DVM Plus III
2010
2 Dimensional drawing 20
2
Downloaded from www.Manualslib.com manuals search engine
Products
III. Installation
1 Outdoor unit combinations 40
Outdoor units
2 Space requirements 41
3 Placing the outdoor units 44
4 Electric specifications 45
5 Wiring works 46
6 Refrigerant piping works 48
7 Option switches & function keys 55
8
Installation
Error codes 57
3
Downloaded from www.Manualslib.com manuals search engine
DVM PLUS III
4
Downloaded from www.Manualslib.com manuals search engine
I. Products
Products
1 Outdoor units..............................................6
2 Indoor units.................................................9
3 Accessories..............................................11
5
Downloaded from www.Manualslib.com manuals search engine
1 Outdoor units
1-1. Nomenclature
Model name
RVX
RVX VV H
H TT 100
100 FF EE
Classification Capacity*
Outdoor unit (R410A) RVX ×1/10 HP(3 digits)
* Index
Type
HP TON BTU(MBH)
Mini DVM M 7.5 6 72
DVM PLUS III 10.0 8 96
V
DVM PLUS III HR 12.5 10 120
6
Downloaded from www.Manualslib.com manuals search engine
1-2. Line-up
Products
TON 6 8 TON 22 24
HP 7.5 10.0 HP 27.5 30.0
Model Name RVXVHT075/100FE Model Name RVXVHT275/300FE
TON 10 TON 26
HP 12.5 HP 32.5
Model Name RVXVHT125FE Model Name RVXVHT325FE
TON 12 14 16 TON 28
HP 15.0 17.5 20.0 HP 35.0
Model Name RVXVHT150/175/200FE Model Name RVXVHT350FE
TON 18 TON 30
HP 22.5 HP 37.5
Model Name RVXVHT225FE Model Name RVXVHT375FE
TON 20
HP 25.0
Model Name RVXVHT250FE
7
Downloaded from www.Manualslib.com manuals search engine
1 Outdoor units
6 7.5 RVXVHT075FE
10 12.5 RVXVHT125FE
2) Combinations
Basic model
Classification Capacity (Ton) Capacity (HP)
RVXVHT075FE RVXVHT100FE RVXVHT125FE
12 15.0 2
14 17.5 1 1
16 20.0 2
18 22.5 1 1
20 25.0 2
Module unit
22 27.5 1 2
24 30.0 3
26 32.5 2 1
28 35.0 1 2
30 37.5 3
8
Downloaded from www.Manualslib.com manuals search engine
2 Indoor units
2-1. Nomenclature
Model name
Products
AVX
RVX CV SH HT 022
100 CF EE
Classification Capacity*
Indoor unit (R410A) AVX ×1/10 kW (3 digits)
* Index
Classification by product group Notation Cooling Heating
Cassette type C 020 6.0 MBH 7.0 MBH
Duct type D 023 7.5 MBH 8.5 MBH
Wall mounted type W 032 9.5 MBH 10.5 MBH
040 12.0 MBH 13.5 MBH
9
Downloaded from www.Manualslib.com manuals search engine
2 Indoor units
2-2. Line-up
Model
name 020 023 032 040 052 060 072 100 110 145
(Notation)
MBH 6.0 7.5 9.5 12.0 18.0 20.0 24.0 30.0 36.0 48.0
Slim
1 way
cassette
Mini
4 way
cassette
4 way
cassette
Slim duct
MSP duct
Vivace
Neo-
Forte
10
Downloaded from www.Manualslib.com manuals search engine
3 Accessories
Products
DMS MIM-D00 DVM Series, FJM, CAC, ERV
Integrated
management Controller S-NET 3 MST-P3P DVM Series, FJM, CAC, ERV
system
Centralized
MCM-A202B DVM Series, FJM, CAC, ERV
controller
Controller
Centralized Operation mode
MCM-C200 DVM Series
control system selection switch
Centralized
Interface Mini DVM(R410A), DVM PLUS II,
controller interface MIM-B13B
module DVM PLUS III, FJM, ERV
module
Wireless remote
MR-BH01U Cassette, Duct(Receiver needed)
controller
Wired remote
controller MWR-WE00 Cassette, Wall-mounted, Duct
(Multi function)
Individual
Controller Simplified wired
control system MWR-SH00 Cassette, Wall-mounted, Duct
remote controller
Wireless
signal MRK-A00 Duct (For wireless remote controller)
Wireless receiver
signal
receiver kit
Receiver
MRW-10A Duct (For wireless remote controller)
wire
Key-tag interface
MIM-B02 DVM Series, FJM
module
Guest room management
system
External contact Mini DVM(R410A), DVM PLUS II,
MIM-B14
interface module DVM PLUS III, FJM
DVM Series : Mini DVM, DVM, DVM PLUS II, DVM PLUS III
11
Downloaded from www.Manualslib.com manuals search engine
3 Accessories
PSSMA
P4SMA
12
Downloaded from www.Manualslib.com manuals search engine
II. Outdoor units
1 Specifications.......................................... 14
2 Dimensional drawing................................20
Outdoor units
3 PCB connector layout...............................22
4 Electrical wiring diagram..........................24
5 Sound pressure level................................25
6 Operation limit...........................................28
7 Cycle operation mode..............................29
8 Cycle function parts..................................36
13
Downloaded from www.Manualslib.com manuals search engine
1 Specifications
Type
14
Downloaded from www.Manualslib.com manuals search engine
Type
Outdoor units
Heating 10.3 12.2
Power Nominal Running Cooling 37.6 47.7
A
Current Heating 45.2 47.5
Circuit Breaker (MCCB/ELB/ELCB) A 50 + 50 50 + 50
Cooling - 3.84 3.79
COP Cooling (US Only) Btu/Wh 13.09 12.92
Heating - 4.61 4.53
Model ZPJ72* ZPJ83* ZPI61* ZPI83* ZPJ72* ZPJ83* ZPI61* ZPI83*
Type - DVI Scroll FVI Scroll DVI Scroll FVI Scroll
Number EA 2 2 2 2
cc/Rev 67.1 58.1 67.1 58.1
Piston Displacement
Compressor in³/Rev 4.095 3.545 4.095 3.545
Output kW 6.94 5.83 6.94 5.83
Type - 3MAF POE 3MAF POE
Lubricant cc 1,685 1,685 1,685 1,685
Charging
fl. oz. 57 57 57 57
Type / Control - Propeller/BLDC Propeller/BLDC
Motor Output W (630) x 2 (630) x 2
3
m /min (170) x 2 (170) x 2
Fan Airflow Rate
CFM (6004) x 2 (6004) x 2
External Static Pa 78.5 78.5
Max.
