You are on page 1of 19

AHU-1, R1-R5,R7

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : THIRD Area : AHU-1, R1-R5,R7 System No. : 1
Floor Area 1251 Sq Ft Ceiling Ht 10 Ft Volume = 12510 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 128 23 0.81 2385 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 24 People X 0 CFM/Person 5.00
S - Glass 58 12 0.81 564 1251 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 195
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.93
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 4742
No. of Rows = 0
N - Wall 469 19 0.36 3208 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 417
SE - Wall 33 0.36 0
S - Wall 215 31 0.36 2399
SW - Wall 29 0.36 0
W - Wall 376 27 0.36 3655
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 24 persons
ITEM Area Temp. diff. U FRESH AIR 417
(Sq ft) (°F) (Btu/h.sq ft) Light 1877 watt
All Glass 186 28 0.55 2864 Equipment 1877 watt
Glass Partition 88 23 0.55 1113
Partition 303 23 0.3 2091
Partition 23 0.35 0
Ceiling 116 23 0.45 1201
Floor 233 23 0.45 2412
INTERNAL HEAT GAIN
People 24 Nos X 230 5520
Light 1877 W X 1.25 3.412 8003
Eq. Load 1877 W 3.412 38982
ROOM SENSIBLE HEAT (RSH) 74396
Supply duct heat Supply duct Heat gain from 2 1488
gain + leak. loss + fan HP(%) HOLD

Safety factor (%) 5.0 3720


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
417 28 0.12 1.08 1513
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 81117
LATENT HEAT
People 24 Nos X 120 2880
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
417 81.7 0.12 0.68 2780
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 5660
Supply duct leakage loss + Safety factor % 5.0 283
EFFECTIVE ROOM LATENT HEAT (ERLH) 5943
EFFECTIVE ROOM TOTAL HEAT (ERTH) 87060
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 417
417 28 0.88 1.08 11097 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 10.08
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 96.7 Monsoon TR= 10.01
417 81.7 0.88 0.68 20387 CFM / Sq ft = 3.79 Deh. CFM= 4742
HEAT SUB TOTAL 118544 Sq ft / TR = 124 CFM(ACPH)= 23
Return duct heat HP Pump + Dehum. & Pipe 2.0 2371
gain & leak. loss + loss (%) CFM/ TR = 471
Selected TR = 10.1
TONS 10.08 GRAND TOTAL HEAT 120915 Selected CFM= 4750
AHU-1, R1-R5,R7
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 128 11 0.81 1140 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 24 People X 0 CFM/Person 5
S - Glass 58 11 0.81 517 1251 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 195
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.92
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 4471
No. of Rows = 0
N - Wall 469 9 0.36 1520 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 417
SE - Wall 0 23 0.36 0
S - Wall 215 21 0.36 1625
SW - Wall 0 19 0.36 0
W - Wall 376 17 0.36 2301
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 186 26 0.5500 2660
Glass Partition 88 21 0.55 1016
Partition glass-NAC 303 21 0.30 1909
Partition wall-NAC 0 10 0.35 0
Ceiling 116 10 0.45 522
Floor 233 10 0.45 1049
INTERNAL HEAT GAIN
People 24.0 Nos X 230 5520
Light 1876.5 W X 1.25 3.412 7975
Eq. Load 1876.5 WX 3.412 38982
ROOM SENSIBLE HEAT (RSH) 66736
Supply duct heat Supply duct Heat gain from 2 5005
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 3337
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
417 26 0.12 1.08 1405
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 76483
LATENT HEAT
People 24 Nos X 120 2880
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
417 99 0.12 0.68 3369
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 6249
EFFECTIVE ROOM TOTAL HEAT (ERTH) 82732
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
417 26 0.88 1.08 10304
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
417 99 0.88 0.68 24704
HEAT SUB TOTAL 117740
Return duct heat HP Pump + Dehum. & Pipe 2.0 2355
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 10.01 TR
TONS 10.01 TOTAL HEAT 120095
AHU-1,R6,R8,R9

GREEN AIR ROOM TYPE 3 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : THIRD Area : AHU-1,R6,R8,R9 System No. : 1
Floor Area 161 Sq Ft Ceiling Ht 10 Ft Volume = 1610 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 76 65 55 74
N - Glass 23 0.81 0 DIFFERENCE 24 XXXX XXXX XXXX 72.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 3 People X 0 CFM/Person 7.00
S - Glass 2 12 0.81 19 161 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 31
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.83
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 19.36 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 170
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 54
SE - Wall 33 0.36 0
S - Wall 51 31 0.36 569
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 3 persons
ITEM Area Temp. diff. U FRESH AIR 54
(Sq ft) (°F) (Btu/h.sq ft) Light 242 watt
All Glass 2 24 0.55 26 Equipment 242 watt
Glass Partition 19 0.55 0
Partition 19 0.3 0
Partition 19 0.35 0
Ceiling 19 0.45 0
Floor 19 0.45 0
INTERNAL HEAT GAIN
People 3 Nos X 230 690
Light 242 W X 1.25 3.412 1030
Eq. Load 242 W 3.412 824
ROOM SENSIBLE HEAT (RSH) 3159
Supply duct heat Supply duct Heat gain from 2 63
gain + leak. loss + fan HP(%) HOLD

