You are on page 1of 9

TECHNICAL DATA Data sheet for sizing

AMBIENT Temperature 0 ... 55ºC (Models from 85 to 365 A) standard operation at rated current Fill out the form below and send it to WEG or to one of our distributors near your company allowing us to provide you the best solution for smooth starts,
CONDITIONS Humidity 20 ... 90%, non condensing smooth stops and protection of your electrical motor.
Altitude 0 ... 1000 m: standard operation at rated current
1000 ... 4000 m: with output current reduction of 1% / 100 m, above 1000 m General information
FINISHING Colour Cover: Opaque Gray
Cabinet: Opaque Blue Company: Phone:
CONFORMITIES/ Safety UL 508 Standard – Industrial Control Equipment City / State: Fax:
STANDARDS Low Voltage EN 60947-4-2 Standard; LVD 73/23/EEC – Low Voltage Directive
EMC EMC directive 89 / 336 / EEC – Industrial Environment
Contact person: E-mail:
UL (USA) / cUL (Canada) Underwriters Laboratories Inc. – USA (Pending) Application / Load:
CE (Europe) Phoenix Test-Lab / Alemanha (Pending)
IRAM (Argentina) Instituto Argentino de Normalización (Pending) Application Data
C-Tick (Australia) Australian Communications Authority (Pending)
Rated Output: No of poles / Rated Speed: Nameplate voltage and current:
........................ kW [ ] 2 Poles ( 3600 rpm ) [ ] 220 V ⇒ ................. A
Service Factor: [ ] 4 Poles ( 1800 rpm ) [ ] 380 V ⇒ ................. A
CODING S.F. = ........................ [ ] 6 Poles ( 1200 rpm ) [ ] 440 V ⇒ ................. A
MOTOR
[ ] 8 Poles ( 900 rpm ) [ ] ........ V ⇒ ................. A
Is it used? [ ] ....... Poles ( .............rpm )
SSW06 0085 T 2257 E O 00 SI A1 DN H1 S3 Z
[ ] No No of starts an hour:
[ ] Yes ................. Starts / Hour
1 2 3 4 5 6 7 8 9 10 11 12 13
Load Type: Load frictional torque reflected to the motor shaft:
1 - Soft-Starter Line SSW-06 [ ] Pumps .........................................Nm
[ ] Centrifugal Pump .........................................kgfm
2 - Soft starter rated output current 0085 = 85 A [ ] Piston Compressor
0130 = 130 A
LOAD
[ ] Screw Compressor
0170 = 170 A [ ] Fan and Exhaustor Load inertia reflected to the motor shaft
0205 = 205 A [ ] Mixer ........................................kgm2
0255 = 255 A
[ ] Centrifugals
0312 = 312 A
0365 = 365 A [ ] Others
Power Supply: Installation Conditions:
[ ] 230 V Altitude: Environment: Temperature:
3 - Power Supply: T= Three-phase
[ ] 400 V [ ] 50 Hz [ ] up to 1000 m [ ] Normal [ ] up to 40 °C
220 / 230 / 240 / 380 / 400 / 415 /
4 - Supply Voltage: 2257 = 220- 575 VAC [ ] 460 V [ ] 60 Hz [ ] .............. m [ ] Agressive [ ] ........... °C
440 / 460 / 480 / 525 / 575 V
[ ] ............... V
INSTALLATION
5 - Manual Language: P = Portuguese Degree of protection required: Control Method:
E = English [ ] IP 00 ( open without protection ) [ ] Start / Stop buttons
S = Spanish [ ] IP 20 ( protection againts touch) [ ] Keypad
[ ] IP 54 ( panel mounted )
[ ] Outdoor ( special rain panel )
6 - Product Version: 11 - Special Hardware:
S = Standard blank = Standard [ ] ................................. ( to be specified )
O = with Optionals Notes
12 - Special Software:
7 - Degree of protection: blank = Standard

771.03/062005 - Data subject to change without previous notice.


blank = Standard (See technical data table )
13 - End of code:
8 - Human Machine Interface (HMI):
Z = Digit indicating end of product codification
blank= Standard (with HMI LED’s + LCD)
SI = without HMI

9 - Expansion cards:
blanck = Standard
A1 = Optional CSI-2 (RS485)
If necessary to send us more specific information, please send them as attachment.

WEG EURO
INDÚSTRIA ELÉCTRICA, S.A.
WEG GERMANY GmbH
Phone: +49 (2234) 9 5353-0
WEG SCANDINAVIA AB
Phone: (46) 300 73400
Soft-Starter
Phone: +351 229 477 708/700 info@weg-germany.de info@weg.se
10 - Fieldbus communication cards Examples: sales@weg.com.pt wg.weg.com.br
www.weg.com.pt
blank = Standard (no extra card) WEG ITALIA S.R.L. WEG IBERIA S.A.
PD = Optional KFB – PD card (Profibus DP) SSW06 0085 T 2257 E S Z Phone: (39) 02 6129-3535 Phone: (34) 916 553 008
info@wegitalia.com wegiberia@wegiberia.es
DN = Optional KFB – DN card (DeviceNet) SSW06 0255 T 2257 E O SI A1 PD Z WEG EXPORTADORA S.A. WEG NETHERLANDS www.wegiberia.es
Phone: +55 47 372 4002 WEG Europe S.A. WEG EUROPE S.A.
Fax: +55 47 372 4060 Phone: +31 (0) 570-620550 Phone: + 32 (67) 88-8420 WEG ELECTRIC MOTORS (U.K.) LTD.
wex-mark@weg.com.br info@weg-netherlands.nl info@wegeurope.be Phone : 44 (01527) 596-748
www.weg.com.br www.weg-netherlands.nl www.wegeurope.be wegsales@wegelectricmotors.co.uk

