Professional Documents
Culture Documents
Industrial Spark-Ignited Generator Set: Demand Response Ready Standby Power Rating
Industrial Spark-Ignited Generator Set: Demand Response Ready Standby Power Rating
9L | 350 kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Certified Stationary Emergency and Non-Emergency
BS5514 and DIN 6271 facilities throughout Wisconsin. Applying natural gas
and LP-fueled engines to generators requires advanced
SAE J1349
engineering expertise to ensure reliability, durability and
® necessary performance. By designing specifically for
these dry, hotter-burning fuels, the engines last longer
NFPA 37, 70, 99, 110 and require less maintenance. Building our own
engines also means we control every step of the supply
®
NEC700, 701, 702, 708 chain and delivery process, so you benefit from single-
source responsibility.
ISO 3046, 7637, 8528, 9001
Plus, Generac Industrial Power’s distribution network
provides all parts and service so you don’t have to deal
NEMA ICS10, MG1, 250, ICS6, AB1
with third-party suppliers. It all leads to a positive
SPEC SHEET
CONTROL SYSTEM • Remote Wireless Software Update Capable 7 Inch Color Touch Screen Display
• Wi-Fi, Bluetooth, BMS and Remote Telemetry • Resistive Color Touch Screen
• Built-In Programmable Logic Eliminates the Need for • Sunlight Readable (1400 NITS)
External Controllers Under Most Conditions • Easily Identifiable Icons
• Ethernet Based Communications • Multi-Lingual
Between Generators • On Screen Editable Parameters
• Programmable I/O Channel Properties
• Key Function Monitoring
• Built-In Diagnostics
• Three Phase Voltage, Amperage, kW, kVA, and kVAr
Protections
• Selectable Line to Line or Line to
Neutral Measurements
• Low Oil Pressure
• Frequency
Power Zone® Pro Sync Controller • Low Coolant Level
• Engine Speed
• High/Low Coolant Temperature
• Engine Coolant Temperature
Program Functions • Sensor Failure
• NFPA 110 Level 1 Compliant
• Engine Oil Pressure
• Oil Temperature
• Engine Oil Temperature
• Engine Protective Functions • Over/Under Speed
• Alternator Protective Functions
• Battery Voltage
• Over/Under Voltage
• Hourmeter
• Digital Engine Governor Control • Over/Under Frequency
• Digital Voltage Regulator
• Warning and Alarm Indication
• Over/Under Current
• Diagnostics
• Multiple Programmable Inputs and Outputs • Over Load
• Remote Display Capability
• Maintenance Events/Information
• High/Low Battery Voltage
• Remote Communication via Modbus® RTU, • Battery Charger Current
SPEC SHEET
PARALLELING CONTROLS • Maximum Power Protection • Optional Programmable Logic Full Auto Back-Up
• Electrically Operated, Mechanically Held Controls (PLS)
• Auto-Synchronization Process Paralleling Switch • Shunt Trip and Auxiliary Contact 2 of 6
• Isochronous Load Sharing • Sync Check System
• Reverse Power Protection • Independent On-Board Paralleling
MG350 | 21.9L | 350 kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Certified Stationary Emergency and Non-Emergency
○ NPT Flexible Fuel Line ○ Level 2 Sound Attenuated ○ 100 dB Alarm Horn
○ Anti-Condensation Heater
○ AC/DC Enclosure Lighting Kit ○ 10 Year Extended Limited Warranty
○ Tropical Coating
○ Enclosure Heaters (Motorized Dampers Only)
○ Door Open Alarm Switch
ENGINEERED OPTIONS
CONTROL SYSTEM
○ Battery Disconnect Switch
SPEC SHEET
3 of 6
MG350 | 21.9L | 350 kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Certified Stationary Emergency and Non-Emergency
ENGINE SPECIFICATIONS
Engine Governing
Governor Electronic
Frequency Regulation (Steady State) ±0.25%
Lubrication System
Oil Pump Type Gear
Oil Filter Type Full Flow Spin-On Cartridge
Crankcase Capacity - qt (L) 31.7 (30)
ALTERNATOR SPECIFICATIONS
4 of 6
MG350 | 21.9L | 350 kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Certified Stationary Emergency and Non-Emergency
COOLING
Standby/Demand Response Prime
Air Flow (Fan Air Flow Across Radiator) scfm (m3/min) 28,004 (793) 28,004 (793)
Coolant Flow gpm (Lpm) 211 (798.6) 211 (798.6)
Coolant System Capacity gal (L) 15.5 (58.7) 15.5 (58.7)
Maximum Operating Ambient Temperature °F (°C) 122 (50) 122 (50)
Maximum Operating Ambient Temperature (Before Derate) See Bulletin No. 0199270SSD
Maximum Radiator Backpressure in H2O (kPa) 0.5 (0.12) 0.5 (0.12)
ENGINE EXHAUST
Standby/Demand Standby/Demand
Prime Prime
Response Response
Rated Engine Speed RPM 1,800 1,800 Exhaust Flow (Rated Output) scfm (m3/min) 2,113 (59.8) 1,894 (53.6)
Horsepower at Rated kW** hp 516 464 Max. Backpressure (Post Silencer) inHg (kPa) 0.75 (2.54) 0.75 (2.54)
Piston Speed ft/min (m/min) 1,680 (512) 1,680 (512) Exhaust Temp (Rated Output - Post Silencer) °F (°C) 1,277 (691.7) 1,250 (676.7)
BMEP psi (kPa) 170 (1,171) 153 (1,054)
** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.
Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions.
Please contact a Generac Power Systems Industrial Dealer for additional details. All performance ratings in accordance with ISO3046, BS5514, ISO8528, and DIN6271 standards.
SPEC SHEET
5 of 6
MG350 | 21.9L | 350 kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Certified Stationary Emergency and Non-Emergency
L W
L W
L
W
Specification characteristics may change without notice. Dimensions and weights are for preliminary purposes only. Please contact a Generac Power Systems Industrial Dealer for detailed installation drawings.
6 of 6
Generac Power Systems, Inc. | P.O. Box 8 | Waukesha, WI 53189 Part No. 10000035519
P: (262) 544-4811 ©2019 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Rev. B 11/15/19