Safety factor (%) 5.0 158


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
54 24 0.12 1.08 167
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 3547
LATENT HEAT
People 3 Nos X 120 360
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
54 72.7 0.12 0.68 318
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 678
Supply duct leakage loss + Safety factor % 5.0 34
EFFECTIVE ROOM LATENT HEAT (ERLH) 712
EFFECTIVE ROOM TOTAL HEAT (ERTH) 4259
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 54
54 24 0.88 1.08 1224 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 0.66
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 49.5 Monsoon TR= 0.72
54 72.7 0.88 0.68 2335 CFM / Sq ft = 1.05 Deh. CFM= 170
HEAT SUB TOTAL 7818 Sq ft / TR = 242 CFM(ACPH)= 6
Return duct heat HP Pump + Dehum. & Pipe 2.0 156
gain & leak. loss + loss (%) CFM/ TR = 255
Selected TR = 0.7
TONS 0.66 GRAND TOTAL HEAT 7975 Selected CFM= 200
AHU-1,R6,R8,R9
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 76 65 55 74
N - Glass 0 11 0.81 0 DIFFERENCE 22 XXXX XXXX XXXX 90
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 3 People X 0 CFM/Person 7
S - Glass 2 11 0.81 18 161 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 31
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.82
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.36 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 167
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 54
SE - Wall 0 23 0.36 0
S - Wall 51 21 0.36 386
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 2 22 0.5500 24
Glass Partition 0 17 0.55 0
Partition glass-NAC 0 17 0.30 0
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 0 10 0.45 0
INTERNAL HEAT GAIN
People 3.0 Nos X 230 690
Light 241.5 W X 1.25 3.412 1026
Eq. Load 241.5 WX 3.412 824
ROOM SENSIBLE HEAT (RSH) 2968
Supply duct heat Supply duct Heat gain from 5 223
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 148
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
54 22 0.12 1.08 153
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 3492
LATENT HEAT
People 3 Nos X 120 360
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
54 90 0.12 0.68 394
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 754
EFFECTIVE ROOM TOTAL HEAT (ERTH) 4246
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
54 22 0.88 1.08 1122
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
54 90 0.88 0.68 2890
HEAT SUB TOTAL 8258
Return duct heat HP Pump + Dehum. & Pipe 5.0 413
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 0.72 TR
TONS 0.72 TOTAL HEAT 8671
AHU-2

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : THIRD Area : AHU-1, R1-R5,R7 System No. : 1
Floor Area 384 Sq Ft Ceiling Ht 10 Ft Volume = 3840 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 9 People X 0 CFM/Person 5.00
S - Glass 58 12 0.81 564 384 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 68
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.92
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 1280
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 128
SE - Wall 33 0.36 0
S - Wall 332 31 0.36 3705
SW - Wall 29 0.36 0
W - Wall 376 27 0.36 3655
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 9 persons
ITEM Area Temp. diff. U FRESH AIR 128
(Sq ft) (°F) (Btu/h.sq ft) Light 576 watt
All Glass 58 28 0.55 893 Equipment 576 watt
Glass Partition 23 0.55 0
Partition 124 23 0.3 856
Partition 23 0.35 0
Ceiling 23 0.45 0
Floor 25 23 0.45 259
INTERNAL HEAT GAIN
People 9 Nos X 230 2070
Light 576 W X 1.25 3.412 2457
Eq. Load 576 W 3.412 5565
ROOM SENSIBLE HEAT (RSH) 20023
Supply duct heat Supply duct Heat gain from 2 400
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 1001


