Ecole Centrale de Lyon - INSA de Lyon - Université Lyon 1

Ampère
Unité Mixte de Recherche du CNRS - UMR 5005
Génie Electrique, Electromagnétisme, Automatique, Microbiologie environnementale
et Applications

CERTIFICATE
Of OPERATION in RAIN CONDITIONS
According to the IEC 60060-1 STANDARD

Tests on the IONIFLASH MACH Early Streamer Emission (ESE)


Air Terminal # CEHT-2010_04_29A

Applicant: FRANCE PARATONNERRES Date: 29th April 2010

Zone d’Activités de CLOCHER


23000 GUERET - FRANCE

Results:
DRY condition RAIN condition Insulation in %
Input Voltage
( kV ) ( kV ) ( RAIN / DRY )
50% electrical
97,23%
breakdown 794 772
Switching
Impulse -
NEGATIVE Withstand
100,00%
POLARITY voltage 750 750

The tests realized on the IONIFLASH MACH Early Streamer Emission (ESE) air-
terminal have shown insulation greater than 97% according to the IEC 60060-1
standard.

Thomas AKA
Head of High Voltage Test Center