Pressure WG 0.315 0.315
- High Pressure Switch High Pressure Switch
Mechanical Type - Comp./Accum. Crank Case Heater Comp./Accum. Crank Case Heater
Safety - Fuse for PCB Fuse for PCB
Devices - Over-voltage Protection Over-voltage Protection
Electronic Type - Current Transformer Current Transformer
- Fan motor Voltage Protection Fan motor Voltage Protection
Ø, mm 12.70 15.88
Liquid
Ø, inch 1/2 5/8
Ø, mm 28.58 28.58
Gas
Ø, inch 1 1/8 1 1/8
Piping Ø, mm 6.35 6.35
Oil (Flare)
Connections Ø, inch 1/4 1/4
m 200 200
Max. Length
Installation ft 656 656
Limitation m 50 (40) 50 (40)
Max. Height
ft 164 (131) 164 (131)
Type - R410A R410A
Refrigerant kg (6.5) x 2 (6.5) x 1 + (7.5) x 1
Factory Charging
lbs (14.33) x 2 (14.33) x 1 + (16.53) x 1
Sound4) Sound Pressure dB(A) 60 61
kg (240) x 2 (240) x 2
Net Weight
lbs (529) x 2 (529) x 2
kg (253) x 2 (253) x 2
Shipping Weight
lbs (558) x 2 (558) x 2
Set Size
mm (880 x 1668 x 765) x 2 (880 x 1668 x 765) x 2
Net Dimensions (WxHxD)
inch (34 5/8 x 65 5/8 x 30 1/8) x 2 (34 5/8 x 65 5/8 x 30 1/8) x 2
mm (948 x 1888 x 832) x 2 (948 x 1888 x 832) x 2
Shipping Dimensions (WxHxD)
inch (37 3/8 x 74 3/8 x 32 3/4) x 2 (37 3/8 x 74 3/8 x 32 3/4) x 2
Main Power (Below 50m) AWG # Separate electrical connection for each outdoor units Separate electrical connection for each outdoor units
Cable
Communication AWG # AWG 16~18 AWG 16~18
°C -5~46.1 -5~46.1
Cooling
Operating °F 23~115 23~115
Temp. Range °C -20~24 -20~24
Heating
°F -4~75 -4~75
15
Downloaded from www.Manualslib.com manuals search engine
1 Specifications
Type
16
Downloaded from www.Manualslib.com manuals search engine
Type
Outdoor units
20.2 19.3
Power Nominal Running Cooling 73.6 76.6
A
Current Heating 66.0 72.4
Circuit Breaker (MCCB/ELB/ELCB) A 60 + 60 50 + 50 + 50
Cooling - 3.29 3.77
COP Cooling (US Only) Btu/Wh 11.21 12.88
Heating - 3.92 4.51
Model ZPJ72* ZPJ83* ZPI61* ZPI83* ZPJ72* ZPJ83* ZPI61* ZPI83*
Type - DVI Scroll FVI Scroll DVI Scroll FVI Scroll
Number EA 2 2 3 3
cc/Rev 77.2 77.2 67.1 58.1
Piston Displacement
Compressor in³/Rev 4.711 4.711 4.095 3.545
Output kW 7.91 7.91 6.94 5.83
Type - 3MAF POE 3MAF POE
Lubricant cc 1,685 1,685 1,685 1,685
Charging
fl. oz. 57 57 57 57
Type / Control - Propeller/BLDC Propeller/BLDC
Motor Output W (630) x 2 (630) x 3
m3/min (180) x 2 (170) x 3
Fan Airflow Rate
CFM (6357) x 2 (6004) x 3
External Static Pa 78.5 78.5
Max.
Pressure WG 0.315 0.315
- High Pressure Switch High Pressure Switch
Mechanical Type - Comp./Accum. Crank Case Heater Comp./Accum. Crank Case Heater
Safety - Fuse for PCB Fuse for PCB
Devices - Over-voltage Protection Over-voltage Protection
Electronic Type - Current Transformer Current Transformer
- Fan motor Voltage Protection Fan motor Voltage Protection
Ø, mm 19.05 19.05
Liquid
Ø, inch 3/4 3/4
Ø, mm 34.93 34.93
Gas
Ø, inch 1 3/8 1 3/8
Piping Ø, mm 6.35 6.35
Oil (Flare)
Connections Ø, inch 1/4 1/4
m 200 200
Max. Length
Installation ft 656 656
Limitation m 50 (40) 50 (40)
Max. Height
ft 164 (131) 164 (131)
Type - R410A R410A
Refrigerant kg (9) x 2 (6.5) x 1 + (7.5) x 2
Factory Charging
lbs (19.84) x 2 (14.33) x 1 + (16.53) x 2
Sound4) Sound Pressure dB(A) 62 63
kg (280) x 2 (240) x 3
Net Weight
lbs (617) x 2 (529) x 3
kg (297) x 2 (253) x 3
Shipping Weight
lbs (655) x 2 (558) x 3
Set Size
mm (1200 x 1668 x 765) x 2 (880 x 1668 x 765) x 3
Net Dimensions (WxHxD)
inch (47 1/4 x 65 5/8 x 30 1/8) x 2 (34 5/8 x 65 5/8 x 30 1/8) x 3
mm (1268 x 1888 x 832) x 2 (948 x 1888 x 832) x 3
Shipping Dimensions (WxHxD)
inch (49 7/8 x 74 3/8 x 32 3/4) x 2 (37 3/8 x 74 3/8 x 32 3/4) x 3
Main Power (Below 50m) AWG # Separate electrical connection for each outdoor units Separate electrical connection for each outdoor units
Cable
Communication AWG # AWG 16~18 AWG 16~18
°C -5~46.1 -5~46.1
Cooling
Operating °F 23~115 23~115
Temp. Range °C -20~24 -20~24
Heating
°F -4~75 -4~75
17
Downloaded from www.Manualslib.com manuals search engine
1 Specifications
Type
18
Downloaded from www.Manualslib.com manuals search engine
Type
Outdoor units
27.3 30.3
Power Nominal Running Cooling 102.5 110.4
A
Current Heating 90.9 99.0
Circuit Breaker (MCCB/ELB/ELCB) A 50 + 60 + 60 60 + 60 + 60
Cooling - 3.41 3.29
COP Cooling (US Only) Btu/Wh 11.63 11.21
Heating - 4.06 3.92
Model ZPJ72* ZPJ83* ZPI61* ZPI83* ZPJ72* ZPJ83* ZPI61* ZPI83*
Type - DVI Scroll FVI Scroll DVI Scroll FVI Scroll
Number EA 1 2 1 2 3 3
cc/Rev 67.1 77.2 58.1 77.2 77.2 77.2
Piston Displacement
Compressor in³/Rev 4.095 4.711 3.545 4.711 4.711 4.711
Output kW 6.94 7.91 5.83 7.91 7.91 7.91
Type - 3MAF POE 3MAF POE
Lubricant cc 1,685 1,685 1,685 1,685 1,685 1,685
Charging
fl. oz. 57 57 57 57 57 57
Type / Control - Propeller/BLDC Propeller/BLDC
Motor Output W (630) x 3 (630) x 3
m3/min (170) x 1 + (180) x 2 (180) x 3
Fan Airflow Rate
CFM (6004) x 1 + (6357) x 2 (6357) x 3
External Static Pa 78.5 78.5
Max.
