Professional Documents
Culture Documents
Exertherm Manual MA-141-1-EN (UCP)
Exertherm Manual MA-141-1-EN (UCP)
MA-141-1-EN
Exertherm® Design, Installation & Operation Manual
This manual contains information that is fundamental both to the operation of the Exertherm
system and to operator safety. Please read the manual thoroughly prior to commencing any
work.
The general hazard (ISO7000-0434) symbol is used where non-observance of the
information/instruction might cause hazards to person(s) or the equipment.
Contents
1. Version Change Control Record ................................................................................................................ 2
2. Using this Manual .................................................................................................................................... 3
3. Ownership, Notes and Critical Disclaimers ............................................................................................... 8
Notices: ................................................................................................................................................................................. 8
Intellectual Property, Patents, Trade Marks and Registered Designs ................................................................................... 8
Standards and approvals ...................................................................................................................................................... 9
Personnel Qualification and Training.................................................................................................................................... 9
Warranty............................................................................................................................................................................... 9
Live Working ....................................................................................................................................................................... 10
4. Exertherm® System ................................................................................................................................11
Exertherm Integration Options ........................................................................................................................................... 12
Core Components ............................................................................................................................................................... 13
Exertherm Non-Contact Infrared (IR) Sensor...................................................................................................................... 13
Exertherm EM Cable Sensor ............................................................................................................................................... 13
Exertherm Contact / Ambient Sensor ................................................................................................................................. 13
Exertherm Modbus Datacard ............................................................................................................................................. 14
ARM XL & loadmap ............................................................................................................................................................. 14
5. Definitions ..............................................................................................................................................15
6. Where to Monitor ..................................................................................................................................16
Switchgear / Switchboards ................................................................................................................................................. 16
MCC .................................................................................................................................................................................... 17
Transformers ...................................................................................................................................................................... 17
7. Install Guide – Infrared Sensors ..............................................................................................................18
General Advice.................................................................................................................................................................... 18
Mounting Distances ............................................................................................................................................................ 19
Target Zone – Sensor Orientation....................................................................................................................................... 20
Optimum Viewing Angle ..................................................................................................................................................... 21
Target Zone – Surface Finishes ........................................................................................................................................... 22
Acceptable Surfaces… ......................................................................................................................................................... 22
Unacceptable Surfaces…..................................................................................................................................................... 23
Target Zone - Dimensions ................................................................................................................................................... 24
IR Sensor Mounting options ............................................................................................................................................... 25
IR Sensor - Cable Length ..................................................................................................................................................... 28
8. Brackets .................................................................................................................................................29
Exertherm IR Sensor Support Brackets ............................................................................................................................... 29
9. Install Guide - EM Cable Sensors .............................................................................................................30
EM Cable Sensor Placement ............................................................................................................................................... 31
EM Cable Sensor Temperature Drop .................................................................................................................................. 32
EM cable sensor placement – multiple cables .................................................................................................................... 33
6 cables per phase - use 2 EM Cable Sensors ..................................................................................................................... 33
7 cables per phase – use 3 EM cable sensors ..................................................................................................................... 33
9 cables per phase – use 3 EM cables sensors .................................................................................................................... 34
12 cables per phase – use 4 EM cable sensors ................................................................................................................... 34
14 cables per phase – use 6 EM cable sensors ................................................................................................................... 35
EM Cable Sensor - Cable Length ......................................................................................................................................... 36
EM Cable Insulation Rating ................................................................................................................................................. 36
10. Install Guide – Contact/Ambient Sensors ................................................................................................37
Contact/Ambient Sensor Placement .................................................................................................................................. 37
Contact/Ambient Sensor – Cable Length ............................................................................................................................ 38
11. Cable Routing .........................................................................................................................................39
12. Exertherm Modbus Datacard ..................................................................................................................40
Safety and Use of Equipment – Exertherm Modbus Datacard ........................................................................................... 40
General ............................................................................................................................................................................... 82
21. Troubleshooting .....................................................................................................................................83
Datacard Troubleshooting Guide........................................................................................................................................ 83
22. Technical Datasheets ..............................................................................................................................88
Data Sheet – IR Sensor Gain Matrix .................................................................................................................................... 88
Exertherm Install & Configuration Record .......................................................................................................................... 89
TABLE OF FIGURES
FIGURE 1 EXERTHERM SYSTEM OVERVIEW ...................................................................................................................................................... 11