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
128 28 0.12 1.08 464
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 21889
LATENT HEAT
People 9 Nos X 120 1080
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
128 81.7 0.12 0.68 853
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 1933
Supply duct leakage loss + Safety factor % 5.0 97
EFFECTIVE ROOM LATENT HEAT (ERLH) 2030
EFFECTIVE ROOM TOTAL HEAT (ERTH) 23919
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 128
128 28 0.88 1.08 3406 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 2.85
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 89.2 Monsoon TR= 2.77
128 81.7 0.88 0.68 6258 CFM / Sq ft = 3.33 Deh. CFM= 1280
HEAT SUB TOTAL 33583 Sq ft / TR = 135 CFM(ACPH)= 20
Return duct heat HP Pump + Dehum. & Pipe 2.0 672
gain & leak. loss + loss (%) CFM/ TR = 448
Selected TR = 2.9
TONS 2.85 GRAND TOTAL HEAT 34255 Selected CFM= 1300
AHU-2
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 9 People X 0 CFM/Person 5
S - Glass 58 11 0.81 517 384 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 68
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.90
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 1152
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 128
SE - Wall 0 23 0.36 0
S - Wall 332 21 0.36 2510
SW - Wall 0 19 0.36 0
W - Wall 376 17 0.36 2301
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 58 26 0.5500 829
Glass Partition 0 21 0.55 0
Partition glass-NAC 124 21 0.30 781
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 25 10 0.45 113
INTERNAL HEAT GAIN
People 9.0 Nos X 230 2070
Light 576.0 W X 1.25 3.412 2448
Eq. Load 576.0 WX 3.412 5565
ROOM SENSIBLE HEAT (RSH) 17134
Supply duct heat Supply duct Heat gain from 2 1285
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 857
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
128 26 0.12 1.08 431
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 19707
LATENT HEAT
People 9 Nos X 120 1080
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
128 99 0.12 0.68 1034
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 2114
EFFECTIVE ROOM TOTAL HEAT (ERTH) 21821
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
128 26 0.88 1.08 3163
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
128 99 0.88 0.68 7583
HEAT SUB TOTAL 32567
Return duct heat HP Pump + Dehum. & Pipe 2.0 651
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 2.77 TR
TONS 2.77 TOTAL HEAT 33218
AHU-3-TAG R1

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
AHU-3,
Floor : THIRD Area : R13,R14,R17- System No. : 1
R9,R21,R27
Floor Area 850 Sq Ft Ceiling Ht 10 Ft Volume = 8500 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 145 23 0.81 2701 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 29 12 0.81 282 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 16 People X 0 CFM/Person 5.00
S - Glass 12 0.81 0 850 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 131
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 4682
No. of Rows = 0
N - Wall 403 19 0.36 2757 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 81 33 0.36 962 'Min. cfm reqd. = 283
SE - Wall 33 0.36 0
S - Wall 31 0.36 0
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 16 persons
ITEM Area Temp. diff. U FRESH AIR 283
(Sq ft) (°F) (Btu/h.sq ft) Light 1275 watt
All Glass 174 28 0.55 2680 Equipment 1275 watt
Glass Partition 24 23 0.55 304
Partition 110 23 0.3 759
Partition 23 0.35 0
Ceiling 194 23 0.45 2008
Floor 110 23 0.45 1139
INTERNAL HEAT GAIN
People 16 Nos X 230 3680
Light 1275 W X 1.25 3.412 5438
Eq. Load 1275 W 3.412 51190
ROOM SENSIBLE HEAT (RSH) 73899
Supply duct heat Supply duct Heat gain from 2 1478
gain + leak. loss + fan HP(%) HOLD

Safety factor (%) 5.0 3695


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
283 28 0.12 1.08 1028
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 80100
LATENT HEAT
People 16 Nos X 120 1920
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
283 81.7 0.12 0.68 1889
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 3809
Supply duct leakage loss + Safety factor % 5.0 190
EFFECTIVE ROOM LATENT HEAT (ERLH) 3999
EFFECTIVE ROOM TOTAL HEAT (ERTH) 84099
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 283
283 28 0.88 1.08 7540 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 8.97
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 126.6 Monsoon TR= 9.02
283 81.7 0.88 0.68 13852 CFM / Sq ft = 5.51 Deh. CFM= 4682
HEAT SUB TOTAL 105491 Sq ft / TR = 95 CFM(ACPH)= 33
Return duct heat HP Pump + Dehum. & Pipe 2.0 2110
gain & leak. loss + loss (%) CFM/ TR = 522
Selected TR = 9.0
TONS 8.97 GRAND TOTAL HEAT 107601 Selected CFM= 4700
AHU-3-TAG R1
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 145 11 0.81 1292 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 29 11 0.81 258 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 16 People X 0 CFM/Person 5
S - Glass 0 11 0.81 0 850 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 131
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 4570
No. of Rows = 0
N - Wall 403 9 0.36 1306 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 81 23 0.36 671 'Min. cfm reqd. = 283
SE - Wall 0 23 0.36 0
S - Wall 0 21 0.36 0
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 174 26 0.5500 2488
Glass Partition 24 21 0.55 277
Partition glass-NAC 110 21 0.30 693
Partition wall-NAC 0 10 0.35 0
Ceiling 194 10 0.45 873
Floor 110 10 0.45 495
INTERNAL HEAT GAIN
People 16.0 Nos X 230 3680
Light 1275.0 W X 1.25 3.412 5419
Eq. Load 1275.0 WX 3.412 51190
ROOM SENSIBLE HEAT (RSH) 68642
Supply duct heat Supply duct Heat gain from 2 5148
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 3432
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
283 26 0.12 1.08 955
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 78177
LATENT HEAT
People 16 Nos X 120 1920
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
283 99 0.12 0.68 2289
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 4209
EFFECTIVE ROOM TOTAL HEAT (ERTH) 82386
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
283 26 0.88 1.08 7001
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
283 99 0.88 0.68 16785
HEAT SUB TOTAL 106172
Return duct heat HP Pump + Dehum. & Pipe 2.0 2123
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 9.02 TR
TONS 9.02 TOTAL HEAT 108296
AHU-3-TAG R3

