You are on page 1of 64

SAMSUNG DVM Air Conditioner

2010

Outdoor Units DVM PLUS III


North America for 60Hz

Downloaded from www.Manualslib.com manuals search engine


Downloaded from www.Manualslib.com manuals search engine
Outdoor Units

Downloaded from www.Manualslib.com manuals search engine


I. Products
1 Outdoor units 6
2 Indoor units 9
3 Accessories 11

II. Outdoor units


1 Specifications 14

2 Dimensional drawing 20

3 PCB connector layout 22

4 Electrical wiring diagram 24

5 Sound pressure level 25


6 Operation limit 28
7 Cycle operation mode 29
8 Cycle function parts 36

2
Downloaded from www.Manualslib.com manuals search engine
Products
III. Installation
1 Outdoor unit combinations 40

Outdoor units
2 Space requirements 41
3 Placing the outdoor units 44
4 Electric specifications 45
5 Wiring works 46
6 Refrigerant piping works 48
7 Option switches & function keys 55
8

Installation
Error codes 57

3
Downloaded from www.Manualslib.com manuals search engine
DVM PLUS III

4
Downloaded from www.Manualslib.com manuals search engine
I. Products

Products
1 Outdoor units..............................................6
2 Indoor units.................................................9
3 Accessories..............................................11

5
Downloaded from www.Manualslib.com manuals search engine
1 Outdoor units

1-1. Nomenclature

Model name

RVX
RVX VV H
H TT 100
100 FF EE

      

 Classification  Capacity*
Outdoor unit (R410A) RVX ×1/10 HP(3 digits)

* Index
 Type
HP TON BTU(MBH)
Mini DVM M 7.5 6 72
DVM PLUS III 10.0 8 96
V
DVM PLUS III HR 12.5 10 120

 Mode  Rating voltage


Heat Pump H 1Ø, 220~240V, 50Hz E
Heat Recovery R 3Ø, 208~230V, 60Hz F
3Ø, 380~415V, 50Hz G
 Airflow direction 3Ø, 380V, 60Hz H
3Ø, 460V. 60Hz J
Upward airflow T
Frontward airflow F
 Version
Export A~Z
Domestic(KOREA) 0~9

6
Downloaded from www.Manualslib.com manuals search engine
1-2. Line-up

Products
TON 6 8 TON 22 24
HP 7.5 10.0 HP 27.5 30.0
Model Name RVXVHT075/100FE Model Name RVXVHT275/300FE

TON 10 TON 26
HP 12.5 HP 32.5
Model Name RVXVHT125FE Model Name RVXVHT325FE

TON 12 14 16 TON 28
HP 15.0 17.5 20.0 HP 35.0
Model Name RVXVHT150/175/200FE Model Name RVXVHT350FE

TON 18 TON 30
HP 22.5 HP 37.5
Model Name RVXVHT225FE Model Name RVXVHT375FE

TON 20
HP 25.0
Model Name RVXVHT250FE

7
Downloaded from www.Manualslib.com manuals search engine
1 Outdoor units

1-3. Outdoor unit combinations


1) Basic models

Classification Capacity (Ton) Capacity (HP) Model

6 7.5 RVXVHT075FE

Single unit 8 10.0 RVXVHT100FE

10 12.5 RVXVHT125FE

2) Combinations
Basic model
Classification Capacity (Ton) Capacity (HP)
RVXVHT075FE RVXVHT100FE RVXVHT125FE

12 15.0 2

14 17.5 1 1

16 20.0 2

18 22.5 1 1

20 25.0 2
Module unit
22 27.5 1 2

24 30.0 3

26 32.5 2 1

28 35.0 1 2

30 37.5 3

8
Downloaded from www.Manualslib.com manuals search engine
2 Indoor units

2-1. Nomenclature

Model name

Products
AVX
RVX CV SH HT 022
100 CF EE

      

 Classification  Capacity*
Indoor unit (R410A) AVX ×1/10 kW (3 digits)

* Index
 Classification by product group Notation Cooling Heating
Cassette type C 020 6.0 MBH 7.0 MBH
Duct type D 023 7.5 MBH 8.5 MBH
Wall mounted type W 032 9.5 MBH 10.5 MBH
040 12.0 MBH 13.5 MBH

 Product notation 052 18.0 MBH 20.0 MBH


060 20.0 MBH 23.0 MBH
Slim 1way S
072 24.0 MBH 27.0 MBH
2way 2
Cassette type 100 30.0 MBH 34.0 MBH
Mini 4way M
110 36.0 MBH 40.0 MBH
4way 4
145 48.0 MBH 54.0 MBH
Slim S
Duct type
Middle Static Pressure U
 Rating voltage
Neo Forte N
Wall mounted type
Vivace V 1Ø, 220V, 60Hz B
1Ø, 208V~230V, 60Hz C
1Ø, 220V~240V, 50Hz E
 Mode
Heat Pump/Heat Recovery H
 Version
Export A~Z
Domestic(KOREA) 0~9

9
Downloaded from www.Manualslib.com manuals search engine
2 Indoor units

2-2. Line-up
Model
name 020 023 032 040 052 060 072 100 110 145
(Notation)
MBH 6.0 7.5 9.5 12.0 18.0 20.0 24.0 30.0 36.0 48.0
Slim
1 way
cassette

Mini
4 way
cassette

4 way
cassette

Slim duct

MSP duct

Vivace

Neo-
Forte

10
Downloaded from www.Manualslib.com manuals search engine
3 Accessories

Classification Product Model Image Application model

Products
DMS MIM-D00 DVM Series, FJM, CAC, ERV

Integrated
management Controller S-NET 3 MST-P3P DVM Series, FJM, CAC, ERV
system

S-NET mini MST-S3W DVM Series, FJM, CAC

Centralized
MCM-A202B DVM Series, FJM, CAC, ERV
controller
Controller
Centralized Operation mode
MCM-C200 DVM Series
control system selection switch

Centralized
Interface Mini DVM(R410A), DVM PLUS II,
controller interface MIM-B13B
module DVM PLUS III, FJM, ERV
module

Wireless remote
MR-BH01U Cassette, Duct(Receiver needed)
controller

Wired remote
controller MWR-WE00 Cassette, Wall-mounted, Duct
(Multi function)

Individual
Controller Simplified wired
control system MWR-SH00 Cassette, Wall-mounted, Duct
remote controller

Wireless
signal MRK-A00 Duct (For wireless remote controller)
Wireless receiver
signal
receiver kit
Receiver
MRW-10A Duct (For wireless remote controller)
wire

Key-tag interface
MIM-B02 DVM Series, FJM
module
Guest room management
system
External contact Mini DVM(R410A), DVM PLUS II,
MIM-B14
interface module DVM PLUS III, FJM

 DVM Series : Mini DVM, DVM, DVM PLUS II, DVM PLUS III

11
Downloaded from www.Manualslib.com manuals search engine
3 Accessories

Classification Feature Model Description Relevant unit Remark


MXJ-YA1509 Below 51MBH
MXJ-YA2512 51~138MBH
MXJ-YA2812 138~160MBH
DVM PLUS II,
Y-joint MXJ-YA2815 160~240MBH Requisite
DVM PLUS III
MXJ-YA3119 240~336MBH
MXJ-YA3819 336~468MBH
MXJ-YA4422 Over 468MBH
Outdoor joint
DVM PLUS II,
(Outdoor MXJ-T3819 Below 30 TON Requisite
DVM PLUS III
Connection)
Below 160MBH
MXJ-HA2512
(for 4 rooms)
160~240MBH DVM PLUS II,
Header joint MXJ-HA3115 Requisite
(for 8 rooms) DVM PLUS III
Over 240MBH
MXJ-HA3819
(for 9 rooms)
Below 12MBH(1 unit) +
MXD-A13K116
18MBH~24MBH(1 unit)
Wall-mounted &
MXD-A13K200 Below 12MBH(2 units) Ceiling
MXD-A16K200 18MBH~24MBH(2 units) (For 2 indoor units)

MXD-A22K200 Over 24MBH(2 units)


Below 12MBH(2 units) +
MXD-A13K216
18MBH~24MBH(1 units)
EEV kits Option
MXD-A13K300 Below 12MBH(3 units) Wall-mounted &
Below 12MBH(1 unit) + Ceiling
MXD-A16K213 (For 3 indoor units)
18MBH~24MBH(2 units)

MXD-A16K300 18~ 24MBH(3 units)

MEV-A13SA Below 12MBH Wall-mounted & Ceiling


Over 18~24MBH (For single unit)
MEV-A16SA

MDP-E075SEE AVXDSH020~072C Series

MDP-E075SEE1 AVXDSH100~145C Series


Drain pump - Option
MDP-M075SGU1 AVXDSH100~110C Series

MDP-M075SGU2 AVXDUH145 Series

PSSMA

Front panel PMSMA - Cassette panels Requisite

P4SMA

12
Downloaded from www.Manualslib.com manuals search engine
II. Outdoor units
1 Specifications.......................................... 14
2 Dimensional drawing................................20

Outdoor units
3 PCB connector layout...............................22
4 Electrical wiring diagram..........................24
5 Sound pressure level................................25
6 Operation limit...........................................28
7 Cycle operation mode..............................29
8 Cycle function parts..................................36

13
Downloaded from www.Manualslib.com manuals search engine
1 Specifications
Type

Model Name RVXVHT075FE RVXVHT100FE RVXVHT125FE


Power Supply Ø/ V/ Hz 3/ 208~230/ 60 3/ 208~230/ 60 3/ 208~230/ 60
Mode1) - Heat Pump Heat Pump Heat Pump
US Ton TON 6.0 8.0 10.0
Horse Power HP 7.5 10.0 12.5
Btu/h 72,000 96,000 120,000
Performance Cooling2)
Nominal US RT 6.0 8.0 10.0
Capacity Btu/h 81,000 108,000 135,000
Heating3)
US RT 6.8 9.0 11.3
Cooling 5.50 7.50 10.70
Nominal Input kW
Heating 5.15 7.08 10.09
Power Nominal Running Cooling 18.80 28.90 36.80
A
Current Heating 22.60 24.90 33.00
Circuit Breaker (MCCB/ELB/ELCB) A 50 50 60
Cooling - 3.84 3.75 3.29
COP Cooling (US Only) Btu/Wh 13.09 12.80 11.21
Heating - 4.61 4.47 3.92
Model ZPJ72KCE-TF5 ZPI61KCE-TF5 ZPJ72KCE-TF5 ZPI61KCE-TF5 ZPJ83KCE-TF7 ZPI83KCE-TF7
Type - DVI Scroll FVI Scroll DVI Scroll FVI Scroll DVI Scroll FVI Scroll
Number EA 1 1 1 1 1 1
cc/Rev 67.1 58.1 67.1 58.1 77.2 77.2
Piston Displacement
Compressor in³/Rev 4.095 3.545 4.095 3.545 4.711 4.711
Output kW 6.94 5.83 6.94 5.83 7.91 7.91
Type - 3MAF POE 3MAF POE 3MAF POE
Lubricant cc 1,685 1,685 1,685 1,685 1,685 1,685
Charging
fl. oz. 57 57 57 57 57 57
Type / Control - Propeller/BLDC Propeller/BLDC Propeller/BLDC
Motor Output W 630 630 630
3
m /min 170 170 180
Fan Airflow Rate
CFM 6004 6004 6357
External Static Pa 78.5 78.5 78.5
Max.
Pressure WG 0.315 0.315 0.315
- High Pressure Switch High Pressure Switch High Pressure Switch
Mechanical Type - Comp./Accum. Crank Case Heater Comp./Accum. Crank Case Heater Comp./Accum. Crank Case Heater
Safety - Fuse for PCB Fuse for PCB Fuse for PCB
Devices - Over-voltage Protection Over-voltage Protection Over-voltage Protection
Electronic Type - Current Transformer Current Transformer Current Transformer
- Fan motor Voltage Protection Fan motor Voltage Protection Fan motor Voltage Protection
Ø, mm 9.52 9.52 12.70
Liquid
Ø, inch 3/8 3/8 1/2
Ø, mm 19.05 22.23 28.58
Gas
Ø, inch 3/4 7/8 1 1/8
Piping Ø, mm - - -
Oil (Flare)
Connections Ø, inch - - -
m 200 200 200
Max. Length
Installation ft 656 656 656
Limitation m 50 (40) 50 (40) 50 (40)
Max. Height
ft 164 (131) 164 (131) 164 (131)
Type - R410A R410A R410A
Refrigerant kg 6.5 7.5 9.0
Factory Charging
lbs 14.33 16.53 19.84
4)
Sound Sound Pressure dB(A) 58 58 60
kg 240 240 280
Net Weight
lbs 529 529 617
kg 253 253 297
Shipping Weight
lbs 558 558 655
Set Size
mm 880 x 1668 x 765 880 x 1668 x 765 1200 x 1668 x 765
Net Dimensions (WxHxD)
inch 34 5/8 x 65 5/8 x 30 1/8 34 5/8 x 65 5/8 x 30 1/8 47 1/4 x 65 5/8 x 30 1/8
mm 948 x 1888 x 832 948 x 1888 x 832 1268 x 1888 x 832
Shipping Dimensions (WxHxD)
inch 37 3/8 x 74 3/8 x 32 3/4 37 3/8 x 74 3/8 x 32 3/4 49 7/8 x 74 3/8 x 32 3/4
Main Power (Below 50m) AWG # AWG 6 AWG 6 AWG 4
Cable
Communication AWG # AWG 16~18 AWG 16~18 AWG 16~18
°C -5~46.1 -5~46.1 -5~46.1
Cooling
Operating °F 23~115 23~115 23~115
Temp. Range °C -20~24 -20~24 -20~24
Heating
°F -4~75 -4~75 -4~75

*1) Mode  HP : Heat Pump, HR : Heat Recovery


*2) Norminal cooling capacities are based on;
 Indoor temperature : 26.7°C DB, 19.4°C WB(80°F DB, 67°F WB)
 Outdoor temperature : 35°C DB, 23.9°C WB(90°F DB, 75°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*3) Norminal heating capacities are based on;
 Indoor temperature : 21.1°C DB, 15.6°C WB(70°F DB, 60°F WB)
 Outdoor temperature : 8.3°C DB, 6.1°C WB(47°F DB, 43°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*4) Sound level was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications are subject to change without prior notice for product improvement.

