Electrical Design Analysis Report
Electrical Design Analysis Report
2
1.0 ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WIRE SIZE: 38mm COPPER WIRES WIRE SIZE: 38mm2 COPPER WIRES
CONVENIENCE OUTLET SERVICE ENTRANCE
WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELEC- DISTANCE: 164 ft
I
TRICAL CODE, THE RULES, REGULATIONS AND REQUIREMENTS OF THE CURRENT: 107.81 AMPS = 22.83KVA x 1000 = 99.26 AMP
WATER HEATER FLA
UTILITY COMPANY AND THE LAWS AND ORDINANCES OF THE LOCAL 230
CODE ENFORCING AUTHORITY REF. OUTLET SERVICE ENTRANCE TO PP M=
100
62.5
2.0 UNLESS OTHERWISE SPECIFIED, CONDUCTORS SHALL BE 99.99% PURE 1.6
COPPER, TYPE THWN/THHN , 75 C/90 C. 600 VOLT INSULATION VOLTAGE DROP = 2 x R x I x L
RANGE OUTLET I
3.0 THE MINIMUM SIZE OF WIRE AND CONDUIT SHALL BE 3.5SQMM AND CM SC-MCB = I FLA X M
15MM DIA. RESPECTIVELY. RANGE HOOD OUTLET = 2 x 12 x 99.27 x 164 99.26 x 62.5
4.0 ALL MATERIALS SHALL BE BRAND NEW AND OF SUITABLE AND APPRO- I SHORT CIRCUIT DIAGRAM
COUNTERTOP OUTLET 83,690 =6.203kA
VED TYPE FOR LOCATION AND PURPOSE. SC-MCB
5.0 ALL 20 AMPERE CIRCUIT HOMERUNS TO PANELBOARD MORE THAN 30 4.67 V AVAILABLE UTILIY KW/M
METERS IN LENGTH SHALL BE 5.5SQMM MINIMUM , UNLESS OTHERWISE WASHING MACHINE OUTLET % VOLTAGE DROP = (4.67 V / 230V) x 100 = 2.03%
NOTED.
LP
ACU
WINDOW TYPE ACU OUTLET 125AT
6.0 STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATION
LP TO C.O
2P
AND OTHER APPURTENANCES FOR THE ENTIRE ELECTRICAL INSTALL-
NEMA3R 230V
ATION SHALL BE USED. LIGHTING OUTLET - L1 VOLTAGE DROP = 2 x R x I x L
125AT
7.0 ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIP- 2P
LIGHTING OUTLET - L2 CM
MENTS SHALL BE EFFECTIVELY GROUNDED. 230V
= 2 x 12 x 13.59 x 98.43
8.0 WHENEVER NECESSARY, PULL BOX SHALL BE PROVIDED EVEN IF NOT
LIGHTING OUTLET - L3 6530
TRANSFORMER
INDICATEDIN THE PLANS.
9.0 ALL DIMENSIONS SHOWN ON THE PLANS ARE APPROXIMATE AND SHALL
HOME RUN 4.92 V
BE VERIFIED AS ACTUAL LOCATIONS, DISTANCES, AND LEVELS ARE
% VOLTAGE DROP =(4.92 V / 230V) x 100 = 2.14% FAULT
GOVERNED BY FIELD CONDITIONS. SERVICE ENTRANCE
10.0 ALL CONDUIT SIZES SHALL BE BASED ON OUTSIDE DIAMETER TOTAL % VOLTAGE DROP = 2.03% + 2.14% = 4.17%
11.0 MAXIMUMSPACING BETWEEN CONDUIT SUPPORTS SHALL BE 1500MM PANEL BOARD
AND 300MM BETWEEN SUPPORT AND FITTINGS OR BOXES. VOLTAGE DROP DIAGRAM M ELECTRIC METER
2W-38mm2 THHN WIRE +
12.0 ALL COPPER BUS BARS SHALL BE SIZED BASED ON 155 AMPERE PER 1W-8.0mm2 THHN WIRE(G) IN:
SQUARE CENTIMETER OF CROSS SECTION COPPER KDENSITY % VD = 2.03% % VD = 2.14%
40mm PVC PIPE
13.0 ALL WORKS SHALL BE DONE IN A NEAT AND WORKMAN LIKE MANNER LP
14.0 ALL UTILITY AND JUNCTION BOXES SHALL BE GAUGE 16 DEEP TYPE CO
PANEL BOARD
15.0
CONCENTRIC KNOCK OUTS SHALL NOT BE ALLOWED.
RUNNING THREADS SHALL NOT BE USED ON CONDUITS FOR CONNECT-
PP
POWER SINGLE LINE DIAGRAM
ION AT COUPLINGS.
