You are on page 1of 6

KVCG202/EN M/E11 Technical Manual

Page 152 KVGC202

1. COMMISSIONING TEST RECORD

Date

Station Circuit

Front plate information

Voltage regulating relay type KVGC202


Model No.
Serial No.

Rated In
Aux Voltage Vx
Frequency Hz
Rated ac voltage Vn

0000 System data settings F E D C B A 9 8 7 6 5 4 3 2 1 0


0002 Password
0003 SD Links
0004 Description
0006 Plant Ref.
0007 Model
0008 Serial No.
0009 Freq
000A Comms Level
000B Relay Address
000C Plant status
000D Control status
000E Group now
000F Load shed/boost stage
0011 Software Ref.
0020 Logic status
0021 Relay status
0022 Alarms

0300 Control 1 F E D C B A 9 8 7 6 5 4 3 2 1 0
0301 CTL Links
0302 CT Ratio
0303 VT Ratio
0304 In
0305 Vs
0306 dV
0307 Vc(volt/In)
0308 Vr(volt/In)
Technical Manual KVCG202/EN M/E11

KVGC202 Page 153

0300 Control 1 F E D C B A 9 8 7 6 5 4 3 2 1 0
0309 Vx(volt/In)
030A PF Angle
030B tINIT DT
030C tINTER
030D tPULSE
030E LSB level 1
030F LSB level 2
0310 LSB level 3
0311 tTapChange

0500 Control (2) F E D C B A 9 8 7 6 5 4 3 2 1 0


0501 CTL Links
0502 CT Ratio
0503 VT Ratio
0504 In
0505 Vs
0506 dV
0507 Vc(volt/In)
0508 Vr(volt/In)
0509 Vx(volt/In)
050A PF Angle
050B tINIT DT
050C tINTER
050D tPULSE
050E LSB level 1
050F LSB level 2
0510 LSB level 3
0511 tTapChange

0400 Logic 1 F E D C B A 9 8 7 6 5 4 3 2 1 0
0401 Log Links
0402 V<<
0403 V<
0404 V>
0405 t V< V>
0406 tFAIL
0407 Ic>
0408 tIc
0409 IL>
040A IL<
040B TpAvail
040C TP>
KVCG202/EN M/E11 Technical Manual

Page 154 KVGC202

0400 Logic 1 F E D C B A 9 8 7 6 5 4 3 2 1 0
040D TP<
040E total ops
040F ops/tP>
0410 tP
0411 Default Display
0412 tTest Relay

0600 Logic (2) F E D C B A 9 8 7 6 5 4 3 2 1 0


0601 Log Links
0602 V<<
0603 V<
0604 V>
0605 t V< V>
0606 tFAIL >
0607 Ic>
0608 tIc
0609 IL>
060A IL<
060B TpAvail
060C TP>
060D TP<
060E totalops
060F ops/tP>
0610 tP
0611 Default Display
0612 tTest Relay

0700 Log Links F E D C B A 9 8 7 6 5 4 3 2 1 0


0701 Remote
0702 Automatic
0703 Manual
0704 Raise V
0705 Lower V
0706 Block
0707 Level 1
0708 Level 2
0709 Level 3
070A Stg GRP2
Technical Manual KVCG202/EN M/E11

KVGC202 Page 155

Series 0800 F E D C B A 9 8 7 6 5 4 3 2 1 0
0801 Raise V
0802 Lower V
0803 Blocked
0804 UnBlocked
0805 V<<
0806 V<
0807 V>
0808 Tap Fail
0809 Ic >
080A IL >
080B IL<
080C TotalOps>
080D FreqOps
080E Irev
080F RUN-AWAY
0810 Tap Limit
0811 Tap Odd
0812 Tap Even
0813 Auto Mode
0814 Manual Mode
0815 Select tst rlys
0816 Test Relays = [0]

Commissioning preliminaries (tick)

1.4 Serial number on case, module and cover checked

CT shorting switches in case checked


Terminals 21 and 22; 23 and 24; 25 and 26; 27 and 28 checked for
continuity with module removed from case
External wiring checked to diagram (if available)
1.5 Earth connection to case checked
1.7 Test block connections checked
1.8 Insulation checked

Auxiliary supply checked

3.1 Auxiliary power checked


3.1.1 Auxiliary voltage at the relay terminals V ac/dc
3.1.2 Watchdog contacts checked
Supply off Terminals 3 and 5
Terminals 4 and 6
Supply on Terminals 3 and 5
KVCG202/EN M/E11 Technical Manual

Page 156 KVGC202

Terminals 4 and 6
3.1.3 Field voltage V ac/dc

Metering Applied Measured


value value
Vs V A

Ic A A

IL A A

Grp1 Grp2

Voltage setting Vs V V
Deadband setting dVs % %
Volts high threshold (VHIGH) V V

Volts low threshold (VLOW) V V

Measured setting (VHIGH + LOW)/2 V V

Actual dead band (VHIGH – VLOW) V V

Load shedding/boosting
-3% -6% -9% +3% +6% +9%

Measured values
-3% -6% -9% +3% +6% +9%

Initial time delay (tINIT) Grp1 Grp2


Setting (definite) s s
Measured (definite) s s
Setting (inverse) s s
Measured (inverse) s s
Inter tap time delay (tINTER) s s
Setting s s
Measured s s
Line drop compensation
Resistive compensation volts V V
setting Vr
Mode setting [0102 STATUS] Manual / Manual /
auto auto
Voltage setting (Vs) V V
Vreg [0202 MEASURE] V V
Measured resistive compensation V V
Vr = reg – Vs
Grp1 Grp2
Reactive compensation volts setting VXL V V
Mode setting [0102 STATUS] Manual / Manual /
auto auto
Voltage setting (Vs) V V
Technical Manual KVCG202/EN M/E11

KVGC202 Page 157

Vreg [0202 MEASURE] V V


Measured reactive compensation V V
x = (Vreg – Vs2)
Circulating current compensation setting V V
Vc

Compensation (Vc) Negative/ Negative/


positive positive
Voltage setting (Vs) V V
Vreg [0202 MEASURE] V V
Measured circulating current V V
compensation Vc = Vreg – Vs

Supervision

Undervoltage detector (V<)


Undervoltage setting V V
Value measured V V
Overvoltage detector (V>)
Overvoltage setting V V
Value measured V V

Load current detector (IL)


Load current setting A A
Value measured A A

Circulating current detector (Ic)


Circulating current setting A A
Value measured A A
Alarm (tFAIL) s s
LOAD check
Volts at receiving end V V
Volts low lamp when Vs is set at V V
Volts high lamp when Vs is set at V V
Average Vs V V
(should  volts at receiving end)

Commissioning Engineer Customer Witness

Date Date