FIGURE 2 EXERTHERM INTEGRATION OPTIONS ................................................................................................................................................. 12
FIGURE 3 EXERTHERM IR SENSOR.................................................................................................................................................................. 13
FIGURE 4 EXERTHERM EM CABLE SENSOR ...................................................................................................................................................... 13
FIGURE 5 EXERTHERM CONTACT/AMBIENT SENSOR .......................................................................................................................................... 13
FIGURE 6 EXERTHERM MODBUS DATACARD .................................................................................................................................................... 14
FIGURE 7 EXERTHERM ARM XL .................................................................................................................................................................... 14
FIGURE 8 WHERE TO MONITOR .................................................................................................................................................................... 16
FIGURE 9 IR SENSOR - DESIGN ADVICE (SIDE VIEW).......................................................................................................................................... 18
FIGURE 10 BUSBAR / CABLE CONNECTION ...................................................................................................................................................... 19
FIGURE 11 POSSIBLE SENSOR LOCATIONS ....................................................................................................................................................... 20
FIGURE 12 VIEWING ANGLE – ELEVATION (SIDE VIEW) ...................................................................................................................................... 21
FIGURE 13 VIEWING ANGLE –PLAN (BIRDS EYE VIEW) ....................................................................................................................................... 21
FIGURE 14 ACCEPTABLE SURFACES ................................................................................................................................................................ 22
FIGURE 15 UNACCEPTABLE SURFACES ............................................................................................................................................................ 23
FIGURE 16 PAINTED TARGET ZONE ................................................................................................................................................................ 24
FIGURE 17 SENSORS MOUNTED OUTSIDE BARS VIEWING INWARD ........................................................................................................................ 25
FIGURE 18 SENSORS MOUNTED IN-BETWEEN BARS ........................................................................................................................................... 25
FIGURE 19 SENSORS MOUNTED AT AN ANGLE (UP TO 45°) ................................................................................................................................. 26
FIGURE 20 SENSORS MOUNTED ABOVE, POINTING DOWN ONTO THE TOP OF BARS .................................................................................................. 26
FIGURE 21 SENSORS MOUNTED VIEWING THE VERTICAL DROPS ........................................................................................................................... 27
FIGURE 22 SENSORS MOUNTED OUTSIDE TWIN BARS VIEWING INWARD ................................................................................................................ 27
FIGURE 23 SENSORS MOUNTED IN-BETWEEN TRIPLE BARS .................................................................................................................................. 27
FIGURE 24 IR SENSOR CABLE EXTENSION........................................................................................................................................................ 28
FIGURE 25 EM CABLE SENSOR INSTALLATION.................................................................................................................................................. 31
FIGURE 26 CABLE SENSOR TEMPERATURE DROP ............................................................................................................................................... 32
FIGURE 27 6 CABLES PER PHASE - USE 2 EM CABLE SENSORS .............................................................................................................................. 33
FIGURE 28 7 CABLES PER PHASE – USE 3 EM CABLE SENSORS ............................................................................................................................. 33
FIGURE 29 9 CABLES PER PHASE - USE 3 EM CABLE SENSORS ............................................................................................................................. 34
FIGURE 30 12 CABLES PER PHASE - USE 4 EM CABLE SENSORS ............................................................................................................................ 34
FIGURE 31 14 CABLES PER PHASE - USE 6 EM CABLE SENSORS ............................................................................................................................ 35
FIGURE 32 EM CABLE SENSOR - CABLE EXTENSION .......................................................................................................................................... 36
FIGURE 33 CONTACT/AMBIENT SENSOR - CABLE EXTENSION .............................................................................................................................. 38
FIGURE 34 EXERTHERM DATACARD OVERVIEW ................................................................................................................................................ 41
FIGURE 35 MOUNTING A DATACARD ............................................................................................................................................................. 41
FIGURE 36 REMOVING A DATACARD .............................................................................................................................................................. 42
FIGURE 37 IR SENSOR TERMINATIONS – CONNECTION TO DATACARD .................................................................................................................. 45
FIGURE 38 EM CABLE SENSOR TERMINATIONS – CONNECTION TO DATACARD....................................................................................................... 46
FIGURE 39 CONTACT/AMBIENT SENSOR TERMINATIONS – CONNECTION TO DATACARD .......................................................................................... 47
FIGURE 40 POWER SUPPLY TERMINATIONS – CONNECTION TO DATACARD............................................................................................................ 48
FIGURE 41 LINKING DATACARDS ................................................................................................................................................................... 49
FIGURE 42 DATACARD PATCH CABLE PIN OUT .................................................................................................................................................. 49
FIGURE 43 CONFIG TOOL - MAIN SCREEN ....................................................................................................................................................... 54
TABLES
TABLE 1 DEFINITIONS .................................................................................................................................................................................. 15
TABLE 2 PATCH CABLES ............................................................................................................................................................................... 50
TABLE 3 SUGGESTED ALARM LEVELS .............................................................................................................................................................. 67
TABLE 4 IR SENSOR VERIFICATION VALUES ...................................................................................................................................................... 72
NOTICES:
The information, products and specifications, configurations, and other technical information
regarding the products and data contained in this document are subject to change without notice.
All the statements, technical information, and recommendations contained in this document are
believed to be accurate and reliable but are presented without warranty of any kind, and users must
take full responsibility for the application of any products or data specified in this document.
IN NO EVENT SHALL EXERTHERM, OR ITS SUPPLIERS BE LIABLE FOR ANY INDIRECT, SPECIAL,
CONSEQUENTIAL, OR INCIDENTAL DAMAGES, INCLUDING, WITHOUT LIMITATION, LOST PROFITS OR
LOSS OR DAMAGE TO EQUIPMENT OR DATA OF ANY KIND WHATSOEVER ARISING OUT OF THE USE
OR INABILITY TO USE THIS DOCUMENT, EVEN IF EXERTHERM HAS BEEN ADVISED OF THE
POSSIBILITY OF SUCH DAMAGES.
THIS LIMITATION OF LIABILITY WILL PREVAIL OVER ANY OTHER TERMS & CONDITIONS RELATING TO
THE SUPPLY OF EXERTHERM PRODUCTS / SERVICES.
WARRANTY
Exertherm IR Sensor, EM Cable Sensor, Contact / Ambient Sensor, Modbus Datacard & ARM XL
Return/Warranty Policy
Exertherm offers a lifetime warranty on IR Sensors, EM Cable Sensors and Contact / Ambient
Sensors from date of sale. We warrant that these products will be free of defects in material and
workmanship and will repair or replace the returned product at no charge during that period. The
warranties are void if the product is misused, mishandled or installed incorrectly (not in accordance
with the methods and procedures specified in this document); keeping the products within specified
temperatures.
Exertherm offers a 2 year warranty on all other Exertherm product from date of sale. We warrant
that these products will be free of defects in material and workmanship and will repair or replace
the returned product at no charge during that 2 year period. The warranty is void if the product is
misused, mishandled or installed incorrectly.
