Electrical Design Analysis Report

This document provides general notes and legends for an electrical installation. It specifies that all electrical work must comply with the Philippine Electrical Code and local regulations. Conductors are to be 99.99% pure copper rated for 75C/90C at 600V. The minimum wire and conduit sizes are 3.5mm2 and 15mm respectively, and all materials must be new and approved for their location and purpose. Circuit homeruns over 30m to the panelboard must be at least 5.5mm2. Standard accessories, splicing devices, and terminations are to be used for the entire installation. A sample voltage drop and short circuit calculation is provided for a 38mm2 copper feeder running 164ft at 107.81

Uploaded by

Christian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
170 views1 page

Electrical Design Analysis Report

This document provides general notes and legends for an electrical installation. It specifies that all electrical work must comply with the Philippine Electrical Code and local regulations. Conductors are to be 99.99% pure copper rated for 75C/90C at 600V. The minimum wire and conduit sizes are 3.5mm2 and 15mm respectively, and all materials must be new and approved for their location and purpose. Circuit homeruns over 30m to the panelboard must be at least 5.5mm2. Standard accessories, splicing devices, and terminations are to be used for the entire installation. A sample voltage drop and short circuit calculation is provided for a 38mm2 copper feeder running 164ft at 107.81

Uploaded by

Christian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

GENERAL NOTES: LEGENDS AND SYMBOLS VOLTAGE DROP CALCULATION SHORT CIRCUIT CALCULATION

2
1.0 ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WIRE SIZE: 38mm COPPER WIRES WIRE SIZE: 38mm2 COPPER WIRES
CONVENIENCE OUTLET SERVICE ENTRANCE
WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELEC- DISTANCE: 164 ft
I
TRICAL CODE, THE RULES, REGULATIONS AND REQUIREMENTS OF THE CURRENT: 107.81 AMPS = 22.83KVA x 1000 = 99.26 AMP
WATER HEATER FLA
UTILITY COMPANY AND THE LAWS AND ORDINANCES OF THE LOCAL 230
CODE ENFORCING AUTHORITY REF. OUTLET SERVICE ENTRANCE TO PP M=
100
62.5
2.0 UNLESS OTHERWISE SPECIFIED, CONDUCTORS SHALL BE 99.99% PURE 1.6
COPPER, TYPE THWN/THHN , 75 C/90 C. 600 VOLT INSULATION VOLTAGE DROP = 2 x R x I x L
RANGE OUTLET I
3.0 THE MINIMUM SIZE OF WIRE AND CONDUIT SHALL BE 3.5SQMM AND CM SC-MCB = I FLA X M
15MM DIA. RESPECTIVELY. RANGE HOOD OUTLET = 2 x 12 x 99.27 x 164 99.26 x 62.5
4.0 ALL MATERIALS SHALL BE BRAND NEW AND OF SUITABLE AND APPRO- I SHORT CIRCUIT DIAGRAM
COUNTERTOP OUTLET 83,690 =6.203kA
VED TYPE FOR LOCATION AND PURPOSE. SC-MCB
5.0 ALL 20 AMPERE CIRCUIT HOMERUNS TO PANELBOARD MORE THAN 30 4.67 V AVAILABLE UTILIY KW/M
METERS IN LENGTH SHALL BE 5.5SQMM MINIMUM , UNLESS OTHERWISE WASHING MACHINE OUTLET % VOLTAGE DROP = (4.67 V / 230V) x 100 = 2.03%
NOTED.
LP
ACU
WINDOW TYPE ACU OUTLET 125AT
6.0 STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATION
LP TO C.O
2P
AND OTHER APPURTENANCES FOR THE ENTIRE ELECTRICAL INSTALL-
NEMA3R 230V
ATION SHALL BE USED. LIGHTING OUTLET - L1 VOLTAGE DROP = 2 x R x I x L
125AT
7.0 ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIP- 2P
LIGHTING OUTLET - L2 CM
MENTS SHALL BE EFFECTIVELY GROUNDED. 230V
= 2 x 12 x 13.59 x 98.43
8.0 WHENEVER NECESSARY, PULL BOX SHALL BE PROVIDED EVEN IF NOT
LIGHTING OUTLET - L3 6530
TRANSFORMER
INDICATEDIN THE PLANS.
9.0 ALL DIMENSIONS SHOWN ON THE PLANS ARE APPROXIMATE AND SHALL
HOME RUN 4.92 V
BE VERIFIED AS ACTUAL LOCATIONS, DISTANCES, AND LEVELS ARE
% VOLTAGE DROP =(4.92 V / 230V) x 100 = 2.14% FAULT
GOVERNED BY FIELD CONDITIONS. SERVICE ENTRANCE
10.0 ALL CONDUIT SIZES SHALL BE BASED ON OUTSIDE DIAMETER TOTAL % VOLTAGE DROP = 2.03% + 2.14% = 4.17%
11.0 MAXIMUMSPACING BETWEEN CONDUIT SUPPORTS SHALL BE 1500MM PANEL BOARD
AND 300MM BETWEEN SUPPORT AND FITTINGS OR BOXES. VOLTAGE DROP DIAGRAM M ELECTRIC METER
2W-38mm2 THHN WIRE +
12.0 ALL COPPER BUS BARS SHALL BE SIZED BASED ON 155 AMPERE PER 1W-8.0mm2 THHN WIRE(G) IN:
SQUARE CENTIMETER OF CROSS SECTION COPPER KDENSITY % VD = 2.03% % VD = 2.14%
40mm PVC PIPE
13.0 ALL WORKS SHALL BE DONE IN A NEAT AND WORKMAN LIKE MANNER LP
14.0 ALL UTILITY AND JUNCTION BOXES SHALL BE GAUGE 16 DEEP TYPE CO
PANEL BOARD

