Professional Documents
Culture Documents
10 1109@cjece 2019 2906007
10 1109@cjece 2019 2906007
curves tool [19]. A Q–V curve has a base case with reactive
power equal to zero. This base case is also named an initial
voltage point.
For a selected bus, if the specified voltage can be reached
without needing additional reactive power compensation when
varying the voltage setting points of the bus, the Q–V curve
for this particular bus may be flat. One example would be to
study the Q–V curve at a real generator’s terminal bus; the
Q–V curve will be flat at zero within the generator’s reactive
power capability. This remains true if the measurements are
taken to obtain the Q–V curve instead of simulation.
Although Q–V curves created through power-flow simula-
tion have been practiced for decades, the accuracy of such
Q–V curves depends on the accuracy of the power-flow sim-
ulation model. To overcome this limitation, a measurement-
based Q–V curve method is proposed in this paper. By using
this measurement-based method, a power system simulation
model and the related procedures are not required; Q–V curves
Fig. 2. Electrical single-line diagram of the sample WPP. are created directly using the field measurement data that
reflect real system operation conditions.
offering a convenient way to evaluate the voltage stability and In this paper, measurements were taken at the POI of the
implement the voltage control at the POI of a WPP. WPP. As a generation system, the whole WPP can be treated
as an equivalent generator, and thus, the POI is practically a
III. S YSTEM U NDER S TUDY generator bus.
A 27-MW grid-connected WPP currently in operation in
NL, Canada, is used as a sample WPP in this paper. There A. Proposed Procedure to Draw Q–V Curves
are nine doubly fed induction generators (DFIG), each rated Three scenarios are considered for creating a measurement-
at 3 MW, in this WPP. The WPP is integrated into the power based Q–V curve at the POI of the sample WPP using the
grid’s 66-kV bus through a step-up transformer. The electrical SCADA data: 1) Scenario 1—base case (the initial voltage
single-line diagram of a wind farm is shown in Fig. 2. point) is the lowest voltage point; 2) Scenario 2—base case
The measurements were conducted on the primary 66-kV (the initial voltage point) is the data point with the reactive
side of the 25-MVA step-up transformer through the SCADA power equal to 0 (Q = 0) or near zero; and 3) directly
system for a whole year in 2016. The data sampling rate plotting the Q–V curve using the measurement data. Similar
is 1 sample point/s; each sample point was stamped with to traditional Q–V curves, a fixed active power value is chosen
a corresponding date and time when it was recorded. Each for each Q–V curve.
measurement point consists of three measured data: the voltage The procedure to draw a Q–V curve for Scenario 1 is shown
magnitude in V, the active power in MW, and the reactive in the following.
power in MVAR. 1) For a given month, choose an active power P value from
It was found that the active power supplied by the WPP the SCADA data, for example, P = 4.1–4.2 MW and
significantly varies during the operation every month, ranging then select all data points within this specified active
from 2 to 27 MW. power range.
2) Rearrange the data points based on their voltages
IV. M EASUREMENT-BASED Q–V C URVE increasing from small to large for Scenario 1 with the
Q–V curves are commonly used for voltage stability eval- lowest voltage point as the very first point in the data
uation and voltage control. The traditional way to generate set.
a Q–V curve at a load bus of interest in a power system 3) The voltage of the first data point is named V 10 , and the
is through off-line successive power-flow simulation. The reactive power of the first data point is named Q10 . This
procedure is to first change the selected load bus to a PV bus point is treated as an initial condition, also known as the
in the power-flow simulation and then, record the required “base case;” therefore, it has reactive power equal to 0
reactive power by placing a variable reactive power source, on the Q–V curve. The first point on the Q–V curve is
such as a fictitious generator (synchronous condenser) at the then determined by Q0 = Q10 − Q10 = 0, V = V 10 ,
selected bus for different bus voltage settings (the active power i.e., (Q0, V 10 ).
remains the same for a particular Q–V curve). The voltage 4) The voltage of the second data point is named V 11
set point of this fictitious generator is varied, and its reactive (V 11 > V 10 ), and the reactive power of the second
power output is allowed to be any value needed to meet data point is named as Q11 . The change in the reactive
the voltage set point; this is how the commercial software, power output for the second data point voltage can be
PowerWorld, computes the Q–V curves in the software’s Q–V calculated as Q1 = Q11 − Q10 . The second point
166 CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 42, NO. 3, SUMMER 2019
TABLE I
G OODNESS OF F IT S TATISTICS FOR P OLYNOMIAL 5 AND G AUSSIAN 2 F ITTING
TABLE III
E RRORS B ETWEEN C ALCULATED D ATA U SING P OLY 11 AND P OLY 22 IN M ETHOD 1 V ERSUS SCADA M EASUREMENT D ATA IN M ARCH 2016
power is taken instead of a single value in order to obtain in Tables I and II and the corresponding reactive power and
enough points for a better curve fitting while maintaining a voltage values measured in March 2016. Method 2 is to use all
practically constant real power P value for each Q–V curve. SCADA data in March 2016. The two methods are discussed
The goodness of fit statistics of the curve fitting using the in the following.
two target equations, (10) and (11), is displayed in Table I.
