/16 - 1/8 - 1/4 DIN PROCESS CONTROLLERS Panel-Mounting
The mounting panel must be rigid, and may be up to 2. SELECT MODE - Parameter Lower Upper Adjustment range & Description Display Display Default Value CONCISE PRODUCT MANUAL (59300-12) 6.0mm (0.25inch) thick. Cut-out sizes are: B Select mode is used to access the configuration and operation menu functions. Dev. Alarm 2 Cut-Out Dim A Cut-Out Dim B It can be accessed at any time by holding down and pressing . Value* 1 Same options as Alarm 1 CAUTION: Installation should be only performed by technically /16 & 1/8 Din = 45mm 1 /16 Din = 45mm In select mode, press or to choose the required mode, press to enter. Alarm 2 1 /4 Din = 92mm 1 /8 & 1/4 Din = 92mm An unlock code is required to prevent unauthorised entry to Configuration, & Setup Hysteresis* competent personnel. It is the responsibility of the installing engineer to ensure that the configuration is safe. Local regulations regarding For n multiple instruments mounted side-by-side, cut-out A modes. Press or to enter the unlock code, then press to proceed. Loop Alarm (disabled) or (enabled) electrical installation & safety must be observed - e.g. US National A is 48n-4mm (1/16 & 1/8 Din) or 96n-4mm (1/4 Din) Mode Upper Lower Description Default Loop Alarm Electrical Code (NEC) and/or Canadian Electrical Code. Impairment of Tolerance +0.5, -0.0mm Unlock Time* 1 sec to 99 mins. 59secs . Display Display protection will occur if the product is used in a manner not specified by the manufacturer. See section 12 for addional installation and 1. Insert instrument into Codes No alarms Inhibited safety information. the panel cut-out. Operator Normal operation None Alarm 1 inhibited Mounting Panel Alarm Inhibit 2. Hold front bezel firmly Set Up Tailor settings to the application Alarm 2 inhibited 1. INSTALLATION Instrument (without pressing on Configuration Configure the instrument for use Alarm 1 and alarm 2 inhibited Some installation details vary between the three model sizes covered by this manual Housing display area), and re-fit Product Info Check manufacturing information None Primary Power mounting clamp. (refer to section 10). These differences have been clearly shown. Ratchets Auto-Tuning Invoke Pre-Tune or Self-Tune Secondary Power Installing Option Modules: 1/16 Din Size Instruments 3. Push clamp forward, Note: The instrument will always return automatically to Operator mode if Alarm 1, Direct there is no key activity for 2 minutes. Gasket using a tool if necessary, Alarm 1, Reverse CPU PCB 3. CONFIGURATION MODE - Mounting Struts until gasket is Alarm 2, Direct compressed and instrument held firmly Alarm 2, Reverse First select Configuration mode from Select mode (refer to section 2). Option Module 1 Option Module A in position. Loop Alarm, Direct Press to scroll through the parameters, then press or to set the required Output 1 Usage value. Press to accept the change, otherwise parameter will revert to previous Loop Alarm, Reverse Option Module 3 CAUTION: For an effective IP66 & NEMA 4X seal against dust and value. To exit from Configuration mode, hold down and press , to return to Logical Alarm 1 OR 2, Direct Option Module 2 moisture, ensure gasket is well compressed against the panel, with the 4 Select mode. Logical Alarm 1 OR 2, Reverse tongues located in the same ratchet slot. Note: Parameters displayed depends on how instrument has been configured. PSU PCB Refer to user guide (available from your supplier) for further details. Logical Alarm 1 AND 2, Direct Rear Terminal Wiring Parameters marked * are repeated in Setup Mode. Logical Alarm 1 AND 2, Reverse 1 1 Installing Option Modules: /8 & /4 Din Size Instruments USE COPPER CONDUCTORS (EXCEPT FOR T/C INPUT). CABLE RATING 80°C MIN Retransmit SP Output Parameter Lower Upper Adjustment range & Description Default Single Strand wire gauge: Max 1.2mm (18SWG) Retransmit PV Output Display Display Value The diagrams below show all possible option combinations. The actual 0 to 5 V DC output Input CPU PCB Mounting Struts connections required depends on the exact model and options fitted. Range/Type See following table for possible codes 0 to 10 V DC output Linear Output 1 CAUTION: Check information label on housing for correct operating Code Input Type & Code Input Type & Code Input Type & Range 2 to 10 V DC output Option Module B voltage before connecting supply to Power Input Range Range Range 0 to 20 mA DC output Option Module A Fuse: 100 – 240V ac – 1Amp anti-surge bC B: 100 - 1824 ºC L.C L: 0.0 - 537.7 ºC PtRh20% vs 40%: 4 to 20 mA DC output 24/48V ac/dc – 315mA anti-surge P24F 32 - 3362 ºF 1 bF B: 211 - 3315 ºF L.F L: 32.0 - 999.9 ºF Retransmit -1999 to 9999 Option Module 2 /16 Din Size Instrument Connections Option Module 3 Output 1 Scale (display value at which output Range max CC C: 0 - 2320 ºC NC N: 0 - 1399 ºC PTC Pt100: –199 - 800 ºC maximum will be maximum) CF C: 32 - 4208 ºF NF N: 32 - 2551 ºF PtF Pt100: –328 - 1472 ºF Retransmit -1999 to 9999 Option Module 1 PSU PCB J: –200 - 1200 ºC Pt.C Pt100: –128.8 - 537.7 ºC Output 1 Scale (display value at which output Range min JC rC R: 0 - 1759 ºC minimum will be minimum) JF J: –328 - 2192 ºF rF R: 32 - 3198 ºF Pt.F Pt100: –199.9 - 999.9 ºF Output 2 Usage Same options as Output 1 Sec or Al2 j.C J: –128.8 - 537.7 ºC SC S: 0 - 1762 ºC 0 - 20 mA DC Linear Output 2 To access modules 1, A or B, first detach the PSU and CPU boards from the front by Range Same options as Output 1 lifting first the upper, and then lower mounting struts. Gently separate the boards. j.F J: –199.9 - 999.9 ºF SF S: 32 - 3204 ºF 4 - 20 mA DC a. Plug the required option modules into the correct connectors, as shown below. Retransmit -1999 to 9999 KC K: –240 - 1373 ºC tC T: –240 - 400 ºC 0 - 50 mV DC b. Locate the module tongues in the corresponding slot on the opposite board. Output 2 Scale (display value at which output Range max c. Hold the main boards together while relocating back on the mounting struts. KF K: –400 - 2503 ºF tF T: –400 - 752 ºF .10 - 50 mV DC maximum will be maximum) Retransmit -1999 to 9999 d. Replace the instrument by aligning the CPU and PSU boards with their guides k.C K: –128.8 - 537.7 ºC t.C T: –128.8 - 400.0 ºC 0 - 5 V DC in the housing, then slowly push the instrument back into position. Output 2 Scale (display value at which output Range min K.F K: –199.9 - 999.9 ºF t.F T: –199.9 - 752.0 ºF 1 - 5 V DC minimum will be minimum) Note: Option modules are automatically detected at power up. LC L: 0 - 762 ºC PtRh20% vs. 40%: 0 - 10 V DC Output 3 Usage Same options as Output 1 Option Module Connectors: 1/16 Din Size Instruments P24C 0 - 1850 ºC LF 2 - 10 V DC Linear Output 3 L: 32 - 1403 ºF Same options as Output 1 Option Slot 1 Option Slot A Note: Decimal point shown in table indicates temperature resolution of 0.1° Range Connectors Connectors Retransmit -1999 to 9999 Parameter Lower Upper Adjustment range & Description Default PL7 & PL8 PL5 & PL6 Display Display Value Output 3 Scale (display value at which output Range max maximum will be maximum) Scale Range Scale Range Lower Limit +100 Range max Upper Limit to Range Maximum (Lin=1000) Retransmit -1999 to 9999 Option Slot 2 Option Slot 3 Output 3 Scale (display value at which output Range min Connector Scale Range Range Minimum to Range min minimum will be minimum) Connector Lower Limit Scale Range Upper Limit -100 (Linear=0) PL4A , , , , or (refer to section 8) 1 PL4B /8 & 1/4 Din Size Instrument Connections Display Strategy Decimal point 0=XXXX, 1=XXX.X, 2=XX.XX, 3=X.XXX position (non-temperature ranges only) 1 ASCII Serial Primary only Mm Modbus with no parity Option Module Connectors: 1/8 & 1/4 Din Size Instruments Control Type Communications Mm Primary & Secondary Protocol Mm Modbus with Even Parity Option Slot B (e.g. heat & cool) Mm Modbus with Odd Parity Connectors Primary Output Reverse Acting . 