The warranty is conditional upon the above caveats and strictly limited to the replacement cost of
the Sensors / Datacard / ARM XL. Labour costs associated with removal of Sensors / Datacards /
ARM XL and/or re-installation are excluded, as is any consequential loss resulting from the Sensor /
Datacard / ARM XL failure.
Exertherm reserves the right to examine and test any returned products to determine the cause of
failure. No returned products will be accepted prior to issue of a Return Material Authorization
(RMA) number by Exertherm.
Please contact Exertherm if you have any questions – support@Exertherm.com, current telephone
numbers can be found at www.Exertherm.com .
LIVE WORKING
DO NOT PERFORM ANY ACTIVITY ON A PIECE OF LIVE SWITCHGEAR. FAILURE TO COMPLY WITH
THESE AND OTHER NATIONAL, REGIONAL OR LOCAL HEALTH AND SAFETY
REGULATIONS/GUIDELINES COULD RESULT IN PERMANENT INJURY OR DEATH.
Prior to undertaking any work the operator MUST ensure that all busbars, connections and sources
of energy are totally isolated and checked prior to any works taking place this should be completed
by a competent trained electrical engineer.
All energy sources onto the panel must be isolated, removed and locked out to prevent the panel
being re-energised while any works are taking place. If the panel being tested is part of an existing
installation then all connections should be bonded to earth potential as an extra precaution and
also to stop any possible back feed from other devices.
4. EXERTHERM® SYSTEM
Max 32 Datacards
Modbus TCP/IP
RELAY CONTACTS
CORE COMPONENTS
EXERTHERM NON-CONTACT INFRARED (IR) SENSOR
Sensor housing is a rugged, resin (UL 94 V-O) moulded head incorporating cable stress relief, to
enable fast, easy installation whilst protecting the delicate temperature sensing element.
5. DEFINITIONS
Word Definition
Edgewise means the side dimension (thickness) of the
busbar, positioned with edges facing each other
Flatwise means the width dimension of the busbar,
positioned facing each other
Infrared radiation emitted particularly by heated objects
having a wavelength just greater than that of
the red end of the visible light spectrum, but less
than that of microwaves. The infrared spectrum
that the IR Sensor detects is in the wavelength
5.5 to 20 µm
Node a node is a single 8 channel Exertherm Datacard
device. Nodes can be interconnected to form a
network of cards, each having a unique Node
address
Target / target zone the area of busbar/cable that the Exertherm IR
Sensor is measuring
Joint the point at which the two busbars or cable and
busbar are connected together
Local Ambient the ambient temperature of the air surrounding
the Sensor head and target
LAN Local area network, an IT network which
connects computers and IT equipment within a
limited area such as a school, laboratory or
office building
WAN Wide area network, an IT network that covers a
broad area. One that links across metropolitan,
regional, national or international boundaries
SELV Safe extra low voltage, a circuit whose voltage is
less than 42.4v ac peak or 60v dc max for no
longer than 200ms during normal operation
MCC A motor control centre is an assembly of one or
more enclosed sections having a common
power bus and principally containing motor
control units. Motor control centres are in
modern practice a factory assembly of several
motor starters
LED Light emitting diode, a semiconductor diode
which glows when a voltage is applied
Table 1 Definitions
6. WHERE TO MONITOR
Exertherm can monitor ‘mission critical’ joints, connections and terminations within an electrical
infrastructure.
The typical installations will focus on those areas in which a thermal issue could lead to either
a) downtime or b) a major risk to the safety of people and equipment and c) locations that
historically would have been subject to routine thermal imaging.
SWITCHGEAR / SWITCHBOARDS
The joints monitored in LV and MV switchgear and switchboards would normally include:
The IR Sensors can be used to monitor joints associated with all types of air insulated breakers (AIS)
used within typical switchgear.
2 1
3 3 3
MCC
NOTE: For thermally monitoring the line/load connections to the individual drawers/buckets
please use the Exertherm MCC Solution (Manual PN# 820201)
TRANSFORMERS
NOTE: For more information please see www.Exertherm.com or contact us via email
support@Exertherm.com
❸
❶
Figure 10 ❺ shows an ideal location for the IR Sensor to monitor both the busbar to busbar joint,
plus all of the cable connections.
To prevent the local ambient of the Sensor being affected, the Sensors should be
placed in ‘free air’ and not in an area of high temperature airflow. As an example they should not
be placed in the hot airflow found directly above a transformer.
MOUNTING DISTANCES
The IR Sensor used for the continuous thermal monitoring of electrical components is calibrated to
optimise accuracy across a wide range of installation conditions.
A single calibration Sensor is used for a wide range of busbar sizes / mounting distances to target
from sensor face.
The IR Sensor requires a simple gain adjustment which is made in the Datacard Configuration Tool.
The correct gain adjustment can be found by using the IR Sensor Gain Matrix.
To use the matrix, simply cross reference the two measurements to arrive at the correct Sensor gain
adjustment (shown in 22.1).
The Exertherm IR Sensors are flexible on the mounting orientation provided that the Sensors are
never aimed upwards.
In Figure 11 we see the acceptable locations for monitoring a joint ‘A’:
① these are the optimum locations as they are the closest to the joint they will produce the best
possible results.
② are all acceptable and will deliver good results.
❸ these are not acceptable because it will be necessary for the Sensor to be pointing upwards.
The locations beyond ❹ are too far away from the joint to provide high accuracy monitoring, this
distance is anything beyond 300mm (12 inch).
❺ Avoid the area on a bend where the busbar may have been distorted and any protective
insulation might not be securely fixed to the busbar. We recommend the target area should be the
nearest flat surface as shown ① and ② below.
The optimum viewing angle of the IR Sensors is perpendicular to the centre of the busbar (❻ in
Figure 12 & Figure 13).