14
Downloaded from www.Manualslib.com manuals search engine
Type

Model Name RVXVHT150FE RVXVHT175FE


RVXVHT075FE 2 1
Model Basic RVXVHT100FE 1
RVXVHT125FE
Power Supply Ø/ V/ Hz 3/ 208~230/ 60 3/ 208~230/ 60
Mode1) - Heat Pump Heat Pump
US Ton TON 12 14
Horse Power HP 15.0 17.5
Btu/h 144,000 168,000
Performance Cooling2)
Nominal US RT 12.0 14.0
Capacity Btu/h 162,000 189,000
Heating3)
US RT 13.5 15.8
Cooling 11.0 13.0
Nominal Input kW

Outdoor units
Heating 10.3 12.2
Power Nominal Running Cooling 37.6 47.7
A
Current Heating 45.2 47.5
Circuit Breaker (MCCB/ELB/ELCB) A 50 + 50 50 + 50
Cooling - 3.84 3.79
COP Cooling (US Only) Btu/Wh 13.09 12.92
Heating - 4.61 4.53
Model ZPJ72* ZPJ83* ZPI61* ZPI83* ZPJ72* ZPJ83* ZPI61* ZPI83*
Type - DVI Scroll FVI Scroll DVI Scroll FVI Scroll
Number EA 2 2 2 2
cc/Rev 67.1 58.1 67.1 58.1
Piston Displacement
Compressor in³/Rev 4.095 3.545 4.095 3.545
Output kW 6.94 5.83 6.94 5.83
Type - 3MAF POE 3MAF POE
Lubricant cc 1,685 1,685 1,685 1,685
Charging
fl. oz. 57 57 57 57
Type / Control - Propeller/BLDC Propeller/BLDC
Motor Output W (630) x 2 (630) x 2
3
m /min (170) x 2 (170) x 2
Fan Airflow Rate
CFM (6004) x 2 (6004) x 2
External Static Pa 78.5 78.5
Max.
Pressure WG 0.315 0.315
- High Pressure Switch High Pressure Switch
Mechanical Type - Comp./Accum. Crank Case Heater Comp./Accum. Crank Case Heater
Safety - Fuse for PCB Fuse for PCB
Devices - Over-voltage Protection Over-voltage Protection
Electronic Type - Current Transformer Current Transformer
- Fan motor Voltage Protection Fan motor Voltage Protection
Ø, mm 12.70 15.88
Liquid
Ø, inch 1/2 5/8
Ø, mm 28.58 28.58
Gas
Ø, inch 1 1/8 1 1/8
Piping Ø, mm 6.35 6.35
Oil (Flare)
Connections Ø, inch 1/4 1/4
m 200 200
Max. Length
Installation ft 656 656
Limitation m 50 (40) 50 (40)
Max. Height
ft 164 (131) 164 (131)
Type - R410A R410A
Refrigerant kg (6.5) x 2 (6.5) x 1 + (7.5) x 1
Factory Charging
lbs (14.33) x 2 (14.33) x 1 + (16.53) x 1
Sound4) Sound Pressure dB(A) 60 61
kg (240) x 2 (240) x 2
Net Weight
lbs (529) x 2 (529) x 2
kg (253) x 2 (253) x 2
Shipping Weight
lbs (558) x 2 (558) x 2
Set Size
mm (880 x 1668 x 765) x 2 (880 x 1668 x 765) x 2
Net Dimensions (WxHxD)
inch (34 5/8 x 65 5/8 x 30 1/8) x 2 (34 5/8 x 65 5/8 x 30 1/8) x 2
mm (948 x 1888 x 832) x 2 (948 x 1888 x 832) x 2
Shipping Dimensions (WxHxD)
inch (37 3/8 x 74 3/8 x 32 3/4) x 2 (37 3/8 x 74 3/8 x 32 3/4) x 2
Main Power (Below 50m) AWG # Separate electrical connection for each outdoor units Separate electrical connection for each outdoor units
Cable
Communication AWG # AWG 16~18 AWG 16~18
°C -5~46.1 -5~46.1
Cooling
Operating °F 23~115 23~115
Temp. Range °C -20~24 -20~24
Heating
°F -4~75 -4~75

*1) Mode  HP : Heat Pump, HR : Heat Recovery


*2) Norminal
 cooling capacities are based on;
 Indoor temperature : 26.7°C DB, 19.4°C WB(80°F DB, 67°F WB)
 Outdoor temperature : 35°C DB, 23.9°C WB(90°F DB, 75°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*3) N
 orminal heating capacities are based on;
 Indoor temperature : 21.1°C DB, 15.6°C WB(70°F DB, 60°F WB)
 Outdoor temperature : 8.3°C DB, 6.1°C WB(47°F DB, 43°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*4) Sound level was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications are subject to change without prior notice for product improvement.

15
Downloaded from www.Manualslib.com manuals search engine
1 Specifications
Type

Model Name RVXVHT200FE RVXVHT225FE


RVXVHT075FE
Model Basic RVXVHT100FE 2 1
RVXVHT125FE 1
Power Supply Ø/ V/ Hz 3/ 208~230/ 60 3/ 208~230/ 60
Mode1) - Heat Pump Heat Pump
US Ton TON 16 18
Horse Power HP 20.0 22.5
Btu/h 192,000 216,000
Performance Cooling2)
Nominal US RT 16.0 18.0
Capacity Btu/h 216,000 243,000
Heating3)
US RT 18.0 20.3
Cooling 15.0 18.2
Nominal Input kW
Heating 14.2 17.2
Power Nominal Running Cooling 57.8 65.7
A
Current Heating 49.8 57.9
Circuit Breaker (MCCB/ELB/ELCB) A 50 + 50 50 + 60
Cooling - 3.75 3.48
COP Cooling (US Only) Btu/Wh 12.80 11.87
Heating - 4.47 4.15
Model ZPJ72* ZPJ83* ZPI61* ZPI83* ZPJ72* ZPJ83* ZPI61* ZPI83*
Type - DVI Scroll FVI Scroll DVI Scroll FVI Scroll
Number EA 2 2 1 1 1 1
cc/Rev 67.1 58.1 67.1 77.2 58.1 77.2
Piston Displacement
Compressor in³/Rev 4.095 3.545 4.095 4.711 3.545 4.711
Output kW 6.94 5.83 6.94 7.91 5.83 7.91
Type - 3MAF POE 3MAF POE
Lubricant cc 1,685 1,685 1,685 1,685 1,685 1,685
Charging
fl. oz. 57 57 57 57 57 57
Type / Control - Propeller/BLDC Propeller/BLDC
Motor Output W (630) x 2 (630) x 2
3
m /min (170) x 2 (170) x 1 + (180) x 1
Fan Airflow Rate
CFM (6004) x 2 (6004) x 1 + (6357) x 1
External Static Pa 78.5 78.5
Max.
Pressure WG 0.315 0.315
- High Pressure Switch High Pressure Switch
Mechanical Type - Comp./Accum. Crank Case Heater Comp./Accum. Crank Case Heater
Safety - Fuse for PCB Fuse for PCB
Devices - Over-voltage Protection Over-voltage Protection
Electronic Type - Current Transformer Current Transformer
- Fan motor Voltage Protection Fan motor Voltage Protection
Ø, mm 15.88 15.88
Liquid
Ø, inch 5/8 5/8
Ø, mm 28.58 28.58
Gas
Ø, inch 1 1/8 1 1/8
Piping Ø, mm 6.35 6.35
Oil (Flare)
Connections Ø, inch 1/4 1/4
m 200 200
Max. Length
Installation ft 656 656
Limitation m 50 (40) 50 (40)
Max. Height
ft 164 (131) 164 (131)
Type - R410A R410A
Refrigerant kg (7.5) x 2 (7.5) x 1 + (9) x 1
Factory Charging
lbs (16.53) x 2 (16.53) x 1 + (19.84) x 1
Sound4) Sound Pressure dB(A) 61 62
kg (240) x 2 (240) x 1 + (280) x 1
Net Weight
lbs (529) x 2 (529) x 1 + (617) x 1
kg (253) x 2 (253) x 1 + (297) x 1
Shipping Weight
lbs (558) x 2 (558) x 1 + (655) x 1
Set Size mm (880 x 1668 x 765) x 2 (880 x 1668 x 765) x 1 + (1200 x 1668 x 765) x 1
Net Dimensions (WxHxD) (34 5/8 x 65 5/8 x 30 1/8) x 1 +
inch (34 5/8 x 65 5/8 x 30 1/8) x 2
(47 1/4 x 65 5/8 x 30 1/8) x 1
mm (948 x 1888 x 832) x 2 (948 x 1888 x 832) x 1 + (1268 x 1888 x 832) x 1
Shipping Dimensions (WxHxD) (37 3/8 x 74 3/8 x 32 3/4) x 1 +
inch (37 3/8 x 74 3/8 x 32 3/4) x 2
(49 7/8 x 74 3/8 x 32 3/4) x 1
Main Power (Below 50m) AWG # Separate electrical connection for each outdoor units Separate electrical connection for each outdoor units
Cable
Communication AWG # AWG 16~18 AWG 16~18
°C -5~46.1 -5~46.1
Cooling
Operating °F 23~115 23~115
Temp. Range °C -20~24 -20~24
Heating
°F -4~75 -4~75

*1) Mode  HP : Heat Pump, HR : Heat Recovery


*2) Norminal cooling capacities are based on;
 Indoor temperature : 26.7°C DB, 19.4°C WB(80°F DB, 67°F WB)
 Outdoor temperature : 35°C DB, 23.9°C WB(90°F DB, 75°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*3) Norminal heating capacities are based on;
 Indoor temperature : 21.1°C DB, 15.6°C WB(70°F DB, 60°F WB)
 Outdoor temperature : 8.3°C DB, 6.1°C WB(47°F DB, 43°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*4) Sound level was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications are subject to change without prior notice for product improvement.

16
Downloaded from www.Manualslib.com manuals search engine
Type

Model Name RVXVHT250FE RVXVHT275FE


RVXVHT075FE 1
Model Basic RVXVHT100FE 2
RVXVHT125FE 2
Power Supply Ø/ V/ Hz 3/ 208~230/ 60 3/ 208~230/ 60
Mode1) - Heat Pump Heat Pump
US Ton TON 20 22
Horse Power HP 25.0 27.5
Btu/h 240,000 264,000
Performance Cooling2)
Nominal US RT 20.0 22.0
Capacity Btu/h 270,000 297,000
Heating3)
US RT 22.5 24.8
Cooling 21.4 20.5
Nominal Input kW
Heating

Outdoor units
20.2 19.3
Power Nominal Running Cooling 73.6 76.6
A
Current Heating 66.0 72.4
Circuit Breaker (MCCB/ELB/ELCB) A 60 + 60 50 + 50 + 50
Cooling - 3.29 3.77
COP Cooling (US Only) Btu/Wh 11.21 12.88
Heating - 3.92 4.51
Model ZPJ72* ZPJ83* ZPI61* ZPI83* ZPJ72* ZPJ83* ZPI61* ZPI83*
Type - DVI Scroll FVI Scroll DVI Scroll FVI Scroll
Number EA 2 2 3 3
cc/Rev 77.2 77.2 67.1 58.1
Piston Displacement
Compressor in³/Rev 4.711 4.711 4.095 3.545
Output kW 7.91 7.91 6.94 5.83
Type - 3MAF POE 3MAF POE
Lubricant cc 1,685 1,685 1,685 1,685
Charging
fl. oz. 57 57 57 57
Type / Control - Propeller/BLDC Propeller/BLDC
Motor Output W (630) x 2 (630) x 3
m3/min (180) x 2 (170) x 3
Fan Airflow Rate
CFM (6357) x 2 (6004) x 3
External Static Pa 78.5 78.5
Max.
Pressure WG 0.315 0.315
- High Pressure Switch High Pressure Switch
Mechanical Type - Comp./Accum. Crank Case Heater Comp./Accum. Crank Case Heater
Safety - Fuse for PCB Fuse for PCB
Devices - Over-voltage Protection Over-voltage Protection
Electronic Type - Current Transformer Current Transformer
- Fan motor Voltage Protection Fan motor Voltage Protection
Ø, mm 19.05 19.05
Liquid
Ø, inch 3/4 3/4
Ø, mm 34.93 34.93
Gas
Ø, inch 1 3/8 1 3/8
Piping Ø, mm 6.35 6.35
Oil (Flare)
Connections Ø, inch 1/4 1/4
m 200 200
Max. Length
Installation ft 656 656
Limitation m 50 (40) 50 (40)
Max. Height
ft 164 (131) 164 (131)
Type - R410A R410A
Refrigerant kg (9) x 2 (6.5) x 1 + (7.5) x 2
Factory Charging
lbs (19.84) x 2 (14.33) x 1 + (16.53) x 2
Sound4) Sound Pressure dB(A) 62 63
kg (280) x 2 (240) x 3
Net Weight
lbs (617) x 2 (529) x 3
kg (297) x 2 (253) x 3
Shipping Weight
lbs (655) x 2 (558) x 3
Set Size
mm (1200 x 1668 x 765) x 2 (880 x 1668 x 765) x 3
Net Dimensions (WxHxD)
inch (47 1/4 x 65 5/8 x 30 1/8) x 2 (34 5/8 x 65 5/8 x 30 1/8) x 3
mm (1268 x 1888 x 832) x 2 (948 x 1888 x 832) x 3
Shipping Dimensions (WxHxD)
inch (49 7/8 x 74 3/8 x 32 3/4) x 2 (37 3/8 x 74 3/8 x 32 3/4) x 3
Main Power (Below 50m) AWG # Separate electrical connection for each outdoor units Separate electrical connection for each outdoor units
Cable
Communication AWG # AWG 16~18 AWG 16~18
°C -5~46.1 -5~46.1
Cooling
Operating °F 23~115 23~115
Temp. Range °C -20~24 -20~24
Heating
°F -4~75 -4~75

