Professional Documents
Culture Documents
INDEX
SL# CONTENT PAGE NO
1 Scope 3
2 Personal protection 3
3 Reference documents 3
4 General requirements 3
4.1 Personnel qualification 3
4.2 Surface preparation 4
4.3 Back scatter radiation check 4
4.4 System of identification 4
4.5 Monitoring density limitations of radiographs 4
5 Equipment and materials 5
5.1 Films 5
5.2 Processing 5
5.3 Intensifying screens 5
5.4 IQI design 5
5.5 Facilities for viewing radiographs 6
6 Calibration 6
6.1 Source size 6
6.2 Step wedge film and densitometer 6
6.3 Verification of Parameters 6
7 Examination 7
7.1 Radiographic technique 7
7.2 Selection of energy of radiation 8
7.3 Source to film & object distance 8
7.4 Location markers 9
7.5 IQI selection 10
7.6 Use of IQI to monitor radiographic examination 12
8 Evaluation of radiography quality 14
8.1 Quality of radiographs 14
8.2 Radiographic density 15
8.3 IQI Sensitivity 15
8.4 Excessive scatter 15
8.5 Geometric unsharpness limitations 15
9 Documentation 16
9.1 Radiographic Technique Information 16
9.2 Records 16
9.3 Reports 16
9.4 Identification of complited work 17
10 Evaluation 17
11 Acceptance criteria 25
12 Report Format 34
Table 5.4.1(a) ASTM Wire Type IQI 5
Table 5.4.1 (b) ISO Wire Type IQI 6
Table 7.1 Radiographic technique 7
Table 7.4 Number Spacing 9
Table 7.5.2 (a) ASME: IQI Selection 10
Table 7.5.2 (b) DIN or/and ISO: IQI Selection 11
Table 7.5.2 (c) IQI Selection: API 1104 11
Table 8.5 Geometric Unshapness limits 16
Table 11. 3 (b) – Acceptance Criteria 28
Table 11.4 – Acceptance Criteria for API STD 1104 30
Table 11. 5 – Rejection Criteria for Statically Loaded Structures, AWS 32
Page 1 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Page 2 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
1 SCOPE
This specification is intended for the use with any standard code referenced & it covers the
minimum requirements used by NDT personnel to carry out the radiographic examination of
weld joints by X-Ray & gamma rays.
2 PERSONAL PROTECTION
Each person using X-ray or gamma ray equipment shall make a radiation survey during the
initial operation and for each additional radiographic exposure.
All necessary steps shall be taken to assure that the radiation intensity outside the established
barriers is such that a person would not receive more than 0.75 mR in any one hour.
Each person using the radiation equipment shall wear a film badge or Thermo Luminescent
Dosimeter (TLD) at waist level or at chest level, a direct reading pocket dosimeter, an
alarming rate meter or Electronic Pocket Dosimeter.
For information on this important aspect of radiography, reference shall be made to current
document of the NDT Corrosion Control Services (NDTCCS) safety manual NDT/RP 001(Latest
Revision).
3 REFERENCE DOCUMENTS
4 GENERAL REQUIREMENTS
Page 3 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
4.1.1 A Level-I may perform any radiographic operation but must be under the direct supervision of
Certified Level-II or Level-III. A Level I cannot interpret the radiographs.
4.1.2 A Level-II may perform any radiographic operation including the processing of the film’s
radiographs. The Level-II may be required to prepare technique sheet and shooting sketch for
each part radiographed and submit these to the Level-III for approval. The Level-II shall be
responsible to the Level-III.
4.1.3 Personnel performing radiographic film interpretation shall have passed NDTCCS internal
Level II Film Interpretation Examination and approved by SATORP.
4.1.4 A Level III shall be responsible for writing the appropriate procedure and techniques to be
applied. He shall be fully responsible for the quality of the radiography job. He shall be
responsible for in-house certification of Level I & II Radiographers.
4.2 SURFACE PREPARATION
4.2.1 The weld joint surfaces may be in "as welded" conditions, ground or machined according to
drawing requirements. The weld crown, if present, shall not exceed the maximum permitted
by the referencing Code Section.
4.2.2 The weld ripples or weld surface irregularities, weld spatter on both sides (inside where
accessible) shall not interfere with the film interpretation. Backing strips need not to be
removed provided they do not interfere with the interpretation of the radiographs.
4.2.3 When the time of examination is not specified stated in the referenced code or project
specification, final radiography for acceptance of the weld / material shall be performed
after final inspection.
4.3 BACK SCATTER RADIATION CHECK
A lead letter "B" with a minimum dimension of 7/16 " (11 mm) in height and 1/16 " (1.5 mm) in
thickness shall be attached to the back of each film holder, during each exposure to
determine if backscatter radiation is exposing the film.
