AS 4214:2018

Gaseous fire-extinguishing systems


This Australian Standard® was prepared by Committee FP-011, Special Hazard Fire
Protection Systems. It was approved on behalf of the Council of Standards Australia on
13 February 2018.
This Standard was published on 16 April 2018.

The following are represented on Committee FP-011:

Australasian Fire and Emergency Service Authorities Council


Australian Chamber of Commerce and Industry
Australian Industry Group
CSIRO
Engineers Australia
Facility Management Association of Australia
Fire Protection Association Australia
National Fire Industry Association

This Standard was issued in draft form for comment as DR AS 4214:2017.

Standards Australia wishes to acknowledge the participation of the expert individuals that
contributed to the development of this Standard through their representation on the
Committee and through the public comment period.

Keeping Standards up-to-date


Australian Standards® are living documents that reflect progress in science, technology and
systems. To maintain their currency, all Standards are periodically reviewed, and new editions
are published. Between editions, amendments may be issued.

Standards may also be withdrawn. It is important that readers assure themselves they are
using a current Standard, which should include any amendments that may have been
published since the Standard was published.

Detailed information about Australian Standards, drafts, amendments and new projects can
be found by visiting www.standards.org.au

Standards Australia welcomes suggestions for improvements, and encourages readers to


notify us immediately of any apparent inaccuracies or ambiguities. Contact us via email at
mail@standards.org.au, or write to Standards Australia, GPO Box 476, Sydney, NSW 2001.
AS 4214:2018

Australian Standard®

Gaseous fire-extinguishing systems

Originated in part as AS 4214.1—1995, AS 4214.2—1995, AS 4214.3—1995, AS 4214.4—1995,


AS 4214.5—1995, AS 4214.6—1998 and AS 4214.7—1998.
AS 4214.1—1995, AS 4214.2—1995, AS 4214.3—1995, AS 4214.4—1995, AS 4214.5—1995,
AS 4214.6—1998 and AS 4214.7—1998 revised, amalgamated and redesignated
as AS 4214—2002.
AS 4214—2002 revised and redesignated, in part, as AS ISO 14520.1—2009,
AS ISO 14520.2—2009, AS ISO 14520.5—2009, AS ISO 14520.6—2009,
AS ISO 14520.8—2009, AS ISO 14520.9—2009, AS ISO 14520.10—2009,
AS ISO 14520.11—2009, AS ISO 14520.12—2009, AS ISO 14520.13—2009,
AS ISO 14520.14—2009 and AS ISO 14520.15—2009.
Revised, amalgamated and redesignated as AS 4214:2018.

COPYRIGHT
© Standards Australia Limited
All rights are reserved. No part of this work may be reproduced or copied in any form or by
any means, electronic or mechanical, including photocopying, without the written
permission of the publisher, unless otherwise permitted under the Copyright Act 1968.
Published by SAI Global Limited under licence from Standards Australia Limited, GPO Box
476, Sydney, NSW 2001, Australia
ISBN 978 1 76072 019 3
AS 4214:2018

Gaseous fire
extinguishing systems
Gaseous media fire-extinguishing
systems—Physical properties and system design

ISO Content Location of modified ISO content


AS 4214:2018

This Standard incorporates Commentary on some clauses. The Commentary directly


follows the relevant clause, is designated by ‘C’ preceding the clause number and is
printed in italics in a panel. The Commentary is for information only and does not need
to be followed for conformance with the Standard.
AS 4214:2018
AS 4214:2018

Page
AS 4214:2018

S AN AR S A S RALIA

ustra ian tan ar


Gaseous fire-extinguishing systems

1 SCOPE

Standards Australia www.standards.org.au


AS 4214:2018

TABLE 1
EXTINGUISHING AGENTS INCLUDED IN THIS STANDARD
Extinguishing
Chemical Formula CAS No. Appendix
agent

2 NORMATIVE REFERENCES

www.standards.org.au Standards Australia


AS 4214:2018

3 DEFINITIONS

3.1 Approved and approval

3.2 Authority having jurisdiction

3.3 Automatic/manual switch

3.4 Clearance

3.5 Competent person

Standards Australia www.standards.org.au


AS 4214:2018

3.6 Concentration
3.6.1 Design concentration

3.6.2 Extinguishing concentration

3.6.3 Maximum concentration

3.7 Engineered system

3.8 Extinguishing agent

3.9 Fill density

3.10 Flooding quantity

3.11 Hold time

3.12 Inspection

3.13 Liquified gas

3.14 Listed

www.standards.org.au Standards Australia


AS 4214:2018

3.15 Lock-off device

3.16 Lowest observed adverse effect level (LOAEL)

3.17 Maintenance

3.18 Maximum developed pressure

3.19 Net volume

3.20 Non-liquified gas

3.21 No observed adverse effect level (NOAEL)

3.22 Normally occupied area

3.23 Normally unoccupied area

3.24 Pre-engineered systems

Standards Australia www.standards.org.au


AS 4214:2018

3.25 Regulated discharge valve system

3.26 Safety factor

3.27 Sea level equivalent of agent

3.28 Sea level equivalent of oxygen

3.29 Selector valve

3.30 Shall

3.31 Should

3.32 Storage Container

3.33 Superpressurization

3.34 Total flooding system

3.35 Unoccupiable area

4 USE AND LIMITATIONS


4.1 General

www.standards.org.au Standards Australia


AS 4214:2018

4.2 Protection of multiple enclosures

C4.2 When protecting multiple enclosures, care should be taken not to exceed the
LOAEL concentration in each normally occupied enclosure.
4.3 Extinguishing agents
4.3.1 General

Standards Australia www.standards.org.au


AS 4214:2018

4.3.2 Environmental properties

4.4 Electrostatic discharge

4.5 Compatibility with other extinguishing agents

4.6 Temperature limitations

5 SAFETY
5.1 Hazard to personnel

www.standards.org.au Standards Australia


AS 4214:2018

5.2 Safety precautions


5.2.1 General

5.2.2 For normally occupied areas

TABLE 2
MINIMUM SAFETY PRECAUTIONS
Time delay Automatic/manual Lock-off
Maximum concentration
device switch device

Standards Australia www.standards.org.au


AS 4214:2018

C5.2.2 Automatic/manual switches are not generally required for manual only systems
or small pre-engineered systems unless the discharge presents a risk to personnel who
are in the immediate vicinity of the protected area. Lock-off valves are required to
permit persons prior to entering the protected area to manually prevent discharge of the
system. The lock-off valve position is monitored so that when it is closed the
extinguishing system inoperative sign will be activated. This will provide visual
indication that this system will not discharge automatically.