*1) Mode  HP : Heat Pump, HR : Heat Recovery


*2) Norminal
 cooling capacities are based on;
 Indoor temperature : 26.7°C DB, 19.4°C WB(80°F DB, 67°F WB)
 Outdoor temperature : 35°C DB, 23.9°C WB(90°F DB, 75°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*3) N
 orminal heating capacities are based on;
 Indoor temperature : 21.1°C DB, 15.6°C WB(70°F DB, 60°F WB)
 Outdoor temperature : 8.3°C DB, 6.1°C WB(47°F DB, 43°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*4) Sound level was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications are subject to change without prior notice for product improvement.

17
Downloaded from www.Manualslib.com manuals search engine
1 Specifications
Type

Model Name RVXVHT300FE RVXVHT325FE


RVXVHT075FE
Model Basic RVXVHT100FE 3 2
RVXVHT125FE 1
Power Supply Ø/ V/ Hz 3/ 208~230/ 60 3/ 208~230/ 60
Mode1) - Heat Pump Heat Pump
US Ton TON 24 26
Horse Power HP 30.0 32.5
Btu/h 288,000 312,000
Performance Cooling2)
Nominal US RT 24.0 26.0
Capacity Btu/h 324,000 351,000
Heating3)
US RT 27.0 29.3
Cooling 22.5 25.7
Nominal Input kW
Heating 21.2 24.3
Power Nominal Running Cooling 86.7 94.6
A
Current Heating 74.7 82.8
Circuit Breaker (MCCB/ELB/ELCB) A 50 + 50 + 50 50 + 50 + 60
Cooling - 3.75 3.56
COP Cooling (US Only) Btu/Wh 12.80 12.14
Heating - 4.47 4.24
Model ZPJ72* ZPJ83* ZPI61* ZPI83* ZPJ72* ZPJ83* ZPI61* ZPI83*
Type - DVI Scroll FVI Scroll DVI Scroll FVI Scroll
Number EA 3 3 2 1 2 1
cc/Rev 67.1 58.1 67.1 77.2 58.1 77.2
Piston Displacement
Compressor in³/Rev 4.095 3.545 4.095 4.711 3.545 4.711
Output kW 6.94 5.83 6.94 7.91 5.83 7.91
Type - 3MAF POE 3MAF POE
Lubricant cc 1,685 1,685 1,685 1,685 1,685 1,685
Charging
fl. oz. 57 57 57 57 57 57
Type / Control - Propeller/BLDC Propeller/BLDC
Motor Output W (630) x 3 (630) x 3
m3/min (170) x 3 (170) x 2 + (180) x 1
Fan Airflow Rate
CFM (6004) x 3 (6004) x 2 + (6357) x 1
External Static Pa 78.5 78.5
Max.
Pressure WG 0.315 0.315
- High Pressure Switch High Pressure Switch
Mechanical Type - Comp./Accum. Crank Case Heater Comp./Accum. Crank Case Heater
Safety - Fuse for PCB Fuse for PCB
Devices - Over-voltage Protection Over-voltage Protection
Electronic Type - Current Transformer Current Transformer
- Fan motor Voltage Protection Fan motor Voltage Protection
Ø, mm 19.05 19.05
Liquid
Ø, inch 3/4 3/4
Ø, mm 34.93 34.93
Gas
Ø, inch 1 3/8 1 3/8
Piping Ø, mm 6.35 6.35
Oil (Flare)
Connections Ø, inch 1/4 1/4
m 200 200
Max. Length
Installation ft 656 656
Limitation m 50 (40) 50 (40)
Max. Height
ft 164 (131) 164 (131)
Type - R410A R410A
Refrigerant kg (7.5) x 3 (7.5) x 2 + (9) x 1
Factory Charging
lbs (16.53) x 3 (16.53) x 2 + (19.84) x 1
Sound4) Sound Pressure dB(A) 63 64
kg (240) x 3 (240) x 2 + (280) x 1
Net Weight
lbs (529) x 3 (529) x 2 + (617) x 1
kg (253) x 3 (253) x 2 + (297) x 1
Shipping Weight
lbs (558) x 3 (558) x 2 + (655) x 1
mm (880 x 1668 x 765) x 3 (880 x 1668 x 765) x 2 + (1200 x 1668 x 765) x 1
Set Size
Net Dimensions (WxHxD) (34 5/8 x 65 5/8 x 30 1/8) x 2 +
inch (34 5/8 x 65 5/8 x 30 1/8) x 3
(47 1/4 x 65 5/8 x 30 1/8) x 1
mm (948 x 1888 x 832) x 3 (948 x 1888 x 832) x 2 + (1268 x 1888 x 832) x 1
Shipping Dimensions (WxHxD) (37 3/8 x 74 3/8 x 32 3/4) x 2 +
inch (37 3/8 x 74 3/8 x 32 3/4) x 3
(49 7/8 x 74 3/8 x 32 3/4) x 1
Main Power (Below 50m) AWG # Separate electrical connection for each outdoor units Separate electrical connection for each outdoor units
Cable
Communication AWG # AWG 16~18 AWG 16~18
°C -5~46.1 -5~46.1
Cooling
Operating °F 23~115 23~115
Temp. Range °C -20~24 -20~24
Heating
°F -4~75 -4~75
*1) Mode  HP : Heat Pump, HR : Heat Recovery
*2) Norminal cooling capacities are based on;
 Indoor temperature : 26.7°C DB, 19.4°C WB(80°F DB, 67°F WB)
 Outdoor temperature : 35°C DB, 23.9°C WB(90°F DB, 75°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*3) Norminal heating capacities are based on;
 Indoor temperature : 21.1°C DB, 15.6°C WB(70°F DB, 60°F WB)
 Outdoor temperature : 8.3°C DB, 6.1°C WB(47°F DB, 43°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*4) Sound level was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications are subject to change without prior notice for product improvement.

18
Downloaded from www.Manualslib.com manuals search engine
Type

Model Name RVXVHT350FE RVXVHT375FE


RVXVHT075FE
Model Basic RVXVHT100FE 1
RVXVHT125FE 2 3
Power Supply Ø/ V/ Hz 3/ 208~230/ 60 3/ 208~230/ 60
Mode1) - Heat Pump Heat Pump
US Ton TON 28 30
Horse Power HP 35.0 37.5
Btu/h 336,000 360,000
Performance Cooling2)
Nominal US RT 28.0 30.0
Capacity Btu/h 378,000 405,000
Heating3)
US RT 31.5 33.8
Cooling 28.9 32.1
Nominal Input kW
Heating

Outdoor units
27.3 30.3
Power Nominal Running Cooling 102.5 110.4
A
Current Heating 90.9 99.0
Circuit Breaker (MCCB/ELB/ELCB) A 50 + 60 + 60 60 + 60 + 60
Cooling - 3.41 3.29
COP Cooling (US Only) Btu/Wh 11.63 11.21
Heating - 4.06 3.92
Model ZPJ72* ZPJ83* ZPI61* ZPI83* ZPJ72* ZPJ83* ZPI61* ZPI83*
Type - DVI Scroll FVI Scroll DVI Scroll FVI Scroll
Number EA 1 2 1 2 3 3
cc/Rev 67.1 77.2 58.1 77.2 77.2 77.2
Piston Displacement
Compressor in³/Rev 4.095 4.711 3.545 4.711 4.711 4.711
Output kW 6.94 7.91 5.83 7.91 7.91 7.91
Type - 3MAF POE 3MAF POE
Lubricant cc 1,685 1,685 1,685 1,685 1,685 1,685
Charging
fl. oz. 57 57 57 57 57 57
Type / Control - Propeller/BLDC Propeller/BLDC
Motor Output W (630) x 3 (630) x 3
m3/min (170) x 1 + (180) x 2 (180) x 3
Fan Airflow Rate
CFM (6004) x 1 + (6357) x 2 (6357) x 3
External Static Pa 78.5 78.5
Max.
Pressure WG 0.315 0.315
- High Pressure Switch High Pressure Switch
Mechanical Type - Comp./Accum. Crank Case Heater Comp./Accum. Crank Case Heater
Safety - Fuse for PCB Fuse for PCB
Devices - Over-voltage Protection Over-voltage Protection
Electronic Type - Current Transformer Current Transformer
- Fan motor Voltage Protection Fan motor Voltage Protection
Ø, mm 19.05 19.05
Liquid
Ø, inch 3/4 3/4
Ø, mm 34.93 34.93
Gas
Ø, inch 1 3/8 1 3/8
Piping Ø, mm 6.35 6.35
Oil (Flare)
Connections Ø, inch 1/4 1/4
m 200 200
Max. Length
Installation ft 656 656
Limitation m 50 (40) 50 (40)
Max. Height
ft 164 (131) 164 (131)
Type - R410A R410A
Refrigerant kg (7.5) x 1 + (9) x 2 (9) x 3
Factory Charging
lbs (16.53) x 1 + (19.84) x 2 (19.84) x 3
Sound4) Sound Pressure dB(A) 64 64
kg (240) x 1 + (280) x 2 (280) x 3
Net Weight
lbs (529) x 1 + (617) x 2 (617) x 3
kg (253) x 1 + (297) x 2 (297) x 3
Shipping Weight
lbs (558) x 1 + (655) x 2 (655) x 3
mm (880 x 1668 x 765) x 1 + (1200 x 1668 x 765) x 2 (1200 x 1668 x 765) x 3
Set Size
Net Dimensions (WxHxD) (34 5/8 x 65 5/8 x 30 1/8) x 1 +
inch (47 1/4 x 65 5/8 x 30 1/8) x 3
(47 1/4 x 65 5/8 x 30 1/8) x 2
mm (948 x 1888 x 832) x 1 + (1268 x 1888 x 832) x 2 (1268 x 1888 x 832) x 3
Shipping Dimensions (WxHxD) (37 3/8 x 74 3/8 x 32 3/4) x 1 +
inch (49 7/8 x 74 3/8 x 32 3/4) x 3
(49 7/8 x 74 3/8 x 32 3/4) x 2
Main Power (Below 50m) AWG # Separate electrical connection for each outdoor units Separate electrical connection for each outdoor units
Cable
Communication AWG # AWG 16~18 AWG 16~18
°C -5~46.1 -5~46.1
Cooling
Operating °F 23~115 23~115
Temp. Range °C -20~24 -20~24
Heating
°F -4~75 -4~75
*1) Mode  HP : Heat Pump, HR : Heat Recovery
*2) Norminal
 cooling capacities are based on;
 Indoor temperature : 26.7°C DB, 19.4°C WB(80°F DB, 67°F WB)
 Outdoor temperature : 35°C DB, 23.9°C WB(90°F DB, 75°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*3) N
 orminal heating capacities are based on;
 Indoor temperature : 21.1°C DB, 15.6°C WB(70°F DB, 60°F WB)
 Outdoor temperature : 8.3°C DB, 6.1°C WB(47°F DB, 43°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*4) Sound level was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications are subject to change without prior notice for product improvement.