4.4 SYSTEM OF IDENTIFICATION
An identification symbol system shall be used in order to ensure a permanent record of the
seam to be radiographed. Each radiograph shall be identified using lead numbers and/or
letters. The radiographic identification shall include the following information:
The information shall not obscure the area of interest on the radiograph.
1.B Number / Job Order Number
2. Manufacturer's name or symbol.
3. Component, vessel or piping identification.
4. Seam or weld identification.
5. Welder Identity No.
6. R1 for repair 1, R2 for repair 2, if necessary etc.
7. Cut out shall be identified as a new weld, e.g. NSW1, etc
8. In case of reshoot, the film shall contain the symbol RS1, RS2, etc, if more than one reshoots.
9. When tracer shots are required for random or spot radiography, the rejected weld number
followed by letter T1, T2 etc., shall be included as a part of the film identification.
10. Date of radiography.
11. Station or location marks shall be spaced in inches or centimeter.
4.5 MONITORING DENSITY LIMITATION OF RADIOGRAPHYS
Only calibrated densitometer shall be used. Either a densitometer or step wedge comparison
film strip shall be used for judging film density. Densitometer performance shall be verified
before each use with a density film strip traceable to a national standard. Densitometer shall
be calibrated at least every 90 days.
Page 4 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
5.1 FILMS
Radiographs shall be made using industrial radiographic film either Class I or II. The films used
shall be either Agfa , Kodak or Fuji and it shall be approved by Project inspection Unit.
5.1.1 Type I film shall be used for radiography of pipe diameters of 8-inch nominal size (NPS) or less.
5.2 PROCESSING
To produce a satisfactory radiograph, the care used in making the exposure must be
followed by equal care in processing. The most careful radiographic techniques can be
nullified by incorrect or improper darkroom procedures. Film shall be processed in
accordance with ASTM E-94.
5.2.1 Automatic Processing:
The essence of automatic processing system is control. The processor maintains the chemical
solutions at the proper temperature, agitates and replenishes the solutions automatically and
transports the films mechanically at a carefully controlled speed throughout the processing
cycle. Film characteristics must be compatible with processing conditions.
5.2.2 Manual Processing:
Technician should follow detailed recommendations on manual film processing as listed in
NDT/CCS MSA-002.1. This shall be used as a guide for processing film. Variation to the film
manufacturer’s processing recommendations to compensate for exposure is not permitted.
5.3 INTENSIFYING SCREENS
Intensifying lead screens shall be used in direct contact with the film unless otherwise
specifically directed. For Radiography using gamma ray sources, the minimum thickness of
the front lead screen shall be 0.125 mm (0.005in.) for Ir- 192 and Se-75.
5.4 IQI DESIGN
5.4.1 The IQI used shall be of the wire type and shall be manufactured and identified in
accordance with the requirements of SE 747 for wire type. Refer table 5.4.1(a). Image Quality
Indicators shall be of the “Wire Type”.
5.4.2 DIN type IQI described in DIN 54 109, ISO type IQI described ISO 1027, EN type IQI as
described in BS EN 462.1 or ASTM type IQI as described in ASTM SE-747 may be used as
alternative to ASME IQI. Refer Table 5.4.1(a), 5.4.1 (b).
Table 5.4.1(a)
ASTM Wire Type IQI
ASTM Set
Wire Diameter mm (inch)
Designation
A .081 (.0032) .102 (.004) .127 (.005) .160 (.0063) .203 (.008) .254 (.010)
B .254 (.010) .330 (.013) .406 (.016) .508 (.020) .635 (.025) .813 (.032)
C .813 (.032) 1.016 (.040) 1.27 (.050) 1.6 (.063) 2.03 (.080) 2.54 (.100)
D 2.54 (.100) 3.2 (.126) 4.06 (.160) 5.08 (.200) 6.35 (.250) 8.13 (.320)
ISO Pack
Wire Diameter mm (inch) and wire number
Page 5 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Designaton
5.4.3 Damaged IQI's shall not be used, e.g., bent wires. IQI's shall not be modified in any way.
5.4.4 IQI's shall be selected from either the same alloy material group or grade as identified in ASTM
E747 or from an alloy material group or grade with less radiation absorption than the material
being radiographed.
5.5 FACILITIES FOR VIEWING RADIOGRAPHYS
The equipment used to view films for radiographic interpretation shall provide a variable high
intensity light source sufficient for the essential wire to be visible for the specific density range.
The viewing conditions shall be such that light coming from around the outer edge or from
low density portions of the radiographic does not interfere with interpretation.
The viewing facilities should provide subdued back ground lighting on an intensity that will not
cause troublesome reflections, shadows, or glare on the radiograph.
Radiographic viewers shall meet the minimum requirements set forth in ISO 5580. and shall
provide a variable light source for the essential designated wire to be visible throughout the
specified density range.
