You are on page 1of 4

Fire Alarm Integration with FFS

System Ready
Device as per

Description /
Device label

Accepted
3rd Party
Loop No.

Location
Address

Lay-out
System
Panel

Type
Description / Location Remarks Date Verify

Location: GFG2 - Airlock Lobby 153 / (Alarm to be


1 5 141 CT1 ZCV SMM/STA/GFG1/D0105141‐INNER CON‐073 FHR ✔ ✔ ✖ ✔ 18-Feb-21
changed to supervisory) / (ZCV-6)
1 5 142 CT1 SMM/STA/GFG1/D0105141‐INNER CON‐073 ZCV Manual Pull Switch 18-Feb-21
1 6 395 CT2 WFS DMM/STA/GFG2/D0106395‐F&B STORE‐202 WFS ✔ ✔ ✖ ✔ Location: GFG2 / (WFS-2) 16-Feb-21
1 6 396 CT2 ZCV DMM/STA/GFG2/D0106396‐F&B STORE‐202 ZCV ✔ ✔ ✖ ✔ Location: GFG2 / (ZCV-2) 16-Feb-21
1 6 397 CT2 WFS DMM/STA/GFG2/D0106397‐F&B KIT‐151 WFS ✔ ✔ ✖ ✔ Location: GFG2 / (WFS-1) 16-Feb-21
1 6 398 CT2 ZCV DMM/STA/GFG2/D0106398‐F&B KIT‐151 ZCV ✔ ✔ ✖ ✔ Location: GFG2 / (ZCV-1) 16-Feb-21
1 6 403 CT2 WFS DMM/STA/GFG2/D0106403‐SHAFT‐G01 WFS ✔ ✔ ✖ ✔ Location: GFG2 / (WFS-5) 16-Feb-21
1 6 404 CT2 ZCV DMM/STA/GFG2/D0106404‐SHAFT‐G01 ZCV ✔ ✔ ✖ ✔ Location: GFG2 / (ZCV-5) 16-Feb-21
1 6 405 CT2 WFS DMM/STA/GFG2/D0106405‐SHAFT‐G01 WFS ✔ ✔ ✖ ✔ Location: GFG2 / (WFS-6) 16-Feb-21
1 6 406 CT2 ZCV DMM/STA/GFG2/D0106406‐SHAFT‐G01 ZCV ✔ ✔ ✖ ✔ Location: GFG2 / (ZCV-6) 16-Feb-21

2 2 459 CT2 DMM/STA/B3H/D0202459‐DRIVEWAY‐652 WFS ✔ ✔ ✖ ✔ Location: B3H / APS 03 18-Feb-21

2 2 460 CT2 DMM/STA/B3H/D0202460‐DRIVEWAY‐652 ZCV ✔ ✔ ✖ ✔ Location: B3H / APS 03 18-Feb-21

2 4 399 CT2 WFS DMM/STA/GFH/D0204399‐F&B CON‐095 WFS ✔ ✔ ✖ ✔ Location: GFH / (WFS-3) 20-Feb-21
2 4 400 CT2 ZCV DMM/STA/GFH/D0204400‐F&B CON‐095 ZCV ✔ ✔ ✖ ✔ Location: GFH / (ZCV-3) 20-Feb-21

3 1 183 CT2 ACV DMM/STA/B3A3/D0301183‐ICV 659 A5 ✖ ✔ ✖ ✔ Location: B3A3 - ICV 659 / ACV-PS 9 (Pressure Switch) 17-Feb-21

3 1 184 CT2 ACV DMM/STA/B3A3/D0301184‐ICV 659 A5 ✖ ✔ ✖ ✔ Location: B3A3 - ICV 659 / ACV-TS 9 (Tamper Switch) 17-Feb-21

3 1 185 CT2 ACV DMM/STA/B3A3/D0301185‐ICV 659 A4 ✖ ✔ ✖ ✔ Location: B3A3 - ICV 659 / ACV-PS 8 (Pressure Switch) 17-Feb-21

3 1 186 CT2 ACV DMM/STA/B3A3/D0301186‐ICV 659 A4 ✖ ✔ ✖ ✔ Location: B3A3 - ICV 659 / ACV-TS 8 (Tamper Switch) 17-Feb-21

3 1 187 CT2 ACV DMM/STA/B3A3/D0301187‐ICV 659 A3 ✖ ✔ ✖ ✔ Location: B3A3 - ICV 659 / ACV-PS 7 (Pressure Switch) 17-Feb-21

3 1 188 CT2 ACV DMM/STA/B3A3/D0301188‐ICV 659 A3 ✖ ✔ ✖ ✔ Location: B3A3 - ICV 659 / ACV-TS 7 (Tamper Switch) 17-Feb-21

3 1 189 CT2 ACV DMM/STA/B3A3/D0301189‐ICV 659 A2 ✖ ✔ ✖ ✔ Location: B3A3 - ICV 659 / ACV-PS 6 (Pressure Switch) 17-Feb-21

