Professional Documents
Culture Documents
EVair03 TRM CI-3090 RevC
EVair03 TRM CI-3090 RevC
CI-3090 (Rev C)
WWW.JUN-AIR.COM
® Registered Trademark/™ Trademark of JUN-AIR Inc. ©Copyright 2011 JUN-AIR Manufacturing Inc. All Rights Reserved. ISO 9001 CERTIFIED
CI-3090 (Rev C) EVair03 Air Compressor Technical Reference Manual
Recommended tools
10 mm Open-End Wrench
13 mm Open-End Wrench
15 mm Open-End Wrench (or 5/8 inch)
17 mm Open-End Wrench
18 mm Open-End Wrench (or 11/16 inch)
10 mm Hex Socket Wrench (with 8 inch extension)
22 mm Hex Socket Wrench
5 mm Allen Wrench
Regular Flat Tip Screw Driver
Loctite 680
WEEKLY
For electrical connection. MONTHLY ANNUALLY
• Verify that your local mains supply voltage and frequency Check motor, air tubes, hoses and equipment
•
for leaks.
matches the rated device voltage and frequency on the
Clean unit or wipe with a soft, damp cloth.
serial number plate of the compressor. If necessary, use mild detergent on rag to
• Connect the power cord to the mains inlet on the rear of the remove sticky adhesions. Dust and dirt •
prevent cooling.
compressor cabinet.
Replace intake filters (P/N 5412400)1. See fig
• Connect the power cord to the wall outlet. 5a. Refer to Notes 1 & 2. •
• Switch on the mains switch. Verify that the ON-OFF switch Check non-return valves per instructions.
on the front of the compressor unit is lit. Replace if necessary, P/N 5414502 •
Note! Empty receiver of air before dismounting.
The pressure switch is preset and inspected from factory. Instructions for checking the non-return valves
Generally, it will not be necessary to make any adjustments.
Compressor check valve: Disconnect the AIR hose from the
The pressure switch determines whether the unit runs on
pipeline source at the compressor. Turn on the compressor
primary or reserve supply. The left scale (Cut in) indicates at
power switch. Check for air coming out of the pipeline
which pressure the unit switches from reserve to primary supply.
connection at the compressor. Air coming out of this connection
The pressure in the left scale (Cut in) minus the differential is an indication of a faulty compressor check valve. Replace
pressure (Diff.) in the right scale indicates when the unit will the check valve (P/N 5414502). Note: Empty the receiver of air
switch from primary to reserve supply. before dismounting.
To adjust the settings, remove the plastic cover. Use the screws Pipeline check valve: Connect the AIR hose to the AIR pipeline
above the scales to adjust the pressure (Cut in)/differential supply at the compressor. Turn the compressor power switch
pressure (Diff.). to OFF. Verify no air flow at the unloader valve hose. You can do
this by placing your finger over the drain hose going to the water
The values for adjusting the pressure switch are: bottle. Replace check valve if necessary. (Assumes the unloader
Cut in: 280 kpa / 40.61 psi valve is open when the compressor is off).
1. Compressor does not start: 6. Compressor does not switch on when primary pressure
is too low or does not switch off when primary pressure
a. No power from mains. Check circuit breaker and plug. is too high:
b. Breakage or loose joints in electrical connections.
a. Check pressure switch for correct adjustment as
c. Defective capacitor. described in "Adjustment of pressure switch".
d. The thermal protection has switched off the pump due b. If this does not work, the pressure switch is defective and
to overheating. When cooled the pump will automatically must be replaced.
switch on at a suitable operation temperature. Go
through the points in point 5 below. 7. Water in tank (see drain valve fig. 3):
e. The compressor has seized. Replace motor. a. Primary air inlet does not provide dry air. Check the 5µm
filter on the primary supply pipeline to the tank. Press
2. Compressor does not start, makes a buzzing sound the manual drain valve at the bottom of the filter bowl. If
followed by a clicking noise (cannot start against high water comes out of this valve, primary air inlet does not
pressure): provide dry air.
a. The compressor has not been unloaded and there is back The 5µ filter is mounted behind the 5µ and 0.01µ filters,
pressure on the piston. Make sure that the compressor is see fig. 6a.
unloaded each time it stops. Check unloader valve and b. The 5µ and 0.01µ filters used for the reserve supply may
replace, if necessary. See fig. 8. be clogged or there may be dirt in the bowls. Replace
b. Leaky non-return valve. Remove the flexible pressure filter elements and clean bowls.
pipe from motor and check for leaking air from the tank. c. Press the test button on the automatic drain for the filter
If so, clean or replace O-ring or non-return valve. bowls to make sure that it is working properly. Clean
drain valve and pipes or replace auto drain assembly.
3. Compressor works, but pressure does not increase:
Timer for automatic drain is to be set to 2 minutes.
a. Intake filter clogged. Replace.
d. Defective dryer. Replace dryer.
b. Leaks in fittings, tubes or pneumatic equipment. Check
e. Plastic lines are re-usable
with soapy water.
c. Defective valve plate. Replace motor.
d. Failure in non-return valve which is creating a flow
restriction. Replace non-return valve.
e. Check relief valve settings, turn clockwise to increase
pressure.
f. Unloader valve does not close. Clean or replace unloader Set at 2.0
valve.
g. Higher leakage in dryer than normally. Disconnect the
tubes to and from the dryer. Assemble the disconnected
tubes and check if the pressure increases. If the pressure
increases replace the dryer.