19
Downloaded from www.Manualslib.com manuals search engine
2 Dimensional drawing

2-1. RVXVHT075/100FE
Unit : mm (inch)

No. Name Description No. Name Description


1 Gas pipe connection Ø57.10, knock-out hole 10 Power & communication wiring conduit Ø34.50, knock-out hole hole-side
2 High pressure gas pipe connection Ø57.10, knock-out hole 11 Power & communication wiring conduit Ø34.50, knock-out hole hole-side
3 Liquid pipe connection Ø37.10, knock-out hole 12 Power & communication wiring conduit Ø34.50, knock-out hole hole-side
4 Oil balance pipe connection between units Ø32.10, knock-out hole 13 Power & communication wiring conduit Ø34.50, knock-out hole hole-side
5 Power & communication wiring conduit Ø34.50, knock-out hole hole-front 14 Power & communication wiring conduit Ø27.80, knock-out hole hole-side
6 Power & communication wiring conduit Ø34.50, knock-out hole hole-front 15 Power & communication wiring conduit Ø34.50, knock-out hole hole-side
7 Power & communication wiring conduit Ø43.70, knock-out hole hole-front 16 Pipe connection through base Pipes connection opening with cover
8 Power & communication wiring conduit Ø43.70, knock-out hole hole-front 17 Condensate drain holes Ø20mm-2 holes
9 Power & communication wiring conduit Ø43.70, knock-out hole hole-front 18 Foundation bolts positions 4-12 x 20 slit-hole

20
Downloaded from www.Manualslib.com manuals search engine
2-2. RVXVHT125FE
Unit : mm (inch)

Outdoor units

No. Name Description No. Name Description


1 Gas pipe connection Ø57.10, knock-out hole 10 Power & communication wiring conduit Ø34.50, knock-out hole hole-side
2 High pressure gas pipe connection Ø57.10, knock-out hole 11 Power & communication wiring conduit Ø34.50, knock-out hole hole-side
3 Liquid pipe connection Ø37.10, knock-out hole 12 Power & communication wiring conduit Ø34.50, knock-out hole hole-side
4 Oil balance pipe connection between units Ø32.10, knock-out hole 13 Power & communication wiring conduit Ø34.50, knock-out hole hole-side
5 Power & communication wiring conduit Ø34.50, knock-out hole hole-front 14 Power & communication wiring conduit Ø27.80, knock-out hole hole-side
6 Power & communication wiring conduit Ø34.50, knock-out hole hole-front 15 Power & communication wiring conduit Ø34.50, knock-out hole hole-side
7 Power & communication wiring conduit Ø43.70, knock-out hole hole-front 16 Pipe connection through base Pipes connection opening with cover
8 Power & communication wiring conduit Ø43.70, knock-out hole hole-front 17 Condensate drain holes Ø20mm-2 holes
9 Power & communication wiring conduit Ø43.70, knock-out hole hole-front 18 Foundation bolts positions 4-12 x 20 slit-hole

21
Downloaded from www.Manualslib.com manuals search engine
3 PCB connector layout

3-1. Main PCB

3 5
1 2 4 6 7 8 9

10

33
31 11
12
32

30 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13

29 28

No. CN # COLOR FUNCTION No. CN # COLOR FUNCTION


1 CN901 Red Power Trans Out (AC 17V) Magnetic contactor control
19 CN72 Blue
2 CN13 Black 5V for Interface Module (Compressor)

3 CN31 Red Communication with Indoor Unit(COM1) 20 CN74 Red Hot gas Bypass Valve

4 CN32 Yellow Communication with Outdoor Unit 21 CN71 White PWM Valve

5 CN12 Blue 12V for Interface Module 22 CN73 Yellow 4 Way Valve

6 CN92 Black Sub Micom Download 23 CN75 White EVI Bypass Valve

7 CN91 Black Main Micom Download Liquid Bypass valve for


24 CN86 Blue
DVI compressor
8 CN10 White Main Micom Download (N/A)
25 CN41 Blue Low Pressure Sensor
9 CN100 White Main Micom Download (N/A)
26 CN42 Red High Pressure Sensor
10 CN83 Yellow 3 Phase Detection
27 CN49 White Sump Sensor, Ambient Sensor
11 OPT1 White Mode Selector (Cooling/Heating)
28 CN48 Red EVI-In Sensor, EVI-Out sensor
12 CN51 Red CT Sensor
Oil Balance Sensor, Cond. Out
13 CN70 Black AC 208~230V Input 29 CN47 White
Sensor, Liquid Tube Sensor
14 CN76 Yellow Comp.1 CCH Comp. Discharge 1,2 Sensor,
30 CN44 White
15 CN15 White Comp.2 CCH Suction Sensor
16 CN81 Black Oil Valve 1 31 CN62 Blue Main EEV 1
17 CN82 Yellow Oil Valve 2 32 CN64 Blue EVI EEV
18 CN80 Red Liquid Bypass valve for FVI compressor 33 CN69 White Main-BLDC Driver PCB Connector

22
Downloaded from www.Manualslib.com manuals search engine
3-2. BLDC Driver PCB

34 39
35
No. CN # COLOR FUNCTION
36 34 CN701 Blue AC 208~230V Input

Outdoor units
35 GT2 White Power Trans In (AC 208~230V)
37 36 CN703 Black AC 208~230V Output
Main-BLDC Driver
37 CN501 White
PCB Connector
38 CN101 White Motor Signal
38
39 CN301 White Motor Power

3-3. Noise filter PCB

40 42

No. CN # COLOR FUNCTION


40 L/N Silver AC 208~230V Input
41 41 CN702 White Earth (Ground)
42 CN701 Blue AC 208~230V Output

3-4. CT PCB

43

No. CN # COLOR FUNCTION


43 CN61 Red Comp. 1,2 CT Output

23
Downloaded from www.Manualslib.com manuals search engine
4 Electrical wiring diagram

6 7 8 9

1 2 3
10
4 5

33
11

32 31 12
29
30 28

27 19 13
26 25 24 23 22 21 20 18 17 16 15 14

42

37 36 43

35

38
34
40 41

39

K13 K14 Unit option


On On MAIN unit
On Off SUB 1 unit
Off On SUB 2 unit

24
Downloaded from www.Manualslib.com manuals search engine
5 Sound pressure level

5-1. Operation sound level

1m(3.3ft) Unit: dB(A)


Model High Model High
Microphone RVXVHT075FE 58 RVXVHT250FE 62
RVXVHT100FE 58 RVXVHT275FE 63
RVXVHT125FE 60 RVXVHT300FE 63
RVXVHT150FE 60 RVXVHT325FE 64
Front RVXVHT175FE 61 RVXVHT350FE 64
RVXVHT200FE 61 RVXVHT375FE 64
RVXVHT225FE 62

Outdoor unit
 Note
 These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of
factors such as the construction of the particular room where the equipment is installed.
 Operation sound level may differ depending on operation and ambient conditions.

5-2. NC curves (Heat Pump)


1) RVXVHT075FE 2) RVXVHT100FE
70 70

65 65
NC 65 NC 65
60 60
Sound pressure level (dB)

Sound pressure level (dB)

NC 60 NC 60
55 55
NC 55 NC 55
50 50
NC 50 NC 50
45
45
NC 45
NC 45
40
40
NC 40
35 NC 40
35
NC 35
30 NC 35
30
NC 30
NC 30
25
63 125 250 500 1000 2000 4000 8000 25
63 125 250 500 1000 2000 4000 8000

Octave band center frequency(Hz) Octave band center frequency(Hz)

3) RVXVHT125FE 4) RVXVHT150FE
70 70

65 65
NC 65 NC 65
60 60
Sound pressure level (dB)

Sound pressure level (dB)

NC 60
NC 60
55
55
NC 55
NC 55
50
50
NC 50
45 NC 50
45
NC 45
40 NC 45
40
NC 40
35 NC 40
35
NC 35
30 NC 35
30
NC 30
25 NC 30
63 125 250 500 1000 2000 4000 8000
25
63 125 250 500 1000 2000 4000 8000

Octave band center frequency(Hz) Octave band center frequency(Hz)

25
Downloaded from www.Manualslib.com manuals search engine
5 Sound pressure level

5-2. NC curves (Heat Pump)


5) RVXVHT175FE 6) RVXVHT200FE
70 70

65 65

NC 65 NC 65
60 60
Sound pressure level (dB)

Sound pressure level (dB)


NC 60 NC 60
55 55

NC 55 NC 55
50 50

NC 50 NC 50
45 45

NC 45 NC 45
40 40

NC 40 NC 40
35 35

NC 35 NC 35
30 30

NC 30 NC 30
25 25
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency(Hz) Octave band center frequency(Hz)

7) RVXVHT225FE 8) RVXVHT250FE
70 70

65 65

NC 65 NC 65
60 60
Sound pressure level (dB)

Sound pressure level (dB)

NC 60 NC 60
55 55

NC 55 NC 55
50 50

NC 50 NC 50
45 45

NC 45 NC 45
40 40

NC 40 NC 40
35 35

NC 35 NC 35
30 30

NC 30 NC 30
25 25
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency(Hz) Octave band center frequency(Hz)

26
Downloaded from www.Manualslib.com manuals search engine
9) RVXVHT275FE 10) RVXVHT300FE
70 70

65 65

NC 65 NC 65
60 60
Sound pressure level (dB)

Sound pressure level (dB)


NC 60 NC 60
55 55

NC 55 NC 55

Outdoor units
50 50

NC 50 NC 50
45 45

NC 45 NC 45
40 40

NC 40 NC 40
35 35

NC 35 NC 35
30 30

NC 30 NC 30
25 25
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency(Hz) Octave band center frequency(Hz)

11) RVXVHT325FE 12) RVXVHT350FE


70 70

65 65

NC 65 NC 65
60 60
Sound pressure level (dB)

Sound pressure level (dB)

NC 60 NC 60
55 55

NC 55 NC 55
50 50

NC 50 NC 50
45 45

NC 45 NC 45
40 40

NC 40 NC 40
35 35

NC 35 NC 35
30 30

NC 30 NC 30
25 25
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Octave band center frequency(Hz) Octave band center frequency(Hz)

13) RVXVHT375FE
70

65

NC 65
60
Sound pressure level (dB)

NC 60
55

NC 55
50

NC 50
45

NC 45
40

NC 40
35

NC 35
30

NC 30
25
63 125 250 500 1000 2000 4000 8000

Octave band center frequency(Hz) 27


Downloaded from www.Manualslib.com manuals search engine
6 Operation limit

6-1. Cooling 6-2. Heating


50
(122)
45
(113)
40 25
(104) (77)
20
Outdoor temperature [ºC(ºF) DB]

35
(95) (68)

Range for warming up operation


Outdoor temperature [ºC(ºF) DB]
15
Range for pull down operation
30
(86) (59)
Range for operation

25 10
(77) (50)
20 5 Range for
(68) (41)
continuous
15 0
(59) (32) operation
10 -5
(50) (23)
5 -10
(41) (14)
0 -15
(32) (5)
-5 -20
(23) (-4) 10 15 20 25 30
10 15 20 25 30
(50) (59) (68) (77) (86) (50) (59) (68) (77) (86)

Indoor temperature [ºC(ºF) DB] Indoor temperature [ºC(ºF) DB]

28
Downloaded from www.Manualslib.com manuals search engine
7 Cycle operation mode

7-1. Description of cycle function parts

No Classification Description
1 A DVI (Digital Vapor Injection) compressor
2 B FVI (Fixed Vapor Injection) compressor
3 C Discharged gas distributor
4 D PWM (Pulse Width Modulation) solenoid valve
5 E Discharged gas temperature sensor of DVI compressor
6 F Discharged gas temperature sensor of FVI compressor 1
7 G Filter

Outdoor unit
8 H Oil separator
9 I Capillary tube from oil separator
10 J High pressure switch
11 K Hot gas bypass solenoid valve
12 L Discharged gas check valve
13 M High pressure sensor
14 N Reversing solenoid valve (4way valve)
15 O Heat exchanger of outdoor unit (Condensing unit)
16 P Ambient air temperature sensor
17 Q Cond_out temperature sensor
18 R Main EEV (Electronic Expansion Valve) for heating operation
19 S Liquid refrigerant check valve
20 T Liquid bypass solenoid valve DVI compressor
21 U Liquid bypass solenoid valve FVI compressor
22 V EVI EEV (Electronic Expansion Valve)
23 W Turbo Intercooler
24 X EVI_in temperature sensor
25 Y EVI_out temperature sensor
26 Z Liquid tube temperature sensor
27 a EVI bypass pilot solenoid valve
28 b Suction temperature sensor
29 c Accumulator
30 d Suction gas distributor
31 e Oil solenoid valve 1
32 f Oil solenoid valve 2
33 g Filter between oil balancing pipes
34 h Oil balancing service valve between units
35 i Low pressure sensor
36 j Check valve
37 k Crank case heater of DVI compressor
38 m Crank case heater of FVI compressor 1
39 n Sump(Base) temperature sensor
40 o Oil temperature sensor
41 p Capillary tube from hot gas bypass valve
42 q Capillary tube from liquid bypass valve for DVI compressor
43 r Capillary tube from liquid bypass valve for FVI compressor
44 s Liquid side service valve
45 t Liquid side filter
46 u Gas side service valve
47 v Gas side filter
48 w EEV of indoor unit
49 x Eva_in temperature sensor
50 y Heat exchanger of indoor unit (Evaporating unit)
51 z Eva_out temperature sensor
52 a Liquid side connection for wall mount unit
53 b Gas side connection for wall mount unit

29
Downloaded from www.Manualslib.com manuals search engine
7 Cycle operation mode

7-1. Description of cycle function parts


Category Description

Temperature Temperature sensor


1 Sensor
Pressure High / Low Pressure sensor

s
Solenoid Solenoid valve

s
Pilot Solenoid Pilot solenoid valve

E
Expansion Electronic Expansion Valve (EEV)
2 Valve
Reversing Reversing valve

Check Check valve

Service Service valve (Angle & ball type)

Pressure Switch High pressure switch (Mechanical type)


