Overview P-003
Accessories
1 Body
1
7 Rear connection plate (optional)
10 Plug-in basement(optional)
2
11 Handheld test module(optional)
5
NXM series moulded case circuit breaker Moulded Case Circuit Breakers P- 002
9
8
11
10
P- 003 Moulded Case Circuit Breakers Overview
The moulded case circuit breaker will provide protection for the circuit and equipment in case
of overload, short circuit and under voltage condition occurred in the power distribution circuit.
Besides, it can also provide protection of overload, short circuit and under voltage for the non-
frequent start of motor
▪ Frame size:
NXM-250S/4300A
NXMS series moulded case circuit breaker: 63A, 125A, 160A, 250A, 400A, 630A, 800A,
1000A, 1250A, 1600A
NXM series moulded case circuit breaker
▪ Rated operational voltage: Ue : 220V/230V/240V, 380V/400V/415V, 500V , 690V
▪ Breaking capacity code: E, S, F, H
▪ Number of poles: 2P, 3P, 4P
▪ Release type:thermal magnetic fixed type; magnetic fixed type; electronic type.
▪ Installation method: Fixed type; plug-in type
NXMS-250H/3300
Nameplate interpretation
NXM-250S/4300A
1
1 Product type: Frame size; breaking capacity; poles number
In:250A
2
Ui:800V 2 In: Rated operational current
3 6
50/60Hz
4 7 3 Ui: Rated insulation voltage
5 Ii:10In 8
4 Frequency of A.C.
9
ZHEJIANG CHINT ELECTRICS CO.,LTD
5 Ii: 10In Multiple of current of transient behavior
6 Uimp: Rated impulsive withstand voltage
7 Cat A: Utilization category of breaker
8 +40℃ : Ambient temperature
9 Electrical symbol for circuit breaker with isolating function
Ue Icu/Ics
10 (V) (kA)
12 10 Ue: Rated operational voltage
220/230/240 50/30
380/400/415 36/20
11 The product is in conformity with standard IEC/EN 60947.2
IT 12 Icu/Ics: Ultimate short circuit breaking capacity/Service short circuit breaking capacity
IEC/EN 60947-2
M
3 50/60Hz Cat A 6
5 Frequency of A.C.
4 Ii:10In 7
5
6 Uimp: Rated impulsive withstand voltage
IEC/EN 60947-2 IT
Electronic release
Run ....0.9Ir
1.2Ir
PTU
160 180 4 5 6 8 t
0.5 1 150 60 80 3 4 10
200 6 tr
140 225 2 8 3 12
OFF OFF 12 100 1.5 OFF 2 OFF
125 250 0.3s
N×(In) Ir(A) tr(S) Isd (Ir ) Ii (xIn)
r r I
1 2 3 4 5 6 7
1 PTU interface
2 Neutral pole protection current setting, with 2 steps of current that is
adjustable and can be turned off (OFF)
3 Rated current setting with 8 steps
4 Long-time-delay (s) setting with 4 steps
5 Short-time-delay current Isd setting with 7 steps that is adjustable and can be
turned off (OFF)
6 Instantaneous action current Ii setting with 7 steps and that can be turned off (OFF)
Nameplate interpretation
Leakage
Test
14
button
IEC/EN 60947-2
M
▪ Frame size: 63A, 125A, 160A, 250A, 320A, 400A, 630A,
▪ Rated operational voltage: Ue(VAC): 380/400/415/690
▪ Number of poles: 3P, 4P
▪ Installation method: fixed type; plug-in type
NXHM-250
NXНM-250
1 Product type: Frame size; poles number
1 Iе:250A 2 Ie: Rated operational current
2 Ui:800V Uimp:8kV
3 Icm 5880A 7 3 Ui: Rated insulation voltage
4 4000A/1S
Icw
5
4 Icm: Rated short-time making capacity
50/60Hz
6
8
5 Icw: Rated short-time withstand current
ZHEJIANG CHINT ELECTRICS CO.,LTD
6 Frequency of A.C.
7 Uimp: Rated impulsive withstand voltage
8 Disconnector Function as per IEC/EN
9 Ue: Rated operational voltage
10 The product is in conformity with standard IEC/EN 60947.3
Ue 415/690V
9 Using category
AC-21A AC-21B
AC-22A AC-22B
IEC/EN 60947-3 IT
10 Arc isolation board must be installed
Nameplate of NXHM
disconnector switch
P- 007 Moulded Case Circuit Breakers Overview
▪ Product standard
IEC 60947-1(General rules)
IEC 60947-2(Breaker)
IEC 60947-3(switch, disconnector)
IEC 60947-4(motor, drive)
The product has passed the environmental test of dry cold, dry heat, and wet heat and the like. It can operate reliably under extreme environmental
conditions.
Overview Moulded Case Circuit Breakers P- 008
Environment temperature
It must calculate according to the temperature compensation coefficient table provided in the sample in the event the temperature is lower than -5℃ or
higher than 40℃ .
The installation altitude of normal operation is 2000 m and below. In The product can operate reliably in pollution degree III environment
case of higher than 2000m, it must consider the decrease of dielectric defined in IEC 60947-1and 60664-1(industrial environment).
strength and colder air. The amendment action shall be implemented
according to the altitude derating factor table provided in the sample.
Protection grade
Code of release
Product Breaking capacity Operation way Number of
Frame size code type and inner
code code2) code poles code
accessories3)
H
Product
Product
selection
selection Moulded Case Circuit Breakers P- 010
2 A 160 Other
M
Usage Product with N pole Rated Code of installation
code the code is selectable current1) or secondary voltage
Table 1
170 180 200 225 250 280 315 320 400 500 600 630 700 800 900 1000 1250 1600
Table 2
NXMS 160 - H P / 3
1000A S: 50kA
H: 70kA
1250A
S: 50kA
1600A H: 70kA
Rated current(A) 32 63 125 160 250 400 630 800 1000 1250 1600
160
250
400
Frame size(A) 630
1000
1250
1600
Number of poles 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P
S
Code of breaking
F
capacity
H
Product selection Moulded Case Circuit Breakers P- 012
Rated
M
Releasing method and code Communication Code of installation or
Usage code secondary voltage
of inner accessories module code current1)
Comparison table of frame size and residual current value and code
A Y J A 100 Other
Note:1) See table 5 for rated current included in each frame size
2)
See table 6 for corresponding poles,breaking capacity.
3)
See page 23-24 for release type and inner accessories.
4)
As for the un-adjustable type, mark the residual current value directly; for the adjustable type, mark the code.
5)
See table 8 for opening time.