P h

h
P
C

P P
C
P

C
P
P

www.standards.org.au Standards Australia


AS 4214:2018

TABLE 3
MAXIMUM ALLOWED INERT GAS AGENT CONCENTRATION
AT THE NOAEL AND LOAEL LIMITS
AS A FUNCTION OF ALTITUDE
NOAEL P O2,NOAEL LOAEL P O2,LOAEL
Partial pressure
(kPa) (kPa)
Atmospheric of oxygen at local
Altitude 12.1 10.2
pressure atmospheric
(h) Maximum allowed Maximum allowed
(P) pressure
agent concentration agent concentration
(P O2,ATM)
(C MAX,NOAEL ) (C MAX,LOAEL )

5.2.3 For normally unoccupied areas

WARNING: Any change to the enclosure volume, or addition or removal of non-


permeable contents that was not covered in the original design will affect the
concentration of extinguishing agent. In such instances the system shall be
recalculated to ensure that the required design concentration is achieved and the
maximum concentration is consistent with Table 2.
5.2.4 For unoccupiable areas

5.3 Occupiable areas

Standards Australia www.standards.org.au


AS 4214:2018

5.4 Electrical hazards

5.5 Electrical earthing

5.6 Electrostatic discharge

C5.6 Electrostatic charging of pipework and nozzles not bonded and earthed may
occur during the discharge of extinguishing agent. Pipework and nozzles may discharge
to other objects with sufficient energy to initiate an explosion (refer to AS/NZS 1020).

www.standards.org.au Standards Australia


AS 4214:2018

5.7 Warning notices

THIS AREA IS FITTED WITH A

(identify extinguishing agent)

GASEOUS FIRE
EXTINGUISHING SYSTEM
EVACUATE AREA ON SOUNDING
OF ALARM

DO NOT ENTER
AFTER EXTINGUISHING AGENT DISCHARGE
UNTIL THE AREA HAS BEEN THOROUGHLY VENTILATED

IG R 1 PICAL WARNING NO IC OB ISPLA A AC N R O


PRO C AR A OR NCLOS R

Standards Australia www.standards.org.au


AS 4214:2018

(insert extinguishing agent)

EXTINGUISHING SYSTEM
MANUAL RELEASE FOR
(identify protected area)

WARNING
ENSURE AREA IS EVACUATED
BEFORE OPERATING

IG R 2 PICAL WARNING NO IC OB ISPLA


A AN AL R L AS

WARNING
LOCK-OFF
(insert extinguishing agent)

SYSTEM BEFORE ENTERING


(identify protected area)

IG R 3 LOC O WARNING S S NO IC

www.standards.org.au Standards Australia


AS 4214:2018

(insert extinguishing agent)

EXTINGUISHING SYSTEM
LOCK-OFF VALVE FOR
(identify protected area)

WARNING
ENSURE AREA IS CLEAR
OF PERSONNEL BEFORE
OPENING VALVE

IG R 4 LOC O AL NO IC

6 SYSTEM DESIGN
6.1 General

6.2 Extinguishing agent supply


6.2.1 Quantity

6.2.2 Quality

6.2.3 Storage container arrangement

Standards Australia www.standards.org.au


AS 4214:2018

6.2.4 Storage containers


6.2.4.1 General

6.2.4.2 Contents indication

6.2.4.3 Marking

www.standards.org.au Standards Australia


AS 4214:2018

6.2.4.4 Manifolded storage containers

6.2.4.5 Operating temperatures

6.3 Distribution
6.3.1 General

Standards Australia www.standards.org.au


AS 4214:2018

6.3.2 Piping

6.3.3 Fittings

www.standards.org.au Standards Australia


AS 4214:2018

6.3.4 Pipe and valve supports

TABLE 4
MAXIMUM PIPEWORK SPANS
Nominal diameter of pipe Maximum pipework span
DN m

6.3.5 Valves

6.3.6 Nozzles
6.3.6.1 Nozzle choice and location

Standards Australia www.standards.org.au


AS 4214:2018

6.3.6.2 Nozzles in ceiling

6.3.6.3 Marking

6.3.6.4 Filters

6.3.7 Pressure reducing orifice assembly

6.4 Detection, actuation and control systems


6.4.1 General

6.4.2 Automatic detection

6.4.3 Operating devices


6.4.3.1 Automatic operation

www.standards.org.au Standards Australia


AS 4214:2018

6.4.3.2 Manual operation

6.4.3.3 Manual mechanical release

6.4.4 Control equipment


6.4.4.1 Electric control equipment

6.4.4.2 Local Control Station (LCS)

6.4.4.3 Pneumatic control equipment

Standards Australia www.standards.org.au


AS 4214:2018

6.4.5 Audible alarms and visual warning devices

‘ IR ALAR ’
‘ O NO N R’

‘ AC A AR A’
‘ ING IS ING S S INOP RA I ’

7 EXTINGUISHING AGENT SYSTEM DESIGN


7.1 General

7.2 Specifications, plans and approvals

7.3 System flow calculations


7.3.1 General

www.standards.org.au Standards Australia


AS 4214:2018

7.3.2 Friction losses

7.3.3 Pressure drop

7.3.4 Valves and fittings

7.3.5 Liquefied gases—Specific requirements

7.4 Enclosures

Standards Australia www.standards.org.au


AS 4214:2018

7.5 Extinguishing agent concentration requirements


7.5.1 Flame extinguishment
Portable fire extinguishers—Classification, rating
and performance testing

www.standards.org.au Standards Australia


AS 4214:2018

7.5.2 Inerting

7.6 Total flooding quantity


7.6.1 General

7.6.2 Liquefied gases

C V
Q
C v

Q
C
V

v
v k k T
k,k

7.6.3 Non-liquefied gas

V C
Q
v C

Standards Australia www.standards.org.au


AS 4214:2018

Q Q v

Q
T
Q

v k k T
k ,k

T
7.7 Altitude adjustment

TABLE 5
CORRECTION FACTORS
Equivalent altitude
Correction factor
m

7.8 Duration of Protection

www.standards.org.au Standards Australia


AS 4214:2018

7.9 System performance


7.9.1 Discharge time
7.9.1.1 Liquefied extinguishing agent

7.9.1.2 Non-liquefied extinguishing agent

7.9.2 Extended discharge

8 COMMISSIONING AND ACCEPTANCE


8.1 General

8.2 Tests
8.2.1 General

8.2.2 Enclosure check

Standards Australia www.standards.org.au


AS 4214:2018

8.2.3 Review of design calculations

8.2.4 Review of mechanical components

www.standards.org.au Standards Australia


AS 4214:2018

WARNING: Pneumatic pressure testing creates a potential risk of injury to


personnel in the area, as a result of airborne projectiles if rupture of the piping
system occurs. Prior to conducting the pneumatic pressure test, the protected area
shall be evacuated and appropriate safeguards shall be provided for test
personnel.

8.2.5 Review of enclosure integrity

8.2.6 Review of electrical components

8.2.7 System functional test

Standards Australia www.standards.org.au


AS 4214:2018

8.2.8 Completion of functional tests

8.3 Completion certificate and documentation

8.4 Block plan

www.standards.org.au Standards Australia


AS 4214:2018

Standards Australia www.standards.org.au


AS 4214:2018

GASEOUS FIRE EXTINGUISHING SYSTEM


BLOCK PLAN
ACME INDUSTRIES, MAIN ST NEWTOWN LEVEL 3 COMPUTER ROOM

SHCIE

2 3

1 AGENT CONTAINER STORAGE

2 SPECIAL HAZARDS CONTROL & INDICATING EQUIPMENT

3 POST DISCHARGE VENTILATION CONTROL PANEL

4 UNCLOSABLE OPENING (1.1m2)

THE GASEOUS SUPPRESSION SYSTEM HAS BEEN DESIGNED AND INSTALLED TO AUSTRALIAN
STANDARD AS 4214 - 2017 WITH THE FOLLOWING PARAMETERS

PROTECTED SPACE(S) IN-ROOM & SUB-FLOOR


GROSS VOLUME 179m3
NET VOLUME 179m3
AGENT HFC-227ea
DESIGN FUEL HIGHER HAZARD CLASS A
DESIGN CONCENTRATION 8.50%
AGENT QTY. REQUIRED 128kg
ESTIMATED MAX CONCENTRATION 8.67%
PRESSURE RELIEF VENT AREA (MIN) 0.68m2
REQUIRED HOLD TIME (MIN) 10 min
COMMISSIONED HOLD TIME 11.3 min
HOLD TIME CRITERIA MECHANICAL MIXING
MAX PROTECTED HEIGHT N/A

INSTALLED BY: ABC GAS SUPPRESSION CO.