15.0
CONCENTRIC KNOCK OUTS SHALL NOT BE ALLOWED.
RUNNING THREADS SHALL NOT BE USED ON CONDUITS FOR CONNECT-
PP
POWER SINGLE LINE DIAGRAM
ION AT COUPLINGS.
16.0 CONDUIT BENDS SHALL BE MADE IN SUCH A WAY THAT THE INTERNAL
DIAMETER WILL NOT BE EFFECTIVELY REDUCED.
17.0 WHERE CONDUITS ENTER A BOX, FITTING OR OTHER ENCLOSURE BUSH-
ING SHALL BE PROVIDED TO PROTECT THE WIRE FROM ABRASION.
18.0 ALL WIRES AND CIRCUIT BREAKERS SHALL BE LOADED AT NOT MORE
THAN EIGHTY PERCENT (80%) OF RATED CAPACITY.
19.0 LIGHTNING SWITCHES SHALL BE QUIET TYPE, SPRING OPERATED. TUMBLER
OPERATION, FLUSH MOUNTED MAXIMUM CAPACITY SHALL BE 10A ,220V
20.0 CONVENIENCE OUTLET SHALL BE DUPLEX GROUNDING TYPE PARALLEL
SLOTS,FLUSH MOUNTED RATED 15A,220V.
ENCLOSURE: NEMA-1 SUFACE MOUNTED MAIN CB : 125AT, 150AF,2P, 230V, 60HZ, 25 KAIC, IT
PANEL : LP VOLTAGE : 230V
DESIGN ANALYSIS PHASE : SINGLE PHASE NO. OF SETS : 1
A. FOR LIGHTING AND CONVINIECE OUTLET LOAD FEEDER :FROM SERVICE ENTRANCE FEEDER WIRE : 2W- 38mm2 THHN WIRE
CKT H.P VA VOLT AMPERES RATING ACB RATING SERVICE WIRE CONDUIT
DESCRIPTION L.O C.O WATTS
TOTAL FLOOR AREA x 24VA/m² NO RATING RATING RATING AB BC CA ABC POLE TRIP AF TYPE SIZE AND TYPE DIAMETER

480.55m² x 24VA/m² = 11,533.2VA 1 LIGHTING OUTLET 24 600 750 230 3.26 1 20 100 B.O X3.5 20mm PVC
2 LIGHTING OUTLET 16 400 500 230 2.17 1 20 100 B.O X3.5 20mm PVC