Table 5
Table 6
400 630
3P 3PN/4P 3PN/4P 3P 3PN/4P
Table 7
NXHM - 63 P / 3 00
250A
400A
630A
Table 8
400 630
≤ 0.1 ≤ 0.1
0.3/0.4/0.5 0.3/0.4/0.5
M
P- 017 Moulded Case Circuit Breakers Code of inner accessories
Handle
NXM-63E/S NXM-63F/H
Accessories code
NXM-125E/S NXM-125F/H
Accessories name
Thermal magnetic
Only magnetic 3P 4P 3P 4P
release
220 320
Auxiliary contact (2NO2NC)
240 340
Shunt release, auxiliary contact (2NO2NC)
270 370
Under voltage release, auxiliary contact (2NO2NC)
NXM-160E/S NXM-160F/H
M
3P 4P 3P 4P
□ □ □ □
● ● ● ●
■ ■ ■ ■
■ ■ ■ ■
● ● ● ●
■ ● ■ ● ■ ● ■ ●
■ ● ■ ● ■ ● ■ ●
● ● ● ● ● ● ● ●
■ ■ ■ ■ ■ ■ ■ ■
● ■ ● ■ ● ■ ● ■
● ■ ● ■ ● ■ ● ■
■ ● ■ ● ■ ● ■ ●
■ ■ ■ ■
■ ■ ■ ■
■ ■ ■ ■
■ ■ ■ ■
● ■ ● ■ ● ■ ● ■
■ ● ■ ● ■ ● ■ ●
■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■
■ ● ■ ● ■ ● ■ ●
■ ■ ■ ■
P- 019 Moulded Case Circuit Breakers Code of inner accessories
220 320
Auxiliary contact (2NO2NC) ■ ■ ■ ■
270 370
Under voltage release, auxiliary contact (2NO2NC) ● ■ ● ■ ● ■ ● ■
■ ■ ■ ■
Auxiliary contact (1NO1NC), alarm contact ■ ■ ■ ■
228 328
■ ■ ■ ■
Auxiliary contact (2NO2NC), alarm contact ■ ■ ■ ■
NXM-400E/S/F/H NXM-800S/F/H
NXM-1250S/H NXM-1600S/H
NXM-630E/S/F/H NXM-1000S/H
3P 4P 3P 4P 3P 4P 3P 4P
■ ■ ■ ■ ■ ■ ■ ■
M
● ● ● ● ● ● ● ●
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■
● ● ● ● ● ● ● ●
■ ● ■ ● ■ ● ■ ● ● ● ● ●
■ ■ ■ ■
■ ● ■ ● ■ ● ■ ● ● ● ● ●
■ ■ ■ ■
● ● ● ● ●
●
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■
■ ● ■ ● ● ■ ● ■ ● ● ● ●
■ ■ ■ ■
● ■ ● ■ ● ■ ● ■ ● ● ● ●
■ ■ ■ ■
■ ● ■ ● ■ ● ■ ● ● ■ ● ■ ● ■ ● ■
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■
■ ● ■ ● ● ■ ● ■ ● ■ ● ■ ● ■ ● ■
■ ■ ■ ■ ● ● ● ●
■ ● ■ ● ■ ● ■ ● ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■
■ ● ■ ● ■ ■ ■ ■ ■ ■ ■ ■
■ ● ■ ● ● ■ ● ■ ● ● ● ●
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
P- 021 Moulded Case Circuit Breakers Code of inner accessories
NXMS series electronic moulded case circuit breaker, code of inner accessories
220 320
Auxiliary contact (2NO2NC) ■ ■ ■ ■
240 340
Shunt release, auxiliary contact (2NO2NC) ■ ● ■ ● ■ ● ■ ●
270 370
Under voltage release, auxiliary contact (2NO2NC) ● ■ ● ■ ● ■ ● ■
■ ■ ■ ■
Auxiliary contact (1NO1NC), alarm contact ■ ■ ■ ■
228 328
■ ■ ■ ■
Auxiliary contact (2NO2NC), alarm contact ■ ■ ■ ■
NXMS-400S/F/H
NXMS-1000S/H NXMS-1250S/H NXMS-1600S/H
NXMS-630S/F/H
3P 4P 3P 4P 3P 4P 3P 4P
■ ■ ■ ■ ■ ■ ■ ■
M
● ● ● ● ● ● ● ●
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■
● ● ● ● ● ● ● ●
■ ● ■ ● ■ ● ■ ● ● ● ● ●
■ ■ ■ ■
■ ● ■ ● ■ ● ■ ● ● ● ● ●
■ ■ ■ ■
● ● ● ● ●
●
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■
■ ● ■ ● ● ■ ● ■ ● ● ● ●
■ ■ ■ ■
■ ■ ● ● ● ●
■ ● ■ ● ● ● ■ ■ ■ ■
■ ● ■ ● ■ ● ■ ● ● ■ ● ■ ● ■ ● ■
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■
■ ● ■ ● ● ■ ● ■ ● ■ ● ■ ● ■ ● ■
■ ■ ■ ■ ● ● ● ●
■ ● ■ ● ■ ● ■ ● ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ● ● ● ●
■ ● ■ ● ● ■ ● ■ ■ ■ ■ ■ ■ ■ ■ ■
P- 023 Moulded Case Circuit Breakers Code of inner accessories
220 320
Auxiliary contact (2NO2NC) ■ ■
270 370
Under voltage release, auxiliary contact (2NO2NC) ● ■
■ ■ ■ ■
Auxiliary contact (1NO1NC), alarm contact ■ ■ ■ ■
228 328
■
Auxiliary contact (2NO2NC), alarm contact ■
NXMLE-400S/F/H
NXMLE-250S/F/H
NXMLE-630S/F/H
3P 3PN/4P 3P 3PN/4P
■ ■ ■ ■
M
● ● ●
■ ■ ■ ■
■ ■ ■ ■
● ● ●
● ■ ■ ●
● ■ ■ ●
■ ■
● ■ ■ ●
● ■ ■ ●
■ ●
■ ■ ■ ■
■ ■ ■ ■
■ ■ ■
■ ■ ■
■ ●
■
■ ●
■
■ ■
■
■ ●
P- 025 Moulded Case Circuit Breakers Code of inner accessories
NXHM-63
NXHM-160
NXHM-125
Accessories name Accessories code
3P 4P 3P 4P
No inner accessories 00
Alarm contact 08 ■ ■ ■ ■
Shunt release 10 ● ● ● ●
20
Auxiliary contact (2NO2NC) ■ ■
70
Under voltage release, auxiliary contact (2NO2NC) ● ■ ● ■
■ ■ ■ ■
Auxiliary contact (1NO1NC), alarm contact ■ ■ ■ ■
28
■ ■
Auxiliary contact (2NO2NC), alarm contact ■ ■
NXHM-250 NXHM-400
NXHM-320 NXHM-630
3P 4P 3P 4P
■ ■ ■ ■
M
● ● ● ●
■ ■ ■ ■
■ ■ ■ ■
● ● ● ●
● ■ ● ■ ■ ● ■ ●
● ■ ● ■ ■ ● ■ ●
● ● ● ● ●
●
■ ■ ■ ■
● ■ ● ■ ■ ● ■ ●
● ■ ● ■ ■ ● ■ ●
● ■ ● ■ ■ ● ■ ●
■ ■ ■ ■
■ ■ ■ ■
■ ■ ■ ■
■ ■ ■ ■
● ■ ● ■ ■ ● ■ ●
■ ■ ■ ■
● ■ ● ■ ■ ● ■ ●
■ ■
■ ■ ■ ■
● ■ ● ■ ■ ● ■ ●
■ ■ ■ ■
P- 027 Moulded Case Circuit Breakers Functions and features
Technical Parameters
10,16,20,25,30,32,
10,16,20,25,30, 32,40,50,60,63,70,75,80,
Rated current In (A), 40℃ , 55℃ 40,50,60,63,70,75, 160,170,180,200,225,250
32,40,50,60,63 100,125,140,150,160
80,100,125
AC690v 4 5 5 6 4 5 5 6 - - - - - 8 - -
AC220/230/240V 18 18 50 50 18 18 50 50 30 30 50 50 30 30 50 50
Rated service short circuit
breaking capacity Ics (kA) AC380/400/415V 15 15 36 36 15 15 36 36 20 20 36 36 20 20 36 36
AC500V - - 15 15 - - 15 15 - - - - - - - -
AC690v 4 4 5 5 4 4 5 5 - - - - - 5 - -
250,280,300,315,320,350,400 400,450,500,600,630 630, 700, 800 800,900,1000 1000, 1250 1000, 1250,1600 M
1000 1000 1000 1000 1000 1000
12 12 12 12 12 12
220/230/240, 380/400/415 220/230/240, 380/400/415 220/230/240, 380/400/415 220/230/240, 380/400/415 220/230/240, 380/400/415 220/230/240, 380/400/415
E S F H E S F H S F H S H S H S H
- - - - - - - - - - - - - - - - -
A A A A A A
- - - -
- - - -
- - - - - - - - - - -
- - - -
140/185 140/185 182/240 210/280 210/280 210/280
257 257 270 280 370 370
108.5/108.5/108.5/108.5 108.5/108.5/108.5/108.5 114/114/114 118/118 153/153 1600A:158/158
<1600A:153/153
P- 029 Moulded Case Circuit Breakers Functions and features
Technical Parameters
3P
Number of poles
4P
AC220/230/240 50 75 50 75 75 75 100
Rated ultimate short circuit
AC380/400/415V 36 50 36 50 50 50 70
breaking capacity Icu(kA)
