You are on page 1of 1

CONECTED LOAD DEMAND DEMAND

No. DESCRIPTION ( COS ) ( SIN


KW KVAR KVA FACTOR LOAD kVA
New Construction Of Isolation (OPD)
1 Vera-Cruz 104.14 78.12 130.20 0.80 0.60 0.80 104.16

TOTAL LOAD PEAK LOAD 104.16


-
- SCALE 1 : 175 SPARE 15% 15.62

TOTAL 119.79

NEW PANEL 700x 300 x 210


CURRENT AMPER LOADING

CONECTED LOAD

POWER OUTLET 3P
FOR EX-RAY 32A

REMARKS
GROUPING
CONECTION PHASE CIRCUIT BREAKER CABLE PHASE
NO BREAKER AND DESCRIPTION
INCOMING CABLE

VA R S T TYPE CAPACITY TYPE SIZE R S T

1 POWER OUTLET 3P FOR EX-RAY 3P-1 21250 1 1 1 MCB 3 32 NYM 4CX 4mm 32.32 32.32 32.32 1

2 MCCB 3 80 POWER OUTLET 3P FOR EX-RAY 3P-2 21250 1 1 1 MCB 3 32 NYM 4CX 4mm 32.32 32.32 32.32 1
FROM PANEL SDP-A 3
NYY 4CX50mm +
NYA 1CX50mm
POWER OUTLET 3P FOR EX-RAY 3P-3 21250 1 1 1 MCB 3 32 NYM 4CX 4mm 32.32 32.32 32.32 1

5 CU BUS BAR 4 POWER OUTLET 3P FOR EX-RAY 3P-4 21250 1 1 1 MCB 3 32 NYM 4CX 4mm 32.32 32.32 32.32 1
20 X 20 X 15 mm 129.30 129.30 129.30 4
TOTAL
TOTAL REACTIVE POWER (KVA) 85.34

kVA + SPARE 20 % 102.40

TOTAL CURRENT (A) 155.77

BREAKER CAPACITY (A) 194.71

MCCB 3 (A) 200

-
- SCALE 1 : 175

PROJECT OWNER PROJECT DETAILS NOTES:


Design by : Project: Drawing Title: Drawing by, Checked by, Approved by, USE FIGURED DIMENSIONS IN PREFERENCE TO SCALE
ALL DIMENSIONS TO BE VERIFIED AND CHECKED ON SITE
CONSTRUCTION FACILITY OF HEALTH ALL DIMENSIONS IS MILLIMETER

DEPARTAMENTO Site:
SCHEDULE LOAD 1
No. ISSUE / AMENDMENT DATE INITIAL
CAICOLI, VERA-CRUZ, DILI
ENFRA-ESTRUTURAS TIMOR-LESTE Frigdiano Olije Cham Alvaro S. Abrantes, ST. Emilia de Jesus Alves Mendonca
1
2
MINISTERIO Scale (Engineer MoH) (Technical Adviser MoH) (Diretora Nasional Administrasaun Logistika i Patrimonio )
3
Building Title:
DA NTS
Issue
Date Date
OPD VERA-CRUZ Drawing No.
SAUDE MED 08