MONTH AND YEAR OF INSTALLATION: JANUARY 2017

IG R 5 BLOC PLAN

9 MAINTENANCE

www.standards.org.au Standards Australia


AS 4214:2018

A1 GENERAL

CA1(a) Where a marine vessel is required to comply with Marine Orders Part 15 and
Safety of Life at Sea (SOLAS) resolutions as administered by the Australian Maritime
Safety Authority (AMSA) certain requirements of this Standard may be of assistance in
the design of distribution pipework systems.
Refer also to the National Standard for Commercial Vessels administered by AMSA.

CA1(b) A marine authority may only accept a gaseous fire extinguishing system that
has been approved by a ship classification society, or has been tested and specifically
listed for the purpose by an internationally recognized fire protection testing and
approval authority.

A2 USE AND LIMITATIONS

Standards Australia www.standards.org.au


AS 4214:2018

A3 AGENT SELECTION
A3.1 Halocarbon agents

A3.2 Use of halocarbon agents

A3.3 Inert gases

A4 SAFETY REQUIREMENTS

www.standards.org.au Standards Australia


AS 4214:2018

A5 SYSTEM DESIGN
A5.1 Specification, plans and approvals

A5.2 Acceptance of installations

A5.3 Approval of components

A5.4 Design concentration


A5.4.1 Agent

A5.4.2 Combination of fuels

A5.5 Total flooding quantity


A5.5.1 General

A5.5.2 Halocarbon or inert gas

Standards Australia www.standards.org.au


AS 4214:2018

A5.5.3 Carbon Dioxide (CO2 )

V C
M

M
V
C

www.standards.org.au Standards Australia


AS 4214:2018

Area C

Ca s ing

Area B

Area A
B ot to m of c a s in g

Eq u al

M i d - l eve l
En g in e
room

Eq u al

Tan k to p

For t h e c a s in g to b e c o n s i d ere d se par ate fro m t h e gro s s vo lum e of t h e


m ac hin er y s pac e, Area B i s to b e 4 0 p er c e nt or l e s s of Area A .

If Area B i s greater t han 4 0 p er c e nt of Area A , t h e vo lu m e of c a s in g u p


to Area C (or w h ere t h e area i s 4 0 p er c e nt or l e s s of Area A) i s to b e
in c lu d e d in t h e gro s s vo lum e of t h e s pac e.

A ny area of t h e c a s in g c o nt ainin g b o il er s, inter nal c o m bu st i o n m ac hin er y or


o il -fire d in st all at i o n s i s to b e in c lu d e d in t h e gr o s s vo lu m e of t h e e n g in e
r o o m.

IG R A1 AC IN R SPAC OL CALC LA ION

Standards Australia www.standards.org.au


AS 4214:2018

A5.5.4 Multiple spaces

A5.6 Special conditions

A5.7 Discharge time


A5.7.1 Halocarbon agents

A5.7.2 Inert gases (including CO2 )

A5.8 Duration of protection

A5.9 System flow calculations

A5.10 Nozzle choice and location

A6 ENCLOSURE REQUIREMENTS

CA6 The formula used in the calculation of total flooding quantities is based on ‘free
efflux’ from the space upon agent discharge. This means that the displaced atmosphere
will contain an air/agent mixtures.

www.standards.org.au Standards Australia


AS 4214:2018

A7 AGENT SUPPLY
A7.1 General

A7.2 Storage container brackets

A7.3 Protection against corrosion

A7.4 Location of storage containers

A8 DISTRIBUTION SYSTEM
A8.1 General

A8.2 Piping

A8.3 Aluminium

A8.4 Penetrations

Standards Australia www.standards.org.au


AS 4214:2018

A9 DETECTION, ACTUATION AND CONTROL


A9.1 General

A9.2 Fire detection


A9.2.1 General

CA9.2.1 Guidelines for the design of the detection system are contained in AS 1670.5.
The authority having jurisdiction may provide further advice.
A9.2.2 Design

A9.2.3 Power supply

A9.2.4 IP rating

A9.2.5 Control panel

A9.3 Agent discharge


A9.3.1 General

A9.3.2 Discharge station

www.standards.org.au Standards Australia


AS 4214:2018

A9.3.3 Lighting and labelling

A9.3.4 Automatic release

A9.3.5 General

A10 MARKING

A11 COMMISSIONING AND ACCEPTANCE


A11.1 General

A11.2 Door fan test

A11.3 Functional test

Standards Australia www.standards.org.au


AS 4214:2018

A12 DOCUMENTATION

A13 INSPECTION AND MAINTENANCE

www.standards.org.au Standards Australia


AS 4214:2018

B1 GENERAL

B2 WORKING DOCUMENTS

Standards Australia www.standards.org.au


AS 4214:2018

B3 SPECIFIC DETAILS
B3.1 Pre-engineered systems

B3.2 Engineered systems

B4 COMPLETION CERTIFICATE AND DOCUMENTATION

www.standards.org.au Standards Australia


AS 4214:2018

TABLE B1
COMMISSIONING CHECKLIST
Conformance
Item Task
Yes/No/N/A Verified by

ontinued

Standards Australia www.standards.org.au


AS 4214:2018

TABLE B1 continued

Conformance
Item Task
Yes/No/N/A Verified by

www.standards.org.au Standards Australia


AS 4214:2018

C R I ICA O CO PL ION
PAR 1: O B CO PL B OR S ING
We name of installer ..............................................................................................
of .........................................................hereby certify that we have completed on
date .................................. name of system .............................................................
.......................................gaseous fire extinguishing installation extension s designed
by ...............................................................and installed in accordance with AS 4214.
Name of client..............................................................................................................
Address of protected area............................................................................................
Premises known as or occupied by..............................................................................
ype of system............................................................................................................

Protected area Agent uantity Number of Agent design Applicable


storage concentration drawing s

Remote system monitoring will be performed by .....................................................


ate of remote monitoring connection ........................................................................
ariations from this Standard previously agreed to by the authority having urisdiction
are attached clause references and related variations should be listed .

Signature of installer .........................................................


ate ..................................................................................

IG R B1 C R I ICA O CO PL ION page 1 of 2

Standards Australia www.standards.org.au


AS 4214:2018

PAR 2: O B CO PL A R S ING
Commissioning test s conducted by .........................................................................
.............................................................. ate ............................................................
Commissioning test s witnessed by ........................................................................
.............................................................. ate ............................................................
oor fan test s conducted by ....................................................................................
.............................................................. ate ............................................................
oor fan test s witnessed by .....................................................................................
.............................................................. ate ............................................................
ischarge test conducted by .....................................................................................
ate ........................................................
ischarge test witnessed by .......................................................................................
.............................................................. ate ............................................................