AC690V 10 10 10 10 10 10 15
AC220/230/240 50 50 50 50 50 75 75
Rated service short circuit
AC380/400/415V 36 36 36 36 36 50 50
breaking capacity Ics(kA)
AC690V 5 5 5 5 7.5 75 75
Utilization category A A B
Isolation function
Distribution protection
Electric release (times)
Motor protection
Auxiliary contact
Alarm contact
Shunt release
Communication module
Motor-driven mechanism
Rear connection
Interphase barrier
M
630 1000 1250 1600
12 12 12 12
S F H S H S H S H
50 50 70 50 70 50 70 50 70
10 10 15 15 20 - 30 - 30
50 75 75 50 75 50 75 50 75
36 50 50 36 50 36 50 36 50
8 12 19.2 19.2
B B B B
- - - - - -
- - - -
- - - -
- -
Technical Parameters
10,16,20,25,32,40,50,
Rated operational current In (A), 40℃ 63,80,100,125 32,40,50,80,100,125,140,160
- -
Rated residual non-operating current I Δno(A) 0.5IΔn 0.5IΔn
Non-delay type 5I Δn, maximum breaking time(s) ≤0.04 ≤0.04
Delayed adjustable 2I Δn limit non-actuating time (s)non-adjustable 0.1/0.2/0.3 , optional 0.1/0.2/0.3 , optional
Delayed adjustable 2I Δn maximum breaking time 0.3/0.4/0.5 , optional 0.3/0.4/0.5 , optional
Breaking capacity code S F H S F H
1P+N
2P
3P
Number of poles
3P+N
4P
M
125,160,180,200,
225,250 250,280,315,320,350,400 400,500,630
- - E: -
0.5IΔn 0.5IΔn 0.5IΔn
≤0.04 ≤0.04 ≤0.04
0.1/0.2/0.3 , optional 0.1/0.2/0.3 , optional 0.1/0.2/0.3 , optional
0.3/0.4/0.5 , optional 0.3/0.4/0.5 , optional 0.3/0.4/0.5 , optional
S F H S F H S F H
50
35 25 50 50 36 70 50 36 70
30
18 25 25 25 36 36 25 36 36
IEC/EN 60947-2
A A A
-25℃ ~+70℃
≤100 ≤100 ≤100
20000 10000 10000
40000 20000 20000
10000 8000 8000
Technical Parameters
Alarm contact ■ ■ ■
Shunt release ■ ■ ■
Motor-driven mechanism ■ ■ ■
Rear connection ■ ■ ■
Plug-in ■ ■ -
Extending terminal bonding bar ■ ■ ■
Interphase barrier ■ ■ ■
M
250 400 630 800 1000
1000 1000 1000 1000 1000
8 12 12 12 12
380/400/415/690 400/415/690 400/415/690 400/415/690 400/415/690
3P/4P 3P/4P 3P/4P 3P/4P 3P/4P
4000 5000 7800 10000 12000
IEC/EN 60947-3
AC-21A(B)/AC-22A(B) AC-21A(B)/AC-22A(B) AC-21A(B)/AC-22A(B) AC-21A(B)/AC-22A(B) AC-21A(B)/AC-22A(B)
-35℃ ~+70℃
≤50 ≤100 ≤100 ≤100 ≤100
20000 10000 10000 8000 5000
40000 20000 20000 10000 10000
10000 8000 8000 5000 2500
■ ■ ■ ■ ■
■ ■ ■ ■ ■
■ ■ ■ ■ ■
■ ■ ■ ■ ■
■ ■ ■ ■ ■
■ ■ ■ ■ ■
■ ■ ■ ■ ■
■ ■ ■ ■ ■
■ ■ ■ ■ ■
■ ■ ■ ■ ■
■ ■ ■ ■ ■
Protection Feature
Only magnetic Setting of short circuit Setting value of short circuit protection
Frame size Inm(A) Rated current In(A) current Ii(A) and allowance Release time
release protection current
Overload protection
63A~1000A 10A~1000A Fixed
I2t=constant
1.05In(cold state), 2h non-trip(In > 63A), 1h non-trip(In≤63A) M
1.30In(heat state), 2h trip(In > 63A), 1h trip(In≤63A)
Thermal magnetic Setting of short circuit Setting value of short circuit protection
release Frame size Inm(A) Rated current In(A) protection current current Ii(A) and allowance Release time
Protection Feature
Electronic release Frame size Inm(A) Rated current In(A) Setting of overcurrent protection IR (A) Release feature/time
32 16-18-20-22-25-28-30-32
63 32-36-40-45-50-56-60-63
160
125 63-70-75-80-90-100-110-125
160 80-90-100-110-125-140-150-160
I2t=constant
250 250 125-140-150-160-180-200-225-250 1.05Ir, no action within 2h
Overload long-time-delay
400 400 200-225-250-280-300-315-350-400 1.3Ir, action with 1h
protection
630 630 400-450-480-500-530-560-600-630 2Ir, tr=(12-60-80-100)s, Inm < 400A
M
and allowance
Residual action Three grades and adjustable B/C/D Delay type 2IΔn limit
non-driving time (s) 0.1 0.2 0.3
current protection Non delay: single grade and Adjustable
50/100/200/300/500/1000
non-adjustable Delay type 2IΔn maximum
breaking time(s) 0.3 0.4 0.5
Three grades and adjustable B/C/D/E Adjustable
400/630 AC Type
Delay type: single grade and
50/100/200/300/500/1000
non-adjustable
Protection Feature
I2t=constant
Overload protection All series 10A~800A Fixed 1.05 In(cold state), 2h non-release(In > 63A),1h non-release(In≤63A)
1.30 In(heat state), 2h release(In > 63A),1h release(In≤63A)
Three grades and adjustable B/C/D Delay type 2IΔn limit non-driving
protection time (s) 0.1 0.2 0.3
Non delay: single grade and Adjustable
50/100/200/300/500/1000
non-adjustable Delay type 2IΔn maximum
breaking time(s) 0.3 0.4 0.5
Adjustable
Three grades and adjustable B/C/D/E
400/630 AC type
Delay type: single grade and
50/100/200/300/500/1000
non-adjustable
Only magnetic Setting of short circuit Setting value of short circuit protection
Frame size I(A)nm Rated current I(A)n Release time
M
release protection current current I(A) and allowancei
Short circuit
250 125~250 Fixed 12In , ±20% Instantaneous action
protection
Setting of neutral pole Setting value of neutral pole overload protection current(A)
Frame size Inm(A) Rated current In(A)
protection current Setting value neutral pole short circuit protection current(A)
Protection Feature
I2t=constant
1.0In(cold state), > 2h non release
1.2In(hot state), ≤2h release
Overload protection 125~800 25~630A Fixed
7.2In(hot state),4s≤T≤10s, 10A≤In≤225A
6s≤T≤20s, 225A < In≤630A(including 800A frame 630A)
Trip class: 10(≤160A), 20(160A < In≤630 A)
Thermal magnetic Setting of short circuit Setting value of short circuit protection
Frame size I (A)nm Rated current I (A)n Release time
release protection current current I(A) and allowancei
Short circuit protection 250 125~250 Fixed 12In ,±20% Instantaneous action
Setting of neutral pole Setting value of neutral pole overload protection current(A)
Frame size I (A)nm Rated current I (A) n