But it is acceptable to view at up to 45° from the perpendicular targeted at the centre of the busbar,
as shown in ❼ in Figure 12 & Figure 13 subject to always being aimed at the middle of the busbar.
❻ 45°
45° 45°
❼ ❼
Never point the IR Sensor at an upward angle from the horizontal perpendicular.
In order to ensure that the IR Sensor accurately measures the temperature of the surface of the
target busbar the surface of the bare metal busbar must be treated to increase its emissivity to
greater than 0.95 and therefore reduce the impact of any reflected IR.
① paint the surface using a high temperature, stove or BBQ matt black paint;
② tight fitting thermoplastic heat-shrink (Raychem type) regardless of the colour or
③ an ‘epoxy dipped’ busbar.
UNACCEPTABLE SURFACES…
The surfaces of the busbar that will not produce acceptable results are:
① bare, unfinished busbar as this has insufficient emissivity;
② loose fitting insulation sleeving;
③ protective ‘boot’ over the joint.
② & ③ are unacceptable because there is an air gap between the busbar and the insulation
material.
As air is a very good thermal insulator this will mean that the surface temperature of the busbar
and the surface of the sleeving will not be the same and so Exertherm will produce inaccurate and
potentially variable results.
② ②
The flexibility of the IR Sensors is such that there are many different options to monitor the busbar
near to a joint.
The following examples show some of the options for monitoring different busbar configurations;
the arrow represents the viewing direction of the IR Sensor.
L1 L2
L3 L4
L1 L2
L3 L4
L1 L2 L3
L1 L2 L3 L4
Figure 20 Sensors mounted above, pointing down onto the top of bars
L1 L2 L3 L4
L1 L1 L3 L3
L2 L2 L4 L4
L1 L1 L1 L2 L2 L2
L3 L3 L3 L4 L4 L4
Cables can be extended but the specification of the extension cable must match the original
cable Belden 9451.
Cable lengths exceeding 12 meters (40ft) are not recommended.
During installation cables MUST be cut to length and suitably dressed back to the Datacard
without unnecessary looping of excess cable.
See Section 12.7.1 for how the IR Sensor cable needs to be prepared for connection to the
Datacard.
8. BRACKETS
EXERTHERM IR SENSOR SUPPORT BRACKETS
The IR Sensor support brackets are an extremely flexible solution manufactured out of Glastic or of
Acetyl Copolymer, trade name Delrin, plastic, and use non-metallic fittings to suit high voltage
environments. The brackets are non-deforming up to a temperature of 110°C (230°F).
Using this linkable design the brackets offer a huge degree of flexibility to suit the vast majority of
applications.
These brackets should under no circumstances be affixed directly to the busbar on either LV or
MV applications.
The EM Cable Sensor cannot be used on multi-core cables, i.e. cables in which more than one
current carrying phase is present.
5cm
❶ ❶
❷
❷
≥5cm
Cables can be extended but the specification of the extension cable must match the original
cable, UL style 2464. Cable lengths exceeding 12 meters (40ft) are not recommended.
During installation cables MUST be cut to length and suitably dressed back to the Datacard
without unnecessary looping of excess cable.
See Section 12.7.2 for how the EM Cable sensor cable needs to be prepared for connection to the
Datacard.
• The Contact/Ambient Sensor can also be used to measure ambient air temperature by
placing the sensor head in free air e.g. not attached to a surface.
• Place the base of the Contact/Ambient sensor with the flat surface in contact with the piece
of equipment, then secure with a cable tie (or suitable adhesive for the application).
• The Contact/Ambient Sensor yellow cable should be routed away from the back of the
Sensor; and secured in compliance with National & Local regulations & guidance for data
cable routing/installation.
Cables can be extended but the specification of the extension cable must match the original
cable, Compensation cable UL13 Type PLTC.
Cable lengths exceeding 12 meters (40ft) are not recommended.
During installation cables MUST be cut to length and suitably dressed back to the Datacard
without unnecessary looping of excess cable.
See Section 12.7.3 for how the Contact/Ambient Sensor needs to be prepared for connection to
the Datacard.
If Sensor cables are to be routed through switchgear, they must be kept away from all busbars and
in accordance with good electrical practice and regulations for installation of communication
cables within electrical panels.
The routing of the Sensor cables should start at the Sensor head and then run back to the
Datacard where it should be cut to the required length, dressed, and connected.
The Sensor or the Sensor cable should never be attached to a busbar, even as a temporary
measure.
Sensor & Communication cables should never be installed in containment containing any power
cables, they should be run in compartments designed for signal and communication cables. They
should never be installed parallel with any high voltage or power cables / busbars. If they must
cross any power cables / busbars, then this should be at right angles and with a suitable clearance
to comply with all appropriate standards.
The Sensors themselves are not affected by EMF found within switchgear operating at 50 or 60Hz.
Both the IR Sensors, EM Cable Sensors and Contact/Ambient Sensors have been tested for EMC /
EMF compliance to immunity when connected with the Exertherm Datacard to EN 55024 (1998) +
A1 (2001) + A2 (2003) standards.
MODBUS DATACARD
Each Datacard has been pre-addressed in the factory
as Modbus address 247.
They contain no settings other than each input
channel is set at:
• type “No Selection”
• address at 247
• data rate at 9600Kb
• 8 data bits, 1 stop bit, No Parity.
To commission the Datacards a software suite called
“Exertherm Datacard Configuration Tool” must be
used.
This described in detail in Section 14.
The Datacard has a moulded clip which allow for mounting on DIN rails (Top hat rail EN 50022) &
can be positioned vertically or horizontally.
TO MOUNT
TO REMOVE
Disconnect/switch off the Power Supply.