6 CALIBRATION
Page 6 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
6.3.1 Before commencement of the actual examination of the welded joints by radiography, test
films are exposed to establish the parameters chosen are adequate to give for radiographs
of acceptable quality for sensitivity, density, and cleanliness.
6.3.2 Whenever there is any change of any radiographic parameters, material thickness, diameter,
material type the procedure 6.3.1 is repeated to establish the changed parameters.
The following are the list of radiographic parameters :
1) Source type, size and strength.
2) Source to film distance & object to film distance.
3) Intensifiers and filters.
4) Type of film.
5) Developer and Fixer.
6) Temperature of Developer and Fixer.
7 EXAMIANTION
≤ 3-1/2 Inch Elliptical Dbl. Wall Exp. Dbl. Wall Viewing 2 (0,90) 2F
≤ 3-1/2 Inch Elliptical Dbl. Wall Exp. Sgl. Wall Viewing 4 (0,90,180,270) 2E or F
≤3-1/2” Inch Superimposed Dbl. Wall Exp. Dbl. Wall Viewing 3 (0,60,120) 2G
≥3-1/2” Inch Contact Dbl. Wall Exp. Sgl wall Viewing 3 (0,120,240) 2D or E
Note:
a) Techniques other than those described in above table may be used with the
approval of SATORP inspection Department.
b) If the minimum number of exposures shown above is not adequate to demonstrate
the required coverage, additional exposure shall be made as specified by the
certified SATORP Film Interpreter.
7.1.1 Single Wall Technique
In the single wall technique, the radiation passes through only one wall of the weld, which is
viewed for acceptance on the radiograph. An adequate number of exposures shall be
made to demonstrate that the required coverage has been obtained.
7.1.2 Double Wall Technique
When it is not practical to use a single wall technique, one of the following double wall
techniques shall be used:
Page 7 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Page 8 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
radiographing butt joints greater than ½ in thick . The minimum width of the edge block shall
be 1 in or half the weld thickness whichever is greater. The edge block shall have a thickness
equal to or greater than the thickness of the weld being radiographed.
Page 9 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Location markers may be placed on either the source or film side joints in curved or spherical
components whose concave side is toward the source and the source to material distance
equals the inside radius of the component.
7.4.2 Double wall viewing
In this case at least one location marker shall be placed on the film side of the object
adjacent to the weld (shall not appear in the area of interest) for each radiograph.
7.4.3 Mapping the placement of location markers
When inaccessibility or other limitations prevent the placement of markers as stipulated in
para. 7.4.1 and para. 7.4.2, a dimensioned map of the actual marker placement shall
accompany the radiographs and shall show the full coverage has been obtained.
Nominal Single-Wall
Material thickness Range Source side Film side
Page 10 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Table 7.5.3 (a) Weld Thickness Vs Diameter of ASTM E747 Wire type IQI
Inch mm Inch mm
Page 11 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Table 7.5.3 (b) Weld Thickness Vs Diameter of ISO Wire type IQI
Inch mm Inch mm
Note: In accordance with API 1104, for purposes of IQI selection, when the SWE/SWV
technique is used, the thickness of the weld means specified wall thickness plus the weld
reinforcement (internal plus external combined). When the elliptical DWE/DWV technique is
used, the thickness of the weld means twice the specified wall thickness plus the single weld
reinforcement (internal plus external combined). When the superimposed DWE/DWV
technique is used , the thickness of the weld means twice the specified wall thickness plus
twice the weld reinforcement (internal plus external combined)
7.6 USE OF IQI TO MONITOR RADIOGRAPHIC EXAMINATION
7.6.1 Placement of IQI
7.6.1.1 Source side IQI(s)
When using separate blocks for IQI placement based onthe thickness of the blocks shall be
such that the image brightness at the body of the IQI isjudged to beequal to or greater than
the image brightness at the area of interest for a negative image format. If verified by
measurement, pixel intensity variations up to 2% are permitted in the determination of “equal
to.” This image brightness requirement is reversed for a positive image format
The IQI shall be placed on the source side of part being examined, except in the condition
described in (b) below. When, due to part or weld configuration or size, it is not practical to
place the IQI(s) may be placed on a separate block. Separate blocks shall be made of the
same or radiographically similar materials (as defined in SE- 1025) and may be used to
Page 12 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
facilitate IQI positioning. There is no restriction on the separate block thickness, provided the
IQI/area-of-interest density tolerance requirements of para 8.2 are met. IQI shall be placed on
the weldment in the area of interest being radiographed as shown in the figure 7.6.1.
a) The IQI on the source side of the separate block shall be placed no closer to the film
than the source side of the part being radiographed.
b) The separate block shall be placed as close as possible to the part being
radiographed.
c) The block dimensions shall exceed the IQI dimensions such that the outline of at least
three sides of the IQI image shall be visible on the radiograph.