FIRST 3,000VA @ 100% DF = 3,000VA 3 LIGHTING OUTLET 10 250 313 230 1.36 1 20 100 B.O X3.5 20mm PVC
4 CONVENIENCE OUTLET 12 2160 2,700 230 11.74 1 20 100 B.O X3.5 20mm PVC
8,533VA @ 35% DF = 2,986.62VA
5 COUNTER TOP OUTLET 5 2500 3,125 230 13.59 1 20 100 B.O X3.5 20mm PVC
NET LOAD FOR LIGHTING AND CO 6 CONVENIENCE OUTLET 10 1800 2,250 230 9.78 1 20 100 B.O X3.5 20mm PVC
= 5,986.62VA
7 CONVENIENCE OUTLET 11 1980 2,475 230 10.76 1 20 100 B.O X3.5 20mm PVC
B. SMALL APPLIANCES (FIXED LOAD) 8 ACU 1.5HP (BR 1) 1,398 230 6.08 1 20 100 B.O X3.5 20mm PVC
9 ACU 1.5HP(BR 2) 1,398 230 6.08 1 20 100 B.O X3.5 20mm PVC
1 - 2.5HP ACU = 2,330VA
10 ACU 1.5HP(BR 3) 1,398 230 6.08 1 20 100 B.O X3.5 20mm PVC
6 - 1.5HP ACU = 8,388VA
11 ACU 1.5HP(BR 4) 1,398 230 6.08 1 20 100 B.O X3.5 20mm PVC
NET LOAD FOR SMALL APPLIANCES = 10,718VA 12 ACU 1.5HP(BR 5) 1,398 230 6.08 1 20 100 B.O X3.5 20mm PVC
13 ACU 1.5HP(BR 6) 1,398 230 6.08 1 20 100 B.O X3.5 20mm PVC
C. SPARE 14 ACU 2.5HP(LIVING ROOM) 2,330 230 10.13 1 30 100 B.O X5.5 25mm PVC
2 - 3000VA SPARE OUTLET = 6,000VA 15 SPARE 230 1 20 100 B.O X3.5 20mm PVC
16 SPARE 230 1 20 100 B.O X3.5 20mm PVC
TOTAL LOAD = 22,704.6VA TOTAL 50 9690 22,833 99.27 - -
COMPUTATION OF LOAD
22,704.62VA
I TOTAL
= 230V It = 99.27 + (10.13 x .25) = 101.80A GROUNDING WIRE: 14MM THHN
= 98.72A + (25% x 10.13)
= 101.25A

FOR MAIN SERVICE FEEDER


SCHEDULE OF LOADS
USE 2W - 38mm² THHN + 1 - 14mm² THHN in 40mm PVC

R.A. 9266 SEC. 33 ARCHITECT ON RECORD CONSULTANT


PROJECT TITLE : PROJECT NO : OWNER : SHEET CONTENTS : SHEET NO. :
(ARCHITECTURE ACT OF 2004)
OWNERSHIP OF PLANS, SPECIFICATION AND OTHER

SLSi CORPORATION CONTRACT DOCUMENTS:


DESIGNED BY : S.L.S
GENERAL NOTES
LEGENDS AND SYMBOLS
2 STOREY RESIDENTIAL JENIFER SEVILLA E-1
DRAWINGS AND SPECIFICATIONS AND OTHER CONTRACT
Construction Company DOCUMENTS DULY SIGNED, STAMPED OR SEALED, AS INSTRUMENTS
OF SERVICE, ARE INSTRUMENTS OF SERVICE, ARE THE INTELLECTUAL JOANNES PAULA V. ESPINO EDUARDO SOLAYAO
VICINITY MAP
SCHEDULE OF LOADS
25 Ipil st. Libis Bulelak Malanday Marikina City PROPERTY AND DOCUMENTS OF THE ARCHITECT, WHETHER THE DRAWN BY :
OBJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. IT SHALL
ARCHITECT PROFESSIONAL ELECTRICAL ENGINEER APPROVED BY: SINGLE LINE DIAGRAM
TEL.NO./FAX NO. 8 253 5171 MOBILE NO. 0947 556 0317
BE UNLAWFUL FOR ANY PERSON TO DUPLICATE OR TO MAKE COPIES
OF SAID DOCUMENTS FOR USE IN THE REPETITION OF AND FOR
OTHER PROJECTS OR BUILDINGS, WHETHER EXECUTED PARTLY OR
REG. NO. 0018738
IAPOA NO. 12136 -286369 -030920
VALIDITY:
DATE:
JUNE 30, 2021
MARCH 11, 2020
REG. NO.
PTR NO.
0002644
9821995
DATE:
PLACE:
JANUARY 4, 2021
MANILA
LOCATION :
RES. CERT.: DATE:
DESIGN ANALYSIS
VOLTAGE DROP
1 3
IN WHOLE, WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT OR Barangay Wenceslao, Maria Aurora, Aurora Province DATE :
AUTHOR OF SAID DOCUMENTS. PTR NO. 9439285 PLACE: MANILA TIN NO. 121027583
TIN: SHORT CIRCUIT ANALYSIS