RESET SWITCH
FACTORY RESET
The reset switch is on the top of the Datacard on the right-hand side. For factory reset of
communication settings:
• Press & hold the reset switch until ALL LEDs on the front of the Datacard flash TWICE
• Then release the reset switch
• If the LED’s do not flash twice then you will need to try again.
• The device will then reset all its communication parameters to factory default settings, the
programmed Sensor configuration remains unaffected
• If no errors are detected the yellow status LED will pulse, (rather than be lit continuously).
This factory default reset sets the address to 247, baudrate to 9600, No parity, 8 bits and 1 stop bit.
So 247,9600,N,8,1
Now use the Exertherm Datacard Configuration Tool to complete the configuration of the reset
Datacard.
DIAGNOSIS LEDS
Three LEDs on the front of the Datacard provide the user with device status and bus activity
information:
The Datacard is intended for thermocouple style input signal levels and therefore only signal
levels with a maximum voltage between Ain+ and Ain- of 5VDC can be used.
Signal levels above these could cause irreversible damage to the unit and possibly, personnel or
other equipment located nearby
Brown+
White-
EM Cable Sensor
IR SensorSsnreo
Yellow+
Red-
Contact/Ambient
Sensor
LINKING DATACARDS
Depending on the limitations of the front-end software being used as the graphical user interface,
up to 32 Datacards can be linked together to form a Modbus daisy-chain.
NOTE: If connecting the Datacards to the Exertherm ARM XL (Max 10 Datacards) please refer to
the ARM XL Manual (PN# 820208)
The Datacards are not Ethernet compatible and the RJ45 connection should not be used to
directly connect to a PC/LAN port.
In order to connect the Datacards together in a ‘daisy-chain’ use a standard Cat5 (or better) patch
cable between the X0/X1 sockets on one Datacard to the X0/X1 sockets on the next. There is no
difference or priority for which socket should be used.
The last Datacard in the daisy chain should connect from the X0/X1 RJ45 socket to any local front-
end hardware or if necessary, a terminal block so that a Belden 9841 cable can be used to connect
to the front-end equipment.
There are several different pre-manufactured cables which are used for communications between
the Datacards. All of these cables have pre-formed and moulded RJ45 connecting plugs on either
end.
Description
Patch Cable – 0.3m / 1 ft, RJ45 Connectors
Patch Cable – 0.9m / 3 ft, RJ45 Connectors
Patch Cable – 3m / 10 ft, RJ45 Connectors
Patch Cable – 5m / 15 ft, RJ45 Connectors
Patch Cable – 10m / 25 ft, RJ45 Connectors
Table 2 Patch Cables
If you need to connect Datacards from different switchboards together we recommend that
depending on the overall length of the Modbus chain then either using a patch cable or the end
Datacards in the two pieces of equipment are both brought to a terminal block and the inter-
equipment link is completed with a Belden 9841 cable.
❺ Click “Continue”.
All parameters must match exactly with the settings in the Datacard in order to communicate
successfully.
Factory default settings are Datacard address 247, baud rate 9600 (9k6) and No parity.
Please note: The Datacard is capable of operating at various baud rates: 4800 (4k8), 9600 (9k6) and
19200 (19k2).
The following error message as shown in Figure 45 may appear for the following reasons:
2. The protocol converter is damaged between the laptop and the Datacard
• When the search has successfully finished, online Datacard address will then show in green
as highlighted in Figure 46
• The Device Address in the system parameters portion of the screen will be pre-set with the
found Datacard address.
SYSTEM PARAMETERS:
The Device Address in the system parameters portion of the screen will be pre-set with the found
Datacard address.
To view the parameters of the connected Datacard, click the read button.
The System parameters section allows you to change the communication settings in the Datacard.
After changing any settings:
• Press the “Program” button
• then “Reset” button
• and then Press the “Read” button in order to check for proper programming.
The changes will take effect after resetting or re-powering up the Datacard.
• Device Address With the device address selector you can select either the device to
communicate with or the new address to program into the current connected Datacard
• Baudrate here you can select the required baudrate to program into the Datacard
• Temp unit Option to change the temperature unit of the presented measurements in °C or
°F
• Parity here you can select the required Parity to program into the Datacard
• Serial # and Firmware version shows the current serial number and firmware version
CHANNEL CONFIGURATION
From the dropdown, select the correct sensor type for each channel of the Datacard, this must be
carried out to allow the Datacard to display the correct temperature data.
The following Sensor types are available:
• No Selection: Channel Inactive;
• IR.EM-06.SC-DeltaT: for IR EM-06.SC Sensor
• IR-01 Absolute: for IR 01 Absolute Sensor
• Cable EM-DeltaT: for EM Cable Sensor
• Cable Absolute: for Contact/Ambient Sensor
The only Sensor that utilises the gain factor is the IR.EM-06.SC-DeltaT Sensor.
When selecting the IR.EM-06.SC-DeltaT the gain adjustment window will appear to the right.
The initial value here when selecting IR.EM-06.SC-DeltaT is 1.00.
You MUST amend the relevant ‘gain factor’. It is imperative that the correct value is entered
otherwise values will be inaccurate.
This gain factor is taken from the Exertherm Install & Configuration Record for that Datacard,
which should be provided by the install team.
For your reference a copy is provided in Section 22.1 and 22.2
PROGRAM DATACARD
Now that all Datacard parameters are complete, they must be programmed into the Datacard.
Ensure the Datacard address in the upper left corner of the screen is correct address you wish to
program.
1. Then press the “Program” button to program the parameters from the PC into the
Datacard.
2. A confirmation message will appear, press OK.
3. Progress bar will move until programming is complete. The TX RX and ACK LEDs will flash
while programming.
11. Now that valid channel types have been programmed, the green status LED will be lit
against the channel name.
