Address unit for conventional units

Salwico NS-AIN1/ID3
Part no. N12010

System: Salwico NSAC-1 Fire alarm system

Description Data
NS-AIN1/ID3 is an addressable interface loop unit Inputs One for conventional detectors
for connecting conventional units, such as smoke, Input max load ~5 conv. detectors or 250 µA
heat or flame detectors, to the analogue fire alarm Max input cable length25 m
system NSAC-1. System voltage 24 V DC
The address is set with a DIP switch. Operating voltage 15 - 35 V DC
The function DIP switch shall be set to ID3 (see Supervision current 1.5 mA
below). Alarm current 11.5 mA
When the unit/units connected to the NS-AIN1/ End of line resistor ELR-33, 33 kΩ
ID3 is in alarm condition, a red LED on the PCB is part no. N1702, included.
lit. The LED is lit until the alarm has been reset at Cable glands Pg16
the control panel. Cable diameter 8 - 14 mm
The included end of line resistor (ELR-33) has to Cable terminals 2.5 mm2
be connected for supervision after the last unit Operating temperature -25ºC to +70ºC
connected to the input. Ambient humidity 0 - 95% RH
Ingress protection IP55
Material PC/ABS
Colour Grey
Weight ~300 g
PCB part number N12015
Dimensions (mm)
4xØ4 mm, mounting holes
66

50

80
15

160

148 6

Connection
NS-AIN1/ID3
Conventional detectors
Loop IN 1 (+)
2 (-)
Loop OUT 3 (+) Detector Last detector
4 (-)
5 (+) 1 1 + + 1 1 + +
ELR-33
6 (-) 2 2 2 2
7 (+)
8 (-)
See detector data sheet for correct detector connection.