1.2 kbps PL2A, PL2B & Control Action Direct Acting Serial . 2.4 kbps PL2C Communications Process High Alarm . 4.8 kbps . Bit Rate Process Low Alarm . 9.6 kbps Option Slot 2 Alarm 1Type Deviation Alarm . 19.2 kbps Connector Band Alarm Comms Address 1 to 255 (Modbus), 1 to 99 (ASCII) PL4A No alarm Ww Read/Write High Alarm 1 Comms Write Ww Range Max Read only Option Slot 1 value* Range Minimum to Range Maximum in display units Digital Input 1 Setpoint 1 / Setpoint 2 select* Connectors Low Alarm 1 Range Min PL7 & PL8 value* Usage Automatic / Manual select Band Alarm 1 1 LSD to span from setpoint in display units Setpoint 1 / Setpoint 2 select* value* Digital Input 2 Usage Automatic / Manual select Dev. Alarm 1 Option Slot A value* +/- Span from setpoint in display units Remote / Local setpoint select Connectors PL5 & PL6 Alarm 1 1 LSD to full span in display units Note: has priority over if both are configured for the same usage. Hysteresis* If or = the remote setpoint input is disabled. Alarm 2 Type* High Alarm 2 Continued on next page… Option Slot 3 value* Range Max Connector PL4B Low Alarm 2 Same options as Alarm 1 Note: At first power-up the message is displayed, as described in value* Range Min section 7 of this manual. Access to other menus is denied until configuration Band Alarm 2 mode is completed value* Parameter Lower Upper Adjustment range & Description Display Display Default Value 5. AUTOMATIC TUNING MODE - 8. OPERATOR MODE - DIGITAL INPUTS Volt-free(or TTL): Open(2 to 24VDC) = SP1, Local SP or Auto Mode, 0 to 20 mA DC input First select Automatic tuning mode from Select mode (refer to section 2). This mode is entered at power on, or accessed from Select mode (see section 2). Closed(<0.8VDC) = SP2, Remote SP or Manual Mode. Press to scroll through the modes, then press or to set the required value. Note: All Configuration mode and Setup mode parameters must be set as required 4 to 20 mA DC input To exit from Automatic tuning mode, hold down and press , to return to Select before starting normal operations. Isolation: Reinforced safety isolation from inputs and other outputs. 0 to 10 V DC input mode. Press to scroll through the parameters, then press or to set the required 2 to 10 V DC input Pre-tune is a single-shot routine and is thus self-disengaging when complete. value. OUTPUTS Remote Setpoint Input Range 0 to 5 V DC input If in Setup mode = , Pre-tune will attempt to run at every power up*. Note: All Operator Mode parameters in Display strategy 6 are read only (see in Relay 1 to 5 V DC input Refer to the full user guide (available from your supplier) for details on controller tuning. configuration mode), they can only be adjusted via Setup mode. Contact Type & Single pole double throw (SPDT); 2A resistive at 120/240VAC. Pre-tune LED flashes and Self-tune LED is solid. Rating: 0 to 100mV DC input Available on Upper Lower Display Strategy and Description Potentiometer full RSP Parameter Lower Upper Display Default Display Display When Visible Lifetime: >500,000 operations at rated voltage/current. (2K minimum) (Slot B) only Display Value PV and target value of selected SP Isolation: Basic Isolation from universal input and SSR outputs. Active SP RSP Upper Limit -1999 to 9999 Range max Pre-Tune or . Indication remains if automatic PV Value Value 1 & 2 (initial screen) Local Setpoints are adjustable in SSR Driver Off Strategy 2 RSP Lower Limit -1999 to 9999 Range min Self-Tune tuning cannot be used at this time* Drive Capability: SSR drive voltage >10V into 500 min. (~20mA) Actual PV and