If a number of the Datacards are being commissioned on a network then ONLY ONE at a time
can be addressed and setup.
Therefore, all units further down the line either need their power removing or network cables
unplugged.
Once each Datacard is commissioned its network cable can be reconnected and new settings
can be programmed into the next Datacard with address 247.
MONITOR MODE
With the monitor function you can test the configuration of the connected Sensors.
1. Press the “Run” button to start the reading of the Sensors
The Sensors will be read every 2 seconds; no other operations can be performed whilst the
monitor is in Run mode.
3. When you are sure that all sensors are functioning correctly, click “Stop” to finish.
Stop MUST be pressed before any other programming functions can take place.
4. This concludes the configuration process and should now be repeated for all Datacards on
the system.
EXERTHERM
15. ALARMS:
The Exertherm Datacards do not provide Alarms, these must be configured in front end systems,
or in the ARM XL HMI if it is included (see separate ARM XL product manual PN# 820208).
Please see Section 9.2 (Cable Sensor Temperature Drop) for further reduction of alarm limits for
multiple cables monitored by a single EM Cable Sensor.
NODE RANGE
The Datacard accepts a node address range of 1…247 which can be programmed by the
configuration software provided.
Field values of channel 1 through 8 are contained in 16bit registers. The register values require a
0.1 multiplier to be used when reading via a SCADA system to provide a true temperature reading.
The temperature value can range from -50°C to +300°C depending on the used Sensor. A negative
temp value will be indicated by setting the most significant bit of the 16bit register to 1.
The measurements are updated constantly and can be retrieved using the function codes 03 or 04,
(read input or holding register, both will deliver the same output).
In Modbus terms referred to as 30001….30008 and 40001….40008.
Example: measured ΔT = +2.5°C
1) therefore register content = 25,
2) calculation 25 x 0.1 = ΔT 2.5°C
SIGNED INTEGER
If possible all values in the Register should be read as a ‘signed integer’. Then if the value is read as
a signed integer the signing is carried out automatically by the system reading the registers.
It has two machined collars that fit onto the IR Sensors so that each test is carried out to the same
tolerances and conditions.
The device operates from a ‘plug top’ 9 volt dc power supply rather than battery to ensure a steady
temperature reference is obtained.
This testing requires placing the verification heat source onto the end of the IR Sensors.
The user MUST ensure that all bus bars, connections and sources of energy are totally isolated
and locked out to prevent re-energisation prior to any works taking place
If the panel being tested is part of an existing installation, then all connections should
be bonded to earth potential as an extra precaution and also to stop any back feed
from other devices.
At no stage during the testing should the IR Sensor be physically held, or any part of your body
be touching the Sensor, this will cause inaccuracies in the test readings due to elevating the
ambient conditions on the sensor.
Before testing takes place, ensure the Exertherm Verification Device (EVD) has been left in the
same ambient conditions as the IR Sensors for at least 30mins to ensure the ambient block
equalises to local conditions.
Follow the stages detailed below to carry out this test procedure: -
1) Plug the power supplies jack style plug into the socket on the end of the verification device.
Figure 53 Power Socket.
2) Plug the power supply into a local 110 / 220 VAC power source. Ensure this is on an extension
lead which can be freely and safely moved around.
3) This verification device has no ‘on/off’ switch so once power is applied the LED will illuminate
‘Red’ to show the device is active. Figure 54 EVD LEDs.
4) The device is ready to operate once the ‘Red’ LED has changed to ‘Green’. This indicates the
heated target has reached 10°C above the ambient target (ΔT10°C). Figure 54 EVD LEDs
5) Place the verification device in front of the IR Sensor to be tested with the IR Sensor fitted
into the white housing in the ‘Ambient’ side all the way to the stop. Figure 55 Ambient
Reading.
6) Hold the verification device in this position without physically handling the IR Sensor for
about three seconds.
7) Note this reading, as displayed in the ‘Monitor mode’ section of the software described in
Section 0
8) Then place the IR Sensor to be tested with the Sensor fitted into the white housing in the
‘Heated’ side all the way to the stop. Figure 56 Heated Reading. Do NOT hold the Sensor in
the heated side for more than 5 seconds.
9) Note this reading, as displayed in the ‘Monitor mode’ section of the software. The difference
between the two readings is now the ΔT (delta T) value and should be in the range of 6°C to
12°C. (This is a wide variance as the Datacard has had its ‘gain’ adjustment added to allow
for a wide range of busbar sizes and mounting distances and this test is carried out at a fixed
distance)
10) Table 4 IR Sensor Verification Values below, identifies the expected values. This is based
on ideal conditions and may differ slightly.
11) This now proves the IR Sensor is reading a correct value as a ΔT (delta T) and is a more
accurate and quicker method than using a heated target and having to either guess or read
an ambient locally with a separate instrument.
Steps 5 to 9 can be repeated a couple of times to double check and prove the Sensors are operating
correctly. Repeat this test for all IR Sensors which are to be verified and note all the readings.
Power socket
Figure 53 Power Socket
PLEASE NOTE THAT THESE READINGS ARE ΔT, (RISE OVER AMBIENT) AND NOT ABSOLUTE.
THEREFORE 0°C ΔT = 0°F ΔT NOT 32°F P ΔT F
F
o i
i
w g
• The Exertherm Verification Device (EVD) MUST be left to acclimatise g
e 4 in the same conditions as
the IR Sensors for at least 30 mins prior to any testing takingr place. 4
. If the device is moved
between extremes of temperature even as low as a difference .
s of52° to 3°C it will have an effect
o
on the reading and must be allowed to reach its calibrated Delta Temperature. This will be 3
shown by the coloured LED changing state from Green to Red. c
• The verification device has a steady state temperature of Deltak Temperature of 10°C (18°F)
over the local ambient target. e
• It is imperative that the Sensor is both not touched during thet testing by hand or the test unit
is held in position on the Sensor for more than 5 seconds. If this happens it will cause an
internal heating of the Sensor and inaccuracies in the results.