7.6.1.2 Film side IQI(s)
Where inaccessibility prevents hand placing the IQI on the source side, it shall be placed on
the film side in contact with the part being examined. A lead letter "F" at least as high as the
IQI identification number shall be placed adjacent to or on the IQI but shall not mask the
essential wires.
7.6.1.3 Wire IQI’s:
The IQI(s) shall be placed on the weld so that the length of the wires is perpendicular to the
length of the weld. The identification numbers and, when used, the lead letter “F”, shall not
be in the area of interest, except when geometric configuration makes it impractical.
7.6.2 Number of IQIs
Number of IQIs. For DWE/SWV or SWE/SWV techniques requiring multiple exposures for
complete inspection of the weld, and where the length of the film to be interpreted is greater
than 127 mm (5 inches), two IQI’s placed across the weld and perpendicular to the weld
length shall be used. One shall be within 25.4 mm (1inch) of the end of the film length to be
interpreted and the other shall be at the center of the film length to be interpreted. When the
film length to be interpreted is 127 mm (5 inches) or less, one IQI’s shall be placed across the
weld and perpendicular to the weld length at the center of the length to be interpreted.
When one or more film holders are used for an exposure, at least one IQI image shall appear
on each radiograph except as outlined in (b) below.
a) Multiple IQIs. If the requirements of 8.2 are met by using more than one IQI, one shall be
representative of the lightest area of interest and the other the darkest area of interest;
the intervening densities on the radiograph shall be considered as having acceptable
density.
b) Special Cases:
1. For Monorail / Structural weld (AWS D14.1), one penetramter centered on the film, shall
be used for film 10 in (250mm) or less in length. Two Penetrameters, one centered and
one at the end of the film, shall be used for radiographs with a film length greater than 10
in (250mm) in length. For Panoramic exposure, three penetrameters shall be paced at
120°apart around the object being radiographed. penetrameters shall be placed on the
source side whenever possible.
2. For cylindrical components where the source is placed on the axis of the component for
a single exposure, at least four IQIs, spaced approximately 90 deg. apart, are required
when the complete circumference is radiographed using one or more film holders or
when a section or sections of the circumference, where the length between the ends of
the outermost sections span 240 or more deg., is radiographed using one or more film
holders. Additional film locations may be required to obtain necessary IQI spacing.
3. For cylindrical components where the source is placed on the axis of the component for
a single exposure, at least four IQIs, with one placed at each end of the span of the
circumference radiographed and one in the approximate center of the span, are
required when a section of the circumference, the length of which is greater than 120
deg. and less than 240 deg., is radiographed using just one film holder or when a section
Page 13 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
or sections of the circumference, where the length between the ends of the outermost
sections span less than 240 deg., is radiographed using more than one film holder.
4. In (1) and (2) above, where sections of longitudinal welds adjoining the circumferential
weld are radiographed simultaneously with the circumferential weld, an additional IQI
shall be placed on each longitudinal weld at the end of the section most remote from the
junction with the circumferential weld being radiographed.
5. For spherical components where the source is placed at the center of the component for
a single exposure, at least four IQIs, spaced approximately 90 deg. apart, are required
when a complete circumference is radiographed using one or more film holders or when
a section or sections of a circumference, where the length between the ends of the
outermost sections span 240 or more deg., is radiographed using one or more film holders.
Additional film locations may be required to obtain necessary IQI spacing.
6. For spherical components where the source is placed at the center of the component for
a single exposure, at least four IQIs, with one placed at each end of the radiographed
span of the circumference radiographed and one in the approximate center of the span,
are required when a section of a circumference, the length of which is greater than 120
deg. and less than 240 deg., is radiographed using just one film holder or when ass section
or sections of a circumference, where the length between the ends of the outermost
sections span less than 240 deg. is radiographed using more than one film holder.
7. In (4) and (5) above, where other welds are radiographed simultaneously with the
circumferential weld, one additional IQI shall be placed on each other weld.
8. When an array of components in a circle is radiographed, at least one IQI shall show on
each component image.
9. In order to maintain the continuity of records involving subsequent exposures, all
radiographs exhibiting IQIs that qualify the techniques permitted in accordance with (1)
through (6) above shall be retained.
Except as provided in item b. below, IQIs shall be placed in contact with the piping.
Wire type IQIs: When a complete weld is radiographed in a single exposure using a source
inside the piping, at least four IQIs placed across the weld and spaced approximately equally
around the circumference shall be used. For the DWE/DWV procedure, one IQI shall be
placed on the source side of the pipe and adjacent to the weld so that its image is not
superimposed onto the weld image. For the DWE/SWV or SWE/SWV procedures requiring
multiple exposures for complete inspection of the weld, and where the length of film to be
interpreted is greater than 5 in. (130 mm), two IQIs placed parallel to the weld and located
on the film side shall be used. One shall be within 1 in. (25 mm) of the end of the film length to
be interpreted and the other shall be at the center of the film. When the film length to be
interpreted is 5 in. (130 mm) or less, one IQI shall be placed on the film side, parallel to the
weld and located at the center of the length to be interpreted. When a repaired weld is
radiographed, at least one IQI shall be placed adjacent to each repaired area.