actual value of selected SP Constrained within Scale Range Upper & Tune Lock 0 to 9999 PV Value 3 & 6 (initial screen) RSP Offset Scale Range Lower limits * Note: Automatic tuning will not engage if either proportional band = 0. SP Value (e.g. ramping SP value). Read only Isolation: Not isolated from universal input or other SSR driver outputs. Process variable only Triac Configuration Also, Pre-tune will not engage if setpoint is ramping, or the PV is less than 5% of PV Value (Blank) 4 (initial screen) Lock Code 0 to 9999 input span from the setpoint. Read only Operating Voltage: 20 to 280Vrms (47 to 63Hz). Active SP Target value of selected setpoint only. (Blank) 5 (initial screen) Current Rating: 0.01 to 1A (full cycle rms on-state @ 25°C); 4. SETUP MODE - 6. PRODUCT INFORMATION MODE - Value Read only derates linearly above 40°C to 0.5A @ 80°C. 1, 3, 4, 5 & 6 if digital Target value of SP Isolation: Reinforced safety isolation from inputs and other outputs. Note: Configuration must be completed before adjusting Setup parameters. First select Product information mode from Select mode (refer to section 2). SP Value input is not and Adjustable except in Strategy 6 First select Setup mode from Select mode (refer to section 2). The MAN LED Press to view each parameter. To exit from Product Information mode, RSP not fitted DC will light solid while in Setup mode. Press to scroll through the parameters, hold down and press to return to Select mode. Digital input = . Target value of SP1 Types / Ranges 0 to 20mA, 4 to 20mA, 0 to 5V, 0 to 10V or 2 to 10V then press or to set the required value. Note: These parameters are all read only. SP1 Value Adjustable except in Strategy 6 To exit from Setup mode, hold down and press to return to Select mode. _ lit if active SP = SP1 Load Resistance: Current Output 500 max, Voltage Output 500 min. Parameter Lower Upper Description Note: Parameters displayed depends on how instrument has been configured. Digital input = . Target value of SP2 Resolution: 8 bits in 250mS (10 bits in 1s typical, >10 bits in >1s typical). Display Display SP2 Value Adjustable except in Strategy 6 Parameter Lower Upper Display Adjustment Default Input type Universal input lit if active SP = SP2 Isolation: Reinforced safety isolation from inputs and other outputs. Display Range & Description Value RSP fitted. Target value of local setpoint Transmitter PSU . No option fitted Local SP Input Filter Time Constant OFF or 0.5 to 100.0 secs or * lit if the Adjustable except in Strategy 6 Power Rating: 20 to 28V DC (24V nominal) into 910 minimum resistance. Relay output Value Process Variable Offset Span of controller active SP = Isolation: Reinforced safety isolation from inputs and other outputs. Option 1 module type fitted SSR drive output Primary Power Ww Current % power levels RSP fitted. Target value of remote setpoint N/A Triac output Remote SP or * lit if the Read only SERIAL COMMUNICATIONS Secondary Power Ww (read only) Value Linear DC voltage / current output active SP = Physical: RS485, at 1200, 2400, 4800, 9600 or 19200 bps. Primary Proportional Band 0.0% (ON/OFF) and 0.5% to Option 2 module type fitted Same as Option 1 Selects local/remote active setpoint Protocols: Selectable between Modbus and West ASCII. . = local SP, = remote SP Secondary Proportional 999.9% of input span No option fitted Isolation: Reinforced safety isolation from all inputs and outputs. RSP is fitted, digital input Band Relay output = selection via digital input (if You cannot connect both configuration port & RS485 port at the same time. , is not and Automatic Reset 1 sec to 99 mins 59 secs and . Option 3 module type fitted SSR drive output configured). Note: selecting or (Integral Time) OFF (blank) or is enabled in OPERATING CONDITIONS (FOR INDOOR USE) Linear DC voltage / current output Setup mode will override digital input, active Rate (Derivative Time) 00 secs (OFF) to 99 mins 59 secs . SP indication changes to * Ambient Temperature: 0°C to 55°C (Operating), –20°C to 80°C (Storage). -20 to +20% of Primary and Transmitter power supply Relative Humidity: 20% to 95% non-condensing. Adjustable except in Strategy 6 Overlap/Deadband Secondary Proportional Band No option fitted Actual SP Actual (ramping) value of Altitude: <2000m 0%(-100% if dual control) to 100% is not blank Manual Reset (Bias) Auxiliary Option A module RS485 communications Value selected SP. Read only Supply Voltage and 100 to 240VAC 10%, 50/60Hz, 7.5VA Primary ON/OFF type fitted Digital Input* enabled in SP ramping rate, in units per hour Power: (for mains powered versions), or Differential 0.1% to 10.0% of input span Ramp Rate Adjustable except in Strategy 6 centered about the setpoint. Remote Setpoint Input (basic)* Setup mode 20 to 48VAC 50/60Hz 7.5VA or 22 to 65VDC 5W Secondary ON/OFF Diff. . (for low voltage versions). (Entered as a percentage No option fitted When one or more L Alarm 2 active Prim. & Sec. ON/OFF Auxiliary Option B module alarms are active. of span) Remote Setpoint Input (full) Active Alarm Alarm 1 active ENVIRONMENTAL Differential type fitted Status ALM indicator will and Digital Input 2* L Loop Alarm active Setpoint Upper Limit Current Setpoint to Range max R/max also flash Standards: CE, UL, cUL & CSA Firmware type Value displayed is firmware type number Setpoint Lower limit Range min to Current Setpoint R/min Manual Control EMI: Complies with EN61326-1:2013. Firmware issue Value displayed is firmware issue number Primary Output Power If is set to in Setup mode, manual control can be selected/de-selected by Safety Considerations: Complies with UL61010-1 Edition 3, EN61010-1 Version 2010 & Limit 0% to 100% of full power Product Revision Level Value displayed is Product Revision level CSA 22.2 No 1010.192. pressing the key in Operator mode, or by changing the status of a digital input if Pollution Degree 2, Installation Category II. Date of manufacture Mm Manufacturing date code (mmyy) Output 1 Cycle Time or have been configured for in Configuration mode. Panel Sealing: Front to IP66 & NEMA 4X when correctly mounted 0.5, 1, 2, 4, 8, 16, 32, 64, 128, Output 2 Cycle Time 256 or 512 secs. Serial number 1 First four digits of serial number – Refer to section 1 While in Manual Control mode, the indicator will flash and the lower display will show Output 3 Cycle Time Serial number 2 Middle four digits of serial number xxx (where xxx is the current manual power level). Switching to/from manual mode is via High Alarm 1 value Range Minimum to Range R/max Serial number 3 Last four digits of serial number PHYSICAL Bumpless Transfer. Press or to set the required output power. Front Bezel Size: 1 /16 Din = 48 x 48mm, 1/8 Din = 96 x 48mm, Low Alarm 1 value Maximum R/min Caution: Manual power level is not restricted by the power limit. 1 /4 Din = 96 x 96mm. Deviation Alarm 1 Value Span from SP in display units 7. MESSAGES & ERROR INDICATIONS 1 Depth Behind Panel: /16 Din = 110mm, 1/8 & 1/4 Din = 100mm. Band Alarm 1 value 1 LSD to span from setpoint These messages indicate that an error has occurred or there is a problem with the process 9. SERIAL COMMUNICATIONS Weight: 0.21kg maximum. variable signal or its wiring. Alarm 1 Hysteresis 1 LSD to full span in display units Refer to the full user guide (available from your supplier) for details. Caution: Do not continue with the process until the issue is resolved. Note: you cannot connect to the configuration port & RS485 at the same time 11. ADDITIONAL INSTALLATION & SAFETY High Alarm 2 value Range Minimum to Range R/max Parameter Upper Lower Description 10. SPECIFICATIONS INFORMATION Low Alarm 2 