• If the Sensors read within ± 3°C (5.4°F) of 9°C (16.2°F) then they have successfully passed
operational verification.
If when tested using the verification device the IR Sensors read within the following ranges then they
have successfully passed operational verification.
Once all Datacards have been commissioned and communication established, the EM Cable sensors
can be verified for correct operation. This can be carried out either by utilising the “Monitor mode”
of the Datacard configuration tool or by utilising the clients own SCADA/BMS system, if connected
and commissioned.
Instructions for the use of the configuration tools’ “Monitor Mode” are described in Section 0 of
this manual.
For the EM cable sensors, a stable heat source is not available as they are in direct contact with the
cable insulation and or local ambient surface i.e. a panel section. Direct heating using heat gun or
similar source is not recommended as this will cause damage to the sensor and or surface they are
attached to. Therefore, the most reliable heat source is the human hand.
This testing requires physically holding or placing your hand on or around the sensors.
The user MUST ensure that all bus bars, connections, and sources of energy are totally isolated
and locked out to prevent re-energisation prior to any works taking place.
If the panel being tested is part of an existing installation, then all connections should
be bonded to earth potential as an extra precaution and also to stop any back feed
from other devices.
At no stage during the testing should the EM Cable sensor head and the ambient grey tube be
held at the same time, this will cause inaccuracies in the test readings due to elevating the
ambient conditions on the sensor.
Follow the stages detailed below to carry out this test procedure: -
1) Utilising either the Exertherm Configuration tool or the local SCADA system, note the reading
of the sensors under test.
2) For the EM Cable Sensor, place your hand around or over the sensor head. Try to make as
good a contact as possible.
4) The sensor will take 10 seconds or so to react, note the reading on the configuration tool or
SCADA for this sensor.
5) Body temperature is around the region of 37°C (98.6°F) so should cause a rise in sensor
reading.
6) The sensor should rise positive, if so then the sensor is terminated correctly. If the sensor
reading was to fall negative, then this shows an incorrect and reversed termination at the
Datacard and will need correcting.
7) Note that under normal conditions, as the sensor reads Delta T i.e. the difference between
the sensor head and the ambient tube, the output would be around the 0°C mark ±2°C so
incorrect termination would not be seen. Only when the sensor head is heated will a rise be
seen if the sensor has been terminated correctly as per section 12.7.2 of this manual.
8) All this data must be recorded on the Exertherm Install & Configuration Record sheet which
is supplied in section 22.2 of this manual.
9) For testing the Contact Ambient sensor please follow the same steps 1 through 6. This
sensor is an absolute temperature reading and therefore shows actual temperature within
the enclosure and not a Delta T reading.
10) Again, the data from the Contact Ambient sensor should be recorded on the Exertherm
Install & Configuration Record sheet which is supplied in section 22.2 of this manual.
11) This now proves the EM Cable sensor is reading a correct value as a ΔT (Delta T) and also
that the Contact Ambient sensor is reading a correct value as an Absolute.
PLEASE NOTE THAT THE EM CABLE SENSORS READINGS ARE ΔT, (RISE OVER AMBIENT) AND NOT
ABSOLUTE. THEREFORE 0°C ΔT = 0°F ΔTPNOT F32°F ΔT
F
o i
i
w g
g
e 4
4
r .
s
.
5
o 3
c
k
e
t
The method detailed here must be adhered to otherwise damage to either Sensors or Datacards
and processor devices will result. This will invalidate the warranty on those particular items and
replacement costs will be the responsibility of the OEM or company carrying out the testing.
DESIGN CHECKLIST
All Sensor distance from busbar locations MUST adhere to all UL, IEC and ANSI standards for
clearance from busbars and cables depending on circuit voltages.
All Sensors cables and containment routes MUST adhere to all UL, IEC and ANSI standards for
clearance from busbars and cables depending on circuit voltages.
If Sensor cables are to be routed through switchgear they MUST be kept away from all busbars
and in accordance with good electrical practice and regulations for installation of
communication cables within electrical panels.
These cables should be never be installed in containment containing any power cables; they
should be run in compartments designed for signal and communication cables.
They should never be installed parallel with any high voltage or power cables /
busbars. If they must cross any busbars then this should be at right angles and with a
suitable clearance to comply with UL, IEC and ANSI clearance standards.
Sensor and all other communication cables must not be run within 150mm (6”) of 13kV circuits.
If circuit voltage exceeds this then clearance must be greater and comply with the previous
standard i.e. UL, IEC and ANSI
Where high electromagnetic fields could be or are present, all Sensor and communication
cables passing through switchgear will be installed as per the previous comment above, i.e.
must be kept a minimum of 150mm (6”) distance from 13kV.
If circuit voltage exceeds this then clearance must be greater and comply with the previous
standard i.e. UL, IEC and ANSI. The Sensors themselves are not affected by EMF found within
switchgear operating at 50 or 60Hz.
DATACARD CONNECTIONS
This device is intended for thermocouple style input signal levels and therefore only signal levels
with a maximum voltage with respect to shield or between Ain+ and Ain- of 5VDC can be used.
Signal levels above these could cause irreversible damage to the unit and possibly, personnel or
other equipment located nearby
Under no circumstance must a ‘Megger or Hipot’ test be carried out on the Datacard.
This device must NOT be powered from a supply whose voltage exceeds 24VDC ±10%.
This includes mains direct 120VAC or 240VAC supply be connected directly to the unit.
This will result in irreversible damage to the unit and possibly, personnel or other equipment
located nearby. The power through any terminal connection should not exceed 5Amps.