9
SSW-06 Series Soft-Starters are static SPECIFICATION TABLE TECHNICAL CHARACTERISTICS
star ters, designed for the acceleration, SOFT-STARTER SSW-06 MAXIMUM MOTOR
Power Supply Voltage
Frequency
220 / 230 / 240 / 380 / 400 / 415 / 440 / 460 / 480 / 525 / 575 V ( + 10 % , - 15 % )
50 / 60 Hz ( +- 10% )
Line
deceleration and protection of three phase Voltage Model I nominal (A)
3-wires connection (3 cables) Inside Delta Connection (6 cables)
Size Enclosure
Electronic
Metallic Cabinet
Switched mode power supply with RFI filter (90 - 250 VAC) / Fan 110 or 220 V only for frame size 4
IP 00
Voltage
induction motors. The voltage control (electronic:
90-250 VCA) (V)
Ta=0...55°C Ta=0...55°C
Control
Method
Power Suppy
Motor voltage variation (Three-phase induction motor)
Switched mode
Ta=0...45°C Ta=0...55°C HP kW HP kW
applied to the motor, by means of thyristor SSW06.85 85 85 30 22 50 37 2 Starting Duty Cycle
CPU
Normal
32 bits RISC Microprocessor
300 % (3 x Inom.) during 30 s
firing angle variation, allows smooth FEATURES SSW06.130 130 130 50 37 75 55 2 ( 10 starts / Hour )
Inputs
Heavy
Digitals
450 % (4.5 x Inom.) during 30 s with 33% rated current reduction
6 programmable isolated inputs 24 VDC
SSW06.170 170 170 60 45 100 75 3

220/230/240/380/400/415/440/460/480/525/575 V
starting and stopping. •Electronic motor protection SSW06.205 205 205 230 75 55 125 90 3
Outputs Relay
Analogues
3 programmable outputs 250 VAC / 2 A: (02 x NO) + (01 x NO + NC - Fault indication)
1 programmable output (14 bits ) 0 -10 VDC
With proper variable adjustment it is possible •Incorporated electronic thermal relay SSW06.255 255 255 100 75 150 110 4 1 programmable output (14 bits ) 0 - 20mA or 4 - 20mA
SSW06.312 312 312 125 90 200 150 4 Safety Protections Over voltage Phase loss power supply
to optimise the motor starting torque so that the •Detachable man-machine interface with double display SSW06.365 365 365 150 110 250 185 4 Under voltage Motor phase loss)
(LED/LCD) SSW06.85 85 85 50 37 75 55 2 Output over current (motor) Thyristor fault
starting current is as low as possible. •Kick-start function for heavy duty and functional loads SSW06.130 130 130 75 55 125 90 2
Immediate over current at motor output
Motor overload – i²t
CPU Error (Watchdog)
Programming error
SSW06.170 170 170 125 90 200 150 3
WEG Soft-Starters, microprocessor based with high starting torque SSW06.205 205 205 400 150 110 250 185 3
Thyristors over temperature / Heat sink
Phase sequency
Serial communication error
Self diagnose error
and totally digital, are products with state-of-the- •Pump Control function for intelligent pumping systems SSW06.255 255 255 175 130 300 220 4 External Fault HMI-SSW06-LCD communication error
Open by-pass contact
art technology and are produced to ensure the •Avoids pipeline water hammer SSW06.312 312 312 200 150 350 260 4
Overcurrent before the By-pass
SSW06.365 365 365 250 185 400 300 4
•Limits current inrush SSW06.85 85 85 75 55 125 90 2
Immediate by-pass overcurrent
highest performance in the starting and •Limits line voltage drop SSW06.130 130 130 125 90 200 150 2
Functions / Standard Built-in operator interface detachable with double display LED + LCD (HMI-SSW06-LCD)
Programming enabling password
Resources
stopping of induction motors, presenting •International voltages (220 to 575 VAC) SSW06.170 170 170 150 110 300 220 3 LCD display Language selection: Portuguese, English, Spanish and German
SSW06.205 205 205 525 175 130 350 260 3 Local / Remote operation selection
themselves as a complete and low-cost •Switched mode power supply with RFI filter SSW06.255 255 255 250 185 400 300 4 Fault self-diagnosis
PUMP CONTROL function (Water hammer protection for pumps)
solution. (90 to 250 VAC) SSW06.312 312 312 270 200 500 370 4
COPY function (Soft-Starter → HMI or HMI → Soft-Starter)
•Incorporated by-pass contactor (85 to 365A) reduces SSW06.365 365 365 350 260 600 450 4 Soft starter integrated by-pass contactor (Models 85 to 365 A)
The man-machine interface permits easy installation size and increases energy savings
SSW06.85 85 85 75 55 150 110 2 Serial Interface RS-232
SSW06.130 130 130 125 90 200 150 2 Motor PTC thermistor input
parameter adjustment, making easier •Thermal image back-up - i x t values SSW06.170 170 170 150 110 300 220 3 Programmable line voltage 220 - 575 VAC
575 Programmable initial (pedestal) voltage 25 - 90% of line voltage
start-up and operation. The incorporated •Protection through voltage and current unbalance SSW06.205 205 205 200 150 350 260 3
Programmable acceleration ramp 1 - 299 s
SSW06.255 255 255 250 185 450 330 4 Programmable deceleration ramp OFF, 2 - 299 s
“Pump Control” feature avoids pipeline •Over/under voltage and over/under current protection SSW06.312 312 312 300 220 550 400 4 Programmable step down voltage for deceleration 100 ... 40% of nominal voltage
•Motor PTC thermistor input SSW06.365 365 365 350 260 650 475 4 Programmable starting current limit OFF, 150 - 500% of motor rated current
water hammer. •Eliminates mechanical shock Programmable immediate overcurrent 0 - 99% of motor rated current
Programmable immediate overcurrent time OFF, 0 - 99 s
•Stress reduction on couplings and other transmission Programmable immediate undercurrent 0 ... 99% of motor rated current
Programmable immediate undercurrent time OFF, 1 - 99 s
devices (gear boxes, sheaves, belts, etc) Level: 30 - 50% of line voltage
Programmable starting torque boost in voltage or
•Increases motor and mechanical parts life current (KICK-START)
Level: 300 - 700% of soft starter rated current
Duration: 1 - 10 s
•Multi-motor starting possibility (parallel or cascade) Programmable fault auto-reset OFF, 10 - 600 s
Programmable motor thermal memory auto-reset OFF, 1 - 600 s
•Easy operation, programming and troubleshooting Motor thermal overload protection class 0 (inactive); 5; 10; 15; 20; 25; 30; 35; 40; 45
through man-machine interface Motor service factor 0 (inactive); 0.8 - 1.50
Optionals Cable for keypad remote connection (1; 2; 3; 5 and 7.5 m) CAB-HMI-SSW06-X
•Simplified electrical wiring Serial interface RS-485
Additional
CSI-2
•Oriented Start-up Operating Interface Command Start / Stop, Reset and Programming
(HMI-SSW06-LCD) Increment and decrement parameters and its content
•Possibility of 3 cables connection or Display readings Output current (Soft-Starter) - (% of soft starter rated current)
Output current (Motor) - (Amps)
6 cables - INSIDE DELTA CONNECTION Output current (Motor) - (% of motor rated current)
•32 bits microprocessor Line frequency (0 - 99.9 Hz)
Line Voltage(0 - 999VAC)
•Surface mounted devices (SMD) Soft starter output voltage - (0 - 999VAC)
•Ambient temperature up to 55 °C without derating Load active power – (kW)
Load apparent power – (kVA)
•Complying with International Standards: Soft starter status
UL, cUL, CE, IRAM and C-Tick Digital and analogue I/Os status
Load Cos (ϕ) – (0.00 - 0.99)
Energyzed time
Enabled time
Four last faults back-up
Soft starter firmware version
Motor thermal protection – (0 - 250)
Current indication in each phase R-S-T
Line voltage indication R-S / S-T / T-R
Size 02 Size 03 Size 04