Remarks

IG R B1 C R I ICA O CO PL ION page 2 of 2

www.standards.org.au Standards Australia


AS 4214:2018

C1 SCOPE

C2 PRINCIPLE

C3 TEST MEDIUM

C4 APPARATUS

C5 PROCEDURE

Standards Australia www.standards.org.au


AS 4214:2018

C6 RE-COMMISSIONING

C7 REPORTING

www.standards.org.au Standards Australia


AS 4214:2018

D1 SCOPE

D2 CHARACTERISTICS AND USES


D2.1 General

TABLE D1
SPECIFICATION FOR CF3 I
Property Requirement

Standards Australia www.standards.org.au


AS 4214:2018

TABLE D2
PHYSICAL PROPERTIES OF CF3 I
Property Units Value

TABLE D3
ENVIRONMENTAL PROPERTIES OF CF 3 I
Property Value

D2.2 Use of CF3 I systems

www.standards.org.au Standards Australia


AS 4214:2018

TABLE D4
CF3 I TOTAL FLOODING QUANTITY
Specific
Temperature CF 3 I mass requirements per unit volume of protected space m/V (kg/m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 3% 4% 5% 6% 7% 8% 9% 10%

m/V
V
V

c V
m
c S

S k k T

k
k
c

Standards Australia www.standards.org.au


AS 4214:2018

TABLE D5
CF3 I REFERENCE EXTINGUISHING AND DESIGN CONCENTRATIONS
Extinguishment Minimum design
Fuel
% by volume % by volume

TABLE D6
CF3 I INERTING AND DESIGN CONCENTRATIONS
Inertion Minimum design
Fuel
% by volume % by volume

D3 SAFETY OF PERSONNEL

www.standards.org.au Standards Australia


AS 4214:2018

TABLE D7
TOXICOLOGICAL INFORMATION FOR CF 3 I
Value
Property
% by volume

D4 SYSTEM DESIGN
D4.1 Fill density

TABLE D8
STORAGE CONTAINER CHARACTERISTICS FOR CF 3 I
Property Unit Value

D4.2 Superpressurization

D4.3 Extinguishing agent quantity

Standards Australia www.standards.org.au


AS 4214:2018

Y
80

70

1
60

2
50

40

30

20

10

0
-40 -20 0 20 40 60 80 10 0
X
L G N :
temperature, C
pressure, bar
1 1 470 kg m 3
2 1 680 kg m 3

IG R 1 P RA R PR SS R GRAP OR C 3I PR SS RI
O 25 BAR WI NI ROG N A 20 C

www.standards.org.au Standards Australia


AS 4214:2018

E1 SCOPE

E2 CHARACTERISTICS AND USES


E2.1 General

TABLE E1
SPECIFICATION FOR FK-5-1-12

Standards Australia www.standards.org.au


AS 4214:2018

TABLE E2
PHYSICAL PROPERTIES OF FK-5-1-12
Property Units Value

TABLE E3
ENVIRONMENTAL PROPERTIES OF FK-5-1-12
Property Value

E2.2 Use of FK-5-1-12 systems

www.standards.org.au Standards Australia


AS 4214:2018

TABLE E4
FK-5-1-12 TOTAL FLOODING QUANTITY
Specific
Temperature FK-5-1-12 mass requirements per unit volume of protected space, m/V (kg/m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 3% 4% 5% 6% 7% 8% 9% 10%

m/V
V
V

c V
m
c S
T
S

S k k T

k
k
c

Standards Australia www.standards.org.au


AS 4214:2018

TABLE E5
FK-5-1-12 REFERENCE EXTINGUISHING AND DESIGN CONCENTRATIONS
Extinguishment Minimum design
Fuel
% by volume % by volume

TABLE E6
FK-5-1-12 CONCENTRATIONS FOR OTHER FUELS
Extinguishment Minimum design
Fuel
% by volume % by volume

www.standards.org.au Standards Australia


AS 4214:2018

TABLE E7
FK-5-1-12 INERTING AND DESIGN CONCENTRATIONS
Inertion Minimum design
Fuel
% %

E3 SAFETY OF PERSONNEL

TABLE E8
TOXICOLOGICAL INFORMATION FOR FK-5-1-12
Value
Property
%

E4 SYSTEM DESIGN
E4.1 Fill density

Standards Australia www.standards.org.au


AS 4214:2018

TABLE E9
25 BAR STORAGE CONTAINER CHARACTERISTICS
FOR FK-5-1-12
Property Unit Value

TABLE E10
34.5 BAR STORAGE CONTAINER CHARACTERISTICS
FOR FK-5-1-12
Property Unit Value

TABLE E11
42 BAR STORAGE CONTAINER CHARACTERISTICS
FOR FK-5-1-12

Property Unit Value

TABLE E12
50 BAR STORAGE CONTAINER CHARACTERISTICS
FOR FK-5-1-12
Property Unit Value

www.standards.org.au Standards Australia


AS 4214:2018

E4.2 Superpressurization

E4.3 Extinguishing agent quantity

Y
120

14 8 0 kg/m 3
100

80 1420 kg/m 3

60

40

1050 kg/m 3
20

0
-20 -10 0 10 20 30 40 50 60 70 80 90 100 X
L G N :
temperature, C
pressure, bar

IG R 1 P RA R PR SS R GRAP OR 5 1 12
S P RPR SS RI WI NI ROG N 25 BAR A 20 C

Standards Australia www.standards.org.au


AS 4214:2018

Y
90
120 0 kg/m 3

80

70

60

50

40

30

20

10

0
-60 -40 -20 0 20 40 60 80 10 0 120 14 0 X
L G N :
temperature, C
pressure, bar

IG R 2 P RA R PR SS R GRAP OR 5 1 12
S P RPR SS RI WI NI ROG N O 34.5 BAR A 20 C

Y
120
1440 kg/m 3

100
1420 kg/m 3

80

60 1050 kg/m 3

40

20

0
-20 -10 0 10 20 30 40 50 60 70 80 90 100 X
L G N :
temperature, C
pressure, bar

IG R 3 P RA R PR SS R GRAP OR 5 1 12
S P RPR SS RI WI NI ROG N O 42 BAR A 20 C

www.standards.org.au Standards Australia


AS 4214:2018

Y
70.0

6 0.0
120 0 kg/m 3

5 0.0

4 0.0

3 0.0

20.0

10.0

0.0
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55
X
L G N :
temperature, C
pressure, bar