Under no circumstance must a ‘Megger or Hipot’ test be carried out on the Power supply or
Datacard.
TESTING PROCEDURE
The following MUST be adhered to in all cases, with no exceptions. Any damage arising from not
adhering to and not following these instructions will invalidate all warranties.
All Sensor cables MUST be routed away from and not in contact with any bar or conductors of
any description.
All Sensors cables MUST NOT have their shield cables connected. Cable ends MUST be
protected by the application of either rubber sleeve or heatshrink sleeve to stop the internal
shield cable being able to contact any metallic surface or other shield or conductor.
All power supply units MUST be totally isolated from any supply by removal of all fuses.
Totally isolate
from any source
All datacards and power supplies MUST have all earth / ground connections removed from
the terminal on both Shield and main power terminations.
Disconnect
GND terminals
All Communication cables MUST be removed from any third party device or meter that is
connected to the datacards
If the final link on communications to either terminals or a third party device utilises a
‘Shield’ or ‘Gnd / Earth’ connection then this MUST be removed from the datacard it is
connected to. Disconnect the patch lead from the datacard.
Any Sensor which is mounted in contravention to all UL, IEC and ANSI standards for
clearance from busbars and cables depending on circuit voltages, MUST be disconnected
from the datacard prior to any testing taking place.
All connections MUST be totally removed from the Exertherm ARM XL. This includes,
power supply, LAN Ethernet cables and Modbus RS485 communication cables.
SCADA / BMS
ARML XL OR
i. …UL uses IEC Standards to investigate both low and medium voltage switchgear. The
following is the requirement for ambient temperature measurement during the
Temperature Test.
ii. …Ambient air temperature limits: Tests may be made at any ambient air temperature
between 10°C and 40°C.
iii. …Measurement of ambient air temperature: Indoor ambient air temperatures shall be
determined by taking the average of the readings of three temperature-measuring
devices, such as thermometers or thermocouples, placed as follows:
a) One level with the top of the structure
b) One 30 cm above the bottom of the structure
c) One midway between the two positions a) and b).
iv. …All temperature-measuring devices shall be placed 30 cm from the structure, not in
front of ventilators, and in locations unaffected by drafts caused by the structure or
appreciable radiation from the equipment. When the ambient air temperature is
subject to variations that might result in errors in measuring the temperature rise, the
temperature-measuring devices should be immersed in a suitable liquid, such as oil in a
suitable container, or reliably attached to a suitable mass of metal.
v. NOTE - A convenient form for such a container consists of a metal cylinder with a hole
drilled partly through it. This is filled with liquid and the temperature-measuring device
is placed therein. The size of the container should be at least 2.5 cm in diameter and 5.0
cm high.
16) The ambient temperature used when calculating the connection Delta temperature will be
the local ambient recorded at the Exertherm Sensor location.
17) All Datacard power supplies will be maintained at 24VDC ±10%.
18) All equipment test apparatus and Sensors to be used during these tests will be left to
acclimatise in the switchgear for a period of a minimum of 1 hour prior to any tests taking
place.
19) This document assumes all Datacards are programmed and commissioned as the relevant
instructions in this Manual.
4) Take a reading of the ambient temperature at the Sensor under test and note this value on
the test check sheet OEM Design Validation Test Record (section Ambient Test Reading)
5) Take a reading from the Datacard software on the Sensor under test and note the value on
the test check sheet OEM Design Validation Test Record (section Sensor Reading Under Test)
6) Take a reading of absolute temperature from the busbar with a suitably calibrated and
certified temperature measurement device and note this reading. This should be an average
reading across the connection point and not just one ‘spot’ temperature and note the value
on the test check sheet OEM Design Validation Test Record (section Absolute Reading At
Sensor)
7) Subtraction of the ambient (at the sensor) from the connection temperature will result in
the Delta T value and note the value on the test check sheet OEM Design Validation Test
Record (section Calculated Delta T Reading). This should agree with the Exertherm IRT/c
sensor reading ±3°C (5.4°F)
8) Note all these readings for future reference.
The results should be compared to the relevant data sheet for the Sensor’s tolerances in terms of
accuracy and repeatability.
21. TROUBLESHOOTING
DATACARD TROUBLESHOOTING GUIDE
When the LEDs are sequentially flashing (R-G-Y-R-G-Y...) the module has detected a failure during
its self-test procedure.
One of 4 errors may exist:
1) Cannot establish Comms – replace any cables or converters with Exertherm product (PN#
800447)
2) Node address out of range, reset to factory stored values (see Factory reset).
3) Under or over voltage of power supply, check power to connections.
4) Module not programmed/initialized, return factory values (see Factory reset).
If after carrying out these troubleshooting steps, the device is still not functioning and the LED’s are
still sequentially flashing (R-G-Y-R-G-Y...). Then the Datacard must be returned for testing and
replacement (under warranty if applicable).
After powering up the module all 3 LEDs will light up shortly indicating the self-test procedure.
It will also allow the user to check the proper operation of the LEDs.
After this start-up sequence the yellow LED should pulse indicating proper operation mode.
Project Name:
Customer:
Section Ref:
Modbus Address: Serial No.:
DATACARD CHANNELS
C C C C C C C C
H H H H H H H H
A A A A A A A A
N N N N N N N N
N N N N N N N N
E E E E E E E E
L L L L L L L L
1 2 3 4 5 6 7 8
Section Reference
Phase Reference
Sensor Type
No Sensor
IR.EM-06.SC – Delta T
IR-01 Absolute
Cable EM – Delta T
Cable – Absolute
IR.EM-06.SC Only
Busbar Size
Mounting Distance
Gain Factor Used
Initial Value
Heat Tested Reading