2 7 8
MAIN FUNCTIONS MAIN APPLICATIONS • Centrifugal Pumps / Alternative Pumps
(Wastewater / Irrigation / Oil)
• Fans / Exhaustors / Blowers
RAMPS KICK-START • Air Compressors / HVAC
• Mixers / Aerators
Voltage
• Centrifuges
Voltage
• Crushers / Grinders
• Wood Chippers
Booster • Paper Refiners
• Rotating Kilns
t (s)
Acceleration Deceleration • Saws and Planers (Wood)
Allows smooth acceleration and deceleration. In the acceleration a
t (s)
• Ball Mils / Hammer Mills
pedestal voltage can be adjusted. In the deceleration a step down Initial voltage pulse which generates a torque peak necessary to start a • Load Transportation:
voltage can be adjusted. Deceleration ramp avoids pump water hammer. high break-away torque load.
- Conveyors / Belts / Chains
- Roller Tables
- Monorails
UNDER / OVER CURRENT PROTECTION BUILT-IN BY-PASS - Escalators
- Baggage Conveyors (Airports)
Current - Bottling Lines
3- phase
Over current level 3-phase
power
supply motor STARTING METHODS
Under current level
COMPARISON
t (s)
Adjustable maximum and minimum current levels for complete motor
protection. Undercurrent protection is ideal to protect pumps Built-in By-pass minimizes the power losses and heat dissipation
running at no load. at the thyristors, providing space reduction and energy saving.

WEIGHT AND DIMENSION HUMAN-MACHINE INTERFACE


Intelligent Interface
W
Double display, intelligent inter face, LED’s (7
Display LEDs
(7 segments)
segments) and LCD (2 lines and 16 characters), that
allow excellent long distance visualisation, besides
incorporating a detailed description of all the
parameters and messages via alphanumeric LCD
H
display.
HEIGHT WIDTH DEPTH WEIGHT
LINE SIZE H (mm) W (mm) D (mm) (kg) Select the Language
Liquid Cristal The intelligent operation interface also permits the user
Display (LCD)
D
2 370 132 244 8.50 of the product to choose, for his/her convenience,
3 440 223 278 18.60 the programming, language reading and
4 550 370 311 39.50 presentation of the parameters and alphanumeric
messages through the LCD display (Liquid Cristal).

LOCAL LED The elevated hardware and software capacity of the


REMOTE LED product gives the user various language options, like:
Portuguese, English, German and Spanish, in order
to adapt it to any user in the world.
COUNTER CLOCKWISE LED

CLOCKWISE LED

6 3
COPY Function ACCESSORIES AND PERIPHERALS
The Intelligent interface also incorporates the “Copy”
function, that permits copying the parameters of one INTERCONNECTION CABLES FOR
Cable length (X): 1; 2; 3; 5; 7.5m.
Soft-Starter to another, allowing higher programming REMOTE INTERFACE
Special cables with larger sizes on request.
speed, reliability and programming repetition in CAB - HMI-SSW06-X
applications of serial manufacturing machines.
Soft-Starter “A” Soft-Starter “B”

CONNECTIONG OPTIONS (SOFT-STARTER MOTOR)

SSW-06 HMI HMI SSW-06 Standard (3 leads) Within the Delta (6 leads)

Remote Human-Machine Interface for remote installation


on panel door or machine console.