IG R 4 P RA R PR SS R GRAP OR 5 1 12
S P RPR SS RI WI NI ROG N O 50 BAR A 20 C

Standards Australia www.standards.org.au


AS 4214:2018

F1 SCOPE

F2 CHARACTERISTICS AND USES


F2.1 General

TABLE F1
SPECIFICATION FOR HCFC BLEND A
Property Requirement

TABLE F2
HCFC BLEND A COMPONENT SPECIFICATION
Component Tolerance (by mass)

www.standards.org.au Standards Australia


AS 4214:2018

TABLE F3
PHYSICAL PROPERTIES OF HCFC BLEND A
Property Units Value

TABLE F4
ENVIRONMENTAL PROPERTIES OF HCFC BLEND A
Property Value

F2.2 Use of HCFC Blend A systems

Standards Australia www.standards.org.au


AS 4214:2018

F3 SAFETY OF PERSONNEL

F4 SYSTEM DESIGN
F4.1 Fill density

F4.2 Superpressurization

F4.3 Extinguishing agent quantity

www.standards.org.au Standards Australia


AS 4214:2018

TABLE F5
HCFC BLEND A TOTAL FLOODING QUANTITY
Specific
HCFC Blend A mass requirements per unit volume of protected space, m/V
Temperature vapour
(kg/m 3 )
volume
T S Design concentration (by volume)
C 3
m /kg 7% 8% 9% 10% 11% 12% 13% 14% 15% 16%

m/V
V
V

c V
m
c S
T
S

S k k T

k
k
c

Standards Australia www.standards.org.au


AS 4214:2018

TABLE F6
HCFC BLEND A REFERENCE EXTINGUISHING
AND DESIGN CONCENTRATIONS
Extinguishment Minimum design
Fuel
% by volume % by volume

TABLE F7
HCFC BLEND A INERTING AND DESIGN CONCENTRATIONS
Minimum
Inertion
Fuel design
% by volume
% by volume

www.standards.org.au Standards Australia


AS 4214:2018

TABLE F8
TOXICOLOGICAL INFORMATION
FOR HCFC BLEND A
Value
Property
% by volume

TABLE F9
25 BAR STORAGE CONTAINER CHARACTERISTICS
FOR HCFC BLEND A
Property Unit Value

TABLE F10
42 BAR STORAGE CONTAINER CHARACTERISTICS
FOR HCFC BLEND A
Property Unit Value

Standards Australia www.standards.org.au


AS 4214:2018

45

40

35

30

25

20

15

10
X -50 -40 -30 -20 -10 0 10 20 30 40 50 60 65 70 X

L G N :
temperature, C
pressure, bar

IG R 1 P RA R PR SS R GRAP OR C C BL N A PR SS RI
WI NI ROG N O 25 BAR A 20 C

www.standards.org.au Standards Australia


AS 4214:2018

Y
65

60

55

50

45

40

35

30

25

X -50 -40 -30 -20 -10 0 10 20 30 40 50 60 65 70 X

L G N :
temperature, C
pressure, bar

IG R 2 P RA R PR SS R GRAP OR C C BL N A PR SS RI
WI NI ROG N O 42 BAR A 20 C

Standards Australia www.standards.org.au


AS 4214:2018

G1 SCOPE

G2 CHARACTERISTICS AND USES


G2.1 General

TABLE G1
SPECIFICATION FOR HFC 125
Property Requirement

www.standards.org.au Standards Australia


AS 4214:2018

TABLE G2
PHYSICAL PROPERTIES OF HFC 125
Property Units Value

TABLE G3
ENVIRONMENTAL PROPERTIES OF HFC 125
Property Value

G2.2 Use of HFC 125 systems

Standards Australia www.standards.org.au


AS 4214:2018

TABLE G4
HFC 125 TOTAL FLOODING QUANTITY
Specific
Temperature vapour HFC 125 mass requirements per unit volume of protected space, m/V (kg/m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 7% 8% 9% 10% 11% 12% 13% 14% 15% 16%

m/V
V
V

c V
m
c S
T

www.standards.org.au Standards Australia


AS 4214:2018

S k k T

k
k
c

TABLE G5
HFC 125 REFERENCE EXTINGUISHING AND DESIGN CONCENTRATIONS
Extinguishment Minimum design
Fuel
% by volume % by volume

Standards Australia www.standards.org.au


AS 4214:2018

TABLE G6
HFC 125 EXTINGUISHING AND DESIGN CONCENTRATIONS
FOR OTHER FUELS
Extinguishment Minimum design
Fuel
% by volume % by volume

G3 SAFETY OF PERSONNEL

TABLE G7
TOXICOLOGICAL INFORMATION FOR HFC 125
Value
Property
% by volume

G4 SYSTEM DESIGN
G4.1 Fill density

www.standards.org.au Standards Australia


AS 4214:2018

TABLE G8
25 BAR STORAGE CONTAINER CHARACTERISTICS
FOR HFC 125
Property Unit Value

TABLE G9
42 BAR STORAGE CONTAINER CHARACTERISTICS
FOR HFC 125
Property Unit Value

G4.2 Superpressurization

G4.3 Extinguishing agent quantity

Standards Australia www.standards.org.au


AS 4214:2018

Y
90

80
929
70 896
867
834
60
801
50

40

30

20

10

0
X -50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 X

L G N :
alue of density in kilograms per cubic metre
temperature, C
pressure, bar

IG R G1 P RA R PR SS R GRAP OR C 125 PR SS RI WI
NI ROG N O 25 BAR A 22 C

16 0

14 0
9 29
896
120
866

10 0

80

60

40

20

0
-20 0 20 40 60 80 10 0 X

L G N :
alue of density in kilograms per cubic metre
temperature, C
pressure, bar

IG R G2 P RA R PR SS R GRAP OR C 125 PR SS RI WI
NI ROG N A 42 BAR AN 22 C

www.standards.org.au Standards Australia


AS 4214:2018

H1 SCOPE

H2 CHARACTERISTICS AND USES


H2.1 General

TABLE H1
SPECIFICATION FOR HFC 227ea
Property Requirement

Standards Australia www.standards.org.au


AS 4214:2018

TABLE H2
PHYSICAL PROPERTIES OF HFC 227ea
Property Units Value

TABLE H3
ENVIRONMENTAL PROPERTIES OF HFC 227ea
Property Value

H2.2 Use of HFC 227ea systems

www.standards.org.au Standards Australia


AS 4214:2018

TABLE H4
HFC 227ea TOTAL FLOODING QUANTITY
Specific
Temperature vapour HFC 227ea mass requirements per unit volume of protected space, m/V (kg/m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 6% 7% 8% 9% 10% 11% 12% 13% 14% 15%

m/V

c V
m
c S

S k k T

Standards Australia www.standards.org.au


AS 4214:2018

TABLE H5
HFC 227ea REFERENCE EXTINGUISHING AND DESIGN CONCENTRATIONS
Extinguishment Minimum design
Fuel
% by volume % by volume

www.standards.org.au Standards Australia


AS 4214:2018

TABLE H6
HFC 227ea EXTINGUISHING AND DESIGN CONCENTRATIONS
FOR OTHER FUELS
Extinguishment Minimum design
Fuel
% by volume % by volume

TABLE H7
HFC 227ea INERTING AND DESIGN CONCENTRATIONS
Inertion Minimum
Fuel % by design
volume % by volume

H3 SAFETY OF PERSONNEL

Standards Australia www.standards.org.au


AS 4214:2018

TABLE H8
TOXICOLOGICAL INFORMATION FOR HFC 227ea
Value
Property
% by volume

H4 SYSTEM DESIGN
H4.1 Fill density

TABLE H9
25 BAR STORAGE CONTAINER CHARACTERISTICS
FOR HFC 227ea
Property Unit Value

TABLE H10
42 BAR STORAGE CONTAINER CHARACTERISTICS
FOR HFC 227ea
Property Unit Value

www.standards.org.au Standards Australia


AS 4214:2018

TABLE H11
50 BAR STORAGE CONTAINER CHARACTERISTICS
FOR HFC 227ea
Property Unit Value