Pressure WG 0.315 0.315
- High Pressure Switch High Pressure Switch
Mechanical Type - Comp./Accum. Crank Case Heater Comp./Accum. Crank Case Heater
Safety - Fuse for PCB Fuse for PCB
Devices - Over-voltage Protection Over-voltage Protection
Electronic Type - Current Transformer Current Transformer
- Fan motor Voltage Protection Fan motor Voltage Protection
Ø, mm 19.05 19.05
Liquid
Ø, inch 3/4 3/4
Ø, mm 34.93 34.93
Gas
Ø, inch 1 3/8 1 3/8
Piping Ø, mm 6.35 6.35
Oil (Flare)
Connections Ø, inch 1/4 1/4
m 200 200
Max. Length
Installation ft 656 656
Limitation m 50 (40) 50 (40)
Max. Height
ft 164 (131) 164 (131)
Type - R410A R410A
Refrigerant kg (7.5) x 1 + (9) x 2 (9) x 3
Factory Charging
lbs (16.53) x 1 + (19.84) x 2 (19.84) x 3
Sound4) Sound Pressure dB(A) 64 64
kg (240) x 1 + (280) x 2 (280) x 3
Net Weight
lbs (529) x 1 + (617) x 2 (617) x 3
kg (253) x 1 + (297) x 2 (297) x 3
Shipping Weight
lbs (558) x 1 + (655) x 2 (655) x 3
mm (880 x 1668 x 765) x 1 + (1200 x 1668 x 765) x 2 (1200 x 1668 x 765) x 3
Set Size
Net Dimensions (WxHxD) (34 5/8 x 65 5/8 x 30 1/8) x 1 +
inch (47 1/4 x 65 5/8 x 30 1/8) x 3
(47 1/4 x 65 5/8 x 30 1/8) x 2
mm (948 x 1888 x 832) x 1 + (1268 x 1888 x 832) x 2 (1268 x 1888 x 832) x 3
Shipping Dimensions (WxHxD) (37 3/8 x 74 3/8 x 32 3/4) x 1 +
inch (49 7/8 x 74 3/8 x 32 3/4) x 3
(49 7/8 x 74 3/8 x 32 3/4) x 2
Main Power (Below 50m) AWG # Separate electrical connection for each outdoor units Separate electrical connection for each outdoor units
Cable
Communication AWG # AWG 16~18 AWG 16~18
°C -5~46.1 -5~46.1
Cooling
Operating °F 23~115 23~115
Temp. Range °C -20~24 -20~24
Heating
°F -4~75 -4~75
*1) Mode HP : Heat Pump, HR : Heat Recovery
*2) Norminal
cooling capacities are based on;
Indoor temperature : 26.7°C DB, 19.4°C WB(80°F DB, 67°F WB)
Outdoor temperature : 35°C DB, 23.9°C WB(90°F DB, 75°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*3) N
orminal heating capacities are based on;
Indoor temperature : 21.1°C DB, 15.6°C WB(70°F DB, 60°F WB)
Outdoor temperature : 8.3°C DB, 6.1°C WB(47°F DB, 43°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*4) Sound level was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications are subject to change without prior notice for product improvement.
19
Downloaded from www.Manualslib.com manuals search engine
2 Dimensional drawing
2-1. RVXVHT075/100FE
Unit : mm (inch)
20
Downloaded from www.Manualslib.com manuals search engine
2-2. RVXVHT125FE
Unit : mm (inch)
Outdoor units
21
Downloaded from www.Manualslib.com manuals search engine
3 PCB connector layout
3 5
1 2 4 6 7 8 9
10
33
31 11
12
32
30 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13
29 28
3 CN31 Red Communication with Indoor Unit(COM1) 20 CN74 Red Hot gas Bypass Valve
4 CN32 Yellow Communication with Outdoor Unit 21 CN71 White PWM Valve
5 CN12 Blue 12V for Interface Module 22 CN73 Yellow 4 Way Valve
6 CN92 Black Sub Micom Download 23 CN75 White EVI Bypass Valve
22
Downloaded from www.Manualslib.com manuals search engine
3-2. BLDC Driver PCB
34 39
35
No. CN # COLOR FUNCTION
36 34 CN701 Blue AC 208~230V Input
Outdoor units
35 GT2 White Power Trans In (AC 208~230V)
37 36 CN703 Black AC 208~230V Output
Main-BLDC Driver
37 CN501 White
PCB Connector
38 CN101 White Motor Signal
38
39 CN301 White Motor Power
40 42
3-4. CT PCB
43
23
Downloaded from www.Manualslib.com manuals search engine
4 Electrical wiring diagram
6 7 8 9
1 2 3
10
4 5
33
11
32 31 12
29
30 28
27 19 13
26 25 24 23 22 21 20 18 17 16 15 14
42
37 36 43
35
38
34
40 41
39
24
Downloaded from www.Manualslib.com manuals search engine
5 Sound pressure level
Outdoor unit
Note
These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of
factors such as the construction of the particular room where the equipment is installed.
Operation sound level may differ depending on operation and ambient conditions.
