Bel D Cc Electro-Mechanical & Commissioning Divi: Standards and Guidelines Mata Development Corporation ‘Section: Design Standards Bulletin No. EMCD-01-001-2016 ‘Subject: Back-up Fire Pump System for High Rise Buildings —_| Revision Code: 5_|Page 1 of 7 Effectivity: 20 May 2018 Prepared By: Approved By: Responsible’ 1. Construction Management, Project-in-Charge, Electro-Mechanical Commissioning D 2. Mechanical Consultants & Fire Pump Suppliers. 3. Project Procurement Team |. Implementatior + Designated personnel listed above are responsible for the full implementation of these guidelines. IL Objectives: + To comply on the standard code provision of fire protection system for all buildings. + To ensure availabilty of alternative fire pump incase primary fire pump becomes non-operational due to loss of power or by mechanical failure. Backup fire pump shall be diesel driven or electric driven fire pump. Intent Code Reference ‘To specify local | Philippine Mechanical Engineering Code 2012 Edition code requirement for backup fire | Chapter 20 - Fire Protection System pump. ‘Section 2009 Fire Pumps. |2009.1 General. Where provided, fire pumps shall be installed in accordance with this section and NFPA 20. }2009.2 Protection Against Interruption of Service. The fire pump, driver, and con- troller shall be protected in accordance with NFPA 20 against possible interruption of service through damage caused by explosion, fire, flood, earthquake, rodents, insects, windstorm, freezing, vandalism and other adverse conditions, To specify code [NFPA 20 Standard for the Install requirement for | 2013 Edi ion of Stationary Pumps for Fire Protection backup fire pump. Chapter 5 5.6.2 Fire Pump Backup. Fire pumps serving zones that are partially or wholly be- }yond the pumping capability ofthe fire department apparatus shall be provided with lone of the following Note: Use diesel (1) A fully independent and automatic backup fire pump unit(s) arranged so that all engine or zones can be maintained in full service with any one pump out of service. electric driven fire | (2) An auxiliary means thatis capable of providing the full fre protection demand pump as backup and that is acceptable to the authority having jurisdiction fire pump. | DC Electro-Mechanical & Commissioning Division Standards and Guidelines Nakai evelopment Corporation ‘Section: Design Standards Bulletin No. EMCD-01-001-2016 ‘Subject: Back-up Fire Pump System for High Rise Buildings [Revision Code: 5 | Page 2 of 7 Effectivity: 20 May 2018 Reviewed By: Approved By: Es laa Intent Code Referbnce To specify code [9.3 Alternate Power. requirement to have an alternate {9-3-1 Unless there is an installed power arrangement as described in 9.3.3, at least fone alternative source of power shall be provided for high rise buildings or where the ee height of the structure is beyond the pumping capacity of the fire department appara- | tus. 19.3.3 An alternate source of power for the primary fire pump shall not be required where a backup engine-driven fire pump, backup steam turbine-driven fire pump. or backup electric motor-driven fire pump with independent power source meeting 8.2.2, is installed in accordance with this standard. Ill, Sequence of Operations: 1, The jockey pump shall be capable of both manual and automatic shutoff 2, The jockey pump [1] shall start (ut in) when system pressure drops to -20psi design of system pres- ‘sure and stop (cut out) when it reaches the design system pressure. 