H4.2 Superpressurization

H4.3 Extinguishing agent quantity

Standards Australia www.standards.org.au


AS 4214:2018

Y
120

1 150
100

1 120

80

1 040
60

800
40

20

0
-20 -10 0 10 20 30 40 50 60 70 80 90 100
X X

L G N :
alue of density in kilograms per cubic metre
temperature, C
pressure, bar

IG R 1 P RA R PR SS R GRAP OR C 227ea
S P RPR SS RI WI NI ROG N O 25 BAR A 21 C

www.standards.org.au Standards Australia


AS 4214:2018

Y
160

1150
140

1120
120

1040
100

80

800
60

40

20

0
X -20 -10 0 10 20 30 40 50 60 70 80 90 100 X

L G N :
alue of density in kilograms per cubic metre
temperature, C
pressure, bar

IG R 2 P RA R PR SS R GRAP OR C 227ea
S P RPR SS RI WI NI ROG N O 42 BAR A 21 C

Standards Australia www.standards.org.au


AS 4214:2018

Y
80

70
10 5 0
60

50

40

30

20

10

0
X -20 -10 0 10 20 30 40 50 60 X

L G N :
temperature, C
pressure, bar

IG R 3 P RA R PR SS R GRAP OR C 227ea—
S P RPR SS RI WI NI ROG N O 50 BAR A 21 C

www.standards.org.au Standards Australia


AS 4214:2018

I1 SCOPE

I2 CHARACTERISTICS AND USES


I2.1 General

TABLE I1
SPECIFICATION FOR HFC 23
Property Requirement

Standards Australia www.standards.org.au


AS 4214:2018

TABLE I2
PHYSICAL PROPERTIES OF HFC 23
Property Units Value

TABLE I3
ENVIRONMENTAL PROPERTIES OF HFC 23
Property Value

I2.2 Use of HFC 23 systems

www.standards.org.au Standards Australia


AS 4214:2018

TABLE I4
HFC 23 TOTAL FLOODING QUANTITY
Specific
Temperature vapour HFC 23 mass requirements per unit volume of protected space, m/V (kg/m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 10% 12% 14% 15% 16% 17% 18% 20% 22% 24%

m/V

c V
m
c S
T
S

S k k T

Standards Australia www.standards.org.au


AS 4214:2018

k
k
c

TABLE I5
HFC 23 REFERENCE EXTINGUISHING AND DESIGN CONCENTRATIONS
Extinguishment Minimum design
Fuel
% by volume % by volume

TABLE I6
HFC 23 EXTINGUISHING AND DESIGN CONCENTRATIONS
FOR OTHER FUELS
Extinguishment Minimum design
Fuel
% by volume % by volume

www.standards.org.au Standards Australia


AS 4214:2018

TABLE I7
HFC 23 INERTING AND DESIGN CONCENTRATIONS
Inertion Minimum design
Fuel
% by volume % by volume

I3 SAFETY OF PERSONNEL

TABLE I8
TOXICOLOGICAL INFORMATION FOR HFC 23
Value
Property
% by volume

I4 SYSTEM DESIGN
I4.1 Fill density

Standards Australia www.standards.org.au


AS 4214:2018

TABLE I9
STORAGE CONTAINER CHARACTERISTICS
FOR HFC 23—41 BAR
Property Unit Value

TABLE I10
STORAGE CONTAINER CHARACTERISTICS
FOR HFC 23—70 BAR
Property Unit Value

I4.2 Superpressurization

I4.3 Extinguishing agent quantity

www.standards.org.au Standards Australia


AS 4214:2018

300

275

4
11 4
25 0

68
10
2 25

01
10
20 0

175

2
2,
94
15 0

0
89
125
8
2,

7
0

3,
80 76
84
10 0

75

50
a

25

0
-20 -10 0 10 20 30 40 50 60 X
L G N :
temperature, C
pressure, bar
a
critical point

IG R I1 P RA R PR SS R GRAP OR C 23
PR SS R O 41 BAR A 20 C

Standards Australia www.standards.org.au


AS 4214:2018

Y
170

16 0

15 0
1
14 0 2
13 0 3

120

110

10 0

90 4

80 5

70

60

50

40
5 10 15 20 25 30 35 40 45 50 X
L G N :
1 850 kg m 3
2 800 kg m 3
3 700 kg m 3
4 600 kg m 3
5 500 kg m 3
temperature, C
pressure, bar

IG R I2 PRA R PR SS R GRAP OR C 23
S P RPR SS RI O 70 BAR A 20 C

www.standards.org.au Standards Australia


AS 4214:2018

J1 SCOPE

J2 CHARACTERISTICS AND USES


J2.1 General

TABLE J1
SPECIFICATION FOR HFC 236fa
Property Requirement

Standards Australia www.standards.org.au


AS 4214:2018

TABLE J2
PHYSICAL PROPERTIES OF HFC 236fa
Property Units Value

TABLE J3
ENVIRONMENTAL PROPERTIES OF HFC 236fa
Property Value

J2.2 Use of HFC 236fa systems

www.standards.org.au Standards Australia


AS 4214:2018

TABLE J4
HFC 236fa TOTAL FLOODING QUANTITY
Specific
Temperature vapour HFC 236fa mass requirements per unit volume of protected space, m/V (kg/m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 5% 6% 7% 8% 9% 10% 11% 12% 13% 14% 15

m/V
V
V

c V
m
c S
T
S

S k k T

k
k
c

Standards Australia www.standards.org.au


AS 4214:2018

TABLE J5
HFC 236fa REFERENCE EXTINGUISHING AND DESIGN CONCENTRATIONS
Extinguishment Minimum design
Fuel
% by volume % by volume

TABLE J6
HFC 236fa EXTINGUISHING AND DESIGN CONCENTRATIONS
FOR OTHER FUELS

Extinguishment Minimum design


Fuel
% by volume % by volume

www.standards.org.au Standards Australia


AS 4214:2018

J3 SAFETY OF PERSONNEL

TABLE J7
TOXICOLOGICAL INFORMATION FOR HFC 236fa
Value
Property
% by volume

J4 SYSTEM DESIGN
J4.1 Fill density

TABLE J8
25 BAR STORAGE CONTAINER CHARACTERISTICS
FOR HFC 236fa
Property Unit Value

Standards Australia www.standards.org.au


AS 4214:2018

TABLE J9
42 BAR STORAGE CONTAINER CHARACTERISTICS
FOR HFC 236fa
Property Unit Value

J4.2 Superpressurization

J4.3 Extinguishing agent quantity

Y
140
1202
120

100

80

60
1122

40
1042

20

0
0 10 20 30 40 50 60 70 80 90 X
L G N :
alue of density in kilograms per cubic metre
temperature, C
pressure, bar

IG R 1 P RA R PR SS R GRAP OR C 236fa PR SS RI
WI NI ROG N O 25 BAR A 22 C

www.standards.org.au Standards Australia


AS 4214:2018

Y
120

110
1202 1122
100

90

80

70
1042
60

50

40

30

20
0 10 20 30 40 50 60 70 80 90 X
L G N :
alue of density in kilograms per cubic metre
temperature, C
pressure, bar