The goodness of fit for the fitting equations can be evaluated A. Method 1
by four parameters: the sum of squares due to error (SSE),
In this method, only a partial of the SCADA data in
the root-mean-squared error (RMSE), the R-square, and the
March 2016 is used. Thirteen active power P values shown
adjusted R-square. An accurate model usually has a smaller
in Tables I and II, together with all associated reactive power Q
SSE or RMSE value but with R-square and adjusted R-square
and voltage V values, serve as input data for the surface fitting.
closer to 1 [2].
Both polynomial 11 (Poly11) and polynomial 22 (Poly22) are
It is found that Gaussian 2 model shows better accuracy for
considered as the target functions. The Q–P–V curve in the
most cases than Polynomial 5 model for March data, showing
form of Poly11 is expressed as follows:
smaller SSE and RMSE errors and larger R-square values. The
determined coefficients for Gaussian 2 mathematical models Q 11 = f 11 (P, V ) = p00 + p01 P + p10 V (12)
for each Q–V curve with a particular active power P are
where p00 , p01 , and p10 are coefficients for Poly11, P is the
provided in Table VIII. Three sample Q–V curves using
active power in MW, and V is the voltage magnitude in p.u.
Gaussian 2 for three different active power values are shown
The Q–P–V curve in the form of Poly22 is expressed by
in Fig. 4.
the following equation:
A further study using the SCADA data measured in
June 2016 for the same WPP indicates that Polynomial 5 Q 22 = f 22 (P, V ) = p00 + p01 P + p10 V
model has better accuracy for more than half cases for the
+ p02 P + p11
2
V P + p20 V2 (13)
June data set. Therefore, either Polynomial 5 or Gaussian 2
where p00 , p , p , p , p , and p are coefficients for
model can be chosen to develop a Q–V curve based on the 01 10 20 11 02
particular data set. Poly22, P is the active power in MW, and V is the voltage
magnitude in p.u.
The goodness of fit statistics of the surface fitting using the
V. M EASUREMENT-BASED Q– P–V C URVE two target equations, (12) and (13), are displayed in Table II.
The Q–P–V curve is required to implement a control action It appears that Poly 11 and Poly 22 have similar accuracy in
for the voltage at the POI. Reference [17] derived such a this fitting, with Poly 22 slightly more accurate than Ploy 11.
relationship based on the manufacturer data of wind turbines. Coefficients for Poly 11 and Poly 22 with 95% confidence
In this paper, a measurement-based Q–P–V characteristic can bounds can be found in Table IX.
be determined through the surface fitting technique using the The accuracy of the fit Poly11 and Poly22 equations are
SCADA data, and a practical control scheme can be developed compared with the SCADA data in March 2016 by choosing
using this curve. the random measurement data points throughout the month as
In this paper, two methods are considered to develop the shown in Table III; relative errors between the calculated data
Q–P–V curves using the SCADA data for a particular month. using the fit equations and the SCADA measurements are also
Method 1 is to use only partial measurement data, for example, shown in Table III. Table V also indicates that Poly11 has a
use data points sorted with 13 specific active power values comparable error as Poly22.
LIANG et al.: MEASUREMENT-BASED CHARACTERISTIC CURVES FOR VOLTAGE STABILITY AND CONTROL AT THE POI OF WPPs 169
Fig. 4. Created Q–V curves by Gaussian 2 model using the SCADA data at the POI of the WPP measured in March 2016. (a) P = 2.1–2.11 MW.
(b) P = 12.1–12.11 MW. (c) P = 20.1–20.11 MW.
