You are on page 1of 1
COLD-INSULATION GM 5.9.01 MECHANICAL ENGINEERING DETAIL 99-09-09, LUGS/SUPPORT STRIP ON COLUMNS/SKIRTS REF. NOTE 2 | 4 T 80 +t mm RE. NOTE 6 —H r T = INSULATION [7 THICKNESS: LUG WIDTH 40mm REF. NOTE 3 REF. NOTE 6 mi 3. x INSULATION THICKNESS REF. NOTE 6 im tr | REF. NOTE 2 | REF, NOTE 2 | REF, NOTE 4 | 4oxé0mm LUGS, WITH HOLE #10mm __| FOR INSULATION SUPPORT REF, NOTE 5 aa LJ FLOATING RING NOTE 1 MATERIALS AND FINISHING IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS AND SPECIFICATION 2 AT A SINGLE LAYER SYSTEM % x INSULATION THICKNESS, AT A DOUBLE LAYER SYSTEM 31 x INSULATION THICKNESS AND AT A TRIPLE LAYER SYSTEM 5% X INSULATION THICKNESS. 3 NUMBER OF LUGS MIN, & PCS, MAXIMUM SPACING 500 mm 4 AT CRYOGENE OPERATION TEMPERATURES, INSTEAD OF LUGS, A CONTINUOUS STRIP To BE INSTALLED, SEAL WELDED. 5 LUGS AT THE INSIDE OF THE SKIRT FOR FLOATING RING. (SEE 5.2.05), 6 SUPPORT RINGS AT EQUIPMENT WALL, MAX. SPACING 4500mm.