3 Switch & Heater
Heater H Electric heater

DVI (Digital Vapor Injection) Compressor


Compressor
FVI (Fixed Vapor Injection) Compressor

Accumulator Accumulator

4 Others Heat Exchanger Condensing or Evaporating unit

Sub cooler Turbo Intercooler or Sub cooler

Capillary Capillary tube

Filter Filter

30
Downloaded from www.Manualslib.com manuals search engine
7-2. Cycle diagrams
1) RVXVHT075/100FE (DVM PLUS III - 6/8 TON)

u
v

Outdoor units
O Q G

E
N S

p
L
J
K I
s

H
T
q s W
C
V

E
r s
D Y X
s
E F U
i b
A B d a Z
j s

k m
H
n H

s
s c t

o e f
s

g
h

31
Downloaded from www.Manualslib.com manuals search engine
7 Cycle operation mode

2) RVXVHT125FE (DVM PLUS III - 10 TON)

u
v

O Q G

E
N S

p
L
J
K I
s

H
T
q s W
C
V

E
r s
D Y X
s
E F U
i b
A B d a Z
j s

k m
H
n H

s
s c t
o e f
s

g
h

32
Downloaded from www.Manualslib.com manuals search engine
3) EEV kits & Indoor units
(1) MXD series (2) MEV series

2 rooms 3 rooms Single room

u u a
b b
E E E
a a
s

Outdoor units
E E

s s

(3) Indoor units

Indoor units with built-in EEV Indoor units without EEV (Wall mounted)

z y x z y x
u b
E
s a
w

33
Downloaded from www.Manualslib.com manuals search engine
34
Unit
4) Cooling operation

Cooling
⑦ E

Cooling operation
Heating operation

E

Downloaded from www.Manualslib.com manuals search engine


Cooling
E

s
⑧ Cooling

   
Outdoor unit
s

E
E

s
s
7 Cycle operation mode

s
Cooling
H H E

s

 

Indoor unit
Cooling
⑤ E

Low temperature & pressure gas


Low temperature & pressure liquid
High temperature & pressure gas Cooling
E
High temperature & pressure liquid

 
Outdoor unit
Unit
5) Heating operation

⑦ Heating
② E

Cooling operation
Heating operation
E

Downloaded from www.Manualslib.com manuals search engine


Heating
E

 
Heating
s ⑧

Outdoor unit
E
E

s
s

s
Heating
H H
⑤ E

 

Indoor unit
Heating
④ E

Low temperature & pressure gas


Low temperature & pressure liquid
High temperature & pressure gas Heating
E
High temperature & pressure liquid

   
Outdoor unit

35
Outdoor units
8 Cycle function parts

8-1. RVXVHT075/100FE

Accumulator Low pressure sensor


Oil separator

Suction temperature sensor


EVI EEV High pressure switch
High pressure sensor
PWM(Pulse Width Modulation) valve Liquid bypass valve
for FVI compressor
DVI(Digital Vapor Injection) compressor 1 Liquid bypass valve
for DVI compressor

Oil balancing valve FVI(Fixed Vapor Injection)


compressor 1

Fan

High
pressure
sensor
Liquid bypass valve
Hot gas Liquid tube for DVI compressor
bypass valve sensor
Liquid bypass valve
Suction for FVI compressor
temperature EVI bypass
sensor valve
4 way valve Hot gas Discharge
bypass temperature sensor
valve
Refrigerant Low pressure sensor
charging port in EVI EEV
heating mode Discharge
Liquid temperature sensor
service valve
Outdoor Cond_out
Main EEV temp.
sensor

Gas service
valve

Sump(Base) temp. sensor Oil balancing valve bracket

36
Downloaded from www.Manualslib.com manuals search engine
8-2. RVXVHT125FE

Liquid bypass valve for


FVI compressor
Liquid bypass valve for
DVI compressor
Low pressure sensor High pressure switch

High pressure sensor Oil separator

Accumulator

Outdoor units
Suction temperature sensor
EVI EEV

PWM(Pulse Width Modulation) valve

DVI(Digital Vapor Injection) compressor 1

Oil balancing valve FVI(Fixed Vapor Injection)


compressor 1

Fan

High
pressure
sensor
Suction
temperature Liquid tube Hot gas
sensor sensor bypass valve
Low pressure
EVI bypass valve sensor
4 way valve

High pressure
switch

Liquid bypass
EVI EEV valve for FVI
compressor
Liquid service
valve Liquid bypass
valve for DVI
Gas service
compressor
valve

Oil balancing Discharge temperature sensor


Outdoor Main EEV service valve
Oil balancing valve bracket
Refrigerant charging Discharge
port in heating mode temperature sensor Sump(Base) temp. sensor

37
Downloaded from www.Manualslib.com manuals search engine
8 Cycle function parts

8-3. A description of cycle function parts


No Cycle parts Functions
DVI compressor coupled with vapor injection controls the capacity 10 to 100% of its
DVI compressor
1 capacity.
(Digital Vapor Injection)
It enhances cooling and heating performance and COP with using vapor injection.
FVI compressor  VI compressor coupled with vapor injection is fixed compressor. It enhances cooling,
F
2
(Fixed Vapor Injection) heating performance and COP with using vapor injection.
|t is used for variation of digital compressor’s capacity. When the valve is open, the DVI
3 PWM valve
compressor keeps the unloading state, otherwise loading state.
It measures the temperature of compressor outlet. The main function of it is to protect
4 Discharge temp. sensor
compressor from overheating.
It separates oil and refrigerant discharged from the compressor and returns the oil into
5 Oil separator
compressor again.
6 High pressure switch It protects the system from abnormal high pressure. (Open : 4.1Mpa, Close : 3.5 Mpa)
 hen the suction pressure becomes abnormal low pressure, it opens.
W
7 Hot gas bypass valve
During the oil balance operation, it makes high pressure for the shell of compressor
 he main function of it controls the capacity of compressor in pursuit of target of high
T
8 High pressure sensor
pressure in heating operation by measuring the value of the system.
9 4way valve It enables to change operating mode into cooling and heating mode.
10 Ambient air temp. sensor It measures the temperature of ambient.
11 Cond_out temp. sensor It has application to know subcooling and the complete point of defrost.
It controls the amount of refrigerant entering outdoor’s heat exchanger in heating
12 Main EEV 1, 2
operation.
13 Liquid bypass valve When the compressor is overheating, it opens to make discharge temperature low.
It enables to secure sufficient subcooling and control the amount of vapor entering into
14 EVI EEV
vapor port of compressor.
 hrough turbo intercooler, heat is exchanged each other between saturated liquid
T
15 Turbo intercooler
refrigerant and a little expanded refrigerant.
16 EVI_in temp. sensor
These temperature sensors enable to control EVI EEV’s step to secure superheat.
17 EVI_out temp. sensor
It is used to know subcooling.
18 Liquid tube temp. sensor
(Subcooling = The saturated temp. of high pressure - Liquid tube temp.)
19 EVI bypass valve This valve closes during application of vapor injection.
20 Suction temp. sensor This is applied to know superheat in heating mode with the low pressure sensor.
21 Accumulator Ambient air temperature sensor (Tair)
22 Oil valve When oil balance operation happens, this valve opens.
 he main function of it is to control the capacity of compressor in pursuit of target of low
T
23 Low pressure sensor
pressure in cooling operation by measuring the low pressure.
With checking sump temperature of compressor, it prevents the compressor from liquid
24 Sump(Base) temp. sensor
back and overheating.
25 Oil temp. sensor While the oil balance is operating, it make a self-diagnosis of the oil valve.
In order to prevent outdoor heat exchanger from refrigerant accumulation in main cooling
26 Outdoor EEV valve
operation, this valve closes, otherwise Main EEV controls the amount of refrigerant.

38
Downloaded from www.Manualslib.com manuals search engine
III. Installation
1 Outdoor unit combinations.......................40
2 Space requirements.................................41
3 Placing the outdoor units..........................44
4 Electric specifications...............................45
5 Wiring works.............................................46

Installation
6 Refrigerant piping works...........................48
7 Option switches & function keys..............55
8 Error codes...............................................57

39
Downloaded from www.Manualslib.com manuals search engine
1 Outdoor unit combinations

1-1. Basic models


Total capacifities of
Maximum number of
Classification Capacity (Ton) Capacity (HP) Model the connectable
connectable indoor units
indoor units(MBH)
6 7.5 RVXVHT075FE 36 ~ 93.6 10
Single unit 8 10.0 RVXVHT100FE 48 ~ 124.8 10
10 12.5 RVXVHT125FE 60 ~ 156.0 14

1-2. Combinations
Basic model Total capacifities of Maximum number
Capacity Capacity
Classification the connectable of connectable
(Ton) (HP) RVXVHT075FE RVXVHT100FE RVXVHT125FE indoor units(MBH) indoor units
12 15.0 2 72 ~ 187.2 16
14 17.5 1 1 84 ~ 218.4 18
16 20.0 2 96 ~ 249.6 20
18 22.5 1 1 108 ~ 280.8 24
20 25.0 2 120 ~ 312.0 28
Module unit
22 27.5 1 2 132 ~ 343.2 30
24 30.0 3 144 ~ 374.4 32
26 32.5 2 1 156 ~ 405.6 34
28 35.0 1 2 168 ~ 436.8 36
30 37.5 3 180 ~ 468.0 40

40
Downloaded from www.Manualslib.com manuals search engine
2 Space requirements

2-1. Single installation


Unit : mm (inch)

Wall height unrestricted


300(12) or more[S2] 300(12) or more

Front 10(3/8)
or more 500(20) or more[S1]
10(3/8) or more 200(8) or more

2-2. Group installation


Unit : mm (inch)

Wall height unrestricted


300(12) or
more[S2]

Installation
300(12) or more

Front
10(3/8) 500(20) or
or more more[S1] Front Front
20(3/4) or more 20(3/4) or more 200(8) or
10(3/8) 400(16)
or more more
or more

20(3/4) or more 20(3/4) or more


300(12) 300(12)
or more or more

Front Front
600(24) or more 500(20) or more
Front 10(3/8) Front 10(3/8) or
or more more

10(3/8) 300(12) or
500(20) or more more
20(3/4)
or more 20(3/4) or more
10(3/8) or more
or more

Front wall height 1500mm(60in) and less


Rear wall height 500mm(20in) and less
1500(60”)

Side wall height Height unrestricted


500(20”)

If the height of the wall exceeds the above value,


Front : S1 + h1/2,
more space should be added to the front and
Rear : S2 + h2/2
rear space individually.

 Note
 The installation space mentioned above is minimum suggested clearance.
 To secure enough service space and performance of system, take account of more sufficient space.
 The required minimum space between outdoor units for service and performance of system is at least
100mm(4in).

41
Downloaded from www.Manualslib.com manuals search engine
2 Space requirements

2-3. Installing duct for horizontal exhaust discharge


It is necessary to install an air-discharge duct (field supply) to direct exhaust from the fan horizontally if it is difficult to provide a
minimum space of 2m(6.6 ft) between the air-discharge duct outlet and a nearby obstacle.

Upper floor Discharged air

Discharged air Louver

Suction air

Ex) Balcony Ex) Mechanical room

2-4. Installing the outdoor unit in harsh environments


In abnormally harsh environments such as cold and/or windy areas, sufficient countermeasures to guard against excessive wind
and snow should be taken to ensure the unit's correct operation. Snow-proof duct (field supply) should be fitted to the unit and
direct exposure to the wind should be avoided as much as possible. When the unit is expected to operate in cooling mode in
condition under 10°C(50°F), in snowy areas, in environments subject to strong winds or rain, install air inlet and outlet ducting as
shown in the below example

CAUTION
 The frame/foundation should be higher than expected snowfall.
 The foundation must be solid and the unit must be secured with anchor bolts.
 Be sure to install unit in a place strong enough to withstand its weight.
 When installing on a roof subject to strong wind, countermeasures must be taken to prevent the unit form being
overturned.
 Any lack of strength may cause unit to fall down, resulting in a personal injury.
 For more detailed information about installation, refer to installation manual.

42
Downloaded from www.Manualslib.com manuals search engine
252 417 252 417
(9-7/8) (16-3/8)
(9-7/8) (16-3/8)

2) RVXVHT125FE
560(22)

560(22)
1) RVXVHT075/100FE

2000(78-3/4)

880(34-5/8)
782(30-3/4)

Downloaded from www.Manualslib.com manuals search engine


2320(91-3/8)
1100(43-1/4)

1200(47-1/4)
560(22)
880(34-5/8) 112(4-3/8) 557(21-7/8)

560(22)
220(8-5/8) 1050(41-3/8) 1207(47-1/2)
880(34-5/8) 112(4-3/8) 557(21-7/8)
1588(62-1/2)
220(8-5/8) 1050(41-3/8) 1207(47-1/2) 1318(51-7/8)
1588(62-1/2) 2256(88-7/8)
1318(51-7/8)
2256(88-7/8)
668(26-1/4)
668(26-1/4) 532(21)
532(21)
2-5. Dimensional drawing of snow-proof duct

871(34-1/4)

871(34-1/4)
765(30-1/8) 550(21-5/8)
105(4-1/8)
105(4-1/8) 880(34-5/8)
880(34-5/8) 220(8-5/8) 1049(41-1/2)
220(8-5/8) 1049(41-1/4)
2226(87-10/16) 2227(87-11/16)

43
Unit : mm (inch)
Unit : mm (inch)

Installation
3 Placing the outdoor units

3-1. Anchor bolts position


A Unit : mm(inch)

745(29-5/16)

765(30-1/8)
Model RVXVHT075/100 RVXVHT125
A 880(34-5/8) 1200(47-1/4)
B 738(29) 1058(41-5/8)
Anchor bolt

3-2. Removing fasteners of compressor’s leg


(Only applied to RVXVHT125F)
(1) Open the bottom cabinet with screw driver.

