Hilti PROFIS Engineering 3.0.

90

www.hilti.com.sg
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-RE 500 V4 + HAS 5.8 M10
Return period (service life in years): 50
Item number: 2390199 HAS 5.8 M10x150 (element) / 2287553
HIT-RE 500 V4 (adhesive)
Filling set or any suitable annular gap filling solution
Effective embedment depth: hef,act = 120.0 mm (hef,limit = - mm)
Material: 5.8
Evaluation Service Report: ETA 20/0541
Issued I Valid: 09/06/2023 | -
Proof: SOFA based on EN 1992-4 and fib bulletin 58, Chemical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 14.0 mm

Anchor plate :
R lx x ly x t = 150.0 mm x 100.0 mm x 14.0 mm; (Recommended plate thickness: 14.0 mm)

Profile: Rectangular hollow, 70 x 40 x 4,0; (L x W x T) = 70.0 mm x 40.0 mm x 4.0 mm


Base material: 2
uncracked concrete, C32/40, fc,cyl = 32.00 N/mm ; h = 500.0 mm, Temp. short/long: 30/30 °C,
User-defined partial material safety factor gc = 1.500
Installation: automatic cleaned drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting acc. to EN 1992-4, 7.2.1.7 (2) b) 2) present

Application also possible with HIT-RE 500 V4 + HAS-U 5.8 M10 under the selected boundary conditions.
More information in section Alternative fastening data of this report.

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = 0.000; Vx = 4.000; Vy = 4.000; no no 69
Mx = 0.000; My = 3.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

2 Load case/Resulting anchor forces

y
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
3 4
Anchor Tension force Shear force Shear force x Shear force y
1 13.340 1.414 1.000 1.000
2 0.000 1.414 1.000 1.000 x
3 13.340 1.414 1.000 1.000 Compression
4 0.000 1.414 1.000 1.000 1 2

max. concrete compressive strain: 0.47 [‰]


max. concrete compressive stress: 14.17 [N/mm ]
2

resulting tension force in (x/y)=(0.0/0.0): 0.000 [kN]


resulting compression force in (x/y)=(137.4/50.0): 26.680 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

3 Tension load EN 1992-4, Section 7.2.1


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 13.340 19.333 69 OK
Combined pullout-concrete cone failure** 26.680 50.778 53 OK
Concrete Breakout Failure** 26.680 85.414 32 OK
Splitting failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

3.1 Steel Strength

N
NEd £ NRd,s = Rk,s EN 1992-4, Table 7.1
gM,s

NRk,s [kN] gM,s NRd,s [kN] NEd [kN]


29.000 1.500 19.333 13.340

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

3.2 Combined pullout-concrete cone failure

N
NEd £ NRd,p = Rk,p EN 1992-4, Table 7.1
gM,p
0 Ap,N
NRk,p = NRk,p · 0
· y g,Np · y s,Np · y re,N · y ec1,Np · y ec2,Np EN 1992-4, Eq. (7.13)
Ap,N
0
NRk,p = y sus · t Rk · p · d · hef EN 1992-4, Eq. (7.14)
y sus =1 EN 1992-4, Eq. (7.14a)

scr,Np = 7.3 · d · √y sus · t Rk £ 3 · hef EN 1992-4, Eq. (7.15)


0,5
y g,Np
0
= y g,Np -
s
s
( ) · (y g,Np - 1) ³ 1.00
cr,Np
0
EN 1992-4, Eq. (7.17)
1,5
0
y g,Np = √n - (√n - 1) · (tt )
Rk

Rk,c
³ 1.00 EN 1992-4, Eq. (7.18)
k3
t Rk,c = · √hef · fck EN 1992-4, Eq. (7.19)
p·d
c
y s,Np = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.20)
ccr,Np £
1
y ec1,Np = 1.00 EN 1992-4, Eq. (7.21)
2 · ec1,N £
1+ (
scr,Np )
1
y ec2,Np = 1.00 EN 1992-4, Eq. (7.21)
2 · ec2,N £
1+ (
scr,Np )
2 0 2 2 2
Ap,N [mm ] Ap,N [mm ] t Rk,ucr,20 [N/mm ] scr,Np [mm] ccr,Np [mm] cmin [mm] fc,cyl [N/mm ]
94,071 79,935 15.00 282.7 141.4 3,000.0 32.00
0
yc t Rk,ucr [N/mm ]
2
k3 t Rk,c [N/mm ]
2
y g,Np y g,Np
1.048 15.72 11.000 21.70 1.159 1.092

ec1,N [mm] y ec1,Np ec2,N [mm] y ec2,Np y s,Np y re,Np


0.0 1.000 0.0 1.000 1.000 1.000
0
y sus asus y sus
0.720 0.000 1.000
0
NRk,p [kN] NRk,p [kN] gM,p NRd,p [kN] NEd [kN]
59.270 76.167 1.500 50.778 26.680