IG R 2 P RA R PR SS R GRAP OR C 236fa PR SS RI
WI NI ROG N O 42 BAR A 22 C

Standards Australia www.standards.org.au


AS 4214:2018

K1 SCOPE

K2 CHARACTERISTICS AND USES


K2.1 General

TABLE K1
SPECIFICATION FOR IG-01
Property Requirement

TABLE K2
PHYSICAL PROPERTIES OF IG-01
Property Units Value

www.standards.org.au Standards Australia


AS 4214:2018

TABLE K3
ENVIRONMENTAL PROPERTIES OF IG-01
Property Value

K2.2 Use of IG-01 systems

TABLE K4
IG-01 TOTAL FLOODING QUANTITY
Specific
IG-01 volume requirements per unit volume of protected space,
Temperature vapour
V/V (m 3 /m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 34% 38% 42% 46% 50% 54% 58% 62%

continued

Standards Australia www.standards.org.au


AS 4214:2018

TABLE K4 continued

Specific
IG-01 volume requirements per unit volume of protected space,
Temperature vapour
V/V (m 3 /m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 34% 38% 42% 46% 50% 54% 58% 62%

V/V Q

Q m S

S k k T

k
k
T
V
m
S c
V

T
S

S k k T

www.standards.org.au Standards Australia


AS 4214:2018

TABLE K5
IG-01 REFERENCE EXTINGUISHING AND DESIGN CONCENTRATIONS
Extinguishment Minimum design
Fuel
% by volume % by volume

TABLE K6
IG-01 INERTING AND DESIGN CONCENTRATIONS
Inertion Minimum design
Fuel
% by volume % by volume

K3 SAFETY OF PERSONNEL

Standards Australia www.standards.org.au


AS 4214:2018

TABLE K7
PHYSIOLOGICAL INFORMATION FOR IG-01
Value
Property
% by volume

K4 SYSTEM DESIGN
K4.1 Fill density

TABLE K8
160 BAR STORAGE CONTAINER CHARACTERISTICS
FOR IG-01
Property Unit Value

TABLE K9
200 BAR STORAGE CONTAINER CHARACTERISTICS
FOR IG-01
Property Unit Value

TABLE K10
300 BAR STORAGE CONTAINER CHARACTERISTICS
FOR IG-01
Property Unit Value

www.standards.org.au Standards Australia


AS 4214:2018

K4.2 Superpressurization

K4.3 Extinguishing agent quantity

450

400

350

300
300

25 0

200
20 0
16 0
15 0

10 0 X
-30 -20 -10 0 10 20 30 40 50 60 70 80

L G N :
temperature, C
pressure, bar

IG R 1 P RA R OR IG 01 PR SS RIS
O 160, 200 AN 300 BAR A 15 C

Standards Australia www.standards.org.au


AS 4214:2018

L1 SCOPE

L2 CHARACTERISTICS AND USES


L2.1 General

TABLE L1
SPECIFICATION FOR IG-100
Property Requirement

www.standards.org.au Standards Australia


AS 4214:2018

TABLE L2
PHYSICAL PROPERTIES OF IG-100
Property Units Value

TABLE L3
ENVIRONMENTAL PROPERTIES OF IG-100
Property Value

L2.2 Use of IG-100 systems

TABLE L4
IG-100 TOTAL FLOODING QUANTITY
Specific
IG-100 volume requirements per unit volume of protected space,
Temperature vapour
V/V (m 3 /m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 34% 38% 42% 46% 50% 54% 58% 62%

continued

Standards Australia www.standards.org.au


AS 4214:2018

TABLE L4 continued

Specific
IG-100 volume requirements per unit volume of protected space,
Temperature vapour
V/V (m 3 /m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 34% 38% 42% 46% 50% 54% 58% 62%

V/V Q

Q m S

S k k T

k
k
T
V
m
S c
V

T
S

S k k T

www.standards.org.au Standards Australia


AS 4214:2018

TABLE L5
IG-100 REFERENCE EXTINGUISHING AND DESIGN
CONCENTRATIONS
Extinguishment Minimum design
Fuel
% by volume % by volume

L3 SAFETY OF PERSONNEL

Standards Australia www.standards.org.au


AS 4214:2018

TABLE L6
PHYSIOLOGICAL INFORMATION FOR IG-100
Value
Property
% by volume

L4 SYSTEM DESIGN
L4.1 Fill density

TABLE L7
200 BAR STORAGE CONTAINER CHARACTERISTICS
FOR IG-100
Property Unit Value

TABLE L8
300 BAR STORAGE CONTAINER CHARACTERISTICS
FOR IG-100
Property Unit Value

www.standards.org.au Standards Australia


AS 4214:2018

L4.2 Superpressurization

L4.3 Extinguishing agent quantity

450

400

350
300
300

25 0
200
20 0

15 0

10 0 X
-30 -20 -10 0 10 20 30 40 50 60 70 80

L G N :
temperature, C
pressure, bar

IG R L1 PR SS R S. P RA R OR IG 100 PR SS RI O 200 BAR


AN 300 BAR A 15 C

Standards Australia www.standards.org.au


AS 4214:2018

M1 SCOPE

M2 CHARACTERISTICS AND USES


M2.1 General

TABLE M1
SPECIFICATION FOR IG-55
Component Argon Nitrogen

www.standards.org.au Standards Australia


AS 4214:2018

TABLE M2
PHYSICAL PROPERTIES OF IG-55
Property Unit Value

TABLE M3
ENVIRONMENTAL PROPERTIES OF IG-55
Property Value

M2.2 Use of IG-55 systems

TABLE M4
IG-55 TOTAL FLOODING QUANTITY
Specific
IG-55 volume requirements per unit volume of protected space,
Temperature vapour
V/V (m 3 /m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 34% 38% 42% 46% 50% 54% 58% 62%

continued

Standards Australia www.standards.org.au


AS 4214:2018

TABLE M4 continued

Specific
IG-55 volume requirements per unit volume of protected space,
Temperature vapour
V/V (m 3 /m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 34% 38% 42% 46% 50% 54% 58% 62%

V/V Q

Q m S

S k k T

k
k
T
V
m
S c
V

T
S

S k k T

www.standards.org.au Standards Australia


AS 4214:2018

TABLE M5
IG-55 REFERENCE EXTINGUISHING AND DESIGN CONCENTRATIONS
Extinguishment Minimum design
Fuel
% by volume % by volume

Standards Australia www.standards.org.au


AS 4214:2018

TABLE M6
IG-55 EXTINGUISHING AND DESIGN CONCENTRATIONS
FOR OTHER FUELS
Extinguishment Minimum design
Fuel
% by volume % by volume

