Professional Documents
Culture Documents
Risk Based Approach To Substation Earthing For SA Power Networks
Risk Based Approach To Substation Earthing For SA Power Networks
Power Networks
Michael A. Brown
Engineering Design and Technical Services
SA Power Networks
Adelaide, Australia
Michael.Brown@sapowernetworks.com.au
Abstract—SA Power Networks has recently adopted the changes coincidence, and is the probability that a person will come into
to earthing philosophy detailed in EG-0 Power System Earthing contact with the substation or surrounding earthed asset at the
Guide. This method determines the risk of fatality for the most time of a fault.
exposed individual based on substation fault level, protection
clearing times, fault frequency, and human contact to Negligible or acceptable values for the probability of
conductive structures. This is currently done using a fault fatality for an individual are detailed in EG-0 and are as shown
frequency based on standard values given in EG-0. This paper in Table I below.
investigates the methods that SA Power Networks use to record TABLE I. TARGET INDIVIDUAL FATALITY PROBABILITY LIMITS
interruptions, and how this information can be used to [1].
determine an observed earth fault frequency for use in touch
Risk
voltage threshold calculations. The last 10 years of fault data for Probability of
classification for
Resulting implication for risk
a sample of 39 substations was examined and negligible risk Single Fatality treatment
public death
touch voltage thresholds were calculated using clearing times of High or Must prevent occurrence regardless
10-4
0.2 seconds and 1.0 seconds. These thresholds were then intolerable risk of costs.
compared to those determined using the calculated fault Must minimize occurrence unless
frequency based on line length, and using the IEEE 80 Intermediate or risk reduction is impractical and
10-4 – 10-6
deterministic method previously used by SA Power Networks. ALARA region costs are grossly disproportionate to
safety gained.
Risk generally acceptable, however,
Index Terms—Earthing, Fault Frequency, Risk, Substation,
Low or tolerable risk treatment may be applied if the
Touch Voltage 10-6
risk cost is low and/or a normally
expected practice.
Where ALARA is ‘as low as reasonably achievable’.
I. INTRODUCTION
The new version of AS 2067 – released in 2016, is based The probability of coincidence is calculated based on two
on EG-0 and details a risk-based earthing philosophy. Risk inputs – the number of touches per year to a potentially
based earthing enables asset owners to best identify the hazardous item, and the number of earth faults that occur at
highest risk among substations or other earthed equipment, the source substation per year.
and act upon those which will give the most benefit - this is EG-0 has standard values that are given for both quantities.
seen as both a potentially safer and more economical approach The number of human contacts per year is determined by the
than previous practice. The main principle of this philosophy location of the substation, being classified as one of four areas
is to quantify the probability of fatality (PFat) for substation – MEN, backyard, urban, and remote. Having a four second
touch voltage hazards, and then assess this number to contact count of 2000, 416, 100, and 4 respectively. For 11 kV
determine whether a touch voltage is of acceptable risk or and 33 kV lines, earth fault frequencies are given as 5 – 10
needs to be rectified. The probability of fatality is based on faults/100km/year for shielded conductors, and 10 – 40
two separate quantities, and is given by faults/100km/year for unshielded conductors [1].
PFat = PFib * PCoinc (1) SA Power Networks has adopted these standard values for
PFib is the probability of fibrillation, which is the distribution lines and has chosen a fault frequency of 20
probability that the heart will undergo ventricular fibrillation faults/100km/year for unshielded lines, and 5
when exposed to a specific current. PCoinc is the probability of faults/100km/year for shielded lines. Shielded lines in this
case are lines which are protected from lightning. For the
Figure 5. Probability of fatality for negligible voltage thresholds determined For a clearing time of 0.2 s, 13 of the 39 touch voltages
using calculated fault frequency (0.2 s clearing time). were in the ALARA region. This indicated that at this fault
duration, IEEE 80 calculated thresholds were still acceptable.