Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-RE 500 V4 + HAS 5.8 M10
Return period (service life in years): 50
Item number: 2390199 HAS 5.8 M10x150 (element) / 2287553
HIT-RE 500 V4 (adhesive)
Filling set or any suitable annular gap filling solution
Effective embedment depth: hef,act = 120.0 mm (hef,limit = - mm)
Material: 5.8
Evaluation Service Report: ETA 20/0541
Issued I Valid: 09/06/2023 | -
Proof: SOFA based on EN 1992-4 and fib bulletin 58, Chemical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 14.0 mm
Anchor plate :
R lx x ly x t = 150.0 mm x 100.0 mm x 14.0 mm; (Recommended plate thickness: 14.0 mm)
Application also possible with HIT-RE 500 V4 + HAS-U 5.8 M10 under the selected boundary conditions.
More information in section Alternative fastening data of this report.
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
y
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
3 4
Anchor Tension force Shear force Shear force x Shear force y
1 13.340 1.414 1.000 1.000
2 0.000 1.414 1.000 1.000 x
3 13.340 1.414 1.000 1.000 Compression
4 0.000 1.414 1.000 1.000 1 2
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
N
NEd £ NRd,s = Rk,s EN 1992-4, Table 7.1
gM,s
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
N
NEd £ NRd,p = Rk,p EN 1992-4, Table 7.1
gM,p
0 Ap,N
NRk,p = NRk,p · 0
· y g,Np · y s,Np · y re,N · y ec1,Np · y ec2,Np EN 1992-4, Eq. (7.13)
Ap,N
0
NRk,p = y sus · t Rk · p · d · hef EN 1992-4, Eq. (7.14)
y sus =1 EN 1992-4, Eq. (7.14a)
Rk,c
³ 1.00 EN 1992-4, Eq. (7.18)
k3
t Rk,c = · √hef · fck EN 1992-4, Eq. (7.19)
p·d
c
y s,Np = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.20)
ccr,Np £
1
y ec1,Np = 1.00 EN 1992-4, Eq. (7.21)
2 · ec1,N £
1+ (
scr,Np )
1
y ec2,Np = 1.00 EN 1992-4, Eq. (7.21)
2 · ec2,N £
1+ (
scr,Np )
2 0 2 2 2
Ap,N [mm ] Ap,N [mm ] t Rk,ucr,20 [N/mm ] scr,Np [mm] ccr,Np [mm] cmin [mm] fc,cyl [N/mm ]
94,071 79,935 15.00 282.7 141.4 3,000.0 32.00
0
yc t Rk,ucr [N/mm ]
2
k3 t Rk,c [N/mm ]
2
y g,Np y g,Np
1.048 15.72 11.000 21.70 1.159 1.092
Group anchor ID
1, 3
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
N
NEd £ NRd,c = Rk,c EN 1992-4, Table 7.1
gM,c
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = 1.00 EN 1992-4, Eq. (7.6)
2 · eN,1 £
1+ (
scr,N )
1
y ec2,N = 1.00 EN 1992-4, Eq. (7.6)
2 · eN,2 £
1+ (
scr,N )
z
y M,N = 2.0 - 1.00 EN 1992-4, Eq. (7.7)
1.5 · hef ³
2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] fc,cyl [N/mm ]
147,600 129,600 180.0 360.0 32.00
Group anchor ID
1, 3
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gM,s
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)
0
VRk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
17.400 1.000 17.400 1.250 13.920 1.414
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gM,c,p
VRk,cp = k8 · min {NRk,c; NRk,p} EN 1992-4, Eq. (7.39c)
0 A
NRk,p = NRk,p · p,N
0
· y g,Np · y s,Np · y re,N · y ec1,Np · y ec2,Np EN 1992-4, Eq. (7.13)
Ap,N
0
NRk,p = y sus · t Rk · p · d · hef EN 1992-4, Eq. (7.14)
y sus =1 EN 1992-4, Eq. (7.14a)
scr,Np = 7.3 · d · √y sus · t Rk £ 3 · hef EN 1992-4, Eq. (7.15)
0,5
y g,Np
0
= y g,Np - (s s )
cr,Np
· (y g,Np - 1) ³ 1.00
0
EN 1992-4, Eq. (7.17)
1,5
0
y g,Np = √n - (√n - 1) · (tt ) Rk
Rk,c
³ 1.00 EN 1992-4, Eq. (7.18)
k3
t Rk,c = · √hef · fck EN 1992-4, Eq. (7.19)
p·d
c
y s,Np = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.20)
ccr,Np £
1
y ec1,Np = 1.00 EN 1992-4, Eq. (7.21)
2 · ec1,N £
1+ (
scr,Np )
1
y ec2,Np = 1.00 EN 1992-4, Eq. (7.21)
2 · ec2,N £
1+ (
scr,Np )
2 0 2 2 2
Ap,N [mm ] Ap,N [mm ] t Rk,ucr,20 [N/mm ] ccr,Np [mm] scr,Np [mm] cmin [mm] fc,cyl [N/mm ]
127,344 79,935 15.00 141.4 282.7 3,000.0 32.00
0
yc t Rk,ucr [N/mm ]
2
k3 t Rk,c [N/mm ]
2
k8 y g,Np
Group anchor ID
1-4
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
V
VEd £ VRd,c = Rk,c fib Bulletin 58, Table (10.2-1)
gM,c
0
VRk,c = VRk,c· y A,V · y h,V ·y s,V · y ec,V · y a,V · y re,V fib Bulletin 58, Eq. (10.2-5)
0 a b 1.5
VRk,c = kv · dnom · lf · √fck · c1 fib Bulletin 58, Eq. (10.2-5a)
0,5
a = 0.1 · (cl ) f
1
fib Bulletin 58, Eq. (10.2-5a1)
0,2
= 0.1 · (
c )
d nom
b fib Bulletin 58, Eq. (10.2-5a2)
1
0 2
Ac,V = 4.5 · c1 fib Bulletin 58, Eq. (10.2-5b)
A
y A,V = 0c,V fib bulletin 58 (07/2011) Section 10.2.5.1.1 b)
Ac,V
Ac,V fib bulletin 58 (07/2011) Figure 10.2-4
c2