TABLE IV TABLE V
G OODNESS OF F IT D ATA C OMPARISON B ETWEEN P OLY 21 AND G OODNESS OF F IT D ATA OF P OLY 21 M ODELS
P OLY 55 M ODELS
TABLE VI
E RRORS B ETWEEN THE C ALCULATION AND F IELD M EASUREMENT A CTUAL D ATA FOR T HREE T YPES OF P OLY 21 M ODELS
TABLE VII
E RRORS B ETWEEN C ALCULATED D ATA U SING P OLY 21 (LAR) AND P OLY 21 (W ITHOUT ROBUSTNESS ) IN M ETHOD 2 V ERSUS SCADA
M EASUREMENT D ATA IN M ARCH 2016
Fig. 5. Errors between the calculated reactive power Q and SCADA Fig. 6. Developed poly21 model through surface fitting using the LAR
measurement data in March 2016 for models developed by Methods 1 and 2. algorithm based on the field measurement data at POI. (a) Surface fitting
diagram. (b) Residuals.
TABLE VIII
C OEFFICIENTS FOR Q–V C URVES U SING G AUSSIAN 2 M ODEL W ITH 95% C ONFIDENCE B OUNDS
TABLE IX TABLE X
C OEFFICIENTS FOR P OLY 11 AND P OLY 22 (M ETHOD 1) C OEFFICIENTS OF P OLY 21 M ODELS (M ETHOD 2)
W ITH 95% C ONFIDENCE B OUNDS W ITH 95% C ONFIDENCE B OUNDS
MATLAB curve fitting toolbox. The accuracy of the Q–P–V Xiaodong Liang (M’06–SM’09) was born in
curves is validated using the SCADA measurement data. Lingyuan, China. She received the B.Eng. and
M.Eng. degrees from Shenyang Polytechnic Univer-
The proposed measurement-based methods do not reply sity, Shenyang, China, in 1992 and 1995, respec-
on the power-flow simulation model and do not need the tively, the M.Sc. degree from the University of
manufacturer data or the system configuration. This data- Saskatchewan, Saskatoon, SK, Canada, in 2004, and
the Ph.D. degree from the University of Alberta,
driven approach can help to achieve voltage stability evalu- Edmonton, AB, Canada, in 2013, all in electrical
ation or real-time voltage control with great accuracy. engineering.
From 1995 to 1999, she was a Lecturer with
VII. A PPENDIX Northeastern University, Shenyang. In 2001, she
joined Schlumberger, Edmonton, a world-leading oil field service company,
See Tables VIII–X. where she was promoted to Principal Power Systems Engineer in 2009.
After serving Schlumberger for almost 12 years, she joined Washington State
University, Vancouver, WA, USA, in 2013. From 2013 to 2015, she was an
R EFERENCES Assistant Professor with Washington State University. In 2015, she joined the
[1] Z. Huang, L. Bao, and W. Xu, “A method to measure QV curves and Memorial University of Newfoundland, St. John’s, NL, Canada, where she is
its applications in power systems,” Electr. Power Energy Syst., vol. 29, currently an Associate Professor. Her current research interests include power
pp. 147–154, Feb. 2007. systems, renewable energy, and electric machines.
[2] C. Andalib-Bin-Karim, X. Liang, N. Khan, and H. Zhang, “Determine Dr. Liang is also a registered Professional Engineer in the province of
Q–V characteristics of grid-connected wind farms for voltage control Newfoundland and Labrador, Canada.
using a data-driven analytics approach,” IEEE Trans. Ind. Appl., vol. 53,
no. 5, pp. 4162–4175, Sep./Oct. 2017. Md. Nasmus Sakib Khan Shabbir (S’17) was born
[3] S.-C. Wang, C.-J. Wu, and P.-H. Huang, “Analysis of power system in Tangail, Bangladesh. He received the B.Sc. degree
QV curve by Fuzzy modeling,” in Proc. ICROS-SICE Int. Joint Conf., in electrical and electronic engineering from the
Aug. 2009, pp. 343–347. Rajshahi University of Engineering & Technology,
[4] T. J. Overbye, I. Dobson, and C. L. DeMarco, “Q-V curve interpretations Rajshahi, Bangladesh, in 2012. He is currently pur-
of energy measures for voltage security,” IEEE Trans. Power Syst., vol. 9, suing the Ph.D. degree with the Memorial University
no. 1, pp. 331–340, Feb. 1994. of Newfoundland, St. John’s, NL, Canada.
[5] R. S. Moura, A. C. Z. de Souza, B. I. L. Lopes, and F. W. Mohn, “Effects From 2013 to 2016, he was a Lecturer with the
of QV curves in the dynamic behaviour of power systems,” IET Gener., Department of Electrical and Electronic Engineer-
Transmiss. Distrib., vol. 10, no. 12, pp. 2861–2870, 2016. ing, Bangladesh University of Business and Tech-
[6] B. H. Chowdhury and C. W. Taylor, “Voltage stability analysis: V-Q nology, Dhaka, Bangladesh, where he was promoted
power flow simulation versus dynamic simulation,” IEEE Trans. Power to Assistant Professor in 2016 and served until 2017. His current research
Syst., vol. 15, no. 4, pp. 1354–1359, Nov. 2000. interests include the design and control of high-performance power electronic
[7] P. Kundur, Power System Stability and Control. New York, NY, USA: converters and their applications in renewable energy integration to power
McGraw-Hill, 1994, p. 965. grids.
