SERVICE ENTRANCE

Ref

S1
5
ENTRANCE CAP
r 6

S3

VERIFY
CO 3/4" Ø RSC
ACU
P P P
CO

S1
4
R.C. TERMINAL
POST
CO

S2 S1 KILOWATT
CO M HOUR METER

CO

1.50
S1

LP

GRADE LINE
CO CO ACU
1

1.20
S2
WP

0.25
900 mm X 900 mm RC
FOOTING WITH
5-16mm O RSB BOTHWAY

POWER LAYOUT PLAN SINGLE LINE DIAGRAM


LIGHTING LAYOUT PLAN

KWHM
POWER SERVICE
ENTRANCE 230V,
1Ø, 3W 60HZ
ELECTRICAL SYMBOLS SHEDULE OF LOAD & COMPUTATION
SYMBOL DESCRIPTION SYMBOL DESCRIPTION CKT. DEMAND LOAD VOLTAGE CURRENT CB RATING
DESCRIPTION WIRE & CONDUIT SIZE
NO. (VA) (V) (A) AT P AF
P
PIN LIGHT SINGLE GANG SWITCH 13-100w LIGHTING 2GANG -CONVENIENCE 1 13-100w LIGHTING OUTLET 1300 230 5.65 15 2 50 2-2.0mm² THWN IN 15mmØ PVC
S1 1 15A 20A 2
OUTLET OUTLET 2 2GANG -CONVENIENCE OUTLET 2880 230 12.52 20 2 50 2-3.5mm² THWN IN 15mmØ PVC
CEILING LIGHT S2 DOUBLE GANG SWITCH
3 ACU OUTLET 1.5 HP 2300 230 10 30 2 50 2-5.5mm² THWN IN 15mmØ PVC
WALL LAMPS S3 THREE GANG SWITCH 4 ACU OUTLET 1.5 HP 2300 230 10 30 2 50 2-5.5mm² THWN IN 15mmØ PVC
ACU OUTLET 1.5 HP 3 30A 30A 4 ACU OUTLET 1.5 HP 5 REF OUTLET 1HP 1840 230 8 30 2 50 2-5.5mm² THWN IN 15mmØ PVC
FLOURESCENT SWITCH LINE
6 RANGE OUTLET 5000 230 21.73 30 2 50 2-5.5mm² THWN IN 15mmØ PVC
CONVENEINCE OUTLET CIRCUIT LINE RUN INSIDE WALL OR UNDER FLOOR TOTAL CONNECTION LOAD 15,620 77.9
CO

WEATHER PROOF OUTLET CIRCUIT LINE RUN INSIDE WALL OR OVER CEILING REF OUTLET 1HP 5 30A 30A 6 RANGE OUTLET ALLYING DEMAND FACTOR OF 80%IN EXCESS FOR MAIN PANEL PROTCTION USED :
WP
IT: 15,620 x 0.80 =12,496 MINIMUM AMPACITY OF MAIN FEEDER: 2P-75 AMP ACB
REFRIGERATOR OUTLET
LP
LOAD PANEL
12,496/230 = 54.33 I=75AMP (0.80)
Ref FOR MAIN FEEDER WIRE LINE
IT : 54.33AMP. I=56AMP
RANGE OUTLET SERVICE ENTRANCE USED :2-22mm² THWN IN 25mm Ø RSC
r SE 7 8
SPARE SPARE
ACU
AIRCONDITION UNIT OUTLET M METER BOARD / KILO WATT HOUR

CIRCUIT HOMERUN
SCHEDULE OF LOADS
15mm Ø x 3.0 M COPPER
CLAD GRD ROD
PANEL DIAGRAM LOCATION MAP

REPUBLIC ACT 545 SECTION 25(4) PROJECT TITLE: PROJECT OWNER: SHEET CONTENTS: REVISIONS: SHEET NO.:
Drawing and Specification duly signed,stamped or sealed as
JOHN DE LA CRUZ (Signature & Seal)
JOHN DE LA CRUZ instrument of service are properties of the Author whether the
Designed By:

CIVIL ENGINEER CIVIL ENGINEER object for which they are madeis executed or not .It is unlawful CAD By:
PRC No. Validity
for any person, without the writter consent of the author of the
said document to duplicate or copy for use in other projects, Approved By:
E-1
100 Malaya ST. San juan, Muntinlupa City
IAPOA No. O.R No. Date whether executed partly or in whole
Tel. 87000 Date: Feb 2022
PTR No. Date.
Place: TIN. LOCATION : ADDRESS: Project No.: 1 20