Motor in star Motor in delta Soft-Starter within the delta connection


connection connection
KEYPAD FUNCTIONS Starts the Soft-Starter
ISoft-Starter = IMotor
ISoft-Starter = IMotor = 57% of IMotor
√3
Stops the Soft-Starter
Errors reset in the Soft-Starter
MOTOR 6 Cable Connection
Increases the parameter number or its content
220 / 380V 220V
380 / 660V 380V
Decreases the parameter number or its content 400/690V 400V
415V 415V
Switches the display between the parameter number and its 440 / 760V 440V
content (position/content) for programming 525V 525V
575V 575V
220 / 380 / 440 / 760V 220 / 440V
While pressed the motor is run at JOG speed
IMPORTANT:
1 - In the standard start-up (3 leads) the motor can be connected either in Star or Delta.
FWD/REV key. When pressed reverses the direction of
2 - For the same motor power, in the connection type within the delta of the motor (6 leads), the Soft-Starter is 43% smaller than the one necessary
rotation with auxiliar of external contactors
in a standard connection (3 leads). With the Soft-Starter within the delta of the motor, one can start a motor with a power 73% greater than in the
standard connection (3 leads).
3 - For the start-up type within the delta of the motor (6 leads), the supply transformer should have the secundary connected in star and grounded.
Selects the soft starter operating mode defining the
commands and references as Local or Remote.

4 5
COPY Function ACCESSORIES AND PERIPHERALS
The Intelligent interface also incorporates the “Copy”
function, that permits copying the parameters of one INTERCONNECTION CABLES FOR
Cable length (X): 1; 2; 3; 5; 7.5m.
Soft-Starter to another, allowing higher programming REMOTE INTERFACE
Special cables with larger sizes on request.
speed, reliability and programming repetition in CAB - HMI-SSW06-X
applications of serial manufacturing machines.
Soft-Starter “A” Soft-Starter “B”

CONNECTIONG OPTIONS (SOFT-STARTER MOTOR)

SSW-06 HMI HMI SSW-06 Standard (3 leads) Within the Delta (6 leads)

Remote Human-Machine Interface for remote installation


on panel door or machine console.

Motor in star Motor in delta Soft-Starter within the delta connection


connection connection
KEYPAD FUNCTIONS Starts the Soft-Starter
ISoft-Starter = IMotor
ISoft-Starter = IMotor = 57% of IMotor
√3
Stops the Soft-Starter
Errors reset in the Soft-Starter
MOTOR 6 Cable Connection
Increases the parameter number or its content
220 / 380V 220V
380 / 660V 380V
Decreases the parameter number or its content 400/690V 400V
415V 415V
Switches the display between the parameter number and its 440 / 760V 440V
content (position/content) for programming 525V 525V
575V 575V
220 / 380 / 440 / 760V 220 / 440V
While pressed the motor is run at JOG speed
IMPORTANT:
1 - In the standard start-up (3 leads) the motor can be connected either in Star or Delta.
FWD/REV key. When pressed reverses the direction of
2 - For the same motor power, in the connection type within the delta of the motor (6 leads), the Soft-Starter is 43% smaller than the one necessary
rotation with auxiliar of external contactors
in a standard connection (3 leads). With the Soft-Starter within the delta of the motor, one can start a motor with a power 73% greater than in the
standard connection (3 leads).
3 - For the start-up type within the delta of the motor (6 leads), the supply transformer should have the secundary connected in star and grounded.
Selects the soft starter operating mode defining the
commands and references as Local or Remote.

4 5
MAIN FUNCTIONS MAIN APPLICATIONS • Centrifugal Pumps / Alternative Pumps
(Wastewater / Irrigation / Oil)
• Fans / Exhaustors / Blowers
RAMPS KICK-START • Air Compressors / HVAC
• Mixers / Aerators
Voltage
• Centrifuges
Voltage
• Crushers / Grinders
• Wood Chippers
Booster • Paper Refiners
• Rotating Kilns
t (s)
Acceleration Deceleration • Saws and Planers (Wood)
Allows smooth acceleration and deceleration. In the acceleration a
t (s)
• Ball Mils / Hammer Mills
pedestal voltage can be adjusted. In the deceleration a step down Initial voltage pulse which generates a torque peak necessary to start a • Load Transportation:
voltage can be adjusted. Deceleration ramp avoids pump water hammer. high break-away torque load.
- Conveyors / Belts / Chains
- Roller Tables
- Monorails
UNDER / OVER CURRENT PROTECTION BUILT-IN BY-PASS - Escalators
- Baggage Conveyors (Airports)
Current - Bottling Lines
3- phase
Over current level 3-phase
power
supply motor STARTING METHODS
Under current level
COMPARISON
t (s)
Adjustable maximum and minimum current levels for complete motor
protection. Undercurrent protection is ideal to protect pumps Built-in By-pass minimizes the power losses and heat dissipation
running at no load. at the thyristors, providing space reduction and energy saving.

WEIGHT AND DIMENSION HUMAN-MACHINE INTERFACE


Intelligent Interface
W
Double display, intelligent inter face, LED’s (7
Display LEDs
(7 segments)
segments) and LCD (2 lines and 16 characters), that
allow excellent long distance visualisation, besides
incorporating a detailed description of all the
parameters and messages via alphanumeric LCD
H
display.
HEIGHT WIDTH DEPTH WEIGHT
LINE SIZE H (mm) W (mm) D (mm) (kg) Select the Language
Liquid Cristal The intelligent operation interface also permits the user
Display (LCD)
D
2 370 132 244 8.50 of the product to choose, for his/her convenience,
3 440 223 278 18.60 the programming, language reading and
4 550 370 311 39.50 presentation of the parameters and alphanumeric
messages through the LCD display (Liquid Cristal).

