MAIN FEATURES
Amperage 40 A
Weight (kg) 27
NF EN 60947
VDE 0660
In Accordance With BS EN 60947
JEM 1038
IEC60947-1 & IEC60947-4
8 Ctra. Murcia - San Javier, km 23.6 | 30730 SAN JAVIER (Murcia) SPAIN | TLF. +34 968 19 11 28 / +34 902 19 11 28
Fax +34 968 19 12 17 | Export Fax +34 968 33 43 03 | E-mail: info@himoinsa.com | www.himoinsa.com
CC2-40
SWITCHING DIAGRAM
ELECTRICITY GENERIC
GRID GENERATOR
SET
CC2 | CEC7
1 km (*1) CENTRAL
GRUPO
VOLTAGE FREE / DRY CONTACT.
SELECTION OF
POWER SOURCE
For communications of over 100 metres a supplemental power supply is necessary, which is equipped
with an auxiliary battery that maintains the power supply in both modules, from the time when a power
failure occurs until the generator set starts up.
9 Ctra. Murcia - San Javier, km 23.6 | 30730 SAN JAVIER (Murcia) SPAIN | TLF. +34 968 19 11 28 / +34 902 19 11 28
Fax +34 968 19 12 17 | Export Fax +34 968 33 43 03 | E-mail: info@himoinsa.com | www.himoinsa.com
CC2-40
MAIN COMPONENTS
2 3
1) Metal cabinet. Made from high-quality sheet metal. IP55 protection rating which guarantees sealing
and insulation levels.
2) CEC7 Control Unit & 3) Measurements module. The control unit and the measurements module are
responsible for monitoring the quality of the grid signal; they are able to order the start-up of an external
generator set and manage its shutdown once the grid supply is re-established. It has a 4-line graphic
display with language selection to view the status of the generator set.
5) Contactor. Pair of mechanically interlocked four-way switches and with status contacts.
(see table pg. 4 - 4 Pole Contactors with AC operating coil Characteristics)
6) Grounding line connection. Ground connection electrical installation with connection ready for
ground spike (not supplied).
10 Ctra. Murcia - San Javier, km 23.6 | 30730 SAN JAVIER (Murcia) SPAIN | TLF. +34 968 19 11 28 / +34 902 19 11 28
Fax +34 968 19 12 17 | Export Fax +34 968 33 43 03 | E-mail: info@himoinsa.com | www.himoinsa.com
CC2-40
GENERAL CHARACTERISTICS
Unit
Degree of protection Conforming to VDE 0106 Protection against direct finger contacts
POLE CHARACTERISTICS
Unit
Irms conforming to
Rated making capacity A 450
IEC-60947-4
Irms conforming to
Rated breaking capacity A 450
220-440V
11 Ctra. Murcia - San Javier, km 23.6 | 30730 SAN JAVIER (Murcia) SPAIN | TLF. +34 968 19 11 28 / +34 902 19 11 28
Fax +34 968 19 12 17 | Export Fax +34 968 33 43 03 | E-mail: info@himoinsa.com | www.himoinsa.com
CC2-40
Unit
50 Hz Coil VA 90
COS φ 0.75
AC 50 Hz
50 Hz Coil VA 7.5
COS φ 0.75
AC 60 Hz
60 Hz Coil VA 8.5
COS φ 0.3
Closing time
msec 15-24
Average operating “C”
time at Uc Opening time
msec 05-19
“O”
In operating
Maximum operating rate 3600
cycle/hour
Unit
12 Ctra. Murcia - San Javier, km 23.6 | 30730 SAN JAVIER (Murcia) SPAIN | TLF. +34 968 19 11 28 / +34 902 19 11 28
Fax +34 968 19 12 17 | Export Fax +34 968 33 43 03 | E-mail: info@himoinsa.com | www.himoinsa.com
CC2-40
NO
PE
PE
H
C
2
2
TERMINAL CONNECTION DIAGRAM
H | CAN H
L | CAN L
18 | C
19 | NO
PE | GROUNDING
LINE CONNECTION
1 | NEGATIVE
20 | POSITIVE
H | CAN H
L | CAN L
18 | C
19 | NO
PE | GROUNDING
LINE CONNECTION
GENERIC GENSET
2 3 4 5 6 PE 1 2 3 4 5 6 PE
NO
PE
PE
H
C
2
H | CAN H
L | CAN L
18 | C
19 | NO
PE | MISE À LA TERRE
1 | NÉGATIF
20 | POSITIF
H | CAN H
L | CAN L
18 | C
19 | NO
PE | MISE À LA TERRE
2 3 4 5 6 PE 1 2 3 4 5 6 PE
INPUTS OUTPUTS
NO
PE
PE
H
C
2
13 Ctra. Murcia - San Javier, km 23.6 | 30730 SAN JAVIER (Murcia) SPAIN | TLF. +34 968 19 11 28 / +34 902 19 11 28
Fax +34 968 19 12 17 | Export Fax +34 968 33 43 03 | E-mail: info@himoinsa.com | www.himoinsa.com
CC2-40
The CEC7 control unit monitors the quality of the grid signal and can order an external generator set to start up and
to then handle its close-down once the grid supply has been reinstated. It is possible to integrate the management
of the genset by using the CEM7 (or CEM7G) control unit which allows you to view the status of the generator
set (measurements, alarms, etc.) from the controller’s interface. If you use any other control unit model in the
generator set, the generator set start-up is ordered by free voltage contact. It has a 4-line graphic display with
language selection to show the status of the generator set.
• Standard O Optional
CEC7 CEC7
Voltage between phase and neutral • Genset start-up in test mode function •
Currents • Genset in reserve •
Frequency • Start-up by load demand •
THD • Multilingual •
Engine Protection Devices Special Applications
Emergency Stop • GPS location O (CEM7)
Modbus RS485 O
C2LAN Ethernet O