Group anchor ID
1, 3

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

3.3 Concrete Breakout Failure

N
NEd £ NRd,c = Rk,c EN 1992-4, Table 7.1
gM,c
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = 1.00 EN 1992-4, Eq. (7.6)
2 · eN,1 £
1+ (
scr,N )
1
y ec2,N = 1.00 EN 1992-4, Eq. (7.6)
2 · eN,2 £
1+ (
scr,N )
z
y M,N = 2.0 - 1.00 EN 1992-4, Eq. (7.7)
1.5 · hef ³

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] fc,cyl [N/mm ]
147,600 129,600 180.0 360.0 32.00

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N


0.0 1.000 0.0 1.000 1.000 1.000
0
z [mm] y M,N k1 NRk,c [kN] gM,c NRd,c [kN] NEd [kN]
112.4 1.375 11.000 81.797 1.500 85.414 26.680

Group anchor ID
1, 3

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

4 Shear load EN 1992-4, Section 7.2.2


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 1.414 13.920 11 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 5.657 149.293 4 OK
Concrete edge failure in direction x+** 2.828 263.240 2 OK

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)

V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gM,s
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)

0
VRk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
17.400 1.000 17.400 1.250 13.920 1.414

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

4.2 Pryout Strength (Bond Strength controls)

V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gM,c,p
VRk,cp = k8 · min {NRk,c; NRk,p} EN 1992-4, Eq. (7.39c)
0 A
NRk,p = NRk,p · p,N
0
· y g,Np · y s,Np · y re,N · y ec1,Np · y ec2,Np EN 1992-4, Eq. (7.13)
Ap,N
0
NRk,p = y sus · t Rk · p · d · hef EN 1992-4, Eq. (7.14)
y sus =1 EN 1992-4, Eq. (7.14a)
scr,Np = 7.3 · d · √y sus · t Rk £ 3 · hef EN 1992-4, Eq. (7.15)
0,5
y g,Np
0
= y g,Np - (s s )
cr,Np
· (y g,Np - 1) ³ 1.00
0
EN 1992-4, Eq. (7.17)
1,5
0
y g,Np = √n - (√n - 1) · (tt ) Rk

Rk,c
³ 1.00 EN 1992-4, Eq. (7.18)
k3
t Rk,c = · √hef · fck EN 1992-4, Eq. (7.19)
p·d
c
y s,Np = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.20)
ccr,Np £
1
y ec1,Np = 1.00 EN 1992-4, Eq. (7.21)
2 · ec1,N £
1+ (
scr,Np )
1
y ec2,Np = 1.00 EN 1992-4, Eq. (7.21)
2 · ec2,N £
1+ (
scr,Np )
2 0 2 2 2
Ap,N [mm ] Ap,N [mm ] t Rk,ucr,20 [N/mm ] ccr,Np [mm] scr,Np [mm] cmin [mm] fc,cyl [N/mm ]
127,344 79,935 15.00 141.4 282.7 3,000.0 32.00
0
yc t Rk,ucr [N/mm ]
2
k3 t Rk,c [N/mm ]
2
k8 y g,Np

1.048 15.72 11.000 21.70 2.000 1.383

y g,Np ec1,V [mm] y ec1,Np ec2,V [mm] y ec2,Np y s,Np


1.186 0.0 1.000 0.0 1.000 1.000
0
y re,Np y sus asus y sus
1.000 0.720 0.000 1.000
0
NRk,p [kN] NRk,p [kN] gM,c,p VRd,cp [kN] VEd [kN]
59.270 111.970 1.500 149.293 5.657

Group anchor ID
1-4

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

4.3 Concrete edge failure in direction x+

V
VEd £ VRd,c = Rk,c fib Bulletin 58, Table (10.2-1)
gM,c
0
VRk,c = VRk,c· y A,V · y h,V ·y s,V · y ec,V · y a,V · y re,V fib Bulletin 58, Eq. (10.2-5)
0 a b 1.5
VRk,c = kv · dnom · lf · √fck · c1 fib Bulletin 58, Eq. (10.2-5a)
0,5
a = 0.1 · (cl ) f