3. The lead fire pump [2] shall start (cut in) when the system pressure drops to ~40psi of the design sys- tem pressure. Firepump shall continue to run until manually shut down, 4, The backup fire pump [3] shall start (cut in) when the design system pressure continues to drop up to ~ 60psi of design system pressure. Firepump shall continue to run until manually shut down. [Failure of the lead pump to start shall not prevent subsequent pumps from starting} Note: 1. Only BFP has the authority to manually turn-off the fire pump during its operations. FDAS Interfa IST ELECTRIC FIRE POW ] 0] or [ATA [ru PONT UST — ENONE-ORVEN FIRE PUM c DESCRIPTION polo [Ao] AT [AU RUNNING (ALARM O8 SUPERVISOR) || = | FAILURE TO START CONTROLLER OFF “AUTOWATIC™ TROUBLE (E.G. LOW OL, | HIGH TEMPERATURE, OVERSPEED) Bed DC Electro-Mechanical & Commissioning Division Standards and Guidelines Moka Gevetopment Corporation Section: Design Standards Bulletin No. EMCD-01-001-2016 ‘Subject: Back-up Fire Pump System for High Rise Buildings [Revision Code: 5 [Page 3 of 7 Effectivity: 20 May 2018 Reviewed By: Approved By: IV. Applicable Project: (je For vertical buildings beyond the pumping capability of the Fire Department. Prepared By: ‘Type of | resioenriat | HorEL |ero/orrice} mau | mixeo use Duty Electric Driven Eleetrie Driven Back-Up Electric Driven Diesel Orven| Note: Each SBU is required to have its own back-up fire pump (optional - if SBU agrees for shared investment when its pump room is located in one location) V. Sample projects with existing install DIESEL ENGINE DRIVEN FIRE PUMP ELECTRIC DRIVEN FIRE PUMP + wu ov > 2418105 iz yo ras IVI. Schematic Dagram (Backup is Electric Fire Pump): aw LEVEL sens09/IDCHTOR ‘ou Eira Blok TO “st fee Go > ly sv Bok 10 1k mw oan S a) tate 180) wo fe OT Oe ov (0587) eat eo eu ov (ose i) jest San Se) Ly To AS (REER To eveu-01-024-2018) va ct "| ED FROW AS 0 ow As FED FROW AS 0 caer 10 A ueRED BOSS 08 (tebe sve. ee eetwecn ten aa CENT 1 ae Wo GEE Vetch she¥netniy Anti-Vortex Plate details fc or (sah Oo wo} NOT USS Ta FL oro 100 -Ragreg ame T St mse rash, og uve] Soir Pa PmeL fecrpe ee i eo oon to Soe toute ‘awstee ech (iste) Pie ste ES EIGN TET) f+ : N Be maw neo Y 15# (SEIGNE INE 2) Sy < Note: ____ fall Sot StL BE gue sss Pe, 8 he SUNLESS Siete ‘Swing check valve, 1/2 (15mm @); shall have 3/32in g hole on flapper LEGEND & SYMBOLS 10) FLOW METER @ [rus Ble | jae PRESSURE GAUGE W/ BALL VANE FLOAT VALVE CHECK VALVE BATTERY 12V_ PRESSURE REGULATING VALVE. WASTE. CONE Symbol] _Cut-in Pressure (psig) (Cut-Out Pressure| (psig) GATE VALVE FIRE PUMP CONTROL Pal [aur AUTOMATIC FIRE SPRINKLER SYSTEM | Remarks [AUTOMATIC AIR RELEASE VALVE FIRE_DEPARTMENT CONNECTI [ALARM CHECK VALVE [SUPERVISORY SWITCH JP (1) |Design System Pressure minus 20psi| Design System Pressure” With Operator Manual GATE VALVE (OS&Y) intrtaced 1 ros| NORMALLY OPEN Shutdown oN SHOx| ple LEXIBLE. CONNECTOR NORWALLY CLOSE EFP (2)|Design System Pressure minus 40psi Manual Shutdown During Fire Emergency, ALARM BELL [DIESEL DRIVEN FIRE PUMP [3] mbDC Makati Development Corperation Electro-Mechanical and Commissioning Division Standards and Guidelines Section: Design Standards ‘Subject: Back-up Fire Pump System for High Rise Buildings Bulletin No. EMCD-01-001-2016 sel) ‘Only BFP can manually stop the pump ANTI-VORTEX PLATE [SENSING UNE CHECK Va ELECTRIC DRIVEN FIRE PUMP EFP (3) |Design System Pressure minus 60psi Manual Shutdown S| During Fire Emergency, ‘Only BFP can manually cv [Ware GLOBE VALVE stop the pump FDAS FIRE_DETECTION AND ALARM SYSTE NOTE: SENSIN si LINE WITH SWING TYP Sidh DIAMETER HOLE INTHE” CLAP * Depends on System Hydra Calculation OPTION 1 | sat Vil. Schematic Dagram (Backup is Diese! Fire Pump): eee reel S 5 anh haere eo come wee " Yo > ei ) 7 ose) wv e > 10 ws (FER To euCD-01-006-2018) fo Oy wae I 1c 10 ac sce 1 a OF cr won Electro-Mechanical and |__|: " Commissioning Division we 10 1 ran sto) ce wos sa 6 WR sot conser ® ®, Standards and Guidelines Section: F/R | Design Standards vs to 0 re rows - a f Subject: dug ® foe || sae je Tar Back-up Fire Pump System for st) High Rise Buildings (SB ova self SHE cra ce Fie et m3 ease | Noy ASS SL) 1 SERENE TNE TY SS ov Bulletin No. EMCD-01-001-2016 50 (SERENE UNE 3) wees ; ra kal 2 AND CHECK VANE _ “50 (SENSING UNE 2) SAUL BE Isa BREE Pp. {bite Green Soe "Se STAMESS STEEL PPE Note: ‘Swing check valve, 1/2 (15mm @); shall have 3/32in @ hole