LOCAL LED The elevated hardware and software capacity of the


REMOTE LED product gives the user various language options, like:
Portuguese, English, German and Spanish, in order
to adapt it to any user in the world.
COUNTER CLOCKWISE LED

CLOCKWISE LED

6 3
SSW-06 Series Soft-Starters are static SPECIFICATION TABLE TECHNICAL CHARACTERISTICS
star ters, designed for the acceleration, SOFT-STARTER SSW-06 MAXIMUM MOTOR
Power Supply Voltage
Frequency
220 / 230 / 240 / 380 / 400 / 415 / 440 / 460 / 480 / 525 / 575 V ( + 10 % , - 15 % )
50 / 60 Hz ( +- 10% )
Line
deceleration and protection of three phase Voltage Model I nominal (A)
3-wires connection (3 cables) Inside Delta Connection (6 cables)
Size Enclosure
Electronic
Metallic Cabinet
Switched mode power supply with RFI filter (90 - 250 VAC) / Fan 110 or 220 V only for frame size 4
IP 00
Voltage
induction motors. The voltage control (electronic:
90-250 VCA) (V)
Ta=0...55°C Ta=0...55°C
Control
Method
Power Suppy
Motor voltage variation (Three-phase induction motor)
Switched mode
Ta=0...45°C Ta=0...55°C HP kW HP kW
applied to the motor, by means of thyristor SSW06.85 85 85 30 22 50 37 2 Starting Duty Cycle
CPU
Normal
32 bits RISC Microprocessor
300 % (3 x Inom.) during 30 s
firing angle variation, allows smooth FEATURES SSW06.130 130 130 50 37 75 55 2 ( 10 starts / Hour )
Inputs
Heavy
Digitals
450 % (4.5 x Inom.) during 30 s with 33% rated current reduction
6 programmable isolated inputs 24 VDC
SSW06.170 170 170 60 45 100 75 3

220/230/240/380/400/415/440/460/480/525/575 V
starting and stopping. •Electronic motor protection SSW06.205 205 205 230 75 55 125 90 3
Outputs Relay
Analogues
3 programmable outputs 250 VAC / 2 A: (02 x NO) + (01 x NO + NC - Fault indication)
1 programmable output (14 bits ) 0 -10 VDC
With proper variable adjustment it is possible •Incorporated electronic thermal relay SSW06.255 255 255 100 75 150 110 4 1 programmable output (14 bits ) 0 - 20mA or 4 - 20mA
SSW06.312 312 312 125 90 200 150 4 Safety Protections Over voltage Phase loss power supply
to optimise the motor starting torque so that the •Detachable man-machine interface with double display SSW06.365 365 365 150 110 250 185 4 Under voltage Motor phase loss)
(LED/LCD) SSW06.85 85 85 50 37 75 55 2 Output over current (motor) Thyristor fault
starting current is as low as possible. •Kick-start function for heavy duty and functional loads SSW06.130 130 130 75 55 125 90 2
Immediate over current at motor output
Motor overload – i²t
CPU Error (Watchdog)
Programming error
SSW06.170 170 170 125 90 200 150 3
WEG Soft-Starters, microprocessor based with high starting torque SSW06.205 205 205 400 150 110 250 185 3
Thyristors over temperature / Heat sink
Phase sequency
Serial communication error
Self diagnose error
and totally digital, are products with state-of-the- •Pump Control function for intelligent pumping systems SSW06.255 255 255 175 130 300 220 4 External Fault HMI-SSW06-LCD communication error
Open by-pass contact
art technology and are produced to ensure the •Avoids pipeline water hammer SSW06.312 312 312 200 150 350 260 4
Overcurrent before the By-pass
SSW06.365 365 365 250 185 400 300 4
•Limits current inrush SSW06.85 85 85 75 55 125 90 2
Immediate by-pass overcurrent
highest performance in the starting and •Limits line voltage drop SSW06.130 130 130 125 90 200 150 2
Functions / Standard Built-in operator interface detachable with double display LED + LCD (HMI-SSW06-LCD)
Programming enabling password
Resources
stopping of induction motors, presenting •International voltages (220 to 575 VAC) SSW06.170 170 170 150 110 300 220 3 LCD display Language selection: Portuguese, English, Spanish and German
SSW06.205 205 205 525 175 130 350 260 3 Local / Remote operation selection
themselves as a complete and low-cost •Switched mode power supply with RFI filter SSW06.255 255 255 250 185 400 300 4 Fault self-diagnosis
PUMP CONTROL function (Water hammer protection for pumps)
solution. (90 to 250 VAC) SSW06.312 312 312 270 200 500 370 4
COPY function (Soft-Starter → HMI or HMI → Soft-Starter)
•Incorporated by-pass contactor (85 to 365A) reduces SSW06.365 365 365 350 260 600 450 4 Soft starter integrated by-pass contactor (Models 85 to 365 A)
The man-machine interface permits easy installation size and increases energy savings
SSW06.85 85 85 75 55 150 110 2 Serial Interface RS-232
SSW06.130 130 130 125 90 200 150 2 Motor PTC thermistor input
parameter adjustment, making easier •Thermal image back-up - i x t values SSW06.170 170 170 150 110 300 220 3 Programmable line voltage 220 - 575 VAC
575 Programmable initial (pedestal) voltage 25 - 90% of line voltage
start-up and operation. The incorporated •Protection through voltage and current unbalance SSW06.205 205 205 200 150 350 260 3
Programmable acceleration ramp 1 - 299 s
SSW06.255 255 255 250 185 450 330 4 Programmable deceleration ramp OFF, 2 - 299 s
“Pump Control” feature avoids pipeline •Over/under voltage and over/under current protection SSW06.312 312 312 300 220 550 400 4 Programmable step down voltage for deceleration 100 ... 40% of nominal voltage
•Motor PTC thermistor input SSW06.365 365 365 350 260 650 475 4 Programmable starting current limit OFF, 150 - 500% of motor rated current
water hammer. •Eliminates mechanical shock Programmable immediate overcurrent 0 - 99% of motor rated current
Programmable immediate overcurrent time OFF, 0 - 99 s
•Stress reduction on couplings and other transmission Programmable immediate undercurrent 0 ... 99% of motor rated current
Programmable immediate undercurrent time OFF, 1 - 99 s
devices (gear boxes, sheaves, belts, etc) Level: 30 - 50% of line voltage
Programmable starting torque boost in voltage or
•Increases motor and mechanical parts life current (KICK-START)
Level: 300 - 700% of soft starter rated current
Duration: 1 - 10 s
•Multi-motor starting possibility (parallel or cascade) Programmable fault auto-reset OFF, 10 - 600 s
Programmable motor thermal memory auto-reset OFF, 1 - 600 s
•Easy operation, programming and troubleshooting Motor thermal overload protection class 0 (inactive); 5; 10; 15; 20; 25; 30; 35; 40; 45
through man-machine interface Motor service factor 0 (inactive); 0.8 - 1.50
Optionals Cable for keypad remote connection (1; 2; 3; 5 and 7.5 m) CAB-HMI-SSW06-X
•Simplified electrical wiring Serial interface RS-485
Additional
CSI-2
•Oriented Start-up Operating Interface Command Start / Stop, Reset and Programming
(HMI-SSW06-LCD) Increment and decrement parameters and its content
•Possibility of 3 cables connection or Display readings Output current (Soft-Starter) - (% of soft starter rated current)
Output current (Motor) - (Amps)
6 cables - INSIDE DELTA CONNECTION Output current (Motor) - (% of motor rated current)
•32 bits microprocessor Line frequency (0 - 99.9 Hz)
Line Voltage(0 - 999VAC)
•Surface mounted devices (SMD) Soft starter output voltage - (0 - 999VAC)
•Ambient temperature up to 55 °C without derating Load active power – (kW)
Load apparent power – (kVA)
•Complying with International Standards: Soft starter status
UL, cUL, CE, IRAM and C-Tick Digital and analogue I/Os status
Load Cos (ϕ) – (0.00 - 0.99)
Energyzed time
Enabled time
Four last faults back-up
Soft starter firmware version
Motor thermal protection – (0 - 250)
Current indication in each phase R-S-T
Line voltage indication R-S / S-T / T-R
Size 02 Size 03 Size 04

