Report generated by Fire Pump Tester Software ™ by Hydro Flow Products, Inc.
Test Results
Date of Test: 2013-06-21
Type: Sample Work Order
Fire Department Attendee: Daniel Hockensmith
Building Representative Attendee: Amanda Davis
Testing Firm Attendee: Terry Johnston
Pump Manufacturer Attendee: Austin Stutes
Flow Device Used: 1 3/4" Nozzle Insert (HM2H)
Other Information: The fire pump passed the test. No failures to report.
Pressures Streams Total Flow Corrected
% Rated
RPM Disch. Vert. Net Flow 1 2 3 Flow GPM Volts Amps Flow % Press.
Capacity
Flow 490 76
- - -
Device
495 80
1 3574 164 9 167.9 PSI 0 0 0 161
493 82
GPM
Flow HMNI1.75 HMNI1.75 487 82
-
Device -HM2H -HM2H
491 85
2 3570 160 9 163.9 PSI 8 9 519 51.9 50.9 157.5
488 87
GPM 251.8 267.1
Flow HMNI1.75 HMNI1.75 486 88
-
Device -HM2H -HM2H
489 92
3 3566 155 9 158.9 PSI 18 18 755.5 75.6 74.2 153.1
487 95
GPM 377.8 377.8
Flow HMNI1.75 HMNI1.75 484 95
-
Device -HM2H -HM2H
487 99
4 3561 144 9 147.9 PSI 33 34 1030.7 103.1 101.3 142.9
485 101
GPM 511.5 519.2
Flow HMNI1.75 HMNI1.75 HMNI1.75 483 94
Device -HM2H -HM2H -HM2H
487 98
5 3561 114 9 117.9 PSI 26 27 28 1387.8 138.8 136.4 113.9
485 100
GPM 454 462.7 471.2
Flow HMNI1.75 HMNI1.75 HMNI1.75 483 94
Device -HM2H -HM2H -HM2H
487 98
6 3563 99 9 102.9 PSI 32 33 34 1534.4 153.4 150.7 99.3
485 100
GPM 503.7 511.5 519.2