on flapper EGEND & SYMBOLS mu_| (Ol | Flow WETER po | @_| PRESSURE Lear neashahirwer tg cev_|N | check (a [artery ipa cease ee rv | ph | PRESSURE REGULATING VANE [APES] AUTOMATIC FRE SPRNKLER SYSTEM "Anti: Vortex Plate details WASTE CO! 7 FIRE PUMP CONTROL PANEL GATE VALVE AUTOM NSFER SWITCH [Cut-Out Pressure anaes AUTOMATIC AR RELEASE Val FIRE_ DEPARTMENT CONNECTION (psig) [ALARM CHECK VALVE SUPERVISORY SWIT( Design System | With Operator Manual GATE VALVE (0S&Y) t [NORMALLY OPEN Pressure* Shutdown c FLEXIBLE_ CONNECTOR NORMALLY CLOSE During Fire Emergency, ALARM SELL [DIESEL DRIVEN FIRE PUMP [3] EFP (2)|Design System Pressure minus 40psi| Manual Shutdown] Only BFP can manually iP ‘ANT|—VOF ELECTRIC DRIVEN FIRE PUMP [3] sto tho bump Se OE cc PO TD ka Symbol] —_Cut-In Pressure (psig) JP (1) |Design System Pressure minus 20psi| DFP (3) [Design system Prssue minus 6ps| Manual Shutdown] Only BEP ean manly d NOT FARING ANE TH SHIRE Ts = stop the pump * Depends on System Hydraulic Calculation OPTION 2 Vil. Electrical Schematic Diagram (Primary Metering): Makati Development Corporation SYMBOLS SYNCHRONIZING SWITCHGEAR TRANSFORMER ji pe ae. ; RVI. 5 a ne wren SS [i i Electro-Mechanical and ' I => OL | ceneraror ser Commissioning Division LOW VOLTAGE) TRANSFORMER CHGEAR! Standards and Guidelines CONTROLLER W/ DISCON SWITCH ieee Section: Design Standards USTED FIRE PUMP ATS GENERATOR SET(S) CIRCUIT BREAKERS ATS—1 ATS—2 ject FIRE PUMP FIRE “PUMP a BACK UP FIRE Subject: Back-up Fire Pump System for High Rise Buildings JOCKEY PUMP Be ATW TRANSFER SWC } S KWHR METER ©) ) MAIN FIRE PUMP BACK-UP FIRE PUMP Bulletin No. EMCD-01-001-2016 = (ELECTRIC DRIVEN) Ravicioncodera ABBREVIATIONS ‘evision Code: 4 | Page 6 of 7 7 OPTION 1 - Fire Pump Feeder System with PLECTeieat iNet eee Electric Driven Back Up Single Line Diagram (Primary Metering) aie SYNCHRONIZING SWITCHGEAR MAIN CIRCUTT BREAKER Mv INCOMING SERVICE RS ORME ; Reviewed By: eos osc SEA : oe 3 LOW VOLTAGE: Pes | eee ee ~ ot SWITCHGEAR} a NOTES | wsPeredo FULL LOAD CAPACITY OF THE GENERATOR SET(S) TWO ELECTRIC-DRIVEN FIRE PUMP SHALL BE CONSIDERED IN SIZING THE FEEDER WIRE FIRE PUMP ATS BATTERY CHARGER FOR DIESEL— DRIVEN SHALL HAVE A DEDICATED] POWER SUPPLY/CIRCUIT . OQ VB W/ LONG TIME, SHORT—TIME, at, AE G)__| INSTANTANEOUS & GROUND MAIN. FIRE PUMP BACK-UP FIRE PUMP seen | geen. | FAULT PROTECTION (DIESEL DRIVEN) sea” OPTION 2 - Fire Pump Feeder System with Diesel Driven Back Up Single Line Diagram (Primary Metering) Vil. Electrical Schematic Diagram (Secondary Metering): SYMBOLS MV INCOMING SERVICE | MV INCOMING SERVIC! GENERATOR SET TRANSFORMER CONTROLLER W/ DISCONNECT ‘SWITCH USTED FIRE PUNP ATS CIRCUIT BREAKERS FIRE PUMP JOCKEY PUMP AUTOMATIC TRANSFER SWITCH KWHR METER ABBREVIATIONS, ELECTRICAL INTERLOCK MECHANICAL INTERLOCK MV INCOMING SERVI MAIN CIRCUTT BREAKER — ENCLOSED CIRCUIT BREAKER MEDIUM VOLTAGE NOTES FULL LOAD CAPACITY OF THE TWO ELECTRIC-DRIVEN FIRE PUMP SHALL BE CONSIDERED IN SIZING THE FEEDER WIRE BATTERY CHARGER FOR DIESEL- DRIVEN SHALL HAVE A DEDICATED POWER SUPPLY/CIRCUIT W/ INSTANTANEOUS PROTECTION | W/_LONG TIME, SHORT-TIME, INSTANTANEOUS é& GROUND FAULT PROTECTION SYNCHRONIZING SWITCHGEAR ¢ TRANSFORMER ae obg GENERATOR SET(S) AIS—2 BACK-UP FIRE PUMP FIRE PUMP a am OO MAIN FIRE PUMP @ L BACK-UP FIRE PUNP (ELECTRIC DRIVEN) OPTION 1 - Fire Pump Feeder System with Electric Driven Back Up Single Line Diagram (Secondary Metering) SYNCHRONIZING SWITCHGEAR TRANSFORMER agile ] LOW VOLTAGE! GENERATOR SET(S) FIRE PUMP ATS |” Xx BACK-UP FIRE PUMP (DIESEL DRIVEN) MAIN FIRE PUMP OPTION 2 - Fire Pump Feeder System with Diesel Driven Back Up Single Line Diagram (Secondary Metering) Electro-Mechanical and Commissioning Division Standards and Guidelines Section: Design Standards Subject: Back-up Fire Pump System for High Rise Buildings Bulletin No. EMCD-01-001-2016 Revision Code: 4 |Page 7 of 7 Effectivity: 10 April 2018 Prepared By: ae

You might also like