M3 SAFETY OF PERSONNEL

TABLE M7
PHYSIOLOGICAL INFORMATION FOR IG-55
Value
Property
% by volume

www.standards.org.au Standards Australia


AS 4214:2018

M4 SYSTEM DESIGN
M4.1 Fill density

TABLE M8
150 BAR STORAGE CONTAINER CHARACTERISTICS
FOR IG-55

Property Unit Value

TABLE M9
200 BAR STORAGE CONTAINER CHARACTERISTICS
FOR IG-55

Property Unit Value

TABLE M10
300 BAR STORAGE CONTAINER CHARACTERISTICS
FOR IG-55

Property Unit Value

M4.2 Superpressurization

M4.3 Extinguishing agent quantity

Standards Australia www.standards.org.au


AS 4214:2018

450

400

350
300
300

25 0
200
20 0
15 0
15 0

10 0 X
-30 -20 -10 0 10 20 30 40 50 60 70 80

L G N :
temperature, C
pressure, bar

IG R 1 PR SS R S. P RA R OR IG 55 PR SS RI O 150, 200,
AN 300 BAR A 15 C

www.standards.org.au Standards Australia


AS 4214:2018

N1 SCOPE

N2 CHARACTERISTICS AND USES


N2.1 General

TABLE N1
SPECIFICATION FOR IG-541
Component Argon Nitrogen Carbon Dioxide

Standards Australia www.standards.org.au


AS 4214:2018

TABLE N2
PHYSICAL PROPERTIES OF IG-541
Property Unit Value

TABLE N3
ENVIRONMENTAL PROPERTIES OF IG-541
Value
Property
% by volume

N2.2 Use of IG-541 systems

TABLE N4
IG-541 TOTAL FLOODING QUANTITY
Specific
IG-541 volume requirements per unit volume of protected space,
Temperature vapour
V/V (m 3 /m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 34% 38% 42% 46% 50% 54% 58% 62%

continued

www.standards.org.au Standards Australia


AS 4214:2018

TABLE N4 continued

Specific
IG-541 volume requirements per unit volume of protected space,
Temperature vapour
V/V (m 3 /m 3 )
volume
T S Design concentration (by volume)
C m 3 /kg 34% 38% 42% 46% 50% 54% 58% 62%

V/V Q

Q m S

S k k T

k
k
T
V
m
S c
V

T
S

S k k T

Standards Australia www.standards.org.au


AS 4214:2018

TABLE N5
IG-541 REFERENCE EXTINGUISHING AND DESIGN CONCENTRATIONS
Extinguishment Minimum design
Fuel
% by volume % by volume

www.standards.org.au Standards Australia


AS 4214:2018

TABLE N6
IG-541 EXTINGUISHING AND DESIGN CONCENTRATIONS
FOR OTHER FUELS
Extinguishment Minimum design
Fuel
% by volume % by volume

Standards Australia www.standards.org.au


AS 4214:2018

TABLE N7
IG-541 INERTING AND DESIGN CONCENTRATIONS
Inertion Minimum design
Fuel
% by volume % by volume

N3 SAFETY OF PERSONNEL

TABLE N8
PHYSIOLOGICAL INFORMATION FOR IG-541
Value
Property
% by volume

N4 SYSTEM DESIGN
N4.1 Fill density

TABLE N9
150 BAR STORAGE CONTAINER CHARACTERISTICS
FOR IG-541
Property Unit Value

www.standards.org.au Standards Australia


AS 4214:2018

TABLE N10
200 BAR STORAGE CONTAINER CHARACTERISTICS
FOR IG-541
Property Unit Value

TABLE N11
300 BAR STORAGE CONTAINER CHARACTERISTICS
FOR IG-541
Property Unit Value

N4.2 Superpressurization

N4.3 Extinguishing agent quantity

Standards Australia www.standards.org.au


AS 4214:2018

450

400

350
300
300

25 0
200
20 0
15 0
15 0

10 0 X
-30 -20 -10 0 10 20 30 40 50 60 70 80

L G N :
temperature, C
pressure, bar

IG R N1 PR SS R S. P RA R OR IG 541 PR SS RI
O 150, 200 AN 300 BAR A 15 C

www.standards.org.au Standards Australia


AS 4214:2018

O1 SCOPE

O2 SAFETY

O3 HAZARDS TO PERSONNEL—POTENTIAL HAZARDS


O3.1 Agent itself

O3.2 Noise

O3.3 Turbulence

O3.4 Low temperature

Standards Australia www.standards.org.au


AS 4214:2018

O4 HALOCARBON AGENTS
O4.1 Toxicity of halocarbons (liquefied gases)

TABLE O1
TOXICITY INFORMATION FOR HALOCARBON CLEAN AGENTS
LC50 or ALC NOAEL LOAEL
Agent
% % %

www.standards.org.au Standards Australia


AS 4214:2018

O4.2 PBPK model

Standards Australia www.standards.org.au


AS 4214:2018

O4.3 Safe exposure guidelines for halocarbons

www.standards.org.au Standards Australia


AS 4214:2018

TABLE O2
TIME FOR SAFE HUMAN EXPOSURE
AT STATED CONCENTRATIONS FOR HFC-125
Property Unit
HFC-125 concentration Human exposure time
vol.% ppm minutes

TABLE O3
TIME FOR SAFE HUMAN EXPOSURE
AT STATED CONCENTRATIONS FOR HFC-227ea
Property Unit
HFC-227ea concentration Human exposure time
vol.% ppm minutes

Standards Australia www.standards.org.au


AS 4214:2018

TABLE O4
TIME FOR SAFE HUMAN EXPOSURE
AT STATED CONCENTRATIONS FOR HFC-236fa
Property Unit
HFC-236fa concentration Human exposure time
vol.% ppm minutes

TABLE O5
TIME FOR SAFE HUMAN EXPOSURE
AT STATED CONCENTRATIONS FOR CF 3 I
Property Unit
CF 3 I concentration Human exposure time
vol.% ppm minutes

www.standards.org.au Standards Australia


AS 4214:2018

O5 INERT GAS (NON-LIQUEFIED GAS)


O5.1 Physiological effects of inert gas agents

TABLE O6
PHYSIOLOGICAL EFFECTS FOR INERT GAS AGENTS
No effect levela Low effect level a
Agent
% %

O5.2 Safe exposure guidelines for inert gas agents

Standards Australia www.standards.org.au


AS 4214:2018

www.standards.org.au Standards Australia


AS 4214:2018
AS 4214:2018
AS 4214:2018
Standards Australia
Standards Australia develops Australian Standards® and other documents of public benefit and national interest.
These Standards are developed through an open process of consultation and consensus, in which all interested
parties are invited to participate. Through a Memorandum of Understanding with the Commonwealth Government,
Standards Australia is recognized as Australia’s peak non-government national standards body. Standards Australia
also supports excellence in design and innovation through the Australian Design Awards.

For further information visit www.standards.org.au

Australian Standards®
Committees of experts from industry, governments, consumers and other relevant sectors prepare Australian
Standards. The requirements or recommendations contained in published Standards are a consensus of the views
of representative interests and also take account of comments received from other sources. They reflect the latest
scientific and industry experience. Australian Standards are kept under continuous review after publication and are
updated regularly to take account of changing technology.

International Involvement
Standards Australia is responsible for ensuring the Australian viewpoint is considered in the formulation of
International Standards and that the latest international experience is incorporated in national Standards. This role is
vital in assisting local industry to compete in international markets. Standards Australia represents Australia at both
the International Organization for Standardization (ISO) and the International Electrotechnical Commission (IEC).

Sales and Distribution


Australian Standards®, Handbooks and other documents developed by Standards Australia are printed and
distributed under licence by SAI Global Limited.
For information regarding the development of Standards contact:
Standards Australia Limited
GPO Box 476
Sydney NSW 2001
Phone: 02 9237 6000
Email: mail@standards.org.au
Internet: www.standards.org.au

For information regarding the sale and distribution of Standards contact:


SAI Global Limited
Phone: 13 12 42
Email: sales@saiglobal.com

ISBN 978 1 76072 019 3


This page has been left intentionally blank.