan
Portugal USA
Slovakia
Slovenia
Spain
Sweden
Switzerland
United Kingdom

Elan Schaltelemente GmbH & Co. KG


L-SRB-G-08/01-1e

Im Ostpark 2 Phone ++49-(0)641-98 94-0 E-Mail: info@elan.schmersal.de


D-35435 Wettenberg Fax ++49-(0)641-98 94-420 Internet: www.elan.de

You might also like