The compressors are fastened with nuts in 4 places of only


following models.
RVXVHT125F

(2) Detach nut washer, washer and stopper nut from


compressors with a tool. Remove

Nut washer Washer Stopper nut

(3) Refasten the nut washer only.

CAUTION
 Pay your attention not to touch the copper pipes as detaching the fasteners.
 The stopper nut and washer should be removed.
If this work is not conducted correctly, it can cause outdoor unit to vibrate and make much noise.

44
Downloaded from www.Manualslib.com manuals search engine
4 Electric specifications

4-1. Basic models


Classification Capacity (Ton) Capacity (HP) Model MCCB(A) ELB
6 7.5 RVXVHT075FE 50 50A, 30mA 0.1 Second or less
Single unit 8 10.0 RVXVHT100FE 50 50A, 30mA 0.1 Second or less
10 12.5 RVXVHT125FE 60 60A, 30mA 0.1 Second or less

Units Power supply Comp. OFM


Model
Hz Volts Min. Max. MCA MFA RLA kW FLA
RVXVHT075FE 60 208~230 187 253 48.1 50 13.8 + 21.8 0.63 7
RVXVHT100FE 60 208~230 187 253 53.8 50 19.6 + 21.8 0.63 7
RVXVHT125FE 60 208~230 187 253 61.1 60 23.4 + 24.6 0.63 7
 All wiring, components and materials to be procured on the site must comply with the applicable local and national codes.

4-2. Combinations
Capacity Capacity Basic model
Classification MCCB(A) ELB
(Ton) (HP) RVXVHT075FE RVXVHT100FE RVXVHT125FE
12 15.0 2 50 + 50

Installation
14 17.5 1 1 50 + 50
16 20.0 2 50 + 50
18 22.5 1 1 50 + 60
20 25.0 2 60 + 60
Module unit
22 27.5 1 2 50 + 50 + 50
24 30.0 3 50 + 50 + 50
26 32.5 2 1 50 + 50 + 60
28 35.0 1 2 50 + 60 + 60
30 37.5 3 60 + 60 + 60
Units Power supply Comp. OFM
Model
Hz Volts Min. Max. MCA MFA RLA kW FLA
RVXVHT150FE 60 208~230 187 253 96.2 50+50 (13.8+21.8)×2 0.63+0.63 7+7
RVXVHT175FE 60 208~230 187 253 101.9 50+50 (13.8+21.8)+(19.6+21.8) 0.63+0.63 7+7
RVXVHT200FE 60 208~230 187 253 107.6 50+50 (19.6+21.8)×2 0.63+0.63 7+7
RVXVHT225FE 60 208~230 187 253 114.9 50+60 (19.6+21.8)+(23.4+24.6) 0.63+0.63 7+7
RVXVHT250FE 60 208~230 187 253 122.2 60+60 (23.4+24.6)×2 0.63+0.63 7+7
RVXVHT275FE 60 208~230 187 253 155.7 50+50+50 (13.8+21.8)+(19.6+21.8)×2 0.63+0.63+0.63 7+7+7
RVXVHT300FE 60 208~230 187 253 161.4 50+50+50 (19.6+21.8)×3 0.63+0.63+0.63 7+7+7
RVXVHT325FE 60 208~230 187 253 168.7 50+50+60 (19.6+21.8)×2+(23.4+24.6) 0.63+0.63+0.63 7+7+7
RVXVHT350FE 60 208~230 187 253 176.0 50+60+60 (19.6+21.8)+(23.4+24.6)×2 0.63+0.63+0.63 7+7+7
RVXVHT375FE 60 208~230 187 253 183.3 60+60+60 (23.4+24.6)×3 0.63+0.63+0.63 7+7+7
 The relationship between the starting time and the starting current (Digital Scroll Comp. + Fixed Scroll Comp)
Starting current

 RLA is based on the following conditions.


- Indoor temp. : 80˚F DB/ 67˚F WB RLA
- Outdoor temp. : 95˚F DB
 Voltage range
Units are suitable for use on electrical systems where voltage Starting time
supplied to unit terminal is not below or above listed range limits.
 Maximum allowable voltage variation between phases is 2%.
 Select wire size based on the value of MCA.
 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
 Abbreviations
- MCA: Min. Circuit Amps. (A)
MCA = 1.25
 X LOAD1 + LOAD2
(LOAD1: RLA of Digital Comp. / LOAD2: RLA of Fixed Comp. + FLA of Fan Motor)
- MFA: Max. Fuse Amps. (A)
- RLA: Rated Load Amps. (A)
- OFM: Outdoor Fan Motor
- FLA: Full Load Amps. (A)
- kW : Rated Motor Output (kW)
45
Downloaded from www.Manualslib.com manuals search engine
5 Wiring works

5-1. External connection diagram of DVM PLUS III


1) 3 phase 3 wires
3 phase 3 wires 3 phase 3 wires
(208~230V) (208~230V)
MCCB MCCB
+ELB +ELB
or or
ELCB ELCB

Earth
Earth
Main unit Sub unit

208~230V 208~230V
Indoor Outdoor Indoor Outdoor

OF1 OF2 R S T N OF1 OF2 R S T N

Earth Communication
cable among
Earth
Communication outdoor units
cable between
indoor and
outdoor units

• Connect the power cable of the outdoor unit after checking that R-S-T(3 phase 3 wires) is properly connected.
• The communication cable between indoor and outdoor units has no polarity.
• Arrange the cables using cable ties.

46
Downloaded from www.Manualslib.com manuals search engine
5-2. Caution of wiring work

3 phase 208~230V
To sub unit
communication cable
MCCB

ELCB

Outdoor Unit

CAUTION
 Make sure that all wiring should not contact with piping line during the field wiring work. If not, the vibration of
compressor can make a damage to wiring and piping. It may result in fire.

Installation
 Make sure to pass electrical wiring of the power cable (3 phase 3 wires) through a conduit hole of the front side.

Connecting the ring terminal of 3 phase cable (CV) Connecting the ring terminal of 3 phase cable (FCV)

Housing cover
Middle frame
Base line Base line

A A
250mm

B B
C C

A B C A B C

A B C A B C
30mm (1-1/8in) 60mm (2-3/8in) 90mm (3-1/2in) 30mm (1-1/8in) 60mm (2-3/8in) 90mm (3-1/2in)

1. Be sure to connect the suitable length of power wiring to the power wiring terminal block using ring terminal
above the figures.
2. Make sure to fix wiring using cable tie like above the figures.
3. After wiring, reinstall the housing cover which has an isolator into the middle frame.

47
Downloaded from www.Manualslib.com manuals search engine
6 Refrigerant piping works

6-1. Notice & Cautions


Cautions Correct piping work Wrong piping work

The refrigerant piping


should be the same level or
lower than connecting
position of piping to
outdoor units.

Piping work should be run


with side direction for
better uniform distribution
of refrigarant and oil like
next diagram.

Outdoor joint kits should


be installed in a horizontal
direction, even it is a low
pressure pipe.

Minimum
Horizontal length = 100mm
over 100mm(3-7/8in) (3-7/8in)

When the piping length


between outdoor and
branch joints is 2m(6.6 ft)
or more, a vertical trap has 200~300mm
(7-3/4~11-3/4in)
to be installed like right
diagram. Less than 1m(3.3 ft) 2m(6.6 ft) or over

2m(6.6 ft) or over

48
Downloaded from www.Manualslib.com manuals search engine
6-2. Example of piping layouts
Example of piping layouts for DVM PLUS III

Using
Y-joint

Installation
Using
Header
joint

49
Downloaded from www.Manualslib.com manuals search engine
6 Refrigerant piping works

6-3. Piping examples


Classification Branch with Y-joint Branch with Y and Header joint Branch with Header joint

One outdoor unit


i
b c d e f g p k
F G a a

installed
a b j
h i j k l m n
c d e f g h b c d e f g h
i

Multiple outdoor b c d e f
F
g
G
p
i
k

units installed
a a
a b j
h i j k l m n
c d e f g h b c d e f g h
i

Items Examples Remarks


a+b+c+d+e+f+g+p≤
Branch with Y joint
200(220)m / 656(722)ft
Piping Equivalent pipe length
200m(656ft) Branch with Y joint a+i+k≤200(220)m / 656(722)ft
(Equivalent Y-joint:0.5m(1.6ft),
220m(722ft) and Header joint a+b+h≤200(220)m / 656(722)ft
piping) Header:1m(3.2ft)
Branch with
Outdoor a+i≤200(220)m / 656(722)ft
header joint
~
Max. a+b+c+d+e+f+g+p+h+i+j+k+l+m+n≤
Indoor unit Branch with Y joint
piping 1000m / 3281ft
length 1000m Branch with Y joint a+b+c+d+e+f+g+p+h+i+j+k≤
Total piping
(3281ft) and Header joint 1000m / 3281ft
Branch with a+b+c+d+e+f+g+p+h+i≤
Header joint 1000m / 3281ft
Outdoor Piping 10m(33ft) r≤10 (33ft), s≤10 (33ft), t≤10m (33ft)
~ Equivalent
Outdoor unit piping 13m(43ft) r≤13 (43ft), s≤13 (43ft), t≤13m (43ft)
Outdoor ~ 50m(164ft)
Piping H1≤50m (164ft) / 40m (131ft)
Indoor unit 40m(131ft)
Level Indoor ~
Piping 15m(49ft) H2≤15m (49ft)
difference Indoor unit
Outdoor ~
Piping 5m(16ft) H3≤5m (16ft)
Outdoor unit
The first Piping 45m(148ft) b+c+d+e+f+g+p≤45 m(148ft), i≤45m(148ft)
Allowable
branch Only apply
length
~ DVM PLUS III
after Piping 90m(295ft) It needs to satisfy required conditions
the farthest (DVM PLUS III HR
branch
indoor unit exclusion)

Distribution kit Model Remarks


From distribution kit to 3m
MEV-A13SA / MEV-A16SA (For 1 indoor unit)
indoor unit (10ft)
MXD-A13K116A / MXD-A13K200A / MXD-A16K200A / For wall-mounted &
Allowable
From distribution kit to 20m MXD-A22K200A (For 2 indoor units) ceiling indoor unit
indoor unit (66ft) MXD-A13K216A / MXD-A13K300A / MXD-A16K213A /
MXD-A16K300A (For 3 indoor units)
Required condition Example
The first branch
If the sum of pipe length (b+c+d+e+f+g+p) is over 45m (148ft), (but
joint ~
not exceed : 90m/295ft) increase pipe size of b,c,d,e,f,g (b,c,d,e,f,g :
the farthest
pipe 1 size up)
indoor unit
If main pipe size is not increased,a+bx2+cx2+dx2+ex2+fx2+gx2+h+i
+j+k+l+m+n+p≤1000m (3281ft)
Total pipe length b c d e f g p
If main pipe size is not increased, ax2+bx2+cx2+dx2+ex2+fx2+gx2+h a
F G

+i+j+k+l+m+n+p≤1000m (3281ft) h i j k l m n

Each Y-joint ~
h,I,j,..p≤45m (148ft)
each indoor
The difference between the distance of the outdoor unit to the farthest
Between
indoor unit and the distance of the outdoor unit to the farthest indoor
indoor units
unit ≤ 45m (148ft) (a+b+c+d+e+f+g+p)-(a+h) ≤ 45m (148ft)
50
Downloaded from www.Manualslib.com manuals search engine
6-4. Pipe selection
Outdoor unit connection pipe size : (A1), (A2), (A3)
A1 : Select the pipes according to the outdoor unit capacity with
10Ton 8Ton 8Ton
following table.
Outdoor unit Pipe size (O.D) Oil balancing
Liquid Gas pipe size
Ton HP
(E) mm inches mm inches mm(inches)
(A1) (A1)
6 7.5 Ø19.05 Ø3/4
Ø9.52 Ø3/8
(A1) (A2) (A3) (B) 8 10.0 Ø22.23 Ø7/8 -
(F)
10 12.5 Ø12.70 Ø1/2 Ø28.58 Ø1-1/8
(D)
A2 : Select the pipes according to sum of outdoor unit capacities
behind the outdoor joint with following table.
(C)
Outdoor unit Pipe size (O.D) Oil balancing
 Example) 26 Ton Liquid Gas pipe size
Ton HP
Pipe size (O. D.mm) mm inches mm inches mm(inches)
Ton HP Mark Liquid Gas 12 15.0 Ø12.70 Ø1/2
14 17.5
mm inches mm inches Ø28.58 Ø1-1/8 Ø6.35
16 20.0 Ø15.88 Ø5/8
8 10 (A1) Ø9.52 Ø3/8 Ø22.23 Ø7/8 (Ø1/4)