Heat shields: IQIs may be placed on a heat shield rather than in contact with the pipe,
provided that the acceptability of such IQI placement is demonstrated prior to production
testing.
8 EVALUATION OF RADIOGRAPHY QUALITY
Page 14 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
a) Fogging
b) Processing defects such as streaks, water marks or chemical stains.
c) Scratches, finger marks, crimps, dirtiness, static marks, smudges, or tears.
d) Loss of detail due to poor screen to film contact.
e) False indications due to defective screens or internal faults.
Page 15 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
F = source size, the maximum projected dimension of the radiating source (or effective focal
spot) in the place perpendicular to the distance D from the weld or object being
radiographed, in.
D = distance from source of radiation to weld or object being radiographed, in.
d = distance from source side of weld or object being radiographed to the film.
D and d shall be measured to the approximate center of the area of interest.
Note: Material thickness to be considered is the thickness on which the IQI is based.
9 DOCUMENTATION
9.2 RECORDS
It is recommended that an X-ray log (a log may consist of a card file, punched card system,
a book, or other record) constituting a record of each job performed, be maintained. This
record should comprise, initially, a job number (which should appear also on the films), the
identification of the parts, material or area radiographed, the date the films are exposed,
and a complete the record of the radiographic procedure, in sufficient detail so that any
Page 16 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
radiographic techniques may be duplicated readily. If calibration data, or other records such
as card files or procedures, are used to determine the procedure, the log need refer only to
the appropriate data or other record. Subsequently, the interpreter's findings and disposition
(acceptance or rejection), if any and his initials, should also be entered for each job.
9.3 REPORTS
Reports should include the following, plus such other items as may be agreed upon:
(EXHIBIT-III)
a) A listing of each radiograph location
b) Identification as required by para. 4.4.
c) The dimensional map of marker placement in accordance with 7.4
d) Number of radiographs (exposure)
e) X-ray voltage or isotope type used.
f) Source size
g) Base material type and thickness, weld thickness, weld reinforcement thickness, as
applicable
h) Source to object distance
i) Distance from source side of object to film
j) Film manufacturer and manufacturer’s type/designation
k) Number of films in each film holder/cassette
l) Single or double wall exposure
m) Single or double wall viewing
n) Achieved sensitivity and Density of each film.
o) Evaluation and disposition of the material(s) or weld(s) examined.
p) Identification (name) of the Manufacturer’s representative who performed the final
acceptance of the radiographs.
q) Date of Manufacturer’s evaluation
r) Report number, date, BI or JO number, names, and badge numbers (if any) of the
radiographers, and the governing acceptance criteria.
s) The radiographic interpreter's full name and badge number, (if any) with signature.
t) IQI, Designated Wire
These information can be obtained directly from the report.
Prior to being presented to the inspector for acceptance the radiographs shall be examined
and interpreted by NDT CCS Level-II Film Interpreter as complying with the referencing code
section. The Level-II Film Interpreter shall record the interpretation of each radiograph and
disposition of the material examined on a radiographic examination report (EXHIBIT-IV) as per
Attachment-I and it should accompany the radiographs. All personnel performing
Radiographic Film Interpretation (RTFI) or having an influence of Radiographic Film
Interpretation shall be certified to level. Personnel shall have in their possession a NDT CCS’s
RTFI certification and in addition shall be qualified by SATORP prior to performing RTFI.
