You are on page 1of 1

Area Residential Area Commercial Area Residential Area Commercial

‫سكني جهد قديم‬ ‫تجاري جهد قديم‬ ‫سكني جهد جديد‬ ‫تجاري جهد جديد‬ C.B. Size
220 Volt 220 Volt 400/230 Volt 230/400 Volt
N Cable Size
K.V.A K.V.A K.V.A K.V.A
From To Fro From To Fro From To Fro From To Ampere
To To To From To
m m m
1 25 125 3 16 25 75 5 13 20
4 x 25mm2
2 25 100 3 13 25 75 5 13 126 175 17 22 76 125 14 22 30
3 101 125 14 16 176 250 23 32 126 175 23 30 40
4 126 200 17 26 76 125 14 22 251 325 33 40 176 225 31 38 50
5 201 300 27 37 126 200 23 34 326 475 41 56 226 325 39 56 70
4 x 50mm2
6 301 375 38 45 201 250 35 43 476 725 57 82 326 475 57 82 100
7 376 475 46 56 726 900 83 101 476 600 83 102 125
8 476 600 57 69 251 375 44 64 901 1125 102 125 601 725 103 124 150
9 601 800 70 90 376 500 65 86 1126 1500 126 166 726 1000 125 166 200 4 x 120mm2
10 801 1000 91 112 501 625 87 107 1501 1900 167 208 1001 1125 167 192 250
4 x 185mm2
11 1001 1200 113 133 626 750 108 128 1901 2300 209 250 1126 1400 193 239 300
12 1201 1500 134 166 751 1000 129 166 2301 3000 251 325 1401 1850 240 316 400 4 x 240mm2
13 1501 2000 167 218 1001 1250 167 214 3001 3600 326 389 1851 2300 317 393 500 2 x 4 x 240mm2
14 2001 2500 219 272 1251 1500 215 256 3601 4400 390 475 2301 2700 394 461 600 2 x 4 x 300mm2
15 2501 3400 273 367 1501 2200 257 363 4401 6000 476 648 2701 3800 462 640 800 2 x 4 x 300mm2
1000 7 x 1 x 630mm2
Dedicated Transformer By 1250
FAWAZ ALDOSSARY 7 x 1 x 630mm2
KVA 1600
500 220 Volt Cable Size 230 / 400 Volt Cable Size 2000 11 x 1 x 630mm2

1000 1250 Ampere 7 x 1 x 630mm2 800 Ampere 4 x 1 x 630mm2


1500 2500 Ampere 14 x 1 x 630mm2 1600 Ampere 7 x 1 x 630mm2