65 65
NC 65 NC 65
60 60
Sound pressure level (dB)
NC 60 NC 60
55 55
NC 55 NC 55
50 50
NC 50 NC 50
45
45
NC 45
NC 45
40
40
NC 40
35 NC 40
35
NC 35
30 NC 35
30
NC 30
NC 30
25
63 125 250 500 1000 2000 4000 8000 25
63 125 250 500 1000 2000 4000 8000
3) RVXVHT125FE 4) RVXVHT150FE
70 70
65 65
NC 65 NC 65
60 60
Sound pressure level (dB)
NC 60
NC 60
55
55
NC 55
NC 55
50
50
NC 50
45 NC 50
45
NC 45
40 NC 45
40
NC 40
35 NC 40
35
NC 35
30 NC 35
30
NC 30
25 NC 30
63 125 250 500 1000 2000 4000 8000
25
63 125 250 500 1000 2000 4000 8000
25
Downloaded from www.Manualslib.com manuals search engine
5 Sound pressure level
65 65
NC 65 NC 65
60 60
Sound pressure level (dB)
NC 55 NC 55
50 50
NC 50 NC 50
45 45
NC 45 NC 45
40 40
NC 40 NC 40
35 35
NC 35 NC 35
30 30
NC 30 NC 30
25 25
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
7) RVXVHT225FE 8) RVXVHT250FE
70 70
65 65
NC 65 NC 65
60 60
Sound pressure level (dB)
NC 60 NC 60
55 55
NC 55 NC 55
50 50
NC 50 NC 50
45 45
NC 45 NC 45
40 40
NC 40 NC 40
35 35
NC 35 NC 35
30 30
NC 30 NC 30
25 25
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
26
Downloaded from www.Manualslib.com manuals search engine
9) RVXVHT275FE 10) RVXVHT300FE
70 70
65 65
NC 65 NC 65
60 60
Sound pressure level (dB)
NC 55 NC 55
Outdoor units
50 50
NC 50 NC 50
45 45
NC 45 NC 45
40 40
NC 40 NC 40
35 35
NC 35 NC 35
30 30
NC 30 NC 30
25 25
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
65 65
NC 65 NC 65
60 60
Sound pressure level (dB)
NC 60 NC 60
55 55
NC 55 NC 55
50 50
NC 50 NC 50
45 45
NC 45 NC 45
40 40
NC 40 NC 40
35 35
NC 35 NC 35
30 30
NC 30 NC 30
25 25
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
13) RVXVHT375FE
70
65
NC 65
60
Sound pressure level (dB)
NC 60
55
NC 55
50
NC 50
45
NC 45
40
NC 40
35
NC 35
30
NC 30
25
63 125 250 500 1000 2000 4000 8000
35
(95) (68)
25 10
(77) (50)
20 5 Range for
(68) (41)
continuous
15 0
(59) (32) operation
10 -5
(50) (23)
5 -10
(41) (14)
0 -15
(32) (5)
-5 -20
(23) (-4) 10 15 20 25 30
10 15 20 25 30
(50) (59) (68) (77) (86) (50) (59) (68) (77) (86)
28
Downloaded from www.Manualslib.com manuals search engine
7 Cycle operation mode
No Classification Description
1 A DVI (Digital Vapor Injection) compressor
2 B FVI (Fixed Vapor Injection) compressor
3 C Discharged gas distributor
4 D PWM (Pulse Width Modulation) solenoid valve
5 E Discharged gas temperature sensor of DVI compressor
6 F Discharged gas temperature sensor of FVI compressor 1
7 G Filter
Outdoor unit
8 H Oil separator
9 I Capillary tube from oil separator
10 J High pressure switch
11 K Hot gas bypass solenoid valve
12 L Discharged gas check valve
13 M High pressure sensor
14 N Reversing solenoid valve (4way valve)
15 O Heat exchanger of outdoor unit (Condensing unit)
16 P Ambient air temperature sensor
17 Q Cond_out temperature sensor
18 R Main EEV (Electronic Expansion Valve) for heating operation
19 S Liquid refrigerant check valve
20 T Liquid bypass solenoid valve DVI compressor
21 U Liquid bypass solenoid valve FVI compressor
22 V EVI EEV (Electronic Expansion Valve)
23 W Turbo Intercooler
24 X EVI_in temperature sensor
25 Y EVI_out temperature sensor
26 Z Liquid tube temperature sensor
27 a EVI bypass pilot solenoid valve
28 b Suction temperature sensor
29 c Accumulator
30 d Suction gas distributor
31 e Oil solenoid valve 1
32 f Oil solenoid valve 2
33 g Filter between oil balancing pipes
34 h Oil balancing service valve between units
35 i Low pressure sensor
36 j Check valve
37 k Crank case heater of DVI compressor
38 m Crank case heater of FVI compressor 1
39 n Sump(Base) temperature sensor
40 o Oil temperature sensor
41 p Capillary tube from hot gas bypass valve
42 q Capillary tube from liquid bypass valve for DVI compressor
43 r Capillary tube from liquid bypass valve for FVI compressor
44 s Liquid side service valve
45 t Liquid side filter
46 u Gas side service valve
47 v Gas side filter
48 w EEV of indoor unit
49 x Eva_in temperature sensor
50 y Heat exchanger of indoor unit (Evaporating unit)
51 z Eva_out temperature sensor
52 a Liquid side connection for wall mount unit
53 b Gas side connection for wall mount unit
29
Downloaded from www.Manualslib.com manuals search engine
7 Cycle operation mode
s
Solenoid Solenoid valve
s
Pilot Solenoid Pilot solenoid valve
E
Expansion Electronic Expansion Valve (EEV)
2 Valve
Reversing Reversing valve
Accumulator Accumulator
Filter Filter
30
Downloaded from www.Manualslib.com manuals search engine
7-2. Cycle diagrams
1) RVXVHT075/100FE (DVM PLUS III - 6/8 TON)
u
v
Outdoor units
O Q G
E
N S
p
L
J
K I
s
H
T
q s W
C
V
E
r s
D Y X
s
E F U
i b
A B d a Z
j s
k m
H
n H
s
s c t
o e f
s
g
h
31
Downloaded from www.Manualslib.com manuals search engine
7 Cycle operation mode
u
v
O Q G
E
N S
p
L
J
K I
s
H
T
q s W
C
V
E
r s
D Y X
s
E F U
i b
A B d a Z
j s
k m
H
n H
s
s c t
o e f
s
g
h
32
Downloaded from www.Manualslib.com manuals search engine
3) EEV kits & Indoor units
(1) MXD series (2) MEV series
u u a
b b
E E E
a a
s
Outdoor units
E E
s s
Indoor units with built-in EEV Indoor units without EEV (Wall mounted)
z y x z y x
u b
E
s a
w
33
Downloaded from www.Manualslib.com manuals search engine
34
Unit
4) Cooling operation
Cooling
⑦ E
Cooling operation
Heating operation
②
E
③
s
⑧ Cooling
Outdoor unit
s
E
E
s
s
7 Cycle operation mode
s
Cooling
H H E
s
④
⑥
Indoor unit
Cooling
⑤ E
Outdoor unit
Unit
5) Heating operation
⑦ Heating
② E
Cooling operation
Heating operation
E
Heating
s ⑧
Outdoor unit
E
E
s
s
s
Heating
H H
⑤ E
③
Indoor unit
Heating
④ E
Outdoor unit
35
Outdoor units
8 Cycle function parts
8-1. RVXVHT075/100FE
Fan
High
pressure
sensor
Liquid bypass valve
Hot gas Liquid tube for DVI compressor
bypass valve sensor
Liquid bypass valve
Suction for FVI compressor
temperature EVI bypass
sensor valve
4 way valve Hot gas Discharge
bypass temperature sensor
valve
Refrigerant Low pressure sensor
charging port in EVI EEV
heating mode Discharge
Liquid temperature sensor
service valve
Outdoor Cond_out
Main EEV temp.