Installation
18 22.5
8 10 (A1) Ø9.52 Ø3/8 Ø22.23 Ø7/8 20 25.0 Ø19.05 Ø3/4 Ø34.93 Ø1-3/8
10 12.5 (A1) Ø12.70 Ø1/2 Ø28.58 Ø1-1/8
A3 : Select the main pipe of outdoor units with the following table.
18 22.5 (A2) Ø15.88 Ø5/8 Ø28.58 Ø1-1/8
Outdoor unit Pipe size (O.D) Oil balancing
26 32.5 (A3) Ø19.05 Ø3/4 Ø34.93 Ø1-3/8 pipe size
Liquid Gas
Ton HP
mm inches mm inches mm(inches)
6 7.5 Ø19.05 Ø3/4
Ø9.52 Ø3/8
8 10.0 Ø22.23 Ø7/8 -
10 12.5
Ø12.70 Ø1/2
12 15.0
14 17.5 Ø28.58 Ø1-1/8
16 20.0 Ø15.88 Ø5/8
18 22.5
20 25.0 Ø6.35
22 27.5 (Ø1/4)
24 30.0
Ø19.05 Ø3/4 Ø34.93 Ø1-3/8
26 32.5
28 35.0
30 37.5
A3 : Select the main pipe of outdoor units with the following table when
if the farthest indoor unit’s length is over 90m(295ft).
Outdoor unit Pipe size (O.D) Oil balancing
Liquid Gas pipe size
Ton HP
mm inches mm inches mm(inches)
6 7.5 Ø22.23 Ø7/8
Ø12.70 Ø1/2
8 10.0 -
Ø28.58 Ø1-1/8
10 12.5
Ø15.88 Ø5/8
12 15.0
14 17.5
16 20.0 Ø19.05 Ø3/4
18 22.5
Ø34.93 Ø1-3/8
20 25.0 Ø6.35
22 27.5 (Ø1/4)
24 30.0
Ø22.23 Ø7/8
26 32.5
28 35.0
Ø41.28 Ø1-5/8
30 37.5
*A1 : Pipes to the outdoor unit (Liquid, Gas)
*A2 : Pipes between outdoor joint kits (Liquid, Gas)
*A3 : Main pipes (Liquid, Gas)
51
Downloaded from www.Manualslib.com manuals search engine
6 Refrigerant piping works

Pipe size between branch joints : (B) Tempers of pipe


Select the pipe size according to the capacity sum of indoor units
which are connected below this pipe.
Pipe size (O.D) Pipe size Thickness
Total Indoor unit’s Material
Liquid Gas mm inches mm inches
capacity
mm inches mm inches Ø6.35 Ø1/4
0.7 0.027
51MBH Ø15.88 Ø5/4 Ø9.52 Ø3/8 C1220T-O
51~79MBH Ø9.52 Ø3/8 Ø19.05 Ø3/4 Ø12.70 Ø1/2 0.8 0.031 (Annealed)
79~96MBH Ø22.23 Ø7/8 Ø15.88 Ø5/8 1.0 0.039
96~138MBH Ø19.05 Ø3/4
Ø12.70 Ø1/2 0.9 0.035
138~160MBH Ø28.58 Ø1-1/8 Ø22.23 Ø7/8
160~240MBH Ø15.88 Ø5/8 Ø25.40 Ø1 1.0 0.039
240~336MBH Ø28.58 Ø1-1/8
Ø19.05 Ø3/4 Ø34.93 Ø1-3/8 1.1 0.043 C1220T-1/2H
336~468MBH Ø31.75 Ø1-1/4
(Drawn temper)
Ø34.93 Ø1-3/8 1.2 0.047
Pipe size between branch joints and indoor unit (C) Ø38.10 Ø1-1/2 1.35 0.053
Select the pipe size according to the indoor unit’s capacity. Ø44.45 Ø1-3/4 1.6 0.062
Pipe size (O.D) Ø50.80 Ø2 2.0 0.079
Indoor unit’s
Liquid Gas
capacity
mm inches mm inches CAUTION
6~20MBH Ø6.35 Ø1/4 Ø12.70 Ø1/2
24~48MBH Ø9.52 Ø3/8 Ø15.88 Ø5/8 Make sure to use C1220T-1/2H pipe for more than
Ø19.05mm(3/4in). In case of using C1220T-O pipe
Branch joiat : (D), (E), (F) for Ø19.05mm(3/4in) pipe may be broken, which
 Branch joint of outdoor unit’s multi connection (D) can result in an injury.
Outdoor multi Capacity of outdoor
Model
connection unit
branch joint (D) MXJ-T3819K 12 ~ 30 Ton
 First branch joint (E)
Select branch joint according to the outdoor unit’s capacity.
Model Capacity of outdoor unit
MXJ-YA2512K 6, 8,10 Ton
Y-joint MXJ-YA2812K 12 Ton
(E) MXJ-YA2815K 14,16,18,20 Ton
MXJ-YA3119K 22, 24, 26, 28 Ton
MXJ-YA3819K 30 Ton

 Branch joint (F)


Select the pipe size according to the capacity sum of
indoor units which are connected below this pipe.
1) Y-joint
Model Capacity of outdoor unit
MXJ-YA1509K 51 MBH and below
MXJ-YA2512K Over 51 MBH ~ 138 MBH and below
Y-joint
MXJ-YA2812K Over 138 MBH ~ 160 MBH and below
(F)
MXJ-YA2815K Over 160 MBH ~ 240 MBH and below
MXJ-YA3119K Over 240 MBH ~ 336 MBH and below
MXJ-YA3819K Over 336 MBH ~ 468 MBH and below

2) Header joint
The connect-
Total Indoor unit’s
Model able quantity of
Header capacity indoor units
joint MXJ-HA2512K 160 MBH and below 4
(F) MXJ-HA3115K Over 160 MBH~ 240 MBH 8
MXJ-HA3819K Over 240 MBH 8

52
Downloaded from www.Manualslib.com manuals search engine
6-5. Additional refrigerant charging

• Additional refrigerant has to be charged according to the length and size of


liquid pipe.
Liquid pipe size Additional Factory charging
Outdoor unit
(O.D.) refrigerant charging kg lbs
Ø12.70(1m/3.3ft)
mm inches kg/m lbs/ft RVXVHT075FE 6.5 14.330
Ø12.70(5m/16.4ft) Ø19.05(5m/16.4ft) Ø6.35 Ø1/4 0.020 0.0134 RVXVHT100FE 7.5 16.535
Ø15.88(10m/32.8ft) Ø9.52 Ø3/8 0.060 0.0403 RVXVHT125FE 9.0 19.824
Ø12.70 Ø1/2 0.125 0.0840
Ø15.88 Ø5/8 0.180 0.1210
Ø9.52(5m/16.4ft) Ø19.05 Ø3/4 0.270 0.1814
Ø15.88(15m/49.2ft) Ø22.23 Ø7/8 0.350 0.2352
Ø9.52(7m/22.9ft) Additional refrigerant charging of
Ø12.70(15m/49.2ft) kg/m lbs/ft Remarks
distribution kit (kg/m)
Regardless of the liquid pipe size,
Ø9.52(8m/26.2ft)
additional refrigerant charging is For wall-mounted &
0.01 0.0067
0.01kg(0.0067lbs) per meter(ft) after ceiling Indoor unit
distribution kit.

Installation
Ø6.35(5m/16.4ft)
Ø6.35(5m/16.4ft) • Example of additional refrigerant charging.
Ø6.35(5m/16.4ft) Pipe length is as below without distribution kit.
Ø9.52(5m/16.4ft) Total piping Additional
Liquid pipe size (O.D.)
lengths refrigerant charging
mm inches m ft kg lbs
Ø6.35 Ø1/4 15 49.21 0.300 0.6614
Ø9.52 Ø3/8 25 82.02 1.500 3.3069
Ø12.70 Ø1/2 21 68.90 2.625 5.7871
Ø15.88 Ø5/8 25 82.02 4.500 9.9208
Ø19.05 Ø3/4 5 16.40 1.350 2.9762
Total 10.275 22.652

CAUTION
Total refrigerant amount of the system must be less then 100kg(220lbs). If total refrigerant amount of system is over
100kg(220lbs) more, the system has to be divided into smaller system, each containing less than 100kg(220lbs).

53
Downloaded from www.Manualslib.com manuals search engine
6 Refrigerant piping works

6-6. Equivalent length calculations


 Equivalent length calculation method
Equivalent length = actual pipe length(m) + number of ‘Y-joint’×0.5(m)+number of ‘Header joint’×1.0(m)+
number of elbows×equivalent length of each elbow

Elbow Equivalent length


Type
Pipe size(O.D.) Equivalent length m ft
mm inches m ft Y joint 0.5 1.64
Ø9.52 Ø3/8 0.18 0.59 Header joint 1.0 3.28
Ø12.70 Ø1/2 0.20 0.66
Ø15.88 Ø5/8 0.25 0.82
Ø19.05 Ø3/4 0.35 1.15
Ø22.23 Ø7/8 0.40 1.31
Ø25.40 Ø1 0.45 1.48
Ø28.58 Ø1-1/8 0.50 1.64
Ø31.75 Ø1-1/4 0.55 1.80
Ø34.93 Ø1-3/8 0.58 1.90
Ø38.10 Ø1-1/2 0.60 1.97
Ø41.30 Ø1-5/8 0.70 2.30
Ø44.45 Ø1-3/4 0.75 2.46
Ø50.80 Ø2 0.80 2.62

54
Downloaded from www.Manualslib.com manuals search engine
7 Option switches & function keys

7-1. Option switches

F012

BC E
3456
D
789A

Switch Setting Function Remarks

Installation
Setting total quantity of Installed indoor units Main unit required only
SW01/SW02 Main unit required only Ex) A s 12 indoor units were installed,
SW01 : The tens digit, SW02 : The units digit SW01:1, SW02: 2
K5 On Manual address setting
SW03
Off Auto address setting
K9 K10 Target evaporating temperature (°C/°F)
On On 7~9(44.6 ~ 48.2)
SW04 On Off 5~7(41.0~44.6) Cooling capacity compensation
Off On 9~11(48.2~51.8)
Off Off 10~12(50.0~53.6)
K11 K12 Target high pressure (kgf /cm2, psig, kPa)
On On 30.0, 426, 2941
SW04 On Off 31.5, 448, 3089
Heating capacity compensation
Off On 33.0, 469, 3236
Off Off 27.0, 384, 2647
K13 K14 Outdoor unit’s address
On On Outdoor unit’s address : No 1 Main unit
On Off Outdoor unit’s address : No 2 Sub I unit
Off On Outdoor unit’s address : No 3 Sub 2 unit
Off Off Outdoor unit’s address : No 4 Sub 3 unit
SW05
K15 K16 Maximum current control
On On Standard Factory default
On Off 90% of standard peak current value
Off On 80% of standard peak current value
Off Off Not use
On Since supplying power, first oil return operation happens after 5hrs and then 7 hrs.
K17
Off Since supplying power, first oil return operation happens after 2hrs and then 2 hrs.
On Standard
K18 Defrost period setting
Off Shorten defrost period by 20% approximately
SW06
On Standard fan step
K19
Off Fan step compensation (Maximum step) 7.5/10 HP : 19 Steps, 12.5 HP : 23 Steps
On Normal
K20
Off Night’s quiet mode
 Factory
 default
SW01, SW02, SW09 : ‘0’
SW03 ~ SW06 : ON

55
Downloaded from www.Manualslib.com manuals search engine
7 Option switches & function keys

7-2. Function keys

K1

K2  LED display alphabet SEG 1 SEG 2 SEG 3 SEG 4


F012

BC E
3456
D
K3
789A

K4

K1 Key function Display LED


Push 1st time Refrigerant charging in heating operation “K” “1” “BLANK” “BLANK”
Push 2nd time Test run in heating mode “K” “2” “BLANK” “BLANK”
Push 3rd time Pump out operation in heating mode (Outdoor unit’s address : NO 1) “K” “3” “BLANK” “1”
Push 4th time Pump out operation in heating mode (Outdoor unit’s address : NO 2) “K” “3” “BLANK” “2”
Push 5th time Pump out operation in heating mode (Outdoor unit’s address : NO 3) “K” “3” “BLANK” “3”
Push 6th time Pump out operation in heating mode (Outdoor unit’s address : NO 4) “K” “3” “BLANK” “4”
Push 7th time Open all valve of outdoor unit for vacuum preparation (Outdoor unit’s address : NO 1) “K” “4” “BLANK” “1”
Push 8th time Open all valve of outdoor unit for vacuum preparation (Outdoor unit’s address : NO 2) “K” “4” “BLANK” “2”
Push 9th time Open all valve of outdoor unit for vacuum preparation (Outdoor unit’s address : NO 3) “K” “4” “BLANK” “3”
Push 10th time Open all valve of outdoor unit for vacuum preparation (Outdoor unit’s address : NO 4) “K” “4” “BLANK” “4”
Push 11th time Open all valve for vacuum preparation (Total outdoor units, indoor unit and MCU units) “K” “4” “BLANK” “4”
Push 12th time Return to normal view mode -
K2 Key function Display LED
Push 1st time Refrigerant charging in cooling operation “K” “5” “BLANK” “BLANK”
Push 2nd time Test run in cooling mode “K” “6” “BLANK” “BLANK”
Push 3rd time Pump down operation in cooling mode (All outdoor units) “K” “7” “BLANK” “BLANK”
Pipe checking (Check whether the pipe connection of MCU correspond with indoor unit’s
Push 4th time “K” “8” “BLANK” “BLANK”
address in HR system.)
th
Push 5 time Judgment system of refrigerant amount “K” “9” “BLANK” “BLANK”
Push 6th time Return to normal view mode -
K3 Key function Display LED
Push 1st time Reset -