value Maximum R/min Display Display -Compliance shall not be impaired when fitted to the final installation. Deviation Alarm 2 Value Span from SP in display units Configuration & Setup required. This screen is UNIVERSAL INPUT -Designed to offer a minimum of Basic Insulation only. Band Alarm 2 value 1 LSD to span from setpoint Instrument seen at first turn on, or if hardware configuration Thermocouple 0.1% of full range, 1LSD (1°C for Thermocouple CJC). -The body responsible for the installation is to ensure that supplementary insulation has been changed. Press to enter the Alarm 2 Hysteresis 1 LSD to full span in display units parameters are in Configuration Mode, next press or to Calibration: BS4937, NBS125 & IEC584. suitable for Installation Category II is achieved when fully installed. default conditions -To avoid possible hazards, accessible conductive parts of the final installation should be Loop Alarm Time 1 LSD to full span in display units . enter the unlock code number, PT100 Calibration: 0.1% of full range, 1LSD. BS1904 & DIN43760 (0.00385//°C). protectively earthed in accordance with EN61010 for Class 1 Equipment. then press to proceed DC Calibration: 0.1% of full range, 1LSD. Auto Pre-tune -Output wiring should be within a Protectively Earthed cabinet. Process variable input > 5% over-range, or wrong -Sensor sheaths should be bonded to protective earth or not be accessible. Auto/manual Control Input Over Range Normal Sampling Rate: 4 per second. sensor type. -Live parts should not be accessible without the use of a tool. selection (disabled) or Process variable input > 5% under-range, or Impedance: >10M resistive, except DC mA (5) and V (47k ). -When fitted to the final installation, an IEC/CSA APPROVED disconnecting device should Setpoint Select shown in Input Under Range Normal Operator Mode (enabled) wrong sensor type. Sensor Break Thermocouple, RTD, 4 to 20 mA, 2 to 10V and 1 to 5V ranges only. be used to disconnect both LINE and NEUTRAL conductors simultaneously. Break detected in process variable input sensor, Detection: Control outputs turn off. -Do not position the equipment so that it is difficult to operate the disconnecting device. Setpoint ramp adjustment Input Sensor Break Normal shown in Operator Mode wiring, or wrong sensor type.The SP goes to 0. Isolation: Isolated from all outputs (except SSR driver). WARNING: This product can expose you to chemicals including arsenic, which is known to the RSP Over Range Normal ** RSP input over-range ** also seen Universal input must not be connected to operator accessible SP Ramp Rate Value 1 to 9999 units/hour or Off (blank) Off State of California to cause cancer. For more information go to www.P65Warnings.ca.gov RSP Under Range Normal ** RSP input under-range wherever RSP circuits if relay outputs are connected to a hazardous voltage source. Supplementary insulation or input grounding would then be Setpoint Value Scale range upper to lower limits. Break detected in RSP value would be RSP Break Normal ** required. (when dual or remote setpoint input signal displayed Local Setpoint Value options are used, Scale Option 1 Error Option 1 module fault REMOTE SETPOINT INPUT (100 device load) is replaced by Range Option 2 Error Option 2 module fault Accuracy: 0.25% of input range 1 LSD. Setpoint 1 Value & or Minimum Option 3 Error Option 3 module fault Sampling Rate: 4 per second. or * before the legend Option A Error Option A module fault or RSP in both A & B Sensor Break 4 to 20 mA, 2 to 10V and 1 to 5V ranges only. Control outputs turn indicates the currently active SP) Setpoint 2 Value Option B Error Option B module fault Detection: off if RSP is the active SP. Isolation: Slot A - Basic isolation, Slot B - Reinforced safety isolation from Setup Lock Code 0 to 9999 other inputs and outputs.