protection current Setting value neutral pole short circuit protection current(A)
160
Electronic release Frame size Inm (A) Frame size Inm (A) Setting of overcurrent protection Ir (A) Release feature/time
M
32 16-18-20-22-25-28-30-32
63 32-36-40-45-50-56-60-63
I2t=constant
100 63-70-75-80-85-90-95-100 1.05Ir No actuation within 2h
160
125 63-70-75-80-90-100-110-125 1.2Ir Actuation within 1h
Overload long-time- delay Release class 10A 10 20 30
160 80-90-100-110-125-140-150-160
protection 1.5Ir 53 107 178 267
200 100-125-140-150-160-170-180-200
2Ir 30 60 100 150
250 250 125-140-150-160-180-200-225-250 7.2Ir 2.3 4.6 7.7 11.6
Delay time accuracy: ±20%
400 400 200-225-250-280-300-315-350-400
Protection Feature
Only magnetic Setting of short circuit Setting value of short circuit protection
Frame size I (A)nm Rated current I (A)n Release time
release protection current current I (A) and allowancei
125 10~125 Fixed 12In ,±20%
160 125,160 Fixed 12In ,±20%
Short circuit
250 160~250 Fixed 12In ,±20% Instantaneous action
protection
400 315~400 Fixed 12In ,±20%
630 400~630 Fixed 12In ,±20%
I2t=constant
1.0In (cold state),>2h non release
M
release circuit protection current
current Ii (A) and allowance
Inner Accessories
AX auxiliary contact
Function: Remote indication of "ON" , ''OFF'' position of the breaker, connect to thecontrol circuit of
breaker.
Model description
AX- □ □ □ □
Installation site code : left side installation (code L) and right side
installation (code R)
FX12
Closing ON FX11
FX14
Electrical characteristics
AC-15 DC-13
Operational voltage (V)
AC380/400/415 DC110 DC220/250
63~320 0.26 0.14 0.14
Operational
400~1000 0.4 0.2 0.2
current (A)
1250,1600 0.47 0.27 0.27
Wiring diagram
Auxiliary contact can be wired with indicator light.
The operator can know the location of switch ‘’ON‘’or‘’OFF‘’ without open the power distribution
cabinet via indicator light.
Power supply
F11 QF
H
F14 loop of
switching on
Loop of
switching off
F12 L12
Functions and features Moulded Case Circuit Breakers P- 046
Inner Accessories
AL alarm contact
Function: It is mainly used to provide signal in case of failure of circuit breaker or free trip.
Reasons for alarm contact to send failure indication signal:
M
■ Overload or short circuit trip
■ Under voltage trip
■ Residual current operated trip
■ Manual free trip
Model description
AL-M6 alarm contact
AX- □ □ □ □
Installation site code : left side installation (code L) and right side
installation (code R)
For instance: the left alarm contact code of 63/125 frame is: AL-M1L
Table1 frame size code
B12
TRIP B11
B14
Electrical characteristics
AC-15 DC-13
Operational voltage (V)
AC380/400/415 DC110 DC220/250
63~320 0.26 0.14 0.14
Operational
400~1000 0.4 0.2 0.2
current (A)
1250,1600 0.47 0.27 0.27
Wiring diagram
Alarm contact can be connected with indicator light, buzzer and the like, and thus the operator can be
timely informed in case of release of circuit breaker.
Power supply
B11 QF
B14
B12
P- 047 Moulded Case Circuit Breakers Functions and features
Inner Accessories
UVT under voltage release
Function: To switch off the circuit breaker in case of under voltage of power supply so as to protect the
electric equipment.
■ The under voltage release shall switch off the circuit breaker reliably when the power supply voltage
decreases (or even decrease slowly) to 70%-35% of rated control power supply voltage.
■ It shall ensure the closing of breaker when the power supply voltage equals to or is more than 85% of
UV T-M4 under voltage release
rated control power supply voltage of under voltage release.
■ The under voltage release shall be able to prevent closing of circuit breaker when the supply voltage is
less than 35% of rated control supply voltage of under voltage release.
Model description
UVT- □ □ □ □ □
Applicable product: Thermal-magnetic (omit),residual current
type(LE): Electronic(E)
Electricalcharacteristics
63/125 3.1 4
160 3.2 3.9
250/320 3.3 4.3
400/630 2.5 3.6
800 1.6 2
1000 1.6 2
1600 1.6 2
Operating characteristics
Wiring diagram
M
X Uc2 Uc P1 P2
power supply
P- 049 Moulded Case Circuit Breakers Functions and features
Inner Accessories
SHT shunt release
Function: Shunt release is an accessory for remote control.
The shunt release shall be able to make circuit breaker operating reliably when the power voltage
equals to any voltage within the range of 70%~110% of rated control power voltage.
Model description
SHT-M2 shunt release
SHT- □ □ □ □ □
Installation site code : left side installation (code L) and right side
installation (code R)
For example: left shunt release code of 63/125 housing 400V: SHT-M1A2L
Table1 frame size code
Electrical characteristics
Operating characteristics
Wiring diagram
Shunt release M
K
C1 C2
SB
P- 051 Moulded Case Circuit Breakers Functions and features
External Accessories
MD motor-driven mechanism
Function: it is applicable for switching circuit breaker on and off and retrip remotely, as well as
automation application.
Model description
MD - □ □ □ □
For example: motor driven code of 63/125 frame moulded case circuit breaker
400V: MD-M1A2
Wiring diagram
X P1 P2 S1 S2 S4
SB1(Making)
SB2(Breaking)
External power source
Motor-driven mechanism
Installation sketch of electric operational mechanism
63A 400A
Frame size 160A 250A 800A 1000A 1250/1600A
125A 630A
External Accessories
ERH manual operational mechanism
Function: It realizes switching on, off and restriping via rotary handle according to human body
mechanics with unique design and transmission device.