Page 17 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
EXHIBIT – I
Page 18 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
EXHIBIT – II
Page 19 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
SENSITIVITY : 2%
REFERENCE MARKER : LEAD MARKER AT EVERY 10 CM AND ID
IQI : AS PER 7.5
PROCESSING : MANUAL PROCESSING DEVELOPMENT
ACCEPTANCE STANDARD : AS APPLICABLE;
SKETCH : EXPOSURE ARRANGEMENT – F
EXHIBIT – III
RADIOGRAPHIC TECHNIQUE DETAILS:-MONORAIL /STRUCTURAL WELD (AWS D14.1)
METHOD : INSPECTION BY GAMMA RAYS
LOCATION : AS APPLICABLE
CLINET : AS APPLICABLE
MATERIAL : STEEL
DIA : AS APPLICABLE
JOB NO./COMP. NO. : AS APPLICABLE
WALL THICKNESS : STD
RADIATION SOURCE : IR-192
TYPE OF EQUIPMENT : EXTERNAL
MANUALLY OPERATED/CABLE : MANUALLY OPERATED
MODEL AND MAKE : 880-DELTA /SIGMA
RADIOGRAPHIC TECHNIQUE : SWE / SWV
NO. OF EXPOSURE : MIN. 1
INTENSIFYING SCREENS : LEAD FOIL SCREENS F&B
(Type & Thickness) 0.0125 mm
FILTER TYPE & PLACEMENT : NONE
GEOMETRIC UNSHARPNESS : MAX. 0.020 in. .up to 2 inches of t(OFD)
GEOMETRIC RELATIONSHIP : SOURCE SIZE - (refer source certificate)
STRENGTH - MAX 100 CI
O F D - IN DIRECT CONTACT
S F D - AS PER SIZE AND THIXK OF BEAM
RADIATION ANGLE -45, 90,120 DEGREE
NO OF FILM - ONE IN A CASSETTE
FIELD LIMITATION DEVICE : COLLIMATORS (TUNGSTEN)
FILM TYPE : MAKE - KODAK/DUPONT/AGFA/FUJI
TYPE – II
SIZE 10x24, 10X40 & 10X48 CM FILMS
Page 20 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
locatio
Exposure Radiograph n
OD technique viewing End Side selection placement marker
source
side
Either
Any Single wall Single wall Table 2
side
Film side
source
side
Either
Any Single wall Single wall Table 2
side
Film side
Page 21 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
source Either
Any Single wall Single wall Table 2
side side
FIGURE: 7.1.1
Double
wall: At source
least 3 side
exposures
at 120 Either
Any Single wall Table 2
deg to side
each
other for
complete Film side
coverage
Double source
wall: At side
least 3
exposures
at 120 Either
Any Single wall Table 2
deg to side
each
other for
complete Film side
coverage
Page 22 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Double
wall: At Double wall
3.5
least 2 (Ellipse):
inch
exposures Read Off-
(88m source Either
at 90 deg set source Table 2
m) side side
to each side and
and
other for film side
Less
complete images
coverage
FIGURE: 7.1.2
DOUBLE WALL RADIOGRAPHIC TECHNIQUES
locat
Exposure ion
techniqu Radiograp placemen mark
OD e h viewing End Side selection t er
Double
wall: At
Double
least 3
wall: Read
exposures
Super-
3.5 inch at 60 deg
imposed source Eithe
(88mm) or 120 Table 2
source side side r side
and Less deg to
and film
each
side
other for
images
complete
coverage
Page 23 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Page 24 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Page 25 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Figure 7.6.1 View of placement of Wire type IQI (Image quality indicator)
11 ACCEPTANCE CRITERIA
The standard of acceptance used by the film interpreter shall be as specified in the
applicablereference codes listed in Para 3. of this document. As a guide to technician
standard of acceptability shall be submitted for approval along with technique sheet.
11.1 ASME SEC VIII D1,
Page 26 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
1) Terminology
Thickness t · the thickness of the weld excluding any allowable reinforcement For a butt weld
joining two members having different thicknesses at the weld, t is the thinner of these two
thicknesses. If a full penetration weld includes a fillet weld, the thickness of the fillet throat shall
be included in the calculation oft.
Acceptance/Rejection Criteria
(-a) Any crack or zone of incomplete fusion or lack of penetration
{-b) Any other linear indication that has a length greater than:
(-1) 6 mm(% in.) for t less than or equal to 19 mm(% in.),
(-2) t / 3 fort greater than 19 mm(% in.) and less than or equal to 57 mm (2-% in.),
(-3) 19 mm(% in.) fort greater than 57 mm (2-1/4 in.).
(-c) Any group of indications in line that has an aggregate length greater than tin a length of
12t except when the distance between the successive imperfections exceeds 6L, where L is
the length of the longest imperfection in the group;
(-d) Internal root weld conditions are acceptable when the density or image brightness
change as indicated in the radiograph is not abrupt. Linear indications on the radiograph at
either edge of such conditions shall be evaluated in accordance with the other sections of
this paragraph.
b) Rounded Indications
2) Terminology
(-a) Rounded Indications - indications with a maximum length of three times the width or less
on the radiograph are defined as rounded indications. These indications may be circular,
elliptical, conical, or irregular in shape and may have tails. When evaluating the size of an
indication, the tail shall be included.
(-b) Aligned Indications - a sequence of four or more rounded indications shall be considered
to be aligned when they touch a line parallel to the length of the weld drawn through the
center of the two outer rounded ind icat ions.
(-c) Thickness t - the thickness of the weld, excluding any allowable reinforcement. For a butt
weld joining two members having different thicknesses at the weld, t is the thinner of these
two thicknesses . If a full penetration weld includes a fillet weld, the thickness of the fillet throat
shall be included in the calculation of t .
Acceptance Criteria
(-a) Rounded Indication Charts relevant rounded indications characterized as
imperfections shall not exceed those shown in Figures 7.5 through 7.10 (ASME SEC VIII -DIV II),
which illustrate various types of assorted, randomly dispersed and clustered rounded
Page 27 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
indications for different weld thicknesses reater than 3 mm1/8in.). The charts for each
thickness range re-present full-scale 150 mm (6 in.) radiographs, and shall not be enlarged or
reduced. The distributions shown are not necessarily the patterns that may appear on the
radiograph, but are typical of the concentration and size of indications permitted.