y s,V = 0.7 + 0.3 · 1.00 fib Bulletin 58, Eq. (10.2-5d)
1.5 · c1 £
0,5
y h,V = (1.5h· c ) 1
³ 1.00 fib Bulletin 58, Eq. (10.2-5c)
1
y ec,V = £ 1.00 fib Bulletin 58, Eq. (10.2-5e)
1+ ( 2 · eV
3 · c1 )
√
1
2
y a,V =
(cos aV) + y V
90°,V
2
(sin a ) ³ 1.00 fib Bulletin 58, Eq. (10.2-5f))
'
c1 = max (c1.5 , 1.5h , s 3 )
2,max 2,max
fib Bulletin 58, Eq. (10.2-5h2)
VRk,c(c1,n1)
VRk,c = fib Bulletin 58, Eq. (10.2-6)
n1
Note: Resistance limit acc. to fib bulletin 58 (07/2011) Eq. (10.2-6) is governing
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
a a
bN + bV £ 1.0
Concrete failure
a a
bN + bV £ 1.0
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
9
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters
of the clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• Characteristic bond resistances depend on short- and long-term temperatures.
• Edge reinforcement is not required to avoid splitting failure
• Design is only valid if hole is filled to remove clearance, clearance as per EN 1992-4 Table 6.1
• Load transfer from supplementary reinforcement to the structural member shall be verified by the responsible structural engineer.
• With supplementary reinforcement and post-installed anchors, please ensure that in the jobsite the rebars are not drilled through.
• The characteristic bond resistances depend on the return period (service life in years): 50
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
(1)
Mallée, R.; Riemann, H. (1990): Ankerplattenbefestigungen mit Hinterschnittdübeln,
Bauingenieur 65 (1990), S. 49 - 57, Springer VDI-Verlag, 1990
Mallée, R.; Burkhardt, F. (1999): Befestigungen von Ankerplatten mit Dübeln, Beton und
Stahlbetonbau 94, Heft 12, S. 502 - 511, Ernst & Sohn Verlag, 1999
8.2 Results
Stress distribution s 11
2
275.00 [N/mm ]
2
-50.90 [N/mm ]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
11
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 12
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
Stress distribution s 22
2
165.49 [N/mm ]
2
-122.99 [N/mm ]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
12
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 13
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
Deformations (z-direction)
0.0 [mm]
-0.1 [mm]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
13
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 14
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
9 Installation data
2 2
Anchor plate, steel: S 275; E = 210,000.00 N/mm ; fyk = 275.00 N/mm Anchor type and diameter: HIT-RE 500 V4 + HAS 5.8 M10
Profile: Rectangular hollow, 70 x 40 x 4,0; (L x W x T) = 70.0 mm x 40.0 mm x Item number: 2390199 HAS 5.8 M10x150 (element) /
4.0 mm 2287553 HIT-RE 500 V4 (adhesive)
Hole diameter in the fixture: df = 12.0 mm Maximum installation torque: 20 Nm
Plate thickness (input): 14.0 mm Hole diameter in the base material: 12.0 mm
Recommended plate thickness: 14.0 mm Hole depth in the base material: 120.0 mm
Drilling method: SafeSet - automatic cleaning Minimum thickness of the base material: 150.0 mm
Cleaning: Automatically performed while drilling
Hilti HAS-U threaded rod with HIT-RE 500 V4 injection mortar with 120 mm embedment h_ef, M10, Steel galvanized, SAFEset - automatic
cleaning installation per ETA 20/0541, with annular gaps filled with Hilti Filling set or any suitable gap solutions
y
75.0 75.0
25.0
50.0
3 4
50.0
0.0
x
50.0
1 2
25.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
14
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 15
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
10 Alternative fastening
10.1 Alternative fastening data
Anchor plate :
R lx x ly x t = 150.0 mm x 100.0 mm x 14.0 mm; (Recommended plate thickness: not calculated)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
15
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 16
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
Hilti HAS-U threaded rod with HIT-RE 500 V4 injection mortar with 120 mm embedment h_ef, M10, Steel galvanized, SAFEset - automatic
cleaning installation per ETA 20/0541, with annular gaps filled with Hilti Filling set or any suitable gap solutions
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
16
Hilti PROFIS Engineering 3.0.90
www.hilti.com.sg
Company: Page: 17
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
17