1
fib Bulletin 58, Eq. (10.2-5a1)
0,2

= 0.1 · (
c )
d nom
b fib Bulletin 58, Eq. (10.2-5a2)
1
0 2
Ac,V = 4.5 · c1 fib Bulletin 58, Eq. (10.2-5b)
A
y A,V = 0c,V fib bulletin 58 (07/2011) Section 10.2.5.1.1 b)
Ac,V
Ac,V fib bulletin 58 (07/2011) Figure 10.2-4
c2
y s,V = 0.7 + 0.3 · 1.00 fib Bulletin 58, Eq. (10.2-5d)
1.5 · c1 £
0,5
y h,V = (1.5h· c ) 1
³ 1.00 fib Bulletin 58, Eq. (10.2-5c)
1
y ec,V = £ 1.00 fib Bulletin 58, Eq. (10.2-5e)
1+ ( 2 · eV
3 · c1 )

1
2
y a,V =
(cos aV) + y V
90°,V
2
(sin a ) ³ 1.00 fib Bulletin 58, Eq. (10.2-5f))

'
c1 = max (c1.5 , 1.5h , s 3 )
2,max 2,max
fib Bulletin 58, Eq. (10.2-5h2)
VRk,c(c1,n1)
VRk,c = fib Bulletin 58, Eq. (10.2-6)
n1

lf [mm] dnom [mm] kV a b fc,cyl [N/mm ]


2

120.0 10.00 2.400 0.024 0.035 32.00


' 0 2
c1 [mm] c1 [mm] Ac,V [mm ]
2
Ac,V [mm ] y A,V
3,270.0 2,000.0 3,025,000 18,000,000 0.168

y s,V y h,V aV [°] y a,V ec,V [mm] y ec,V y re,V


1.000 2.449 45.00 1.265 0.0 1.000 1.000
0
y 90°,V VRk,c [kN] VRk,c [kN] n1 gM,c VRd,c [kN] VEd [kN]
2.000 1,516.648 789.720 2 1.500 263.240 2.828

Note: Resistance limit acc. to fib bulletin 58 (07/2011) Eq. (10.2-6) is governing

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

5 Combined tension and shear loads (EN 1992-4, Section 7.2.3)


Steel failure

bN bV a Utilization bN,V [%] Status


0.690 0.102 2.000 49 OK

a a
bN + bV £ 1.0

Concrete failure

bN bV a Utilization bN,V [%] Status


0.525 0.038 1.500 39 OK

a a
bN + bV £ 1.0

6 Displacements (highest loaded anchor)


Short term loading:

NSk = 9.881 [kN] dN = 0.1311 [mm]


VSk = 1.048 [kN] dV = 0.0629 [mm]
dNV = 0.1453 [mm]
Long term loading:

NSk = 9.881 [kN] dN = 0.3407 [mm]


VSk = 1.048 [kN] dV = 0.0838 [mm]
dNV = 0.3509 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters
of the clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• Characteristic bond resistances depend on short- and long-term temperatures.
• Edge reinforcement is not required to avoid splitting failure
• Design is only valid if hole is filled to remove clearance, clearance as per EN 1992-4 Table 6.1
• Load transfer from supplementary reinforcement to the structural member shall be verified by the responsible structural engineer.
• With supplementary reinforcement and post-installed anchors, please ensure that in the jobsite the rebars are not drilled through.
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

10
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

8 Anchor plate stress check


Scope: For the loads / load combinations applied on the anchor plate, an anchor plate stress check is performed (based on the results of a FE
calculation). This stress check contains normal stresses resulting from bending moments in two directions. The user is responsible to select
an anchor plate thickness that meets the requirement per guideline for a rigid anchor plate (to ensure that the assumed load distribution is
(1)
correct). A detailed description can be found in Mallée.

(1)
Mallée, R.; Riemann, H. (1990): Ankerplattenbefestigungen mit Hinterschnittdübeln,
Bauingenieur 65 (1990), S. 49 - 57, Springer VDI-Verlag, 1990
Mallée, R.; Burkhardt, F. (1999): Befestigungen von Ankerplatten mit Dübeln, Beton und
Stahlbetonbau 94, Heft 12, S. 502 - 511, Ernst & Sohn Verlag, 1999

8.1 Base material properties

Steel type: S 275


2
Yield stress: fy = 275.00 [N/mm ]
Partial safety factor: gm,s = 1.000
2
Ultimate strength: fu = 430.00 [N/mm ]
2
Young's modulus: Es = 210,000.00 [N/mm ]
Poisson ratio: n = 0.3

8.2 Results

Relevant load combination: LC 01

Stress distribution s 11

2
275.00 [N/mm ]

2
-50.90 [N/mm ]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

11
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 12
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

Stress distribution s 22

2
165.49 [N/mm ]

2
-122.99 [N/mm ]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

12
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 13
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

Deformations (z-direction)
0.0 [mm]

-0.1 [mm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

13
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 14
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