GREEN AIR ROOM TYPE 3 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
AHU-3,R16,R22-
Floor : THIRD Area : System No. : 1
26
Floor Area 766 Sq Ft Ceiling Ht 10 Ft Volume = 7660 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 76 65 55 74
N - Glass 29 23 0.81 540 DIFFERENCE 24 XXXX XXXX XXXX 72.7
NE - Glass 12 0.81 0
E -GLASS 23 12 0.81 224 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 10 People X 0 CFM/Person 7.00
S - Glass 12 0.81 0 766 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 116
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.96
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 19.36 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3210
No. of Rows = 0
N - Wall 89 19 0.36 609 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 151 33 0.36 1794 'Min. cfm reqd. = 255
SE - Wall 33 0.36 0
S - Wall 31 0.36 0
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 10 persons
ITEM Area Temp. diff. U FRESH AIR 255
(Sq ft) (°F) (Btu/h.sq ft) Light 1149 watt
All Glass 52 24 0.55 686 Equipment 1149 watt
Glass Partition 19 0.55 0
Partition 227 19 0.3 1294
Partition 19 0.35 0
Ceiling 111 19 0.45 949
Floor 22 19 0.45 188
INTERNAL HEAT GAIN
People 10 Nos X 230 2300
Light 1149 W X 1.25 3.412 4900
Eq. Load 1149 W 3.412 48500
ROOM SENSIBLE HEAT (RSH) 61984
Supply duct heat Supply duct Heat gain from 2 1240
gain + leak. loss + fan HP(%) HOLD

Safety factor (%) 5.0 3099


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
255 24 0.12 1.08 794
0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 67118
LATENT HEAT
People 10 Nos X 120 1200
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
255 72.7 0.12 0.68 1515
0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 2715
Supply duct leakage loss + Safety factor % 5.0 136
EFFECTIVE ROOM LATENT HEAT (ERLH) 2850
EFFECTIVE ROOM TOTAL HEAT (ERTH) 69968
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 255
255 24 0.88 1.08 5824 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 7.39
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 115.7 Monsoon TR= 7.92
255 72.7 0.88 0.68 11108 CFM / Sq ft = 4.19 Deh. CFM= 3267
HEAT SUB TOTAL 86900 Sq ft / TR = 104 CFM(ACPH)= 26
Return duct heat HP Pump + Dehum. & Pipe 2.0 1738
gain & leak. loss + loss (%) CFM/ TR = 435
Selected TR = 7.9
TONS 7.39 GRAND TOTAL HEAT 88638 Selected CFM= 3300
AHU-3-TAG R3
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 76 65 55 74
N - Glass 29 11 0.81 258 DIFFERENCE 22 XXXX XXXX XXXX 90
NE - Glass 0 11 0.81 0
E - Glass 23 11 0.81 205 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 10 People X 0 CFM/Person 7
S - Glass 0 11 0.81 0 766 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 116
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.96
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.36 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3267
No. of Rows = 0
N - Wall 89 9 0.36 288 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 151 23 0.36 1250 'Min. cfm reqd. = 255
SE - Wall 0 23 0.36 0
S - Wall 0 21 0.36 0
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 52 22 0.5500 629
Glass Partition 0 17 0.55 0
Partition glass-NAC 227 17 0.30 1158
Partition wall-NAC 0 10 0.35 0
Ceiling 111 10 0.45 500
Floor 22 10 0.45 99
INTERNAL HEAT GAIN
People 10.0 Nos X 230 2300
Light 1149.0 W X 1.25 3.412 4883
Eq. Load 1149.0 WX 3.412 48500
ROOM SENSIBLE HEAT (RSH) 60071
Supply duct heat Supply duct Heat gain from 5 4505
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 3004
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
255 22 0.12 1.08 728
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 68307
LATENT HEAT
People 10 Nos X 120 1200
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
255 90 0.12 0.68 1875
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 3075
EFFECTIVE ROOM TOTAL HEAT (ERTH) 71383
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
255 22 0.88 1.08 5339
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
255 90 0.88 0.68 13751
HEAT SUB TOTAL 90473
Return duct heat HP Pump + Dehum. & Pipe 5.0 4524
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 7.92 TR
TONS 7.92 TOTAL HEAT 94996
AHU-4,R28,R29