2 7 8
SSW-06 Series Soft-Starters are static SPECIFICATION TABLE TECHNICAL CHARACTERISTICS
star ters, designed for the acceleration, SOFT-STARTER SSW-06 MAXIMUM MOTOR
Power Supply Voltage
Frequency
220 / 230 / 240 / 380 / 400 / 415 / 440 / 460 / 480 / 525 / 575 V ( + 10 % , - 15 % )
50 / 60 Hz ( +- 10% )
Line
deceleration and protection of three phase Voltage Model I nominal (A)
3-wires connection (3 cables) Inside Delta Connection (6 cables)
Size Enclosure
Electronic
Metallic Cabinet
Switched mode power supply with RFI filter (90 - 250 VAC) / Fan 110 or 220 V only for frame size 4
IP 00
Voltage
induction motors. The voltage control (electronic:
90-250 VCA) (V)
Ta=0...55°C Ta=0...55°C
Control
Method
Power Suppy
Motor voltage variation (Three-phase induction motor)
Switched mode
Ta=0...45°C Ta=0...55°C HP kW HP kW
applied to the motor, by means of thyristor SSW06.85 85 85 30 22 50 37 2 Starting Duty Cycle
CPU
Normal
32 bits RISC Microprocessor
300 % (3 x Inom.) during 30 s
firing angle variation, allows smooth FEATURES SSW06.130 130 130 50 37 75 55 2 ( 10 starts / Hour )
Inputs
Heavy
Digitals
450 % (4.5 x Inom.) during 30 s with 33% rated current reduction
6 programmable isolated inputs 24 VDC
SSW06.170 170 170 60 45 100 75 3