sensor
Gas service
valve
36
Downloaded from www.Manualslib.com manuals search engine
8-2. RVXVHT125FE
Accumulator
Outdoor units
Suction temperature sensor
EVI EEV
Fan
High
pressure
sensor
Suction
temperature Liquid tube Hot gas
sensor sensor bypass valve
Low pressure
EVI bypass valve sensor
4 way valve
High pressure
switch
Liquid bypass
EVI EEV valve for FVI
compressor
Liquid service
valve Liquid bypass
valve for DVI
Gas service
compressor
valve
37
Downloaded from www.Manualslib.com manuals search engine
8 Cycle function parts
38
Downloaded from www.Manualslib.com manuals search engine
III. Installation
1 Outdoor unit combinations.......................40
2 Space requirements.................................41
3 Placing the outdoor units..........................44
4 Electric specifications...............................45
5 Wiring works.............................................46
Installation
6 Refrigerant piping works...........................48
7 Option switches & function keys..............55
8 Error codes...............................................57
39
Downloaded from www.Manualslib.com manuals search engine
1 Outdoor unit combinations
1-2. Combinations
Basic model Total capacifities of Maximum number
Capacity Capacity
Classification the connectable of connectable
(Ton) (HP) RVXVHT075FE RVXVHT100FE RVXVHT125FE indoor units(MBH) indoor units
12 15.0 2 72 ~ 187.2 16
14 17.5 1 1 84 ~ 218.4 18
16 20.0 2 96 ~ 249.6 20
18 22.5 1 1 108 ~ 280.8 24
20 25.0 2 120 ~ 312.0 28
Module unit
22 27.5 1 2 132 ~ 343.2 30
24 30.0 3 144 ~ 374.4 32
26 32.5 2 1 156 ~ 405.6 34
28 35.0 1 2 168 ~ 436.8 36
30 37.5 3 180 ~ 468.0 40
40
Downloaded from www.Manualslib.com manuals search engine
2 Space requirements
Front 10(3/8)
or more 500(20) or more[S1]
10(3/8) or more 200(8) or more
Installation
300(12) or more
Front
10(3/8) 500(20) or
or more more[S1] Front Front
20(3/4) or more 20(3/4) or more 200(8) or
10(3/8) 400(16)
or more more
or more
Front Front
600(24) or more 500(20) or more
Front 10(3/8) Front 10(3/8) or
or more more
10(3/8) 300(12) or
500(20) or more more
20(3/4)
or more 20(3/4) or more
10(3/8) or more
or more
Note
The installation space mentioned above is minimum suggested clearance.
To secure enough service space and performance of system, take account of more sufficient space.
The required minimum space between outdoor units for service and performance of system is at least
100mm(4in).
41
Downloaded from www.Manualslib.com manuals search engine
2 Space requirements
Suction air
CAUTION
The frame/foundation should be higher than expected snowfall.
The foundation must be solid and the unit must be secured with anchor bolts.
Be sure to install unit in a place strong enough to withstand its weight.
When installing on a roof subject to strong wind, countermeasures must be taken to prevent the unit form being
overturned.
Any lack of strength may cause unit to fall down, resulting in a personal injury.
For more detailed information about installation, refer to installation manual.
42
Downloaded from www.Manualslib.com manuals search engine
252 417 252 417
(9-7/8) (16-3/8)
(9-7/8) (16-3/8)
2) RVXVHT125FE
560(22)
560(22)
1) RVXVHT075/100FE
2000(78-3/4)
880(34-5/8)
782(30-3/4)
1200(47-1/4)
560(22)
880(34-5/8) 112(4-3/8) 557(21-7/8)
560(22)
220(8-5/8) 1050(41-3/8) 1207(47-1/2)
880(34-5/8) 112(4-3/8) 557(21-7/8)
1588(62-1/2)
220(8-5/8) 1050(41-3/8) 1207(47-1/2) 1318(51-7/8)
1588(62-1/2) 2256(88-7/8)
1318(51-7/8)
2256(88-7/8)
668(26-1/4)
668(26-1/4) 532(21)
532(21)
2-5. Dimensional drawing of snow-proof duct
871(34-1/4)
871(34-1/4)
765(30-1/8) 550(21-5/8)
105(4-1/8)
105(4-1/8) 880(34-5/8)
880(34-5/8) 220(8-5/8) 1049(41-1/2)
220(8-5/8) 1049(41-1/4)
2226(87-10/16) 2227(87-11/16)
43
Unit : mm (inch)
Unit : mm (inch)
Installation
3 Placing the outdoor units
745(29-5/16)
765(30-1/8)
Model RVXVHT075/100 RVXVHT125
A 880(34-5/8) 1200(47-1/4)
B 738(29) 1058(41-5/8)
Anchor bolt
CAUTION
Pay your attention not to touch the copper pipes as detaching the fasteners.
The stopper nut and washer should be removed.
If this work is not conducted correctly, it can cause outdoor unit to vibrate and make much noise.
