1 2 3 4 1 2 3 4

5
A ACU ACU
S1e ACU CO ACU
LP LP

f g CO CO CO ELECTRICAL SYMBOLS
e
SYMBOL DESCRIPTION

S1f S1g CO CO
CEILING LIGHT
B CONVENEINCE OUTLET
Ref
d CO
LOAD PANEL
4 LP
i h
S1i SE
SERVICE ENTRANCE

S1d S1h M METER BOARD / KILO WATT HOUR

C CH CIRCUIT HOMERUN
c S1j CO CO CO
SWITCH LINE
CO
2 CIRCUIT LINE RUN INSIDE WALL OR UNDER FLOOR
j CIRCUIT LINE RUN INSIDE WALL OR OVER CEILING

S1 SINGLE GANG SWITCH


1
b S2 DOUBLE GANG SWITCH
S1c
CO S3 THREE GANG SWITCH
D ACU

S2ab CO 3

E ELECTRICAL GENERAL NOTES:

1. ALL ELECTRICAL INSTALLATIONS HEREIN AND OTHER RELATED WORKS TO BE DONE IN


THIS BUILDING SHALL BE IN ACCORDANCE WITH THE PROVISIONS AND STANDARDS OF
THE FOLLOWING:
1 LIGHTING LAYOUT 2 POWER LAYOUT 1.1
1.2
THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE.
REPUBLIC ACT 7926 OTHERWISE KNOWN AS THE NEW ELECTRICAL
SCALE: 1:100mts SCALE: 1:100mts
E 1 E 1 ENGINEERING LAW
1.3 THE NATIONAL BUILDING CODE OF THE PHILIPPINES.
1.4 FIRE CODE OF THE PHILIPPINES.
1.5 EXISTING RULES AND REGULATION OF THE LOCAL POWER UTILITY COMPANY.
1.6 THE EXISTING CITY/MUNICIPAL ORDINANCES AND,
M 1.7 THE BUREAU OF LABOR STANDARDS.
POWER 2. ALL ELECTRICAL INSTALLATIONS HEREIN SHALL BE DONE UNDER THE DIRECT
SHEDULE OF LOAD & COMPUTATION SUPERVISION OF A DULY REGISTERED ELECTRICAL ENGINEER. HE SHALL BE RESPONSIBLE
SERVICE IN THE INTERPRETATION OF THE PLANS AND SPECIFICATION AND THE REQUIRED
ENTRANCE CKT. DEMAND LOAD VOLTAGE CURRENT CB RATING STANDARDS OF THE ELECTRICAL CODE.
DESCRIPTION WIRE & CONDUIT SIZE 3. MATERIALS AND EQUIPMENT TO BE USED SHALL HAVE INSPECTED COMMODITY
230V, 1Ø, 3W NO. (VA) (V) (A) AT P AF
75A CLEARANCE (ICC) LABEL FOR FOREIGN MADE PRODUCTS AND P.S. MARK FOR LOCAL IN
NATURE OF THE BUREAU OF PRODUCT STANDARD (BPS).
60HZ 1 10-100w LIGHTING OUTLET 1000 230 3.91 15 2 50 2-2.0mm² THWN IN 15mmØ PVC
4. PROVIDE GROUNDING WIRE TO ALL OUTLETS AND LIGHTING CIRCUITS, ALL NON CURRENT
2 2GANG -CONVENIENCE OUTLET 3960 230 17.22 20 2 50 2-3.5mm² THWN IN 15mmØ PVC CARRYING METAL PARTS SHALL BE GROUNDED AND BOBDED INCLUDING FENCE AND
13-100w 2GANG GATE.
1 15A 20A 2
3 ACU OUTLET 1.5 HP 2300 230 10 30 2 50 2-5.5mm² THWN IN 15mmØ PVC
LIGHTING -CONVENIENCE 5. ALL PANEL BOARDS, MAIN DISTRIBUTION PANELS, ETC., SHALL HAVE GROUNDING BUS FOR
OUTLET BRANCH CIRCUITS AND SUB FEEDER GROUNDING SYSTEM SHALL BE BONDED TO THE