(-b) Relevant Indications (see Table 7.7(ASME SEC VIII -DIV II). for examples)· only those
rounded indications that exceed the following dimensions shall be considered relevant and
compared to the acceptance charts for disposition.
(-1) t/10 fort less than 3mm (1/8 in)
(-2) 0.4 mm ( 1 / 6 4 in.) for t greater than or equal to 3 mm(1/8 In) and less than or equal to 6
mm (1/4 inch)
(-3) 0.8 mm ( 1/32in.) for t greater than 6 mm (% in.) and less than or equal to 50 mm (2 in.)
(-4) 1.5 mm ( 1 / 1 6 in.) for t greater than 50 mm (2 in.)
(-5) Maximum Size of Rounded Indication · the maximum permissible size of any
indication shall be t/4 or 4 mm (5/32 in.), whichever is smaller; except that an isolated
indication separated from an adjacent indication by 25 mm (1 in.) or more may be t/3, or
6 mm(% in.), whichever is less. Fort greater than 50 mm (2 in.) the maximum permissible size of
an isolated indication shall be increased to 10 mm (3/8 in.).
(-6) Aligned Rounded Indications· aligned rounded indications are acceptable when the
summation of the dia- meters of the indications is less than t in a length of 12t (see Figure 7.3
(ASME SEC VIII -DIV II)). The length of groups of aligned rounded in- dications and the spacing
between the groups shall meet the requirements of Figure 7.4 (ASME SEC VIII -DIV II).
(-7) Clustered Indications - the illustrations for clustered indications show up to four times as
many indica- tions in a local area, as that shown in the illustrations for random indications. The
length of an acceptable cluster shall not exceed the lesser of 25 mm (1 in.) or 2t . Where more
than one cluster is present, the sum of the lengths of the clus- ters shall not exceed 25 mm (1
in.) in a 150 mm (6 in.) length weld.
(-8) Weld Thickness t less than 3 mm(1/8 in.) - fort less than 3 mm (1/8 in.) the maximum
number of rounded indications shall not exceed 12 in a 150 mm (6 in.) length of weld. A
proportionally fewer number of indications shall be permitted in welds less than 150 mm (6
in.) in len gth.
(-c) Image Density - density or image brightness within the image of the indication may vary
and is not a criter- ion for acceptance or rejection.
(·d) Spacing - the distance between adjacent rounded indications is not a factor in
determining acceptance or rejection, except as required for isolated indications or groups of
aligned indications.
Page 28 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Page 29 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
K Depth of root surface concavity Total joint thickness, incl. weld reinf., ≤ Tw
Height of reinforcement or internal For Tw mm (in.) Height, mm (in.)
L
protrusion [Note (8)] in any plane ≤ 6 (¼) ≤ 1.5 (1/16)
through the weld shall be within limits > 6 (¼), ≤ 13 (½) 3 (1/8)
of the applicable height value in the > 13 (½), ≤ 25.4 (1) 4.0 (5/32)
tabulation at right. Weld metal shall > 25 (1) ≤ 5 (3/16)
merge smoothly into the component
surfaces.
Height of reinforcement or internal
M Limit is twice the value applicable for L above
protrusion [Note (8)] as describe in L
Tw = Nominal wall thickness of the thinner of two components joined by a butt weld.
Notes:
(1) Criteria given are for required examination. More stringent criteria may be specified in the
engineering design. See also paragraphs. 341.5 and 341.5.3 of ASME/ANSI B31.3
(2) Branch connection weld includes pressure containing welds in branches and fabricated
laps
(3) Longitudinal groove weld includes straight and spiral seam. Criteria are not intended to
apply to welds made in accordance with a standard listed in Table A-I or Table 326.1 of
ASME B31.1.
Page 30 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
(4) Fillet weld includes socket and seal welds, and attachment for slip-on flanges and branch
reinforcement.
(5) These imperfections are evaluated only for welds 5 mm (3/16 in.) in nominal thickness.
(6) Where two limiting values are separated by "and", the lesser of the values determines
acceptance. Where two sets of values are separated by "or", the larger value is
acceptable.
(7) Tightly butted unfused root faces are unacceptable.
(8) For groove welds, height is the lesser of the measurements made from the surfaces of the
adjacent components. For fillet welds, height is measured from the theoretical throat, Fig.
328.5.2A, of ASME/ANSI B31.3 internal protrusion does not apply.
(9) For welds in aluminum alloy only, internal protrusion shall not exceed the following values
(a) 1.5mm ((1/16in.) for thickness 2 mm 5/64 in)
(b) 2.5mm (3/32in.) for thickness > 2 mm and 6 mm (¼ in.)
