Anti-Burst Reinforcement Check for Foundation Plies

Supported Column Dimension


Diameter (DIA) = 600 mm

Vertical Load(P*) = 5340 kN

Pile Parameters
Size = 750 mm
Concrete Grade = 40 MPa

Pile Reinforcement Details


Main Bar size = 24 mm
Total No of Bars = 5
Diameter of Ties = 12 mm
Spacing of Ties = 200 mm
No of legs = 2
Critical depth for bursting = 750 mm
No of ties within bursting zone = 5
Total Area of steel ties = 1131 mm2
Strength of Steel(fsy) = 500 MPa

Anti-Burst Reinforcement Check


T1 (Transverse Tensile Force) = 0.25P(1-Kr1) AS3600: Clause 12.5.4
T2 (Transverse Tensile Force) = 0.25P(1-Kr2) AS3600: Clause 12.5.4
Kr1 = 0.80 AS3600: Clause 12.5.4
Kr2 = 0.80 AS3600: Clause 12.5.4
T1 (Transverse Tensile Force) = 267 kN
T2 (Transverse Tensile Force) = 267 kN
Tmax = 267 kN
Area of Reo Required (Tmax/0.85fsy) = 628 mm2 < 1131 mm2 OK