Pictures/figures
Primary supply
Reserve supply
Fig. - 5 Intake filter and key Fig. 6a - 5μ and 0.01μ filters for reserve
supply.
The 5μm filter for primary supply, is mounted
behind these filters.
Pictures/figures
Fig. 7a - Non-return valve Fig. 7b - Non-return valve Fig. 8 - Unloader valve and dryer
(compressor) 5414500 (pipeline) 5414502 connection.
Solenoid Nut torque 2.5 Newton Meter.
(22.1 pound Inch or 354.0 oz inch)
February 9, 2004
R1.20
CI-3090 (Rev C)
Safety valve
See spec.
All pipes 6mm
Pressure switch Non-return
See spec. valve
Pipeline output
Reserve supply 1.5 l tank
w/manual
Heat Filter Membrane Non-return drain
Pump Filter 5µ
exchanger 0.01µ dryer DA valve
Muffler
Intake filter
1l water
drain bottle
R1.18
M
Thermal
switch
Pressure switch cutout Temperature
180 °C for 230 V switch for fans
170 °C for 120 V
Fan Fan
Circuit breaker
230V: 5A
120V: 9A
AWG16
L
AC outlet for auxiliary equipment
AC inlet IEC 320 10A socket
IEC 320 15A plug
N
CI-3090 (Rev C)
11
CI-3090 (Rev C) EVair03 Air Compressor Technical Reference Manual
Drawings
Drawings
#7181001
#4785602 230 V
#4785652 120 V
#4147000
#5095001
#4779900
#4141840
#4799502 230 V
#4799602 120 V
Drawings
#6984512
#5370055
#2882110 230V
#2882210 120V #5412400
#7024002
#6452028
#6984492 #6985062
#6984569 230V
#6984570 120V
#4783955 230V
#4783956 120V
#5150025
#6253701 #4781555
#7568055
#6984508
#4752000 230V
#4752200 120V
#6985795
#5237007 230V #4141701
#5240609 120V
#5414500
#5414502
7167101 & 6243715
#7070500
#7565000
#5417700
#7160500
#5425500
#3001599
© 2011, GAST Manufacturing Inc.
14 We reserve the right to make changes due to technical improvements
Printed in the USA
EVair03 Air Compressor Technical Reference Manual CI-3090 (Rev C)
In the following parts list, assemblies are printed in capital
letters. Parts that are included with an assembly are listed and
indented directly beneath it. When an assembly is ordered, the
assembly and all parts indented beneath it are included in the
shipment.
Spare parts
2882110 Motor compressor OF302 230 V/50 Hz Datex 6984492 Front plate complete f/OF302-1.5SDA
2882210 Motor compressor OF302 120 V/60 Hz Datex 6984508 Cabinet plate f/OF302-1.5SDA 120 V complete
Receiver 1.5 l with inspection plug and internally coated, 6984512 Top f/OF302-1.5SDA complete
3001599
silver CE
6984569 Back f/OF302-1.5SDA 230 V complete
4071000 Filter 5 um w/manual drain
6984570 Back f/OF302-1.5SDA 120 V complete
4071001 Filter 5 um (without manual drain)
6985062 ASL Snap lock (complete set) old version
4071056 Filter 0.01 um (without manual drain)
6985795 Filter mat f/air intake f/OF302-1.5SDA
4071220 Spare parts kit relief valve 3407-80
7020000 Double nipple 1/8”
4071293 O-ring filter bowl seal
7024000 Double nipple 1/4” L= 26 mm
4082300 Membrane dryer (DA)
7025000 Double nipple 1/4”x 1/8”
4141700 Rapid fitting 1/4” external x Ø6
7025310 Bushing f/autodrain f/metal cabinet 1/8”
4141701 Rapid fitting elbow 1/4” external cyl. x Ø6
7070500 Connection piece f/non-return valve model 12
4141820 Rapid fitting elbow 1/8”internal x Ø6
7071500 T-piece 1/4” (3 x internal)
4142300 Rapid fitting 1/8”xØ4
7074500 Coupling 1/4”
4146800 Rapid fitting Ø6 mm x 1/4” elbow
7181001 Elbow 1/4” ext./ext. with plastic gasket
4147000 Rapid fitting straight 1/8” ext. x Ø6 mm
7568055 Bushing f/OF302-1.5SDA
4147555 Rapid fitting T-piece Ø06 x 1/4”
5471001 Filter kit f/OF302-1.5SDA
4147556 Rapid fitting T-piece Ø 06 x 1/4” (1/4” side thread)
2x4071210 Spare parts kit f/5 um filter regulator 3652-19
4383205 Bracket f/membrane dryer Ø18 mm
4071240 Spare parts kit f/0.01 um filter 4141-12
4752000 Hour counter 230 V
2x5412400 Intake filter f/OF301 and OF302 motors
4752200 Hour counter 120 V
6985795 Filter mat f/air intake f/OF302-1.5SDA
4779900 Bimetal switch
5471002 10,000-hour kit 230 V/50 Hz
4781555 Plug type 0712 f/cabinet (f/2 mm plate)
4772610 Motor compressor OF302 230/50 Hz Datex
4783955 Switch 230 V (A32-4-F-050-CO-AZMO3)
4785602 Solenoid valve f/unloader 230 V w/plug
4783956 Switch 120 V (A34-4-F-090-CO-AZMO3)
4799502 Auto drain 220-240V series 590
4785602 Solenoid valve f/unloader 230 V w/plug
5414500 Non return valve
4785652 Solenoid valve f/unloader 120 V w/plug
5414502 Non return valve f/Datex complete