[8] G. G. Rao, H. P. Kecincha, and D. Thukaram, “Voltage stability: Some
reflections on Q-V characteristics of loads,” in Proc. Int. Conf. Energy
Manage. Power Del. (EMPD), Mar. 1998, pp. 79–84.
[9] Y. Fu, T. S. Chug, and X. Y. Li, “An improved approach to voltage sta- Nahidul Khan was born in Dhaka, Bangladesh. He
bility analysis via network equivalence,” in Proc. Int. Conf. Adv. Power received the B.Sc. degree in electrical and electronic
Syst. Control, Operation Manage. (APSCOM), Nov. 1997, pp. 231–235. engineering from the Khulna University of Engineer-
[10] Y.-Y. Hong and C.-C. Liu, “A heuristic and algorithmic approach to ing & Technology (KUET), Khulna, Bangladesh,
VAR planning,” IEEE Trans. Power Syst., vol. 7, no. 2, pp. 505–512, in 2004, and the M.Eng. and Ph.D. degrees in elec-
May 1992. trical engineering from the Memorial University of
[11] R. R. Austria, X. Xu, and M. Power, “Voltage stability assessment of the Newfoundland, St. John’s, NL, Canada, in 2008 and
National Grid system using modern analytical tools,” in Proc. IEEE/PES 2015, respectively.
Transmiss. Distrib. Conf. Expo., Nov. 2001, pp. 229–234. From 2005 to 2006, he was a Lecturer with Stam-
[12] M. H. Haque, “Use of V-I characteristic as a tool to assess the static ford University Bangladesh, Dhaka. From 2013 to
voltage stability limit of a power system,” IEE Proc.-Gener., Transmiss. 2015, he was a Protection and Control Engineer
Distrib., vol. 151, no. 1, pp. 1–7, Jan. 2004. with Newfoundland and Labrador Hydro - a Nalcor Energy company, St.
[13] M. Sobierajski, K. Wilkosz, J. Bertsch, and M. Fulczyk, “Using bus John’s, where he is currently a System Operation Engineer. His current
impedance and bus P-Q curve for voltage stability control,” in Proc. research and teaching interests include renewable energy integration, energy
IEEE/PES Transmiss. Distrib. Conf. Expo., Nov. 2001, pp. 79–84. storage application, multiterminal high-voltage direct current transmission,
[14] M. Sobierajski and M. Fulczyk, “Voltage stability study by P-Q curve and power system operation and control, developing transient analysis and
with rectangular probability distribution of bus load,” in Proc. 8th Int. creating operational philosophies.
Conf. Probabilistic Methods Appl. Power Syst., 2004, pp. 894–899. Dr. Khan is also a registered Professional Engineer in the province of
[15] S. H. Li and H. D. Chiang, “Continuation power flow with nonlinear Newfoundland and Labrador, Canada.
power injection variations: A piecewise linear approximation,” IEEE
Trans. Power Syst., vol. 23, no. 4, pp. 1637–1643, Nov. 2008.
[16] P. Prabhakar and A. Kumar, “Performance evaluation of voltage stability Xiaodi Yan was born in Beijing, China. He is
index to assess steady state voltage collapse,” in Proc. 6th IEEE Power currently pursuing the bachelor’s degree in electrical
India Int. Conf. (PIICON), Dec. 2014, pp. 1–6. engineering and computer science with the Memo-
[17] W. Edmondson and S. Mukherjee, “Adaptive capacitor switching for rial University of Newfoundland, St. John’s, NL,
wind energy generation,” in Proc. IEEE Ind. Appl. Soc. Annu. Meeting, Canada.
Oct. 2017, pp. 1–6. He has done a co-op work term working on data
[18] Y. Wang, “Advanced load shedding scheme for voltage collapse pre- mining of grid-connected wind-farm measurement
vention,” Ph.D. dissertation, Dept. Elect. Comput. Eng., Univ. Alberta, data at the Department of Electrical and Computer
Edmonton, AB, Canada, 2011. Engineering, Memorial University of Newfoundland,
[19] (Jan. 1, 2019). QV Curves. [Online]. Available: https://www.powerworld. from 2017 to 2017.
com/WebHelp/Content/MainDocumentation_HTML/QV_Curves.htm