UPS SYSTEM, Type: PDW 3100-220/400-EN-R
TABLE OF CONTENTS:
1. Elimination of simple Malfunctions
2. Trouble-Shooting at Alarm Indication
11-03-30 JIT
11-03-30 HJP
11-03-30
7RA9093GB -
-
-
4A-1100475001/20GB 1 1/5
TROUBLE-SHOOTING
Depending upon the system configuration, the switches mentioned in this description can be circuit breakers, switch-disconnectors (fuse switch-
disconnectors) and the designation can be made according to customer's request see «Single line diagram».
7RA9093GB
-
-
- 4A-1100475001/20GB 1 2/5
TROUBLE-SHOOTING
7RA9093GB
-
-
- 4A-1100475001/20GB 1 3/5
TROUBLE-SHOOTING
ASYNCHRONOUS ¨ Bypass frequency out of tolerance ¨ Measure the voltage between bypass and ¨ Controller A070
(30 s) ¨ Inverter asynchronous to the bypass mains system output ¨ Interface A071
BYPASS MAINS FAULT ¨ Bypass mains voltage or frequency out of tolerance ¨ Measure the mains voltage and frequency at ¨ Interface A071/ X010: F006/F007/F008
the input of the static switch EN
(30 s)
MANUAL BYPASS ON ¨ Manual bypass switch Q050 not at position «AUTO» ¨ Check the position of manual bypass switch ¨ Manual bypass switch Q050
(5 s)
Q050 ¨ Adapter board A068
EN INHIBITED ¨ Bypass mains voltage or -frequency out of tolerance ¨ Measure the bypass mains voltage ¨ Static switch EN — A035
(30 s) ¨ Overtemperature on the static switch EN ¨ Measure the bypass voltage after F028 ¨ Controller A070
(F029...F030) ¨ Interface A071/ X010: F006/F007/F008
7RA9093GB
-
-
- 4A-1100475001/20GB 1 4/5
TROUBLE-SHOOTING
7RA9093GB
-
-
- 4A-1100475001/20GB 1 5/5