For external reinforcement and for greater thicknesses , refer the tabulation for L symbol
Page 31 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Burn-Through (BT) Pipe OD ≥ 2.375 in.(60.3 mm) Pipe OD < 2.375 in.(60.3 mm)
1. Maximum dimension 1. Maximum dimension
exceeds exceeds
6 mm (¼") and the density of 6 mm (¼") and the density of
the the
BT's image exceeds that of BT's image exceeds that of
the the
thinnest adjacent base metal thinnest adjacent base metal
2. Maximum dimension 2. Maximum dimension
exceeds exceeds
the thinner of nominal wall the thinner of nominal wall
thicknesses joined, and the thicknesses joined, and the
density of the BT's image density of the BT's image
exceeds that of the thinnest exceeds that of the thinnest
adjacent base metal adjacent base metal
3. Sum of maximum 3. More than one BT of any
dimensions of size is
separate BTs whose image present and the density of
density exceeds that of the more
thinnest adjacent base metal than one of the images
exceeds 13 mm (½") in 300 exceeds
mm (12") of weld or the total that of the thinnest adjacent
weld length, whichever is less. base
metal.
Slag Inclusions
Pipe OD ≥2.375 in.(60.3 mm) Pipe OD < 2.375 in.(60.3 mm)
Elongated (ESI)
Isolated (ISI) 1. ESI length > 2" (50 mm) 1. ESI > 3 X nominal WT of the
Note: ESI indications 2. ESI width > 1/16" (1.6 mm) thinner thickness joined.
separated by approx. 3. Sum of the lengths of ISI > 2. ESI width > 1/16"
width of root bead ½" 3. Sum of ISI lengths > 2 X
(wagon tracks) to be (13 mm) in 12" (300 mm) of nominal WT of thinner
considered as a single weld. thickness
indication unless the 4. Width of ISI > 1/8" (3 mm) joined and ISI width > ½
width of either > 1/32". In 5. more than four ISI with nominal WT of thinner
that event, they shall be maximum width of 1/8" (3 thickness
considered as separate mm) joined.
in any 12" (300mm) of weld. 4. Aggregate length of ESI &
6. Sum of the lengths of ESI & ISI >
ISI 8% of weld length.
> 8% of weld length.
Porosity - individual / 1. Size of individual pore exceeds 1/8" (3 mm)
Scattered (P) 2. Size of individual pore exceeds 25% of thinner WT joined
Note: Size based on 3. Distribution of Porosity exceeds API STD 1104 Porosity Charts.
maximum dimensions
1. Diameter of the cluster (CP) exceeds ½" (13 mm)
Porosity - Cluster (CP)
2. Aggregate length of CP > ½" (13 mm) in any continuous 12"
(300 mm) length of weld
1. Length of individual indication of HB exceeds ½" (13 mm)
Porosity - Hollow-Bead (HB)
2. Sum of HB lengths > 2" ( 50 mm) in any continuous 12" (300
mm) of weld
3. Individual HB each > ¼"( 6 mm) separated by less than
2"(50 mm)
4. Sum of HB lengths > 8% weld length.
Any size or location of cracks are unacceptable except for
Cracks (C)
shallow crater or star cracks. Shallow crater or star crack with
Page 32 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Table 11. 5 – Rejection Criteria for Statically Loaded Structures, AWS D1.1 Para 8.15.3.2
Page 33 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Figure 11.5.2 Weld Quality Requirements for Discontinuities Occurring in Welds (Limitation of
Porosity & Fusion-Type Discontinuities)
Page 34 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Note: Adjacent discontinuities, spaced less than the minimum required clearance shall be
measured as one length equal tothe sum of the total length of the discontinuities plus the
length of the space between them and evaluated as a single discontinuity.
1) The greatest dimension of any porosity or fusion type discontinuity indications that are
1/16inch (2mm) or larger shall not exceed the size B, indicated in the above figure 11.5.2
for the effective throat of a groove weld or weld size of a fillet weld. The distance from
any indication of porosity or fusion type discontinuity to another such indication, to an
edge, or any intersecting weld shall not be less than the minimum clearance allowed, C,
indicated in the above figure 11.5.2 for the size of discontinuity under examination.
2) Discontinuities meeting the requirements of visual weld examination and having a
greatest dimension of less than 1/16 inch (2mm) are nevertheless not acceptable if the
sum of their greatest dimensions exceeds 3/18 inch (10 mm) in any linear inch (25 mm) of
weld.
3) The limitations for 1-½ (40 mm) groove weld effective throat in the above figure 11.5 shall
apply to all welds with larger effective throats.
12 RADIOGRAPHY EXAMINATION REPORT
Page 35 of 36
NDT Corrosion Control Services Co. DOC NO: NDT/SA/SARORP/RT/60, Rev01
Dammam – Saudi Arabia Date: 15th AUG 2023
Page 36 of 36