9 Installation data
2 2
Anchor plate, steel: S 275; E = 210,000.00 N/mm ; fyk = 275.00 N/mm Anchor type and diameter: HIT-RE 500 V4 + HAS 5.8 M10
Profile: Rectangular hollow, 70 x 40 x 4,0; (L x W x T) = 70.0 mm x 40.0 mm x Item number: 2390199 HAS 5.8 M10x150 (element) /
4.0 mm 2287553 HIT-RE 500 V4 (adhesive)
Hole diameter in the fixture: df = 12.0 mm Maximum installation torque: 20 Nm
Plate thickness (input): 14.0 mm Hole diameter in the base material: 12.0 mm
Recommended plate thickness: 14.0 mm Hole depth in the base material: 120.0 mm
Drilling method: SafeSet - automatic cleaning Minimum thickness of the base material: 150.0 mm
Cleaning: Automatically performed while drilling

Hilti HAS-U threaded rod with HIT-RE 500 V4 injection mortar with 120 mm embedment h_ef, M10, Steel galvanized, SAFEset - automatic
cleaning installation per ETA 20/0541, with annular gaps filled with Hilti Filling set or any suitable gap solutions

9.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • No accessory required • Dispenser including cassette and mixer
• Properly sized drill bit for SAFEset - • Torque wrench
automatic cleaning (TE-CD / TE-YD)
• Vacuum cleaner

y
75.0 75.0
25.0

50.0

3 4
50.0
0.0

x
50.0

1 2
25.0

25.0 100.0 25.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -50.0 -25.0 3,170.0 3,270.0 3,000.0 3,050.0
2 50.0 -25.0 3,270.0 3,170.0 3,000.0 3,050.0
3 -50.0 25.0 3,170.0 3,270.0 3,050.0 3,000.0
4 50.0 25.0 3,270.0 3,170.0 3,050.0 3,000.0

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

14
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 15
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

10 Alternative fastening
10.1 Alternative fastening data

Anchor type and diameter: HIT-RE 500 V4 + HAS-U 5.8 M10


Return period (service life in years): 50
Item number: 2223709 HAS-U 5.8 M10x170 (element) / 2287553
HIT-RE 500 V4 (adhesive)
Filling set or any suitable annular gap filling solution
Effective embedment depth: hef,act = 120.0 mm (hef,limit = - mm)
Material: 5.8
Evaluation Service Report: ETA 20/0541
Issued I Valid: 09/06/2023 | -
Proof: SOFA based on EN 1992-4 and fib bulletin 58, Chemical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 14.0 mm

Anchor plate :
R lx x ly x t = 150.0 mm x 100.0 mm x 14.0 mm; (Recommended plate thickness: not calculated)

Profile: Rectangular hollow, 70 x 40 x 4,0; (L x W x T) = 70.0 mm x 40.0 mm x 4.0 mm


Base material: 2
uncracked concrete, C32/40, fc,cyl = 32.00 N/mm ; h = 500.0 mm, Temp. short/long: 30/30 °C,
User-defined partial material safety factor gc = 1.500
Installation: automatic cleaned drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting acc. to EN 1992-4, 7.2.1.7 (2) b) 2) present

Max. Utilization with HIT-RE 500 V4 + HAS-U 5.8 M10: 69 %


Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

15
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 16
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

10.2 Installation data


2
Anchor plate, steel: S 275; E = 210,000.00 N/mm ; fyk = 275.00 N/mm
2 Anchor type and diameter: HIT-RE 500 V4 + HAS-U 5.8
M10
Profile: Rectangular hollow, 70 x 40 x 4,0; (L x W x T) = 70.0 mm x 40.0 mm x Item number: 2223709 HAS-U 5.8 M10x170 (element) /
4.0 mm 2287553 HIT-RE 500 V4 (adhesive)
Hole diameter in the fixture: df = 12.0 mm Maximum installation torque: 20 Nm
Plate thickness (input): 14.0 mm Hole diameter in the base material: 12.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 120.0 mm
Drilling method: SafeSet - automatic cleaning Minimum thickness of the base material: 150.0 mm
Cleaning: Automatically performed while drilling

Hilti HAS-U threaded rod with HIT-RE 500 V4 injection mortar with 120 mm embedment h_ef, M10, Steel galvanized, SAFEset - automatic
cleaning installation per ETA 20/0541, with annular gaps filled with Hilti Filling set or any suitable gap solutions

10.2.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • No accessory required • Dispenser including cassette and mixer
• Properly sized drill bit for SAFEset - • Torque wrench
automatic cleaning (TE-CD / TE-YD)
• Vacuum cleaner

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

16
Hilti PROFIS Engineering 3.0.90

www.hilti.com.sg
Company: Page: 17
Address: Specifier:
Phone I Fax: | E-Mail:
Design: B25A to existing beam (1) Date: 15/01/2024
Fastening point:

11 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with
regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to
interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability
for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

17