Air System Design Load Summary for 1

Project Name: EIGHTEEN MAINTAINANCE BUILDING 02/09/2024


Prepared by: M A C 06:57PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 105.8 °F / 84.1 °F HEATING OA DB / WB 44.6 °F / 41.1 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 118 ft² 1473 - 118 ft² 894 -
Roof Transmission 86 ft² 409 - 86 ft² 219 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 86 ft² 1313 - 86 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 129 W 440 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 6824 - 0 0 -
People 1 295 455 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 10% 1613 46 0% 0 0
>> Total Zone Loads - 12367 501 - 1112 0
Zone Conditioning - 12332 501 - 1098 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 680 CFM 0 - 680 CFM 0 -
Ventilation Load 0 CFM 0 0 0 CFM 0 0
Supply Fan Load 680 CFM 0 - 680 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 12332 501 - 1098 0
Central Cooling Coil - 12332 522 - 0 0
Central Heating Coil - 0 - - 1098 -
>> Total Conditioning - 12332 522 - 1098 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 1 of 1