44
Downloaded from www.Manualslib.com manuals search engine
4 Electric specifications
4-2. Combinations
Capacity Capacity Basic model
Classification MCCB(A) ELB
(Ton) (HP) RVXVHT075FE RVXVHT100FE RVXVHT125FE
12 15.0 2 50 + 50
Installation
14 17.5 1 1 50 + 50
16 20.0 2 50 + 50
18 22.5 1 1 50 + 60
20 25.0 2 60 + 60
Module unit
22 27.5 1 2 50 + 50 + 50
24 30.0 3 50 + 50 + 50
26 32.5 2 1 50 + 50 + 60
28 35.0 1 2 50 + 60 + 60
30 37.5 3 60 + 60 + 60
Units Power supply Comp. OFM
Model
Hz Volts Min. Max. MCA MFA RLA kW FLA
RVXVHT150FE 60 208~230 187 253 96.2 50+50 (13.8+21.8)×2 0.63+0.63 7+7
RVXVHT175FE 60 208~230 187 253 101.9 50+50 (13.8+21.8)+(19.6+21.8) 0.63+0.63 7+7
RVXVHT200FE 60 208~230 187 253 107.6 50+50 (19.6+21.8)×2 0.63+0.63 7+7
RVXVHT225FE 60 208~230 187 253 114.9 50+60 (19.6+21.8)+(23.4+24.6) 0.63+0.63 7+7
RVXVHT250FE 60 208~230 187 253 122.2 60+60 (23.4+24.6)×2 0.63+0.63 7+7
RVXVHT275FE 60 208~230 187 253 155.7 50+50+50 (13.8+21.8)+(19.6+21.8)×2 0.63+0.63+0.63 7+7+7
RVXVHT300FE 60 208~230 187 253 161.4 50+50+50 (19.6+21.8)×3 0.63+0.63+0.63 7+7+7
RVXVHT325FE 60 208~230 187 253 168.7 50+50+60 (19.6+21.8)×2+(23.4+24.6) 0.63+0.63+0.63 7+7+7
RVXVHT350FE 60 208~230 187 253 176.0 50+60+60 (19.6+21.8)+(23.4+24.6)×2 0.63+0.63+0.63 7+7+7
RVXVHT375FE 60 208~230 187 253 183.3 60+60+60 (23.4+24.6)×3 0.63+0.63+0.63 7+7+7
The relationship between the starting time and the starting current (Digital Scroll Comp. + Fixed Scroll Comp)
Starting current
Earth
Earth
Main unit Sub unit
208~230V 208~230V
Indoor Outdoor Indoor Outdoor
Earth Communication
cable among
Earth
Communication outdoor units
cable between
indoor and
outdoor units
• Connect the power cable of the outdoor unit after checking that R-S-T(3 phase 3 wires) is properly connected.
• The communication cable between indoor and outdoor units has no polarity.
• Arrange the cables using cable ties.
46
Downloaded from www.Manualslib.com manuals search engine
5-2. Caution of wiring work
3 phase 208~230V
To sub unit
communication cable
MCCB
ELCB
Outdoor Unit
CAUTION
Make sure that all wiring should not contact with piping line during the field wiring work. If not, the vibration of
compressor can make a damage to wiring and piping. It may result in fire.
Installation
Make sure to pass electrical wiring of the power cable (3 phase 3 wires) through a conduit hole of the front side.
Connecting the ring terminal of 3 phase cable (CV) Connecting the ring terminal of 3 phase cable (FCV)
Housing cover
Middle frame
Base line Base line
A A
250mm
B B
C C
A B C A B C
A B C A B C
30mm (1-1/8in) 60mm (2-3/8in) 90mm (3-1/2in) 30mm (1-1/8in) 60mm (2-3/8in) 90mm (3-1/2in)
1. Be sure to connect the suitable length of power wiring to the power wiring terminal block using ring terminal
above the figures.
2. Make sure to fix wiring using cable tie like above the figures.
3. After wiring, reinstall the housing cover which has an isolator into the middle frame.
47
Downloaded from www.Manualslib.com manuals search engine
6 Refrigerant piping works
Minimum
Horizontal length = 100mm
over 100mm(3-7/8in) (3-7/8in)
48
Downloaded from www.Manualslib.com manuals search engine
6-2. Example of piping layouts
Example of piping layouts for DVM PLUS III
Using
Y-joint
Installation
Using
Header
joint
49
Downloaded from www.Manualslib.com manuals search engine
6 Refrigerant piping works
installed
a b j
h i j k l m n
c d e f g h b c d e f g h
i
Multiple outdoor b c d e f
F
g
G
p
i
k
units installed
a a
a b j
h i j k l m n
c d e f g h b c d e f g h
i
+i+j+k+l+m+n+p≤1000m (3281ft) h i j k l m n
Each Y-joint ~
h,I,j,..p≤45m (148ft)
each indoor
The difference between the distance of the outdoor unit to the farthest
Between
indoor unit and the distance of the outdoor unit to the farthest indoor
indoor units
unit ≤ 45m (148ft) (a+b+c+d+e+f+g+p)-(a+h) ≤ 45m (148ft)
50
Downloaded from www.Manualslib.com manuals search engine
6-4. Pipe selection
Outdoor unit connection pipe size : (A1), (A2), (A3)
A1 : Select the pipes according to the outdoor unit capacity with
10Ton 8Ton 8Ton
following table.
Outdoor unit Pipe size (O.D) Oil balancing
Liquid Gas pipe size
Ton HP
(E) mm inches mm inches mm(inches)
(A1) (A1)
6 7.5 Ø19.05 Ø3/4
Ø9.52 Ø3/8
(A1) (A2) (A3) (B) 8 10.0 Ø22.23 Ø7/8 -
(F)
10 12.5 Ø12.70 Ø1/2 Ø28.58 Ø1-1/8
(D)
A2 : Select the pipes according to sum of outdoor unit capacities
behind the outdoor joint with following table.
(C)
Outdoor unit Pipe size (O.D) Oil balancing
Example) 26 Ton Liquid Gas pipe size
Ton HP
Pipe size (O. D.mm) mm inches mm inches mm(inches)
Ton HP Mark Liquid Gas 12 15.0 Ø12.70 Ø1/2
14 17.5
mm inches mm inches Ø28.58 Ø1-1/8 Ø6.35
16 20.0 Ø15.88 Ø5/8
8 10 (A1) Ø9.52 Ø3/8 Ø22.23 Ø7/8 (Ø1/4)
Installation
18 22.5
8 10 (A1) Ø9.52 Ø3/8 Ø22.23 Ø7/8 20 25.0 Ø19.05 Ø3/4 Ø34.93 Ø1-3/8
10 12.5 (A1) Ø12.70 Ø1/2 Ø28.58 Ø1-1/8
A3 : Select the main pipe of outdoor units with the following table.