OUTLET 4 REF OUTLET 1 HP 1840 230 8 30 2 50 2-5.5mm² THWN IN 15mmØ PVC NEAREST METAL WATER PIPE.
5 ACU OUTLET 1 HP 1840 30 2 50 2-5.5mm² THWN IN 15mmØ PVC 6. MOUNTING HEIGHT FOR ALL WIRING DEVICES AND PANEL BOARDS SHALL BE.
REF OUTLET 1.5 HP 230 8
ACU OUTLET 1.5 HP
3 30A 30A 4 6.1 LIGHTING OUTLETS 1.40M ABOVE FLOOR FINISH.
6 ACU OUTLET 1 HP 1840 230 8 30 2 50 2-5.5mm² THWN IN 15mmØ PVC 6.2 CONVENIENCE OUTLETS 0.30M ABOVE FLOOR FINISH.
6.3 TELEPHONE OUTLETS 0.30M ABOVE FLOOR FINISH.
7 SPARE 1840 230 8 30 2 50 2-5.5mm² THWN IN 15mmØ PVC 6.4 PANEL BOARDS & CABINETS 1.40M ABOVE FLOOR FINISH.
7. WIRING METHODS SHALL BE AS FOLLOWS:
REF OUTLET 1 HP
5 30A 30A 6 REF OUTLET 1 HP 8 SPARE NOT WIRE
7.1 SERVICE ENTRANCE RESISTS INTERMEDIATE METALLIC
TOTAL CONNECTION LOAD 14620 CONDUIT (IMC).
63.13
7.2 LIGHTING AND POWER SYSTEM POLYVINYL CHLORIDE (PVC).
7.3 TELEPHONE OUTLETS POLYVINYL CHLORIDE (PVC).
SPARE 7 30A 8 ALLYING DEMAND FACTOR OF 80%IN EXCESS FOR MAIN PANEL PROTECTION USED : 7.4 ALL VIBRATING EQUIPMENTS LIQUID TIGHT FLEXIBLE METAL
SPARE CONDUIT.
IT: 14620x 0.80 = 11696 MINIMUM AMPACITY OF MAIN FEEDER: 2P-75 AMP ACB
8. NO CHANGES OR MODIFICATION SHALL BE MADE WITHOUT THE DESIGNERS WRITTEN
11696/230 = 53.7 I=75AMP (0.80) CONSENT.
IT : 50.85 AMP. I=60AMP FOR MAIN FEEDER WIRE LINE 9. ALL WORKS SHALL BE EXECUTED IN A WORKMANSHIP MANNER AND SHALL PREVENT A
15mm Ø x 3.0 M USED :2-22mm² THWN IN 25mm Ø RSC NEAT AND ORDERLY ACCEPTANCE. ALL WIRING SHALL BE CONCEALED IN THE LEAST
COPPER CLAD POSSIBLE WAY.

GRD ROD

3 RISER DIAGRAM
SCALE: NTS
E 1
REPUBLIC ACT 545 SECTION 25(4) PROJECT TITLE: PROJECT OWNER: SHEET CONTENTS: REVISIONS: DRAWING NO.
Drawing and Specification duly signed,stamped Designed By:
or sealed as instrument of service are properties
CIVIL ENGINEER of the Author whether the object for which they RESIDENTIAL BUILDING CAD By:
are madeis executed or not .It is unlawful for any BIEJAY D. LAPPAY AS SHOWN E1
PRC No. Validity
person, without the writter consent of the author
w/ ROOFDECK Approved By:
IAPOA No. O.R No. Date of the said document to duplicate or copy for use (AS BUILT) Date: SHEET NO.:
PTR No. Date. in other projects, whether executed partly or in
Place: TIN. whole LOCATION : INGUD NORTE, ANGADANAN, ISABELA ADDRESS: INGUD NORTE, ANGADANAN, ISABELA Project No.: 11 13