GREEN AIR ROOM TYPE 3 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : THIRD Area : AHU-4,R28,R29 System No. : 1
Floor Area 1281 Sq Ft Ceiling Ht 10 Ft Volume = 12810 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 76 65 55 74
N - Glass 23 0.81 0 DIFFERENCE 24 XXXX XXXX XXXX 72.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 9 People X 0 CFM/Person 7.00
S - Glass 87 12 0.81 846 1281 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 140
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 19.36 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 1801
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 0
E - Wall 33 0.36 0 'Min. cfm reqd. = 0
SE - Wall 33 0.36 0
S - Wall 366 31 0.36 4085
SW - Wall 29 0.36 0
W - Wall 19 27 0.36 185
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 9 persons
ITEM Area Temp. diff. U FRESH AIR 140
(Sq ft) (°F) (Btu/h.sq ft) Light 1922 watt
All Glass 87 24 0.55 1148 Equipment 1922 watt
Glass Partition 309 19 0.55 3229
Partition 1461 19 0.3 8328
Partition 19 0.35 0
Ceiling 16 19 0.45 137
Floor 19 0.45 0
INTERNAL HEAT GAIN
People 9 Nos X 230 2070
Light 1922 W X 1.25 3.412 8195
Eq. Load 1922 W 3.412 6556
ROOM SENSIBLE HEAT (RSH) 34778
Supply duct heat Supply duct Heat gain from 2 696
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 1739


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
140 24 0.12 1.08 435
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 37648
LATENT HEAT
People 9 Nos X 120 1080
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
140 72.7 0.12 0.68 830
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 1910
Supply duct leakage loss + Safety factor % 5.0 95
EFFECTIVE ROOM LATENT HEAT (ERLH) 2005
EFFECTIVE ROOM TOTAL HEAT (ERTH) 39653
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 140
140 24 0.88 1.08 3190 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 4.16
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 39.0 Monsoon TR= 4.28
140 72.7 0.88 0.68 6084 CFM / Sq ft = 1.41 Deh. CFM= 1801
HEAT SUB TOTAL 48927 Sq ft / TR = 308 CFM(ACPH)= 8
Return duct heat HP Pump + Dehum. & Pipe 2.0 979
gain & leak. loss + loss (%) CFM/ TR = 433
Selected TR = 4.3
TONS 4.16 GRAND TOTAL HEAT 49906 Selected CFM= 1850
AHU-4,R28,R29
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 76 65 55 74
N - Glass 0 11 0.81 0 DIFFERENCE 22 XXXX XXXX XXXX 90
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 9 People X 0 CFM/Person 7
S - Glass 87 11 0.81 775 1281 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 140
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.95
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 19.36 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 1736
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 0.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 0
SE - Wall 0 23 0.36 0
S - Wall 366 21 0.36 2767
SW - Wall 0 19 0.36 0
W - Wall 19 17 0.36 116
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 87 22 0.5500 1053
Glass Partition 309 17 0.55 2889
Partition glass-NAC 1461 17 0.30 7451
Partition wall-NAC 0 10 0.35 0
Ceiling 16 10 0.45 72
Floor 0 10 0.45 0
INTERNAL HEAT GAIN
People 9.0 Nos X 230 2070
Light 1921.5 W X 1.25 3.412 8166
Eq. Load 1921.5 WX 3.412 6556
ROOM SENSIBLE HEAT (RSH) 31916
Supply duct heat Supply duct Heat gain from 5 2394
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 1596
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
140 22 0.12 1.08 399
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 36304
LATENT HEAT
People 9 Nos X 120 1080
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
140 90 0.12 0.68 1027
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 2107
EFFECTIVE ROOM TOTAL HEAT (ERTH) 38411
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
140 22 0.88 1.08 2924
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
140 90 0.88 0.68 7532
HEAT SUB TOTAL 48868
Return duct heat HP Pump + Dehum. & Pipe 5.0 2443
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 4.28 TR
TONS 4.28 TOTAL HEAT 51311
AHU-4,R30