18 22.5 (A2) Ø15.88 Ø5/8 Ø28.58 Ø1-1/8
Outdoor unit Pipe size (O.D) Oil balancing
26 32.5 (A3) Ø19.05 Ø3/4 Ø34.93 Ø1-3/8 pipe size
Liquid Gas
Ton HP
mm inches mm inches mm(inches)
6 7.5 Ø19.05 Ø3/4
Ø9.52 Ø3/8
8 10.0 Ø22.23 Ø7/8 -
10 12.5
Ø12.70 Ø1/2
12 15.0
14 17.5 Ø28.58 Ø1-1/8
16 20.0 Ø15.88 Ø5/8
18 22.5
20 25.0 Ø6.35
22 27.5 (Ø1/4)
24 30.0
Ø19.05 Ø3/4 Ø34.93 Ø1-3/8
26 32.5
28 35.0
30 37.5
A3 : Select the main pipe of outdoor units with the following table when
if the farthest indoor unit’s length is over 90m(295ft).
Outdoor unit Pipe size (O.D) Oil balancing
Liquid Gas pipe size
Ton HP
mm inches mm inches mm(inches)
6 7.5 Ø22.23 Ø7/8
Ø12.70 Ø1/2
8 10.0 -
Ø28.58 Ø1-1/8
10 12.5
Ø15.88 Ø5/8
12 15.0
14 17.5
16 20.0 Ø19.05 Ø3/4
18 22.5
Ø34.93 Ø1-3/8
20 25.0 Ø6.35
22 27.5 (Ø1/4)
24 30.0
Ø22.23 Ø7/8
26 32.5
28 35.0
Ø41.28 Ø1-5/8
30 37.5
*A1 : Pipes to the outdoor unit (Liquid, Gas)
*A2 : Pipes between outdoor joint kits (Liquid, Gas)
*A3 : Main pipes (Liquid, Gas)
51
Downloaded from www.Manualslib.com manuals search engine
6 Refrigerant piping works
2) Header joint
The connect-
Total Indoor unit’s
Model able quantity of
Header capacity indoor units
joint MXJ-HA2512K 160 MBH and below 4
(F) MXJ-HA3115K Over 160 MBH~ 240 MBH 8
MXJ-HA3819K Over 240 MBH 8
52
Downloaded from www.Manualslib.com manuals search engine
6-5. Additional refrigerant charging
Installation
Ø6.35(5m/16.4ft)
Ø6.35(5m/16.4ft) • Example of additional refrigerant charging.
Ø6.35(5m/16.4ft) Pipe length is as below without distribution kit.
Ø9.52(5m/16.4ft) Total piping Additional
Liquid pipe size (O.D.)
lengths refrigerant charging
mm inches m ft kg lbs
Ø6.35 Ø1/4 15 49.21 0.300 0.6614
Ø9.52 Ø3/8 25 82.02 1.500 3.3069
Ø12.70 Ø1/2 21 68.90 2.625 5.7871
Ø15.88 Ø5/8 25 82.02 4.500 9.9208
Ø19.05 Ø3/4 5 16.40 1.350 2.9762
Total 10.275 22.652
CAUTION
Total refrigerant amount of the system must be less then 100kg(220lbs). If total refrigerant amount of system is over
100kg(220lbs) more, the system has to be divided into smaller system, each containing less than 100kg(220lbs).
53
Downloaded from www.Manualslib.com manuals search engine
6 Refrigerant piping works
54
Downloaded from www.Manualslib.com manuals search engine
7 Option switches & function keys
F012
BC E
3456
D
789A
Installation
Setting total quantity of Installed indoor units Main unit required only
SW01/SW02 Main unit required only Ex) A s 12 indoor units were installed,
SW01 : The tens digit, SW02 : The units digit SW01:1, SW02: 2
K5 On Manual address setting
SW03
Off Auto address setting
K9 K10 Target evaporating temperature (°C/°F)
On On 7~9(44.6 ~ 48.2)
SW04 On Off 5~7(41.0~44.6) Cooling capacity compensation
Off On 9~11(48.2~51.8)
Off Off 10~12(50.0~53.6)
K11 K12 Target high pressure (kgf /cm2, psig, kPa)
On On 30.0, 426, 2941
SW04 On Off 31.5, 448, 3089
Heating capacity compensation
Off On 33.0, 469, 3236
Off Off 27.0, 384, 2647
K13 K14 Outdoor unit’s address
On On Outdoor unit’s address : No 1 Main unit
On Off Outdoor unit’s address : No 2 Sub I unit
Off On Outdoor unit’s address : No 3 Sub 2 unit
Off Off Outdoor unit’s address : No 4 Sub 3 unit
SW05
K15 K16 Maximum current control
On On Standard Factory default
On Off 90% of standard peak current value
Off On 80% of standard peak current value
Off Off Not use
On Since supplying power, first oil return operation happens after 5hrs and then 7 hrs.
K17
Off Since supplying power, first oil return operation happens after 2hrs and then 2 hrs.