220/230/240/380/400/415/440/460/480/525/575 V
starting and stopping. •Electronic motor protection SSW06.205 205 205 230 75 55 125 90 3
Outputs Relay
Analogues
3 programmable outputs 250 VAC / 2 A: (02 x NO) + (01 x NO + NC - Fault indication)
1 programmable output (14 bits ) 0 -10 VDC
With proper variable adjustment it is possible •Incorporated electronic thermal relay SSW06.255 255 255 100 75 150 110 4 1 programmable output (14 bits ) 0 - 20mA or 4 - 20mA
SSW06.312 312 312 125 90 200 150 4 Safety Protections Over voltage Phase loss power supply
to optimise the motor starting torque so that the •Detachable man-machine interface with double display SSW06.365 365 365 150 110 250 185 4 Under voltage Motor phase loss)
(LED/LCD) SSW06.85 85 85 50 37 75 55 2 Output over current (motor) Thyristor fault
starting current is as low as possible. •Kick-start function for heavy duty and functional loads SSW06.130 130 130 75 55 125 90 2
Immediate over current at motor output
Motor overload – i²t
CPU Error (Watchdog)
Programming error
SSW06.170 170 170 125 90 200 150 3
WEG Soft-Starters, microprocessor based with high starting torque SSW06.205 205 205 400 150 110 250 185 3
Thyristors over temperature / Heat sink
Phase sequency
Serial communication error
Self diagnose error
and totally digital, are products with state-of-the- •Pump Control function for intelligent pumping systems SSW06.255 255 255 175 130 300 220 4 External Fault HMI-SSW06-LCD communication error
Open by-pass contact
art technology and are produced to ensure the •Avoids pipeline water hammer SSW06.312 312 312 200 150 350 260 4
Overcurrent before the By-pass
SSW06.365 365 365 250 185 400 300 4
•Limits current inrush SSW06.85 85 85 75 55 125 90 2
Immediate by-pass overcurrent
highest performance in the starting and •Limits line voltage drop SSW06.130 130 130 125 90 200 150 2
Functions / Standard Built-in operator interface detachable with double display LED + LCD (HMI-SSW06-LCD)
Programming enabling password
Resources
stopping of induction motors, presenting •International voltages (220 to 575 VAC) SSW06.170 170 170 150 110 300 220 3 LCD display Language selection: Portuguese, English, Spanish and German
SSW06.205 205 205 525 175 130 350 260 3 Local / Remote operation selection
themselves as a complete and low-cost •Switched mode power supply with RFI filter SSW06.255 255 255 250 185 400 300 4 Fault self-diagnosis
PUMP CONTROL function (Water hammer protection for pumps)
solution. (90 to 250 VAC) SSW06.312 312 312 270 200 500 370 4
COPY function (Soft-Starter → HMI or HMI → Soft-Starter)
•Incorporated by-pass contactor (85 to 365A) reduces SSW06.365 365 365 350 260 600 450 4 Soft starter integrated by-pass contactor (Models 85 to 365 A)
The man-machine interface permits easy installation size and increases energy savings
SSW06.85 85 85 75 55 150 110 2 Serial Interface RS-232
SSW06.130 130 130 125 90 200 150 2 Motor PTC thermistor input
parameter adjustment, making easier •Thermal image back-up - i x t values SSW06.170 170 170 150 110 300 220 3 Programmable line voltage 220 - 575 VAC
575 Programmable initial (pedestal) voltage 25 - 90% of line voltage
start-up and operation. The incorporated •Protection through voltage and current unbalance SSW06.205 205 205 200 150 350 260 3
Programmable acceleration ramp 1 - 299 s
SSW06.255 255 255 250 185 450 330 4 Programmable deceleration ramp OFF, 2 - 299 s
“Pump Control” feature avoids pipeline •Over/under voltage and over/under current protection SSW06.312 312 312 300 220 550 400 4 Programmable step down voltage for deceleration 100 ... 40% of nominal voltage
•Motor PTC thermistor input SSW06.365 365 365 350 260 650 475 4 Programmable starting current limit OFF, 150 - 500% of motor rated current
water hammer. •Eliminates mechanical shock Programmable immediate overcurrent 0 - 99% of motor rated current
Programmable immediate overcurrent time OFF, 0 - 99 s
•Stress reduction on couplings and other transmission Programmable immediate undercurrent 0 ... 99% of motor rated current
Programmable immediate undercurrent time OFF, 1 - 99 s
devices (gear boxes, sheaves, belts, etc) Level: 30 - 50% of line voltage
Programmable starting torque boost in voltage or
•Increases motor and mechanical parts life current (KICK-START)
Level: 300 - 700% of soft starter rated current
Duration: 1 - 10 s
•Multi-motor starting possibility (parallel or cascade) Programmable fault auto-reset OFF, 10 - 600 s
Programmable motor thermal memory auto-reset OFF, 1 - 600 s
•Easy operation, programming and troubleshooting Motor thermal overload protection class 0 (inactive); 5; 10; 15; 20; 25; 30; 35; 40; 45
through man-machine interface Motor service factor 0 (inactive); 0.8 - 1.50
Optionals Cable for keypad remote connection (1; 2; 3; 5 and 7.5 m) CAB-HMI-SSW06-X
•Simplified electrical wiring Serial interface RS-485
Additional
CSI-2
•Oriented Start-up Operating Interface Command Start / Stop, Reset and Programming
(HMI-SSW06-LCD) Increment and decrement parameters and its content
•Possibility of 3 cables connection or Display readings Output current (Soft-Starter) - (% of soft starter rated current)
Output current (Motor) - (Amps)
6 cables - INSIDE DELTA CONNECTION Output current (Motor) - (% of motor rated current)
•32 bits microprocessor Line frequency (0 - 99.9 Hz)
Line Voltage(0 - 999VAC)
•Surface mounted devices (SMD) Soft starter output voltage - (0 - 999VAC)
•Ambient temperature up to 55 °C without derating Load active power – (kW)
Load apparent power – (kVA)
•Complying with International Standards: Soft starter status
UL, cUL, CE, IRAM and C-Tick Digital and analogue I/Os status
Load Cos (ϕ) – (0.00 - 0.99)
Energyzed time
Enabled time
Four last faults back-up
Soft starter firmware version
Motor thermal protection – (0 - 250)
Current indication in each phase R-S-T
Line voltage indication R-S / S-T / T-R
Size 02 Size 03 Size 04