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : THIRD Area : AHU-4,R30 System No. : 1
Floor Area 474 Sq Ft Ceiling Ht 10 Ft Volume = 4740 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 4 People X 0 CFM/Person 7.00
S - Glass 58 12 0.81 564 474 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 56
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.96
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2263
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 158
SE - Wall 33 0.36 0
S - Wall 166 31 0.36 1853
SW - Wall 29 0.36 0
W - Wall 19 27 0.36 185
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 4 persons
ITEM Area Temp. diff. U FRESH AIR 158
(Sq ft) (°F) (Btu/h.sq ft) Light 711 watt
All Glass 58 28 0.55 893 Equipment 711 watt
Glass Partition 43 23 0.55 544
Partition 147 23 0.3 1014
Partition 19 0.35 0
Ceiling 19 0.45 0
Floor 19 0.45 0
INTERNAL HEAT GAIN
People 4 Nos X 230 920
Light 711 W X 1.25 3.412 3032
Eq. Load 711 W 3.412 26636
ROOM SENSIBLE HEAT (RSH) 35641
Supply duct heat Supply duct Heat gain from 2 713
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 1782


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
158 28 0.12 1.08 573
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 38709
LATENT HEAT
People 4 Nos X 120 480
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
158 81.7 0.12 0.68 1053
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 1533
Supply duct leakage loss + Safety factor % 5.0 77
EFFECTIVE ROOM LATENT HEAT (ERLH) 1610
EFFECTIVE ROOM TOTAL HEAT (ERTH) 40319
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 158
158 28 0.88 1.08 4205 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 4.44
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 112.4 Monsoon TR= 4.78
158 81.7 0.88 0.68 7725 CFM / Sq ft = 4.77 Deh. CFM= 2314
HEAT SUB TOTAL 52248 Sq ft / TR = 107 CFM(ACPH)= 29
Return duct heat HP Pump + Dehum. & Pipe 2.0 1045
gain & leak. loss + loss (%) CFM/ TR = 509
Selected TR = 4.8
TONS 4.44 GRAND TOTAL HEAT 53293 Selected CFM= 2350
AHU-4,R30
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 4 People X 0 CFM/Person 7
S - Glass 58 11 0.81 517 474 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 56
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.96
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 2314
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 158
SE - Wall 0 23 0.36 0
S - Wall 166 21 0.36 1255
SW - Wall 0 19 0.36 0
W - Wall 19 17 0.36 116
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 58 26 0.5500 829
Glass Partition 43 21 0.55 497
Partition glass-NAC 147 21 0.30 926
Partition wall-NAC 0 10 0.35 0
Ceiling 0 10 0.45 0
Floor 0 10 0.45 0
INTERNAL HEAT GAIN
People 4.0 Nos X 230 920
Light 711.0 W X 1.25 3.412 3022
Eq. Load 711.0 WX 3.412 26636
ROOM SENSIBLE HEAT (RSH) 34718
Supply duct heat Supply duct Heat gain from 5 2604
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 1736
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
158 26 0.12 1.08 532
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 39590
LATENT HEAT
People 4 Nos X 120 480
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
158 99 0.12 0.68 1276
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 1756
EFFECTIVE ROOM TOTAL HEAT (ERTH) 41346
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
158 26 0.88 1.08 3904
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
158 99 0.88 0.68 9360
HEAT SUB TOTAL 54611
Return duct heat HP Pump + Dehum. & Pipe 5.0 2731
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 4.78 TR
TONS 4.78 TOTAL HEAT 57341
AHU-4,R31

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : THIRD Area : AHU-4,R31 System No. : 1
Floor Area 108 Sq Ft Ceiling Ht 10 Ft Volume = 1080 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 4 People X 0 CFM/Person 7.00
S - Glass 35 12 0.81 340 108 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 34
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.90
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 407
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 36
SE - Wall 33 0.36 0
S - Wall 72 31 0.36 804
SW - Wall 29 0.36 0
W - Wall 27 0.36 0
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 4 persons
ITEM Area Temp. diff. U FRESH AIR 36
(Sq ft) (°F) (Btu/h.sq ft) Light 162 watt
All Glass 35 28 0.55 539 Equipment 162 watt
Glass Partition 43 23 0.55 544
Partition 107 23 0.3 738
Partition 19 0.35 0
Ceiling 108 19 0.45 923
Floor 39 19 0.45 333
INTERNAL HEAT GAIN
People 4 Nos X 230 920
Light 162 W X 1.25 3.412 691
Eq. Load 162 W 3.412 553
ROOM SENSIBLE HEAT (RSH) 6385
Supply duct heat Supply duct Heat gain from 2 128
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 319