Model description
ERH - □ □
For example: manual operational mechanism code of 63/125 frame residual current
operating: ERH-M1LE
Table1 frame size code
Φ78
H
18
Scheme diagram of assembly of
manual operational mechanism
with the body frame current:63, 125, 160, 250,
400, 630, 800, 1000
10
53
Φ36
30.5
45
D
°
77
Min=150mm 2- 5.5Φ
63A 400A
Frame size 160A 250A 800A 1000A 1250/1600A
125A 630A
PIA- □ □
For example: plug-in basement code of 160 frame three-pole circuit breaker: PIA-M2 3
Code M1 M2 M3 M4 M5 M6 M7
P- 055 Moulded Case Circuit Breakers Functions and features
External Accessories
FCP front connection plate
Function: It grants the breaker a flexible line connecting way. The phase spacing can increase via
accessories so as to increase the electrical space between the adjacent phases of line terminal of input
and output of breaker, and thus increase the safety among the lines.
FCP-M4
Model description
FCP - □ □
Pole number code of adaptive product: two poles (code 2), three poles
(code 3), four poles (code 4)
For example: 63/125 frame three-pole circuit front connection place code: FCP-M13
Table1 frame size code
Assembly scheme diagram of
front connection plate and the Frame size 63/125 160 250 400/630 800 1000 1250/1600
body
Code M1 M2 M3 M4 M5 M6 M7
Model description
RCP-M3 FCP - □ □
Pole number code of adaptive product: two poles (code 2), three poles
(code 3), four poles (code 4)
For example: 63/125 frame three-pole circuit breaker with rear connection plate
code: RCP-M 13
Altitude (m)
1In
3000
0.94In
4000
0.88In
5000
0.85In
M
Maximum operationnal voltage (V) 690 600 500 440
500 450
630
630 520
700 650
800
800 720
900 850
1000
1000 920
Maximum operation
69
60
50
44
2000 3000 4000 5000 Altitude (m)
Long-time delay
Frame size Rated current -25℃ -20℃ -15℃ -10℃ -5℃ -0℃ Rated current 40℃ 45℃ 50℃ 55℃ 60℃ 65℃ 70℃
current setting
32A、63A、 Ir<0.65In 1.2Ir 1.2Ir 1.1Ir 1.1Ir 1.05Ir 1.05Ir 32A、63A、125A 1.0In 0.9In 0.85In 0.8In 0.8In
NXMS-160
125A、160A Ir>0.65In 1.0Ir 160A 1.0In 0.9In 0.85In 0.8In 0.7In 0.7In
NXMS-1000 800A、1000A ALL 1.0Ir 800A 1.0In 0.9In 0.85In 0.8In 0.8In
Functions and features Moulded Case Circuit Breakers P- 058
The above reference section is the reference value under 40 degrees operating environmental temperature.
The recommended value of tightening torque of different housing current connecting cable/copper bar is as follows:
Rated current (A) 63A/125A 160A 250A/320A 400A/630A 800A 1000A 1250A/1600A
Torque (N m)1) 3/64) 10 12 30 30 40 30
Torque (N m)2) 3/64) 10 12 30 30 40 30
Torque (N m)3) 3/64) 10 12 30 30 40 30
1)
Tighten the torque of busbar (or extension busbar/connection lug) in case of connecting with the body directly.
2)
Tighten the torque of connecting terminal behind the stationary breaker/tighten the torque of connecting terminal of plug in breaker.
3)
Tighten the torque of extension busbar of terminal on the plug-in pedestal.
4)
Value of torque is 3 for 10A~63A of frame current 63 and 125A breaker, value of torque is 6 for 70A~125A for frame current 125A breaker.
Dimensions and installation Moulded Case Circuit Breakers P- 060
75 D2
50 50 D1
25 25 25 S:21 D
H:31
49
49
2P 3P 4P
49
1 3 5LINE 1 3 5 N
1 3LINE LINE
27.5
X X X X
ON
ON
ON
121
121
121
135
55.5
55.5
55.5
27.5
27.5
OFF
OFF
OFF
LOAD 6LOAD LOAD
2 4 2 4 2 4 6 N
Y Y Y
18 18 18
26 23
26
Z
56 78 103
NXMLE-125S/F/H
75 D2
50 D1
50 25
25 25 21 D
49
49
1PN/2P 3PN/4P
49
3P
1 N 1 3 5 1 3 5 N
LINE LINE LINE
38
38
38
ON
ON
ON
55.5
55.5
55.5
X X X X
150
142
142
142
OFF
OFF
OFF
1
LOAD
N 2 4 LOAD
6 2 4 6 N
LOAD
Y Y Y
18 18 18
23 23 23
78 Z
56 103
50
25 25
12.5 12.5 12.5
1PN/2P 3P 3 4PN/P
(H1/2)
(H1/2)
X X X
H1
H1
H1
Y Y Y
Specification H1
D1 D2 D Remark
and model 1PN/2P 3P 3PN/4P
NXM-63E/S、125E/S 71 90 7 117 117 117 2P/3P/4P
NXM-63F/H、125F/H 81 100 7 - 117 117 3P/4P
NXMLE-125S 71 90 7 138 138 138 1PN/2P/3P/3PN/4P
NXMLE-125F/H 81 100 7 - 138 138 3P/3PN/4P
NXHM-63、125 71 90 7 - 117 117 3P/4P
P- 061 Moulded Case Circuit Breakers Dimensions and installation
100.5
100.5
67.5
67.5 3PN/4P
3P
H3
H2
Y
50
Y
50
50
M8
M8
75
25
50 50
25
12.5 12.5
3P 3PN/4P
41.7
X X
H3
H3
H4
H4
4-Φ4.5 6-Φ4.5
6 -Φ11.8 8 -Φ11.8
Y Y
50.5
44.5 106(3PN/4P)
29.5 80(3P)
8.5 40
3PN/4P
3PN/4P
M5
25
X 50 25
X
H7
H8
H6
H5
(H5)
H10
H9
4-Φ5.5
M6
2
NXM-63, 125
NXHM-63, 125 NXMLE-125
25 25 25
1PN/2P 3P 3PN/4P
M
X X X X X
57.5
57.5
D3 ≤2 D3 ≤2 57.5
Y Y Y
Z Z
NXM-63、125
NXHM-63、125 NXMLE-125
58 80 105
16.5 40 40 D
1PN/2P 3P 3PN/4P
X X X X X
H11
H11
H11
≤2 ≤2
D4 D4 Y Y Y
Z Z
Specification H11
D3 D4 Remark
and model 1PN/2P 3P 3PN/4P
NXM-63E/S、125E/S 71.5 64.5 88 88 88 2P/3P/4P
NXM-63F/H、125F/H 81.5 74.5 - 88 88 3P/4P
NXMLE-125S 71 64 110 110 110 1PN/2P/3P/3PN/4P
NXMLE-125F/H 81 74 - 110 110 3P/3PN/4P
NXHM-63、125 71 64 - 87.5 87.5 3P/4P
NXM-160E/S/F/H, NXHM-160
90 D5
60 60 D6
30
30 30 24.5 D
50
50
50
2P 3P 4P
1 N 1 3 5 1 3 5 N
LINE LINE LINE