2 7 8
TECHNICAL DATA Data sheet for sizing
AMBIENT Temperature 0 ... 55ºC (Models from 85 to 365 A) standard operation at rated current Fill out the form below and send it to WEG or to one of our distributors near your company allowing us to provide you the best solution for smooth starts,
CONDITIONS Humidity 20 ... 90%, non condensing smooth stops and protection of your electrical motor.
Altitude 0 ... 1000 m: standard operation at rated current
1000 ... 4000 m: with output current reduction of 1% / 100 m, above 1000 m General information
FINISHING Colour Cover: Opaque Gray
Cabinet: Opaque Blue Company: Phone:
CONFORMITIES/ Safety UL 508 Standard – Industrial Control Equipment City / State: Fax:
STANDARDS Low Voltage EN 60947-4-2 Standard; LVD 73/23/EEC – Low Voltage Directive
EMC EMC directive 89 / 336 / EEC – Industrial Environment
Contact person: E-mail:
UL (USA) / cUL (Canada) Underwriters Laboratories Inc. – USA (Pending) Application / Load:
CE (Europe) Phoenix Test-Lab / Alemanha (Pending)
IRAM (Argentina) Instituto Argentino de Normalización (Pending) Application Data
C-Tick (Australia) Australian Communications Authority (Pending)
Rated Output: No of poles / Rated Speed: Nameplate voltage and current:
........................ kW [ ] 2 Poles ( 3600 rpm ) [ ] 220 V ⇒ ................. A
Service Factor: [ ] 4 Poles ( 1800 rpm ) [ ] 380 V ⇒ ................. A
CODING S.F. = ........................ [ ] 6 Poles ( 1200 rpm ) [ ] 440 V ⇒ ................. A
MOTOR
[ ] 8 Poles ( 900 rpm ) [ ] ........ V ⇒ ................. A
Is it used? [ ] ....... Poles ( .............rpm )
SSW06 0085 T 2257 E O 00 SI A1 DN H1 S3 Z
[ ] No No of starts an hour:
[ ] Yes ................. Starts / Hour
1 2 3 4 5 6 7 8 9 10 11 12 13
Load Type: Load frictional torque reflected to the motor shaft:
1 - Soft-Starter Line SSW-06 [ ] Pumps .........................................Nm
[ ] Centrifugal Pump .........................................kgfm
2 - Soft starter rated output current 0085 = 85 A [ ] Piston Compressor
0130 = 130 A
LOAD
[ ] Screw Compressor
0170 = 170 A [ ] Fan and Exhaustor Load inertia reflected to the motor shaft
0205 = 205 A [ ] Mixer ........................................kgm2
0255 = 255 A
[ ] Centrifugals
0312 = 312 A
0365 = 365 A [ ] Others
Power Supply: Installation Conditions:
[ ] 230 V Altitude: Environment: Temperature:
3 - Power Supply: T= Three-phase
[ ] 400 V [ ] 50 Hz [ ] up to 1000 m [ ] Normal [ ] up to 40 °C
220 / 230 / 240 / 380 / 400 / 415 /
4 - Supply Voltage: 2257 = 220- 575 VAC [ ] 460 V [ ] 60 Hz [ ] .............. m [ ] Agressive [ ] ........... °C
440 / 460 / 480 / 525 / 575 V
[ ] ............... V
INSTALLATION
5 - Manual Language: P = Portuguese Degree of protection required: Control Method:
E = English [ ] IP 00 ( open without protection ) [ ] Start / Stop buttons
S = Spanish [ ] IP 20 ( protection againts touch) [ ] Keypad
[ ] IP 54 ( panel mounted )
[ ] Outdoor ( special rain panel )
6 - Product Version: 11 - Special Hardware:
S = Standard blank = Standard [ ] ................................. ( to be specified )
O = with Optionals Notes
12 - Special Software:
7 - Degree of protection: blank = Standard

771.03/062005 - Data subject to change without previous notice.


blank = Standard (See technical data table )
13 - End of code:
8 - Human Machine Interface (HMI):
Z = Digit indicating end of product codification
blank= Standard (with HMI LED’s + LCD)
SI = without HMI

9 - Expansion cards:
blanck = Standard
A1 = Optional CSI-2 (RS485)
If necessary to send us more specific information, please send them as attachment.

WEG EURO
INDÚSTRIA ELÉCTRICA, S.A.
WEG GERMANY GmbH
Phone: +49 (2234) 9 5353-0
WEG SCANDINAVIA AB
Phone: (46) 300 73400
Soft-Starter
Phone: +351 229 477 708/700 info@weg-germany.de info@weg.se
10 - Fieldbus communication cards Examples: sales@weg.com.pt wg.weg.com.br
www.weg.com.pt
blank = Standard (no extra card) WEG ITALIA S.R.L. WEG IBERIA S.A.
PD = Optional KFB – PD card (Profibus DP) SSW06 0085 T 2257 E S Z Phone: (39) 02 6129-3535 Phone: (34) 916 553 008
info@wegitalia.com wegiberia@wegiberia.es
DN = Optional KFB – DN card (DeviceNet) SSW06 0255 T 2257 E O SI A1 PD Z WEG EXPORTADORA S.A. WEG NETHERLANDS www.wegiberia.es
Phone: +55 47 372 4002 WEG Europe S.A. WEG EUROPE S.A.
Fax: +55 47 372 4060 Phone: +31 (0) 570-620550 Phone: + 32 (67) 88-8420 WEG ELECTRIC MOTORS (U.K.) LTD.
wex-mark@weg.com.br info@weg-netherlands.nl info@wegeurope.be Phone : 44 (01527) 596-748
www.weg.com.br www.weg-netherlands.nl www.wegeurope.be wegsales@wegelectricmotors.co.uk

You might also like