You are on page 1of 1

BRY AIR DEHUMIDIFIERS

System Flow Diagram

PROJECT : Vcool KLM /E- 0 Date : 16-Aug-23


AREA : PE 6

CONDITIONED SPACE SUPPLY AIR


Aftercooling
1,000 CFM TEMPERATURE 72.5 +/- 5 Deg.F Coil / AHU
72.5 FDBT REL. HUMIDITY 30.0 +/- 5 % RH 1,000 CFM
35.4 GRS/LB ABS. HUMIDITY 35.4 Grs/ Lb 55.0 FDBT 1,000 CFM
26.0 GRS/LB 83.2 FDBT
26.0 GRS/LB

RETURN 647 CFM BY PASS AIR


AIR 72.5 FDBT
35.4 GRS/LB
353 CFM
8.8 GRS/LB
102.8 FDBT
353 CFM PROCESS OUT 2.27 % RH
72.5 FDBT H F
35.4 GRS/LB REACT IN
DB

PROCESS IN F
RB REACT OUT
353 CFM
72.5 FDBT
35.4 GRS/LB Bry-Air DEHUMIDIFIER
MODEL : FFB-600 1 Unit(s)
---- ---- Unit(s)

Enthalpy Deh.Inlet Deh.Outlet Delta E


(Btu/Lb) 22.93 27.32 4.39
Heat Addition by Dehumidifier(s) : 11,400 BTUH

Unit Dimensions Width Depth Height LEGEND


FFB-600 (Std.Unit) mm 886 630 494 DB DESSICANT BED
---- ---- ---- ---- ---- ---- H HEATER BANK
F FILTER
Electrical Connection (Each Unit) PB PROCESS BLOWER
FFB-600 415 V/ 3 Ph / 50 Hz 7.9 KW RB REACTIVATION BLOWER
---- ----

You might also like