Installation Instructions
PK
(Catalog Numbers 1756-PA72, -PB72)
needle-nose pliers
20181–M
crimping tool
For this power supply And this voltage Set jumper to this position
1756-PA72 120V ac
low1
lo
1756-PB72 16-32V dc
1756-PA72 240V ac
high
ig
1756-PB72 19-32V dc2
1 Default setting for 1756-PA72 is low; default setting for 1756-PB72 is high.
2 If your input voltage falls below 19V for intervals of two minutes or less (e.g., motor cranking) and your
inputs and outputs are not affected by system input power voltages of 15V, set the the input jumper to the
low position.
20787–M
1. Align the circuit board of the power supply with the card guides on
the left side of the chassis.
20264a–M
20264a–M
push
20264a–M
Use the following figure to connect safety ground from the power
supply to the chassis.
Wiring terminal
block
Equipment grounding
conductor (ground lug Stationary nut
with 2.1 mm2 (14 AWG)
wire) safety ground
from power supply Equipment grounding
conductor (ground lug
with 2.1 mm2 (14 AWG)
Nut with captive wire) safety ground
star washer from chassis to ground
bus 30188
Earth Ground
20231a–M
Connect Power
1756-PA72
1756-PB72
20264b–M
Turn power ON
20789-M
Troubleshooting
The following warnings apply to products having CSA certification for use in hazardous locations.
l’étiquette du produit.
Les avertissements suivants s’appliquent aux produits ayant la certification CSA pour leur
utilisation dans des emplacements dangereux.
ÎÎ
Î
ÎÎ
Class I Div 2 Hazardous6
Î
marked for all applicable directives
1 Input may drop to 16 V for a maximum of two minutes each hour for motor starting.
2 To comply with CE low voltge directives, a safety extra low voltage (SELV) or a protected extra low voltage power supply
is required.
3 The combination of all output power (5 V backplane, 24 V backplane, 3.3 V backplane, and 1.2 V backplane) cannot
exceed 70 W.
4 Use time-delay type overcurrent protection in all ungrounded conductors.
5 This fuse is intended to guard against fire hazard due to short circuit conditions and may not protect the power supply
from damage under overload conditions.
6 CSA certification – Class I, Division 2, Group A, B, C, D or nonhazardous locations.
FM approved – Class I, Division 2, Group A, B, C, D or nonhazardous locations.
Worldwide representation.
Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC •
Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador •
Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India •
Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia •
Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal •
Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore • Slovakia • Slovenia •
South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey •
United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia