SELECTION
SUPPLY
SOUND POWER, PRESSURE DROP THROW
(FOR PANEL EXECUTION, SEE CORRECTION FACTORS) (FOR PANEL EXECUTION, SEE CORRECTION FACTORS)
? [mm] 160 200 250 315 400 ? [mm] 160 200 250 315 400
700 30
600 JD150 / JD160 / JD170 JD150 / JD160 / JD170
25 "T [K]=0
500
45
400 20
40
300 40
16
250 35 14
L W [NR] 35
200 30 12
180
" P tot [Pa]
160
L T0.2 [m]
30 25 10
140
9
120 20
25 8
100 LW [dB(A)]
7
80 20 6
70
60 5
15
50
40 4
30 Q v [m³/h]
3 Q v [m³/h]
200 300 400 500 600 800 1000 1500 2000 3000 4000 6000
75 100 150 200 250300 400 500600 800 1000 1500 2000 3000
Q v [l/s]
Q v [l/s]
75 100 150 200 300 400 500 700 9001100 1500 1900
25 30 40 50 60 70 80 100 125150 200 300 400 500 700
THROW
Ø [mm]
160 200 250 315 400 LT0.2 [m] 5 10 15 20
AK [m²] 0,0057 0,0102 0,0168 0,0259 0,0408 JD1-0P2 x1.11 x1.29 x1.32 x1.34
SOUND POWER
LW
JD1-0P2 +3
JD1-0P3 +5
PRESSURE LOSS
Use graph for JD1-0 with the flow rate of 1 unit.
To calculate the airflow behavior in rooms as well as performance data such as sound level and pressure loss,
please consult our FACT selection software.
SELECTION
SELECTION EXAMPLE
Known data
supply air flow rate, Qv [m³/h] 300
supply air temperature,T0 [°C] 26
room temperature, Ta [°C] 26
max. allowable sound pressure, Lp [dB(A)] 35
room sound attenuation, ΔLr [dB(A)] 8
max. allowable velocity in occupied [m/s] 0,2
zone @ 20 m
Selection from graphs
proposal of diffuser size [mm] 315
throw, LT0.2 [m] 17,3
sound power, Lw [dB(A)] <20
sound pressure, Lp (= LW - ΔLr) [dB(A)] <20
total pressure loss, ΔPtot [Pa] 7
LEGEND
Symbol Unit
Ak [m²] effective air discharge surface area (measured)
LT0.2 [m] distance at which the jet centreline velocity decreases to 0.2 m/s
To calculate the airflow behavior in rooms as well as performance data such as sound level and pressure loss,
please consult our FACT selection software.