ELSEWEDY CABLES Technical Offer

Power Cables Division Rev. no. 0


Technical Department

Multi Core Cable with Copper Conductors , XLPE Insulated , Galvanized Steel Wire Armored and PVC Sheathed 0.6/1 kV

3 X 70 mm²

General Data:

- Cable Designation standards: BS EN 60228 , BS 5467 , BS EN 60332‐1


- No. of Cores: 3
- Cable Size: 70 mm²
- Cores Identification: Red , Yellow , Blue
- Outer Sheath Color: Black
- Approx. Cable Weight: 2950 kg/km
- Approx. Cable Outer diameter: 31.5 mm
- Min. Bending Radius 255 mm
- Cable Marking :
EL SEWEDY CABLES ELECTRIC CABLE 3 X 70 MM2 600/1000 V Cu/XLPE/SWA/PVC BS 5467
Manufacturing Year

Electrical Data:

- Rating Voltage: 0.6/1 (1.2) kV

- Max. Conductor DC Resistance at 20 °C: 0.268 ohm/km


- Max. Conductor AC resistance at maximum
0.3425 ohm/km
Operating Temperature and 50 HZ: Cable Construction

- Maximum conductor operating Temp.: 90 °C 1. Copper Conductor


- Maximum Conductor Temperature During S.C: 250 °C 2. XLPE Insulation
3. Polypropylene Tape
- Conductor S.C.C for 1 sec.: 10 kA 4. PVC Bedding
5. Galvanized Steel Wire Armor
- Current Carrying Capacity: 6. Polypropylene Tape
* Laying Conditions: 7. PVC Sheath
- Soil Thermal Resistivity 1.2 C.m/W
- Burial Depth 0.5 m
- Ground Temperature 35 °C
- Air Temperature 40 °C
Cables are protected from direct solar radiation and no other thermal sources in the
neighborhood.

When laid in:


1. Ground 235 A
2. Ducts 180 A
3. Free Air 235 A

Packing:

- Cutting Length (Standard): 1000 [± 3 %] m


- Drum Size (Diameter / Width): 1850 / 1100 mm
- Drum Type: Wooden Drum - Fully Lagged

- Cable shall be supplied in lengths as indicated in technical schedule on wooden or steel reels up to the manufacturer.
- Both ends of the Cable shall be sealed to prevent the ingress of moisture during transportation and storage.
- Each reel shall be marked with type, size and length of Cable, net weight and gross weight.
- This information shall be written on metallic tag nailed properly to the flange.

Testing:

- All routine tests required by BS 5467 are performed on the cable & a test certificate will be supplied on request.

Prepared By

Ahmed Farag
Senior Design Engineer

C.R 1656/09 TC-FR-16 Rev.(0) Issue Date: 1/1/2010 CX1-T103-W15-TO.xls