On Standard
K18 Defrost period setting
Off Shorten defrost period by 20% approximately
SW06
On Standard fan step
K19
Off Fan step compensation (Maximum step) 7.5/10 HP : 19 Steps, 12.5 HP : 23 Steps
On Normal
K20
Off Night’s quiet mode
Factory
default
SW01, SW02, SW09 : ‘0’
SW03 ~ SW06 : ON
55
Downloaded from www.Manualslib.com manuals search engine
7 Option switches & function keys
K1
BC E
3456
D
K3
789A
K4
Display LED
K4 Key function
SEG 1 SEG 2, 3, 4
Push 1st time Outdoor capacity 1 Ex) 16 HP Off, 1, 6
Push 2nd time Digital comp loading time 2 Ex) Loading 13 sec Off, 1, 3
Push 3rd time High pressure (kg/cm2) 3 Ex) High pressure 15.2 (kg/cm2) 1, 5, 2
Push 4th time Low pressure (kg/cm2) 4 Ex) Low pressure 4.3 (kg/cm2) 0, 4, 3
Push 5th time Discharge temperature of compressor 1 5 Ex) 87°C 0, 8, 7
Push 6th time Discharge temperature of compressor 2 6 Ex) 87°C 0, 8, 7
Push 7th time Discharge temperature of compressor 3 7 Ex) 87°C 0, 8, 7
Push 8th time CT sensor value of compressor 1 8 Ex) 2A 0, 0, 2
Push 9th time CT sensor value of compressor 2 9 Ex) 2A 0, 0, 2
Push 10th time CT sensor value of compressor 3 A Ex) 2A 0, 0, 2
Push 11th time Suction temperature B Ex) -5 °C -, 0, 5
Push 12th time Cond_out temperature C Ex) 35 °C 0, 3, 5
Push 13th time Liquid tube temperature D Ex) 35 °C 0, 3, 5
Push 14th time Oil temperature sensor on oil balancing pipe E Ex) 35 °C 0, 3, 5
Push 15th time Sump temperature of compressor 1 F Ex) 35 °C 0, 3, 5
Push 16th time Ambient air temperature G Ex) 35 °C 0, 3, 5
Push 17th time EVI_in temperature H Ex) 35 °C 0, 3, 5
Push 18th time EVI_out temperature I Ex) 35 °C 0, 3, 5
Push 19th time Main EEV1 step J Ex) 2000 steps 2, 0, 0
Push 20th time Main EEV2 step K Ex) 2000 steps 2, 0, 0
Push 21th time EVI EEV step L Ex) 300 steps 3, 0, 0
Push 22th time HR EEV step M Ex) 300 steps 3, 0, 0
Push 23th time Fan step ( SSR or BLDC ) N Ex) 13 steps Off, 1, 3
Push 24th time Version
56
Downloaded from www.Manualslib.com manuals search engine
8 Error codes
F012
BC E
3456
D
789A
Installation
2 E-102 Communication error between indoor and outdoor unit. It displays in indoor unit.
3 E-121 Room temperature sensor of indoor unit. (Open or Short)
4 E-122 Eva_in temperature sensor of indoor unit. (Open or Short)
5 E-123 Eva_out temperature sensor of indoor unit. (Open or Short)
6 E-124 Communication error between indoor and outdoor unit. It displays in outdoor unit.
7 E-125 Mid 2 temperature sensor of indoor unit. (Open or Short)
8 E-128 Eva_in temperature sensor is detached from eva_in pipe of indoor unit.
9 E-129 Eva_out temperature sensor is detached from eva_out pipe of indoor unit.
Eva_in and Eva_out temperature sensors are detached from eva_in and out pipes of indoor unit at the same
10 E-130
time.
11 E-137 VOC sensor of ERV product. (Open or Short)
12 E-138 Gas sensor of ERV product. (Open or Short)
13 E-139 CO2 sensor of ERV product. (Open or Short )
14 E-151 EEV opening error of indoor unit (2nd detection)
15 E-152 EEV closing error of indoor unit (2nd detection)
16 E-153 Floating switch error of indoor unit (2nd detection)
17 E-154 RPM feed back error of indoor unit.
18 E-155 RPM feed back error of indoor unit. (The second motor of indoor unit)
Mixed operation mode of indoor units. It occurs when outdoor unit is operating or going to operate in
19 E-161 cooling mode(or heating mode) and then other indoor unit is going to operate in heating mode (or cooling
mode).
20 E-162 EEPROM error of MICOM. (Physical damage)
21 E-163 Option code error of indoor unit’s EEPROM.
22 E-167 Option setting error of indoor unit’s dip switch.
Temperature display setting error for USA market product.
23 E-170
(Mixed setting with Celsius and Fahrenheit temperature)
24 E-180 Opening error of cooling and heating solenoid valve simultaneously in MCU (1st detection)
25 E-181 Opening error of cooling and heating solenoid valve simultaneously in MCU (2nd detection)
26 E-185 Cross wiring error between communication and power of indoor unit.
27 E-190 No matching between indoor unit’s address and eva_in sensor in pipe checking operation.
28 E-191 No matching between indoor unit’s address and eva_out sensor in pipe checking operation.
29 E-199 It displays when pipe checking operation is not operated.
Communication error between indoor and outdoor unit (Tracking failure or the setting quantity of indoor unit
30 E-201
on outdoor unit’s PCB differs from the quantity of installed indoor unit.)
Communication error between indoor and outdoor unit.
31 E-202
(After tracking is completed, and then no response from indoor unit)
32 E-203 Communication error between main and sub outdoor unit
33 E-204 The setting quantity of MCU on outdoor unit’s PCB differs from the quantity of installed MCU.
57
Downloaded from www.Manualslib.com manuals search engine
8 Error codes
Installation
99 E-604 Tracking failure error between wired remote controller and indoor unit.
Communication error.
100 E-605
(7-day scheduler Wired remote controller or 7-day scheduler Centralized controller)
101 E-606 COM1/COM2 communication setting error. (Wired remote controller)
102 E-607 Two masters of wired remote controllers were installed in one COM2 communication line.
103 E-608 Can’t detect ERV controller.
104 E-609 Indoor unit is not detected for synchronous control.
105 E-610 Communication error between centralized controller and interface module.
106 E-611 Communication error between DMS and centralized controller.
107 E-613 Communication error between DMS and SIM interface module.
108 E-614 Communication error between SIM and power meter.
109 E-615 Communication error between interface module and indoor unit.
110 E-616 Communication error between interface module and outdoor unit.
111 E-618 The connected indoor units to ERV exceeded 16 units.
112 E-619 Mixed temperature display setting of indoor units which was connected to MWR-WS00 (Celsius/Fahrenheit)
113 E-620 Temperature display setting error of MWR-WS00 (Celsius/Fahrenheit)
114 E-621 Option switch setting error of wired remote controller (Master/Slave)
115 E-652 Two wired remote controllers were set to the master mode. (COM 1 wiring)
116 E-653 Room temperature sensor in the wired remote controller. (Open or Short)
117 E-654 Memory data error in the wired remote controller. (MWR-WS00)
118 P-701 Floating switch error of indoor unit. (1st detection)
119 P-702 EEV closing error of indoor unit. (1st detection)
120 P-703 EEV opening error of indoor unit. (1st detection)
59
Downloaded from www.Manualslib.com manuals search engine
DVM Technical Data Book
DVM
2009.12
DB98-31306A(1)
Specification may be subject to change without prior notice for the continuous product improvement.