24.5
24.5
24.5
X X X X
ON
ON
ON
135
135
135
51.7
51.7
OFF
OFF
OFF
Y Y Y
17 17 17
32 32 29
Z
63 90 120
P- 063 Moulded Case Circuit Breakers Dimensions and installation
NXMS-160F/H
90 D5
60 60 D6
30 30 24.5 D
50
50
3P 4P
1 3 5 1 3 5 N
LINE LINE
24.5
24.5
X X X
45.5
ON
ON
135
155
135
45.5
OFF
OFF
LOAD LOAD
6 N
2 4 6 2 4
Y Y
17 17
29 29
29
Z
120 120
NXMLE-160S/F/H
90 D5
60 30 30 D6
30 60 24.5 D
50
50
50
1PN/2P 3P 3PN/4P
1 N 1 3 5
LINE LINE
29
X X X X
ON
ON
51.7
28.5
51.7
51.7
160
140
140
27
140
OFF
OFF
LOAD LOAD
2
N
2 4 6
Y Y Y
17 17 17
29 29 29
Z
63 90 120 120
60
30 30
15 15 15
1PN/2P R 3P R 3PN/4P R
6
6
X X X
H12
H12
H12
Y Y Y
96.5
63.5
96.5
3PN/4P
M
63.5
3P
60
Y Y X
H13
H14
60
60
M8
M8
90
60
60 30
30 15 15
3P 3PN/4P
30
X X
H15
H14
H15
H14
R 6-Φ11 R 8-Φ11
6
6
4.5 Y 4.5 Y
Specification and model H13 H14 H15 Remark
NXM-160E/S/F/H 155 135 130.5 3P/4P
NXMLE-160F/H 155 135 130.5 3P/4P
NXMLE-160S/F/H 160 140 135.5 3P/3PN/4P
NXHM-160 155 135 130.5 3P/4P
135
124(3PN/4P)
38 94(3P)
3P/4P 3PN 13 3P/3PN/4P 46
60 30
X
(H16)
H16
H18
X
H20
H21
M5
6- 8
M10
4
Y
Specification H16 H18 H20 H21 Remark
and model
NXM-160E/S/F/H 72 135 106 167 3P/4P
NXMLE-160F/H 72 135 106 167 3P/4P
NXMLE-160S/F/H 77 140 111 172 3P/3PN/4P
NXHM-160 72 135 106 167 3P/4P
P- 065 Moulded Case Circuit Breakers Dimensions and installation
32 32 32
1PN/2P 3P 3PN/4P
X X X X
H22
H22
H22
D7
Y Y Y
≤2
65 92 122
17.5 46
1PN/2P 3P 3PN/4P
X X X X
H23
H23
H23
D8
Y Y Y
≤2
NXM-250E/S/F/H, NXHM-250
105
70 70
35 D10
35 35
D9
101.5
101.5
101.5
2P 3P 4P 25 D
1 3 1 3 5 1 3 5 N
LINE LINE
NXM-320
30.5
30.5
33
x x x x
ON
ON
ON
145
145
145
56
165
56
56
OFF
OFF
OFF
LOAD LOAD
4 2 4 6 2 4 6 N
2
D9”
Y Y Y
23.5 23.5 23.5
29 29 29 Z
78 105 140
NXM series moulded case circuit breaker Moulded Case Circuit Breakers P- 066
NXMS-250F/H
105
70 70
D10
35 35
D9
101.5
101.5
3P 24.5 D
M
4P
1 3 5 1 3 5 N
LINE LINE
30.5
30.5
x x x
51.5
51.5
ON
ON
145
145
165
OFF
OFF
LOAD LOAD
2 4 6 2 4 6 N
D9 ’’
Y Y
23.5 23.5
Z
29 29
105 140
NXMLE-250S/F/H
105
70 70
D10
35 35 35
D9
101.5
101.5
101.5
1PN/2P 3P 3PN/4P 25 D
1 N 1 3 5 1 3 5 N
LINE LINE LINE
33
x
33
ON
ON
ON
x x x
56
33
56
170
150
150
150
OFF
OFF
OFF
56
D9’’
Y Y Y
23.5 23.5 23.5
29 29 29 Z
78 105 140
70
35
17.5 35 17.5
1PN/2P 3P 3PN/4P
x x x
H24
H24
H24
2-Φ4.5 4-Φ4.5
6-Φ4.5
Y Y Y
108.5
108.5 67.5
67.5 3PN/4P
3P
70
H25
X X X
H26
70
M10
70
M10
NXM-250E/S/F/H, NXMS-250F/H, NXMLE-250S/F/H, NXHM-250, 320
105
70
70 35
3P 35 3PN/4P 17.5 17.5
35
X X
H27
H26
H27
H26
4 -Φ4.2
8 -Φ12
6 -Φ12 6 -Φ4.2
Y Y
150
132 140(3PN/4P)
47.5 105(3P)
13
3P/3PN/4P 52.5
3P/3PN/4P
M6
70 35
X 35
H28
H30
X
(H28)
H32
H33
M8
6 -Φ8
5.5
31 31 31
1PN/2P 3P 3PN/4P
X X X M
H34
X
H34
H34
D11 Y Y Y
≤2
Z
80 107 142
23.5 53.5
1PN/2P 3P 3PN/4P
104
X X X
104
104
D12 Y Y Y
≤2
Z Specification and model H34 D11 D12 Remark
NXM-250E/S 58 77.5 62.8 2P/3P/4P
NXM-250F/H 58 102.5 87.8 3P/4P
NXMS-250F/H 53.5 102.5 87.8 3P/4P
NXMLE-250S 58 77.5 62.8 1PN/2P/3P/3PN/4P
NXMLE-250F/H 58 80.5 65.5 3P/3PN/4P
NXHM-250, 320 58 77.5 62.8 3P/4P
132
88 88
161
44 44
108.5
D13 D
104
104
3P 4P
1 3 5 1 3 5 N
LINE LINE
X X X
H34
H35
H34
H35
H36
ON
ON
OFF
OFF
LOAD LOAD
2 4 6 2 4 6 N
D14
Y Y
30 30 Z
54 54
140 185
P- 069 Moulded Case Circuit Breakers NXM series moulded case circuit breaker
NXMS-400S/F/H, 630S/F/H
132
88 88
44 160
44
107.5
105.5
105.5
D13 D
3P 4P
1 3 5 1 3 5 N
LINE LINE
H37
H37
H36
H35
X X X
H34
H34
ON
ON
H35
OFF
OFF
LOAD LOAD
2 4 6 2 4 6 N
D14
Y Y
30 30 Z
54 54
140 185
NXMLE-400S/F/H, 630S/F/H
Front connection, dimension (mm)
132
88 88 160
105.5
105.5
44 44 107.5
D13 D
3P 3PN/4P
1 3 5 1 3 5 N
LINE LINE
H34
H35
X X X
ON
H36
ON
OFF
OFF
LOAD LOAD
2 4 6 2 4 6 N
D14
Y Y
30 30
Z
54 54
140 185
88 Specification
44 22
H34 H35 H36 H37 H38 D13 D14 D Remark
and model
3P 3PN/4P
39.5 37.5 250A-280A
37.5 300A-315A-320A
44
NXM-400E/S/F/H 40.5 38 350A-380A
92 225 257 46 194 11
NXM-630E/S/F/H 39 400A-450A
H38
H38
X X
39 500A-550A
41.5
4-Φ7 6-Φ7 40.5 600A-630A
Y Y 39 38.5 250A-280A
39.5 300A-315A-320A
93
93 58
58 3PN/4P M10
18
3P
M
18
H35
12
H36
88
X X
88
88
12
8
NXM-400E/S/F/H, 630E/S/F/H, NXMS-400E/F/H, 630E/F/H, NXMLE-400S/F/H, 630S/F/H, NXHM-400, 630
132
88 88
44 44
3P 3PN/4P
22
H40
H39
X X
H40
H39
4- 7 6- 7
6 - 33 8 - 33
Y Y
111
88
187
60 3P 142 3PN//4P 71.5
23
3P
88 132
X X
H41
H45
H46
(H41)
X
H42
H43
H44
(H41)
H45
H46
4- 9 4- 9
M8
M12
8.5
Y Y
Specification and model H41 H42 H43 H44 H45 H46 Remark
NXM-400E/S/F/H, 630E/S/F/H 145 171 225 281 168 283 3P/4P
NXMS-400S/F/H, 630S/F/H 145 171 225 281 168 283 3P/4P
NXMLE-400S/F/H 155 181 235 291 178 293 3P/3PN/4P
NXMLE-630S/F/H 155 181 235 291 178 293 3P/3PN/4P
NXHM-400, 630 145 171 225 281 168 283 3P/4P
P- 071 Moulded Case Circuit Breakers NXM series moulded case circuit breaker
52 52
3P 3PN/4P
X X X
H47
H47
107.5
≤2
Y Y
Y
187
152
X X X
152
D15
≤2
Y Y
Z
NXM-800S/F/H, NXHM-800
174
116 116
58 58
165
114
104
104
3P 4P D16 D