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
36 28 0.12 1.08 131
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 6963
LATENT HEAT
People 4 Nos X 120 480
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
36 81.7 0.12 0.68 240
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 720
Supply duct leakage loss + Safety factor % 5.0 36
EFFECTIVE ROOM LATENT HEAT (ERLH) 756
EFFECTIVE ROOM TOTAL HEAT (ERTH) 7719
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 36
36 28 0.88 1.08 958 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 0.89
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 98.6 Monsoon TR= 0.87
36 81.7 0.88 0.68 1760 CFM / Sq ft = 3.77 Deh. CFM= 407
HEAT SUB TOTAL 10437 Sq ft / TR = 122 CFM(ACPH)= 23
Return duct heat HP Pump + Dehum. & Pipe 2.0 209
gain & leak. loss + loss (%) CFM/ TR = 459
Selected TR = 0.9
TONS 0.89 GRAND TOTAL HEAT 10646 Selected CFM= 450
AHU-4,R31
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 4 People X 0 CFM/Person 7
S - Glass 35 11 0.81 312 108 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 34
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.89
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 359
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 36
SE - Wall 0 23 0.36 0
S - Wall 72 21 0.36 544
SW - Wall 0 19 0.36 0
W - Wall 0 17 0.36 0
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 35 26 0.5500 501
Glass Partition 43 21 0.55 497
Partition glass-NAC 107 21 0.30 674
Partition wall-NAC 0 10 0.35 0
Ceiling 108 10 0.45 486
Floor 39 10 0.45 176
INTERNAL HEAT GAIN
People 4.0 Nos X 230 920
Light 162.0 W X 1.25 3.412 689
Eq. Load 162.0 WX 3.412 553
ROOM SENSIBLE HEAT (RSH) 5350
Supply duct heat Supply duct Heat gain from 5 401
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 268
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
36 26 0.12 1.08 121
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 6140
LATENT HEAT
People 4 Nos X 120 480
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
36 99 0.12 0.68 291
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 771
EFFECTIVE ROOM TOTAL HEAT (ERTH) 6911
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
36 26 0.88 1.08 890
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
36 99 0.88 0.68 2133
HEAT SUB TOTAL 9933
Return duct heat HP Pump + Dehum. & Pipe 5.0 497
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 0.87 TR
TONS 0.87 TOTAL HEAT 10430
AHU-5,R32,33

GREEN AIR ROOM TYPE 1 COOLING LOAD ESTIMATION


Project Name : SHANNAYA HOSPITAL Location KOLKATA
Floor : THIRD Area : AHU-4,R31 System No. : 1
Floor Area 428 Sq Ft Ceiling Ht 10 Ft Volume = 4280 CFT
SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 87 49 146.7
(Sq ft) (Btu/h.sq ft) ROOM 72 61 55 65
N - Glass 23 0.81 0 DIFFERENCE 28 XXXX XXXX XXXX 81.7
NE - Glass 12 0.81 0
E -GLASS 12 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 12 0.81 0 2 People X 0 CFM/Person 7.00
S - Glass 70 12 0.81 680 428 Area X 0 CFM/Sqft 0.06
SW - Glass 85 0.81 0 CFM VENTILATION 40
W - Glass 163 0.81 0
NW - Glass 138 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.98
Indicated ADP = 56 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54 °F
ITEM Area Eq. temp. diff. U 'Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3945
No. of Rows = 0
N - Wall 19 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 25 0.36 0 'Min. Air Changes/ hr= 2
E - Wall 33 0.36 0 'Min. cfm reqd. = 143
SE - Wall 33 0.36 0
S - Wall 232 31 0.36 2589
SW - Wall 29 0.36 0
W - Wall 181 27 0.36 1759
NW - Wall 21 0.36 0
Roof Sun 47 0.32 0
Roof Shaded 23 0.32 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy 2 persons
ITEM Area Temp. diff. U FRESH AIR 143
(Sq ft) (°F) (Btu/h.sq ft) Light 642 watt
All Glass 70 28 0.55 1078 Equipment 642 watt
Glass Partition 21 23 0.55 266
Partition 281 23 0.3 1939
Partition 19 0.35 0
Ceiling 76 19 0.45 650
Floor 19 0.45 0
INTERNAL HEAT GAIN
People 2 Nos X 230 460
Light 642 W X 1.25 3.412 2738
Eq. Load 642 W 3.412 50431
ROOM SENSIBLE HEAT (RSH) 62590
Supply duct heat Supply duct Heat gain from 2 1252
gain + leak. loss + fan HP(%)

