Control wiring — 1.5 sq. mm PVC insulated copper wire 16. Control supply ~ Iph, 230 VAC obtained from phase and neutral. 17. Makes of components a, Switchgear— SIEMENS b. Control gear —Teknic Indicating meters — AE/IMP/RISHABH(L&7) Il) LOCAL PUSH-BUTTON STATION Local push button stations are not considered, as drives are very near to Dist. Board. A\ll drives will be start / stop from Distribution board MM) CABLES 1. Make~Incab / Polycab 2. Power cables ~ PVC insulated, PVC sheathed, GI armoured, Aluminium conductor cables as per IS 1554, Minimum power-cable size shall be 3c x 4-sq. mm 3. Control cables ~ PVC insulated, PVC sheathed, GI armoured, solid copper conductor cables as per IS 1554. Control cable size shall be 1.5 sq.mam. IV) OUTDOOR CABLE-ROUTING Cables shall be run buried underground in un-constructed excavated and back- filled trenches upto individual equipment,Civil work for trenches to be done by client Y) EARTHING Main below ground earth-grid, earth stations (pits, electrodes etc.) and two earth connections near the distribution board shall be provided by the client. Equipment earthing from distribution board to motors. shall be provided by us using GI wire / strip depending on motor rating, MOTORS ‘Make — Crompton / Siemens Motors will be as per IS 325, totally enclosed, fan cooled squirrel cage induction motors. Degree of protection will be IPSS. Motors are suitable for supply voltage of 415 volts + 10% and frequency of 50 Hz. + 5%, and combined variation + 10%, weg NOTE :Thermax has the right to select the vendor from the alternative vendors mentioned above, [ COMMITTED TOA CLEAN ENVIRONMENT — ra ‘SHAPOORIT PALLONGT- 300 KLD STPIFABS00 300725 052009