1 3 5 1 3 5 N
LINE LINE
45
45
235
X X X
ON
ON
235
270
91
91
OFF
OFF
LOAD LOAD
2 4 6 2 4 6 N
D17
Y
Y
33 33
54 54 Z
182 240
NXM series moulded case circuit breaker Moulded Case Circuit Breakers P- 072
NXM-800S/F/H, NXHM-800
W1 W2
(W1/2) 3PN/4P (W2/2)
3P
M
(W2/4)
X X
H48
H48
4 - 7.5 6 - 7.5
Y Y
NXM-800S/F/H, NXHM-800
W6
W7
W6
3PN/4P
W7
3P
16 M16
16
H61
X X X
H49
H60
H50
H60
20
10
20
P- 073 Moulded Case Circuit Breakers NXM series moulded case circuit breaker
NXM-800S/F/H, NXHM-800
3×W8
2×W8 2×W8
3P W8 3PN/4P W8/2 W8
W8
W8
H51
H50
X X
H51
H50
4- 7 6 - 78 - 40
6 - 7.5
Y Y
NXM-800S/F/H, NXHM-800
Plug-in rear connection, dimension (mm)
110 236(3PN/4P)
92
178(3P)
3P/3PN/4P 60 3P/3PN/4P
23
100 66
M8
H56
H57
X X
(H52)
H54
H55
H52
6- 9
M12
12H53
Specification and model H52 H53 h54 H55 H56 H57 Remark
NXM-800S/F/H 124 170 235 300 168 302 3P/4P
NXHM-800 124 170 235 300 168 302 3P/4P
NXM-800S/F/H, NXHM-800
Cabinet gate hole (small) size (mm)
W3 W3
3P 3PN/4P
X X X
H58
H58
D18 Y Y
≤2
Y
NXM series moulded case circuit breaker Moulded Case Circuit Breakers P- 074
NXM-800S/F/H, NXHM-800
W5
W4 (W4/2)
3P 3PN/4P
X X X
M
H59
H59
D19 ≤2 Y Y
NXM-1000S/H, NXHM-1000
Front connection, dimension (mm)
210
140 140 168
70 70 118
D20 D
106
106
3P 4P
1 3 5 LINE 1 3 5 N LINE
52
X
52
X
280
ON
X
100
243
ON
100
243
OFF
OFF
LOAD
2 4 6 LOAD
2 4 6 N
D21
Y
Y
45 45
Y
60 60
210 280
NXMS-1000S/H
210
140 140 168
70 70 118
D20 D
106
3P 4P
106
1 3 5 LINE
1 3 5 N LINE
52
X
280
52
X
ON
94
243
243
X
ON
100
OFF
OFF
LOAD
2 4 6 LOAD
2 4 6 N
D21
Y Y
45 45
Y
60 60
210 280
P- 075 Moulded Case Circuit Breakers NXM series moulded case circuit breaker
140
3P 70 4P 35
70
X X
243
243
4 - 7.5 6 - 7.5
Y Y
84
4P
84
3P M16
20
16
16
280
243
X X
210
140
70
10
210
140 140
3P 70 4P 70
X X
243
243
4 - 76 - 40 8 - 40
6- 7
Y Y
NXM series moulded case circuit breaker Moulded Case Circuit Breakers P- 076
158.5
143.5 284(4P)
87 214(3P)
27 107
M
3P/4P
3P/4P
90 95
M10
X X
(146)
177
309
243
305
146
181
6 - 12
M12
10
3P 62 4P 62
X X X
H60
H60
117 Y
≤2 Y
282
3P 212 4P 106
X X X
172
172
105 ≤2 Y
NXM-1250S/H,1600S/H
242
92.5
92.5
70 140 158
D22 D
3P 4P
1 3 5 N 1 3 5
LINE LINE
37.8
37.8
X X X
370
ON
ON
120
120
OFF
OFF
LOAD
2 4 6LOAD N 2 4 6
Y Y
53.5 53.5
78 78
Z
210 280
NXMS-1250S/H,1600S/H
242
70 140 158
92.5
92.5
D22 D
3P 4P
1 3 5 N 1 3 5
LINE LINE
40
40
X X X
ON
ON
120
120
370
OFF
OFF
LOAD
2 4 6 N 2 4 6LOAD
Y Y
53.5 53.5
78 78 Z
210 280
NXM-1250S/H,1600S/H,NXMS-1250S/H,1600S/H
Installation size of baseplate (mm)
140
70 70
3P 4P
35
X X
314
314
4 -Φ6 6 -Φ6
Y Y
NXM-1250S/H,1600S/H,NXMS-1250S/H,1600S/H
80 80
M
3P 4P
X
X X
122
127
1)
158.5
≤2
Y Y
Z
282
3P 212 4P 106
X
X X
177
177
2)
149
≤2
Y
Z Y
P- 079 Moulded Case Circuit Breakers NXM series moulded case circuit breaker
10000
160
155
1000 150
145
140
100 135
130
125
10000
160
155
1000 150
145
140
135
100
130
125
120
10 115
Rated current (%)
110
t(s)
105
1 100
95
90
0.1 85
80
75
0.01 70
65
60
0.001 -35 -30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0.1 1 10 100 1000
I/Ir Ambient temperature (°C)
10000
160
155
1000 150
145
140
100 135
130
125
10 120
115
Rated current (%)
t(s) 110
1 105
100
95
90
0.1 85
80
75
0.01 70
65
60
0.001
-35 -30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0.1 1 10 100 1000
I/Ir Ambient temperature (°C)
NXM series moulded case circuit breaker Moulded Case Circuit Breakers P- 080
10000
160
155
1000 150
145
140
100 135
M
130
125
10000
160
155
1000 150
145
140
100 135
130
125
120
10
115
Rated current (%)
t(s) 110
105
1
100
95
90
0.1 85
80
75
0.01 70
65
60
0.001 -35 -30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0.1 1 10 100 1000
I/Ir Ambient temperature (°C)
10000
160
155
1000 150
145
140
100 135
130
125
10 120
115
Rated current (%)
t(s) 110
1 105
100
95
90
0.1
85
80
75
0.01
70
65
60
0.001 -35 -30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0.1 1 10 100 1000
I/Ir Ambient temperature (°C)
P- 081 Moulded Case Circuit Breakers NXM series moulded case circuit breaker
10000
160
155
1000 150
145
140
100 135
130
125
10000
160
155
1000 150
145
140
100 135
130
125
10 120
115
Rated current (%)
t(s) 110
1 105
100
95
90
0.1 85
80
75
0.01 70
65
60
0.001 -35 -30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0.1 1 10 100 1000
I/Ir Ambient temperature (°C)
10000
160
155
1000 150
145
140
100 135
130
125
10 120
115
Rated current (%)
t(s) 110
1 105
100
95
90
0.1 85
80
75
0.01 70
65
60
0.001
-35 -30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0.1 1 10 100 1000
I/Ir Ambient temperature (°C)
NXM series moulded case circuit breaker Moulded Case Circuit Breakers P- 082
10000
160
155
1000 150
145
140
100 135
M
130
125
10000
160
155
1000 150
145
140
100 135
130
125
120
10
115
Rated current (%)
t(s) 110
105
1
100
95
90
0.1 85
80
75
0.01 70
65
60
0.001 -35 -30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0.1 1 10 100 1000
I/Ir Ambient temperature (°C)