Safety factor (%) 5.0 3130


OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
143 28 0.12 1.08 518
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 67489
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
143 81.7 0.12 0.68 951
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH) 1191
Supply duct leakage loss + Safety factor % 5.0 60
EFFECTIVE ROOM LATENT HEAT (ERLH) 1251
EFFECTIVE ROOM TOTAL HEAT (ERTH) 68740
OUTSIDE AIR HEAT (SENSIBLE) Summmary
CFM °F 1 - BF FACTOR Fresh Air Air 143
143 28 0.88 1.08 3797 CFM
OUTSIDE AIR HEAT (LATENT) CHECK FIGURES Summer TR= 6.76
CFM GR/LB 1 - BF FACTOR Btu/h/ Sq ft = 189.5 Monsoon TR= 7.16
143 81.7 0.88 0.68 6975 CFM / Sq ft = 9.22 Deh. CFM= 4004
HEAT SUB TOTAL 79511 Sq ft / TR = 63 CFM(ACPH)= 56
Return duct heat HP Pump + Dehum. & Pipe 2.0 1590
gain & leak. loss + loss (%) CFM/ TR = 584
Selected TR = 7.2
TONS 6.76 GRAND TOTAL HEAT 81102 Selected CFM= 4050
AHU-5,R32,33
MONSOON
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 98 88 85 164
(Sq ft) (Btu/h.sq ft) ROOM 72 65 55 65
N - Glass 0 11 0.81 0 DIFFERENCE 26 XXXX XXXX XXXX 99
NE - Glass 0 11 0.81 0
E - Glass 0 11 0.81 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 11 0.81 0 2 People X 0 CFM/Person 7
S - Glass 70 11 0.81 624 428 Sq ft X 0 CFM/Sq ft 0.06
SW - Glass 0 113 0.81 0 CFM VENTILATION 40
W - Glass 0 165 0.81 0
NW - Glass 0 118 0.81 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.98
0 Indicated ADP = 56.00 °F
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 54.00 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 15.84 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 4004
No. of Rows = 0
N - Wall 0 9 0.36 0 AS PER REQD. AIR CHANGES
NE - Wall 0 15 0.36 0 'Min. Air Changes/ hr= 2.0
E - Wall 0 23 0.36 0 'Min. cfm reqd. = 143
SE - Wall 0 23 0.36 0
S - Wall 232 21 0.36 1754
SW - Wall 0 19 0.36 0
W - Wall 181 17 0.36 1108
NW - Wall 0 11 0.36 0
Roof Sun 0 37 0.32 0
Roof Shaded 0 13 0.32 0
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff. U
(Sq ft) (°F) (Btu/h.sq ft)
All Glass 70 26 0.5500 1001
Glass Partition 21 21 0.55 243
Partition glass-NAC 281 21 0.30 1770
Partition wall-NAC 0 10 0.35 0
Ceiling 76 10 0.45 342
Floor 0 10 0.45 0
INTERNAL HEAT GAIN
People 2.0 Nos X 230 460
Light 642.0 W X 1.25 3.412 2729
Eq. Load 642.0 WX 3.412 50431
ROOM SENSIBLE HEAT (RSH) 60461
Supply duct heat Supply duct Heat gain from 5 4535
gain + leak. loss + fan HP(%)
Safety factor (%) 5.0 3023
OUTSIDE & INFILTRATED AIR
CFM °F BF FACTOR
143 26 0.12 1.08 481
0 0 0.12 1.08 0
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 68499
LATENT HEAT
People 2 Nos X 120 240
OUTSIDE & INFILTRATED AIR
CFM GR/LB BF FACTOR
143 99 0.12 0.68 1153
0 0 0.12 0.68 0
ROOM LATENT HEAT (RLH)
Supply duct leakage loss + Safety factor% 5.0 0
EFFECTIVE ROOM LATENT HEAT (ERLH) 1393
EFFECTIVE ROOM TOTAL HEAT (ERTH) 69892
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF FACTOR
143 26 0.88 1.08 3525
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF FACTOR
143 99 0.88 0.68 8452
HEAT SUB TOTAL 81869
Return duct heat HP Pump + Dehum. & Pipe 5.0 4093
gain & leak. loss + loss (%) TOTAL MONSOON LOAD = 7.16 TR
TONS 7.16 TOTAL HEAT 85962
SHANNAYA HOSPITAL AC LOAD SUMMERY - GROUND FLOOR

MAINTAIN MAINTAIN MAINTAIN


SL.NO. FLOOR LOCATION AREA Dehumidified AC Load OCCUPANCY ROOM ROOM RELATIVE FRESH AIR LIGHTING EQ. LOAD UNIT TYPE
(Sqft) CFM (TR) HEIGHT TEMP IN HUMIDITY CFM LOAD W/SQ.FT
(FT) (F) IN (%) W/SQ.FT.

1 FIRST #REF! #REF! #REF! #REF! #REF! #REF! #REF! 55 #REF! 1.5 1.5 AHU
2 FIRST #REF! #REF! #REF! #REF! #REF! #REF! #REF! 55 #REF! 1.5 1.5 CASSETTE
3 FIRST #REF! #REF! #REF! #REF! #REF! #REF! #REF! 55 #REF! 1.5 1.5 HI WALL
4 FIRST #REF! #REF! #REF! #REF! #REF! #REF! #REF! 55 #REF! 1.5 1.5 HI WALL
5 FIRST AHU-1, R1-R5,R7 1251 4750 10.1 24 10.0 72 55 417 1.5 1.5 HI WALL