16.0 CONDUIT BENDS SHALL BE MADE IN SUCH A WAY THAT THE INTERNAL
DIAMETER WILL NOT BE EFFECTIVELY REDUCED.
17.0 WHERE CONDUITS ENTER A BOX, FITTING OR OTHER ENCLOSURE BUSH-
ING SHALL BE PROVIDED TO PROTECT THE WIRE FROM ABRASION.
18.0 ALL WIRES AND CIRCUIT BREAKERS SHALL BE LOADED AT NOT MORE
THAN EIGHTY PERCENT (80%) OF RATED CAPACITY.
19.0 LIGHTNING SWITCHES SHALL BE QUIET TYPE, SPRING OPERATED. TUMBLER
OPERATION, FLUSH MOUNTED MAXIMUM CAPACITY SHALL BE 10A ,220V
20.0 CONVENIENCE OUTLET SHALL BE DUPLEX GROUNDING TYPE PARALLEL
SLOTS,FLUSH MOUNTED RATED 15A,220V.
ENCLOSURE: NEMA-1 SUFACE MOUNTED MAIN CB : 125AT, 150AF,2P, 230V, 60HZ, 25 KAIC, IT
PANEL : LP VOLTAGE : 230V
DESIGN ANALYSIS PHASE : SINGLE PHASE NO. OF SETS : 1
A. FOR LIGHTING AND CONVINIECE OUTLET LOAD FEEDER :FROM SERVICE ENTRANCE FEEDER WIRE : 2W- 38mm2 THHN WIRE
CKT H.P VA VOLT AMPERES RATING ACB RATING SERVICE WIRE CONDUIT
DESCRIPTION L.O C.O WATTS
TOTAL FLOOR AREA x 24VA/m² NO RATING RATING RATING AB BC CA ABC POLE TRIP AF TYPE SIZE AND TYPE DIAMETER
480.55m² x 24VA/m² = 11,533.2VA 1 LIGHTING OUTLET 24 600 750 230 3.26 1 20 100 B.O X3.5 20mm PVC
2 LIGHTING OUTLET 16 400 500 230 2.17 1 20 100 B.O X3.5 20mm PVC
FIRST 3,000VA @ 100% DF = 3,000VA 3 LIGHTING OUTLET 10 250 313 230 1.36 1 20 100 B.O X3.5 20mm PVC
4 CONVENIENCE OUTLET 12 2160 2,700 230 11.74 1 20 100 B.O X3.5 20mm PVC
8,533VA @ 35% DF = 2,986.62VA
5 COUNTER TOP OUTLET 5 2500 3,125 230 13.59 1 20 100 B.O X3.5 20mm PVC
NET LOAD FOR LIGHTING AND CO 6 CONVENIENCE OUTLET 10 1800 2,250 230 9.78 1 20 100 B.O X3.5 20mm PVC
= 5,986.62VA
7 CONVENIENCE OUTLET 11 1980 2,475 230 10.76 1 20 100 B.O X3.5 20mm PVC
B. SMALL APPLIANCES (FIXED LOAD) 8 ACU 1.5HP (BR 1) 1,398 230 6.08 1 20 100 B.O X3.5 20mm PVC
9 ACU 1.5HP(BR 2) 1,398 230 6.08 1 20 100 B.O X3.5 20mm PVC
1 - 2.5HP ACU = 2,330VA
10 ACU 1.5HP(BR 3) 1,398 230 6.08 1 20 100 B.O X3.5 20mm PVC
6 - 1.5HP ACU = 8,388VA
11 ACU 1.5HP(BR 4) 1,398 230 6.08 1 20 100 B.O X3.5 20mm PVC
NET LOAD FOR SMALL APPLIANCES = 10,718VA 12 ACU 1.5HP(BR 5) 1,398 230 6.08 1 20 100 B.O X3.5 20mm PVC
13 ACU 1.5HP(BR 6) 1,398 230 6.08 1 20 100 B.O X3.5 20mm PVC
C. SPARE 14 ACU 2.5HP(LIVING ROOM) 2,330 230 10.13 1 30 100 B.O X5.5 25mm PVC
2 - 3000VA SPARE OUTLET = 6,000VA 15 SPARE 230 1 20 100 B.O X3.5 20mm PVC
16 SPARE 230 1 20 100 B.O X3.5 20mm PVC
TOTAL LOAD = 22,704.6VA TOTAL 50 9690 22,833 99.27 - -
COMPUTATION OF LOAD
22,704.62VA
I TOTAL
= 230V It = 99.27 + (10.13 x .25) = 101.80A GROUNDING WIRE: 14MM THHN
= 98.72A + (25% x 10.13)
= 101.25A