10000
160
155
1000 150
145
140
100 135
130
125
10 120
115
Rated current (%)
t(s) 110
1 105
100
95
90
0.1
85
80
75
0.01
70
65
60
0.001 -35 -30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0.1 1 10 100 1000
I/Ir Ambient temperature (°C)
P- 083 Moulded Case Circuit Breakers NXM series moulded case circuit breaker
NXM-250 NXM-250
Tripping curve of power distribution Temperature compensation curve
10000
160
155
150
1000
145
140
135
100
130
125
NXM-250 NXM-250
Tripping curve of motor protection Temperature compensation curve
10000
160
155
150
1000
145
140
135
100
130
125
120
10 115
Rated current (%)
t(s) 110
105
1 100
95
90
0.1 85
80
75
0.01 70
65
60
0.001 -35 -30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0.1 1 10 100 1000
I/Ir Ambient temperature (°C)
NXM-400、630 NXM-400、630
Tripping curve of power distribution Temperature compensation curve
10000
160
155
1000
150
145
140
100 135
130
125
10 120
115
Rated current (%)
t(s) 110
1 105
100
95
90
0.1
85
80
75
0.01 70
65
60
0.001
-35-30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0.1 1 10 100 1000
I/Ir Ambient temperature (°C)
NXM series moulded case circuit breaker Moulded Case Circuit Breakers P- 084
NXM-400、630 NXM-400、630
Tripping curve of motor protection Temperature compensation curve
10000
160
155
1000 150
145
140
100 135
M
130
125
NXM-800(W630) NXM-800(W630)
Tripping curve of power distribution Temperature compensation curve
10000 160
155
150
1000
145
140
135
100 130
125
120
10 115
Rated current (%)
110
t(s)
105
1 100
95
90
0.1 85
80
75
0.01 70
65
60
0.001 -35 -30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 6570
0.1 1 10 100 1000
I/Ir Ambient temperature (°C)
NXM-800(W630) NXM-800(W630)
Tripping curve of motor protection Temperature compensation curve
10000
160
155
1000 150
145
140
100 135
130
125
10 120
115
Rated current (%)
t(s) 110
1 105
100
95
90
0.1
85
80
75
0.01
70
65
60
0.001
-35 -30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 6570
0.1 1 10 100 1000
I/Ir Ambient temperature (°C)
P- 085 Moulded Case Circuit Breakers NXM series moulded case circuit breaker
NXM-1000(W800) NXM-1000(W800)
Tripping curve of power distribution Temperature compensation curve
10000
160
155
1000 150
145
140
100 135
130
125
NXM-1000(W800) NXM-1000(W800)
Tripping curve of motor protection Temperature compensation curve
10000
160
155
1000 150
145
140
135
100
130
125
120
10
115
Rated current (%)
t(s) 110
105
1
100
95
90
0.1
85
80
75
0.01
70
65
60
0.001
-35 -30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
0.1 1 10 100 1000
I/Ir Ambient temperature (°C)
NXM-1250、1600 NXM-1250、1600
Tripping curve of power distribution Temperature compensation curve
10000
160
155
1000 150
145
140
100 135
130
125
10 120
115
Rated current (%)
t(s) 110
1 105
100
95
0.1 90
85
80
0.01 75
70
65
0.001 60
0.1 1 10 100 1000 -35 -30-25-20-15-10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
2 2 2 2
I t[A s] I t[A s]
1.E+08 1.E+08
1.E+07 1.E+07
M
NXM-160(W125) S、
F、
H 160A
NXM-125E、S、F、H 125A
1.E+06 1.E+06
NXM-63、125E、
S、F、H 63A
1.E+05 1.E+05
NXM-63、125E、
S、F、H 10A
1.E+04 1.E+04
1.E+03 1.E+03
1 10 100 1 10 100
I[KA] I[KA]
250 frame let-through current curve 400/630 frame let-through current curve
NXM-250 let-through current curve NXM-400/630 let-through current curve
I2t[A2s] I2t[A2s]
1.E+08 1.E+08
NXM-630E、S、
F、H 630A
NXM-250S、H、R
1.E+07 250A 1.E+07
NXM-400E、S、
F、H 400A
1.E+06 1.E+06
1.E+05 1.E+05
1.E+04 1.E+04
1.E+03 1.E+03
1 10 100 1 10 100
I[KA] I[KA]
800 (W630)/1000 (W800) frame let-through current curve 1250/1600 frame let-through current curve
NXM-800 (W630)/1000 (W800) let-through current curve NXM-1250/1600 let-through current curve
I2t[A2s] I2t[A2s]
1.E+08 1.E+08
NXM-1000(W800)S、F、H NXM-1600S、H
1000A 1600A
1.E+06 1.E+06
1.E+05 1.E+05
1.E+04 1.E+04
1 10 100 1 10 100
I[KA] I[KA]
P- 087 Moulded Case Circuit Breakers NXM series moulded case circuit breaker
IP[kA]
1000
300
200
100
NXM-1250
NXM-800(W630)、
1000(W800)
50
NXM-400、630
30
NXM-250
NXM-160(W125)
20
NXM-63、125
10
1 I[KA]
1 2 3 5 10 20 30 50 100 1000
NXM series moulded case circuit breaker Moulded Case Circuit Breakers P- 088
4h
2h
M
1h
30min
14min
10min
6min Long-time-delay actuating current IR
4min Long-time-delay actuation time 2R±20%
2min (12~150S)
150s
1min
100s
80s
30sec 60s
Actuation time
20sec
10sec
12s
5sec
1sec
0.5sec
Short-time-delay
0.2sec actuation time t2
0.3±0.06s
0.1sec
0.05sec
0.05sec
Instantaneous
actuating current Ii
0.02sec
(2~12)IR
Maximum instantaneous
0.01sec
actuation time
4h
2h
1h
30min
14min
10min
6min
Overload actuating current IR
4min Overload actuating release class
2min
1min Class30
Class20
30sec
Class10
Actuation time
20sec
10sec
Class10A
5sec
1sec
0.5sec
Short-time-delay
0.2sec actuating time tsd
0.3±0.06s
0.1sec
0.05sec
0.05sec
Instantaneous
actuating current Ii
0.02sec
(2~14)IR
Instantaneous actuation time
0.01sec