4799502 Auto drain 220-240V series 590
5471003 10,000-hour kit 120 V/60 Hz
4799602 Auto drain 120 V series 590
4772608 Motor compressor OF302 120/60 Hz Datex
5095001 Pressure switch - customized
4785652 Solenoid valve f/unloader 120 V w/plug
5150025 Gauge Ø40 built-in
4799602 Auto drain 120 V series 590
5237007 Capacitor, run complete 20 uF/230 V AC f/OF300 (40 cm)
5414500 Non return valve
5240609 Capacitor, run complete 60uF OF300/OF1200 (45 cm)
5414502 Non return valve f/Datex complete
5412400 Intake filter f/OF301 and OF302 motors
5417700 Drain cock 1/4 inch
5414500 Non return valve
7565000 Bushing 1/4 ext. and 1/8 int.
5414502 Non return valve f/Datex complete
5370055 Service handle
5416555 Relief valve V07-254-NNLG
6253701 Rubber base
5425500 Safety valve TÜV 10 bar
6985562 Mounting plate f/ OF302-1.55DA
5447035 Radiator complete
7171855 Distance piece f/ motor vertical
5450155 Fan 120 V 4606Z
4141840 Rapid fitting elbow 1/8 int x 04
5451055 Fan 230 V 4656Z
7070500 Conn. piece f/ non-return valve
6295500 Grommet 170211
7167101 Plug 1/8 inch w/o o-ring
6452028 Teflon hose 1/4” 28 cm with elbow
6243715 O-ring 07 x 1.5 Viton
6976000 Silencer 1/8”
7160500 Cross connections 1/4 inch w/ thru 1/4 inch
Spare parts
Repair Procedure
Remove back panel by releasing the four quarter-turn fasteners; release the four quarter-turn fasteners on the front panel
and swing panel open. (Take caution as to not cut/damage wires or air lines that are connected).
Loo
Hint: Loosen and remove lower mount screws on the front side of the unit, while compressor is still resting on mounts. (Reminder:
Ensure that the 11/16 inch (or 18 mm) wrench is engaged with the hex part of the mount). Lay compressor on its top supported by a
cushion/block, so that the wires and/or lines are not pulled, pinched, nor cut.
Proceed with the removal of the mounts via the 11/16 inch (or 18 mm) open-end wrench and 5 mm allen wrench. (Ensuring that the
wrench is engaged with the hex part of the mount).
6.) The installation of these mounts is accomplished by carrying out these procedures in reverse order.
Loctite may be applied to the threads of the bolts prior to assembly to ensure that they do not vibrate loose during normal use. Ensure
that the open-end wrench is engaged with the hex of the mount when being used for the tightening of these bolts.
Parts List
Tools required
• Loctite 242
• 10 mm, 13 mm, 17 mm open-end wrench
• 22 mm hex socket wrench
• Small flat-blade screwdriver
Procedure
Prior to removing the unit from the ventilator, a leak rate on the compressor should be established as a reference. Do this by ensuring
the ventilator is off and disconnect the pipeline supply. Turn on the compressor and allow it to build up to maximum pressure. Make
a note of this pressure, and then turn off the compressor. Wait one minute and then record the current pressure. The difference in
these valves will be the leak rate of this assembly. After re-assembly, perform this test again to ensure the leak rate is no larger than
the original. Due to the numerous differences in system configuration, a specification for an unacceptable leak is not possible. The
purpose of this test is to ensure a leak rate hasn't increased during the repair process.
6. Remove the 13 mm nut that secures the motor capacitor 3. Remove the top section of the non-return valve using a
to the lower assembly. 22 mm socket.
7. Carefully lower the assembly onto its back as pictured.
.
4. Remove the internal components of the check valve.
5. Remove the bottom section of the non-return valve using
8. Pull the lower section away from the top as pictured. a 22 mm socket.
NOTE: You do not have to disconnect any tubing. 6. Apply a small amount of Loctite 242 to the thread of the
new non-return valve. Install it into the connector piece.
7. Clean the old Loctite from the threads of the tubing
adapter.
8. Apply a small amount of Loctite 242 to the thread on the
top of the non-return valve. Reinstall the tubing fitting
removed in step 2.
9. Re-assemble the compressor in reverse order.
10. Ensure all tubing and wiring is properly connected and
routed.
11. Perform the leak check to ensure no additional leakage is
noted.
Contact information