Display LED
K4 Key function
SEG 1 SEG 2, 3, 4
Push 1st time Outdoor capacity 1 Ex) 16 HP  Off, 1, 6
Push 2nd time Digital comp loading time 2 Ex) Loading 13 sec  Off, 1, 3
Push 3rd time High pressure (kg/cm2) 3 Ex) High pressure 15.2 (kg/cm2)  1, 5, 2
Push 4th time Low pressure (kg/cm2) 4 Ex) Low pressure 4.3 (kg/cm2)  0, 4, 3
Push 5th time Discharge temperature of compressor 1 5 Ex) 87°C  0, 8, 7
Push 6th time Discharge temperature of compressor 2 6 Ex) 87°C  0, 8, 7
Push 7th time Discharge temperature of compressor 3 7 Ex) 87°C  0, 8, 7
Push 8th time CT sensor value of compressor 1 8 Ex) 2A  0, 0, 2
Push 9th time CT sensor value of compressor 2 9 Ex) 2A  0, 0, 2
Push 10th time CT sensor value of compressor 3 A Ex) 2A  0, 0, 2
Push 11th time Suction temperature B Ex) -5 °C  -, 0, 5
Push 12th time Cond_out temperature C Ex) 35 °C  0, 3, 5
Push 13th time Liquid tube temperature D Ex) 35 °C  0, 3, 5
Push 14th time Oil temperature sensor on oil balancing pipe E Ex) 35 °C  0, 3, 5
Push 15th time Sump temperature of compressor 1 F Ex) 35 °C  0, 3, 5
Push 16th time Ambient air temperature G Ex) 35 °C  0, 3, 5
Push 17th time EVI_in temperature H Ex) 35 °C  0, 3, 5
Push 18th time EVI_out temperature I Ex) 35 °C  0, 3, 5
Push 19th time Main EEV1 step J Ex) 2000 steps  2, 0, 0
Push 20th time Main EEV2 step K Ex) 2000 steps  2, 0, 0
Push 21th time EVI EEV step L Ex) 300 steps  3, 0, 0
Push 22th time HR EEV step M Ex) 300 steps  3, 0, 0
Push 23th time Fan step ( SSR or BLDC ) N Ex) 13 steps  Off, 1, 3
Push 24th time Version
56
Downloaded from www.Manualslib.com manuals search engine
8 Error codes

F012

BC E
3456
D
789A

   

Display alphabet at  Description


E It displays from error 101 to error 700.
P It displays from error 701 to error 800.
It displays the address of outdoor unit.
U
Ex) U200 : Outdoor unit 1, U201: Outdoor unit 2, U202: Outdoor unit 3, U203 : Outdoor unit 4
It displays the address of indoor unit.
A
Ex) A000 : Indoor address 1, A001: Indoor address 1, A002 : Indoor address 2

No. Error code Description


1 E-101 Communication error in indoor unit. It displays when the indoor unit receives no data from the outdoor unit.

Installation
2 E-102 Communication error between indoor and outdoor unit. It displays in indoor unit.
3 E-121 Room temperature sensor of indoor unit. (Open or Short)
4 E-122 Eva_in temperature sensor of indoor unit. (Open or Short)
5 E-123 Eva_out temperature sensor of indoor unit. (Open or Short)
6 E-124 Communication error between indoor and outdoor unit. It displays in outdoor unit.
7 E-125 Mid 2 temperature sensor of indoor unit. (Open or Short)
8 E-128 Eva_in temperature sensor is detached from eva_in pipe of indoor unit.
9 E-129 Eva_out temperature sensor is detached from eva_out pipe of indoor unit.
Eva_in and Eva_out temperature sensors are detached from eva_in and out pipes of indoor unit at the same
10 E-130
time.
11 E-137 VOC sensor of ERV product. (Open or Short)
12 E-138 Gas sensor of ERV product. (Open or Short)
13 E-139 CO2 sensor of ERV product. (Open or Short )
14 E-151 EEV opening error of indoor unit (2nd detection)
15 E-152 EEV closing error of indoor unit (2nd detection)
16 E-153 Floating switch error of indoor unit (2nd detection)
17 E-154 RPM feed back error of indoor unit.
18 E-155 RPM feed back error of indoor unit. (The second motor of indoor unit)
Mixed operation mode of indoor units. It occurs when outdoor unit is operating or going to operate in
19 E-161 cooling mode(or heating mode) and then other indoor unit is going to operate in heating mode (or cooling
mode).
20 E-162 EEPROM error of MICOM. (Physical damage)
21 E-163 Option code error of indoor unit’s EEPROM.
22 E-167 Option setting error of indoor unit’s dip switch.
Temperature display setting error for USA market product.
23 E-170
(Mixed setting with Celsius and Fahrenheit temperature)
24 E-180 Opening error of cooling and heating solenoid valve simultaneously in MCU (1st detection)
25 E-181 Opening error of cooling and heating solenoid valve simultaneously in MCU (2nd detection)
26 E-185 Cross wiring error between communication and power of indoor unit.
27 E-190 No matching between indoor unit’s address and eva_in sensor in pipe checking operation.
28 E-191 No matching between indoor unit’s address and eva_out sensor in pipe checking operation.
29 E-199 It displays when pipe checking operation is not operated.
Communication error between indoor and outdoor unit (Tracking failure or the setting quantity of indoor unit
30 E-201
on outdoor unit’s PCB differs from the quantity of installed indoor unit.)
Communication error between indoor and outdoor unit.
31 E-202
(After tracking is completed, and then no response from indoor unit)
32 E-203 Communication error between main and sub outdoor unit
33 E-204 The setting quantity of MCU on outdoor unit’s PCB differs from the quantity of installed MCU.

57
Downloaded from www.Manualslib.com manuals search engine
8 Error codes

No. Error code Description


34 E-210 Communication error between MCU and outdoor unit.
35 E-211 Indoor unit’s address overlapped on the MCU.
35 E-213 No matching between installed indoor unit’s address and indoor unit’s address on the MCU.
35 E-214 Setting error of MCU’s quantity in outdoor unit’s PCB
36 E-215 Indoor unit’s address setting error on the MCU. (There is same address among the MCUs)
Setting error of indoor unit activating dip switch on MCU’s PCB. (The indoor unit is not connected with the
37 E-216
MCU’s port but indoor unit activating dip switch on MCU’s PCB turns on.)
Setting error of indoor unit activating dip switch on MCU’s PCB. (The indoor unit is connected with the
38 E-217
MCU’s port but indoor unit activating dip switch on MCU’s PCB turns off.)
Setting error of indoor unit’s quantity on MCU’s PCB.
39 E-218
(The quantity of installed indoor units exceeds the setting number of the MCU’s PCB.)
40 E-221 Ambient air temperature sensor of outdoor unit. (Open or Short)
41 E-226 Ambient air temperature sensor is detached from outdoor unit.
42 E-231 Cond_out temperature sensor of main outdoor unit. (Open or Short)
43 E-236 Cond_out temperature sensor of the outdoor unit. (Open or Short)
44 E-237 Cond temperature sensor of outdoor unit. (Open or Short)
45 E-241 Cond_mid temperature sensor is detached from sensor hold of the pipe.
46 E-246 Cond_out 1 temperature sensor is detached from sensor hold of the pipe.
47 E-251 Discharge temperature sensor of compressor 1. (Open or Short)
48 E-256 Discharge temperature sensor of compressor 1. (Open or Short)
49 E-257 Discharge temperature sensor of compressor 2. (Open or Short)
50 E-258 Discharge temperature sensor of compressor 3. (Open or Short)
51 E-261 Discharge temperature sensor of compressor 1 is detached from the sensor hold of the pipe.
52 E-262 Discharge temperature sensor of compressor 1 is detached from the sensor hold of the pipe.
53 E-263 Discharge temperature sensor of compressor 2 is detached from the sensor hold of the pipe.
54 E-264 Discharge temperature sensor of compressor 3 compressor is detached from the sensor hold of the pipe.
55 E-265 Sump(Base) temperature sensor of main unit’s compressor is detached from the base of the compressor.
56 E-266 Sump(Base) temperature sensor of sub1 unit’s compressor is detached from the base of the compressor.
57 E-267 Sump(Base) temperature sensor of sub2 unit’s compressor is detached from the base of the compressor.
58 E-268 Sump(Base) temperature sensor of sub3 unit’s compressor is detached from the base of the compressor.
58 E-269 Suction temperature sensor is detached from the sensor hold of the pipe.
59 E-271 Sump(Base) temperature sensor of compressor 1. (Open or Short)
60 E-276 Sump(Base) temperature sensor of compressor 1. (Open or Short)
61 E-277 Sump(Base) temperature sensor of compressor 2. (Open or Short)
62 E-278 Sump(Base) temperature sensor of compressor 3. (Open or Short)
63 E-291 High pressure sensor. (Open or Short)
64 E-296 Low pressure sensor. (Open or Short)
65 E-307 Oil balance temperature sensor. (Open or Short)
66 E-308 Suction temperature sensor. (Open or Short)
67 E-311 Double tube / Liquid temperature sensor. (Open or Short)
68 E-312 Main cooling solenoid valve opening error.
69 E-321 EVI_in temperature sensor. (Open or Short)
70 E-322 EVI_out temperature sensor. (Open or Short)
71 E-407 Compressor stop by high pressure’s protection control.
72 E-410 Compressor stop by low pressure’s protection control.
73 E-413 Protection control by sump sensor.
74 E-416 Compressor stop by discharge temperature’s protection control.
75 E-425 Reverse phase or phase open. (3ø Wiring of outdoor unit, R-S-T-N)
76 E-428 Compressor stop by abnormal compression ratio.
77 E-431 Self-diagnosis of oil solenoid valve. (Open and Close error)
78 E-438 EVI EEV opening error.
79 E-440 Prohibition of heating operation when the ambient air temperature is over 30°C
80 E-442 Prohibition of refrigerant charging with heating operation when outdoor ambient air temperature is over 15°C.
81 E-443 Prohibition of operating when the high pressure of system is too low.
82 E-452 Power failure temporarily or zero crossing error.
58
Downloaded from www.Manualslib.com manuals search engine
No. Error code Description
83 E-453 Overload error of outdoor unit’s motor (by temperature).
84 E-454 RPM error of outdoor unit’s motor
85 E-455 IPM overload error of outdoor unit’s motor (by temperature)
86 E-456 Over Current error of outdoor unit’s motor
87 E-457 Backlash error of outdoor unit’s motor
88 E-458 Over current of CT sensor. (Or outdoor’s motor locking of inverter system.)
89 E-461 Low current of CT sensor. (Or compressor starting failure of inverter system.)
Liquid refrigerant incoming protection error in digital / 1st fixed scroll compressor with sump temperature
90 E-477
sensor.
91 E-559 Indoor unit stop by unidentified error from outdoor units.
92 E-560 Option switch setting error of outdoor unit. (napplicable option switch turns on.)
93 E-561 Fan RPM error of ERV SA (Supply air).
94 E-562 Fan RPM error of ERV RA (Return air).
95 E-563 Model mismatching of Indoor unit.
96 E-601 Communication error between remote controller and indoor unit.
97 E-602 Communication error between master and slave wired remote controller.
98 E-603 Communication packet error (Baud rate error)

Installation
99 E-604 Tracking failure error between wired remote controller and indoor unit.
Communication error.
100 E-605
(7-day scheduler  Wired remote controller or 7-day scheduler  Centralized controller)
101 E-606 COM1/COM2 communication setting error. (Wired remote controller)
102 E-607 Two masters of wired remote controllers were installed in one COM2 communication line.
103 E-608 Can’t detect ERV controller.
104 E-609 Indoor unit is not detected for synchronous control.
105 E-610 Communication error between centralized controller and interface module.
106 E-611 Communication error between DMS and centralized controller.
107 E-613 Communication error between DMS and SIM interface module.
108 E-614 Communication error between SIM and power meter.
109 E-615 Communication error between interface module and indoor unit.
110 E-616 Communication error between interface module and outdoor unit.
111 E-618 The connected indoor units to ERV exceeded 16 units.
112 E-619 Mixed temperature display setting of indoor units which was connected to MWR-WS00 (Celsius/Fahrenheit)
113 E-620 Temperature display setting error of MWR-WS00 (Celsius/Fahrenheit)
114 E-621 Option switch setting error of wired remote controller (Master/Slave)
115 E-652 Two wired remote controllers were set to the master mode. (COM 1 wiring)
116 E-653 Room temperature sensor in the wired remote controller. (Open or Short)
117 E-654 Memory data error in the wired remote controller. (MWR-WS00)
118 P-701 Floating switch error of indoor unit. (1st detection)
119 P-702 EEV closing error of indoor unit. (1st detection)
120 P-703 EEV opening error of indoor unit. (1st detection)

59
Downloaded from www.Manualslib.com manuals search engine
DVM Technical Data Book

DVM

Downloaded from www.Manualslib.com manuals search engine


Downloaded from www.Manualslib.com manuals search engine
Outdoor Units

2009.12
DB98-31306A(1)

Samsung Electronics Co., LTD.


Digital Air Solution Business Team, SE Dept.
Head Office (Suwon Korea) 416, Maetan-3Dong, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 443-742
TEL : 82-31-200-6119 Website : www.dvmsystem.com Email: Airconditioner@samsung.com

 Specification may be subject to change without prior notice for the continuous product improvement.

Downloaded from www.Manualslib.com manuals search engine

You might also like