Location: B3A3 - ICV 659 / ACV-TS 6 (Tamper Switch) /


3 1 190 CT2 ACV DMM/STA/B3A3/D0301190‐ICV 659 A2 ✖ ✔ ✖ ✖ 17-Feb-21
NOT ALIGNED

3 1 191 CT2 ACV DMM/STA/B3A3/D0301191‐ICV 659 A1 ✖ ✔ ✖ ✔ Location: B3A3 - ICV 659 / ACV-PS 5 (Pressure Switch) 17-Feb-21

3 1 192 CT2 ACV DMM/STA/B3A3/D0301192‐ICV 659 A1 ✖ ✔ ✖ ✔ Location: B3A3 - ICV 659 / ACV-TS 5 (Tamper Switch) 17-Feb-21

3 1 237 CT2 DMM/STA/B3A3/D0301237‐DRIVEWAY‐645 FHR Location: B3A1 / SPARE 17-Feb-21


3 1 238 CT2 DMM/STA/B3A3/D0301238‐DRIVEWAY‐645 ZCV Location: B3A1 / SPARE 17-Feb-21

3 2 404 CT2 ACV DMM/STA/B3A1/D0302404‐DW‐645 WFS‐100F‐A1A ✖ ✔ ✖ ✔ Location: B3A1 - ICV 658 / ACV-PS 4 (Pressure Switch) 16-Feb-21

Location: B3A1 - ICV 658 / ACV-TS 4 (Tamper Switch) /


3 2 405 CT2 ACV DMM/STA/B3A1/D0302405‐DW‐645 WFS‐100F‐A1A ✖ ✔ ✖ ✖ 16-Feb-21
LEAKAGE & NOT ALIGNED

3 2 406 CT2 ACV DMM/STA/B3A1/D0302406‐DW‐645 WFS‐100F‐A1A ✖ ✔ ✖ ✔ Location: B3A1 - ICV 658 / ACV-PS 3 (Pressure Switch) 16-Feb-21

Location: B3A1 - ICV 658 / ACV-TS 3 (Tamper Switch) /


3 2 407 CT2 ACV DMM/STA/B3A1/D0302407‐DW‐645 WFS‐100F‐A1A ✖ ✔ ✖ ✖ 16-Feb-21
LEAKAGE & NOT ALIGNED

3 2 408 CT2 ACV DMM/STA/B3A1/D0302408‐DW‐645 WFS‐100F‐A1A ✖ ✔ ✖ ✔ Location: B3A1 - ICV 658 / ACV-PS 2 (Pressure Switch) 18-Feb-21

3 2 409 CT2 ACV DMM/STA/B3A1/D0302409‐DW‐645 WFS‐100F‐A1A ✖ ✔ ✖ ✔ Location: B3A1 - ICV 658 / ACV-TS 2 (Tamper Switch) 18-Feb-21

3 2 410 CT2 ACV DMM/STA/B3A1/D0302410‐DW‐645 WFS‐100F‐A1A ✖ ✔ ✖ ✔ Location: B3A1 - ICV 658 / ACV-PS 1 (Pressure Switch) 18-Feb-21

3 2 411 CT2 ACV DMM/STA/B3A1/D0302411‐DW‐645 WFS‐100F‐A1A ✖ ✔ ✖ ✔ Location: B3A1 - ICV 658 / ACV-TS 1 (Tamper Switch) 18-Feb-21

3 3 156 CT2 DMM/STA/B3A4/D0303156‐DW‐645 WFS‐100F‐A2B NOT YET PROGRAMMED / SPARE 18-Feb-21


3 3 157 CT2 DMM/STA/B3A4/D0303157‐DW‐645 ZCV‐100F‐A2B NOT YET PROGRAMMED / SPARE 18-Feb-21
Location: B2A2 / Alarm found in Supervisory (Wrong
3 4 421 CT2 WFS DMM/STA/B2A1/D0304421‐SHAFT‐A05 ZCV ✔ ✔ ✖ ✔ 21-Feb-21
Programming) / (WFS-1)
3 4 422 CT2 ZCV DMM/STA/B2A1/D0304422‐SHAFT‐A05 ZCV ✔ ✔ ✖ ✔ Location: B2A2 / (ZCV-1) 21-Feb-21
Location: B2A2 / Alarm found in Supervisory (Wrong
3 4 423 CT2 WFS DMM/STA/B2A1/D0304423‐SHAFT‐A05 ZCV ✔ ✔ ✖ ✔ 21-Feb-21
Programming) / (WFS-2)
3 4 424 CT2 ZCV DMM/STA/B2A1/D0304424‐SHAFT‐A05 ZCV ✔ ✔ ✖ ✔ Location: B2A2 / (ZCV-2) 21-Feb-21
3 4 425 CT2 WFS DMM/STA/B2A1/D0304425‐SHAFT‐A05 ZCV ✖ ✖ ✖ ✖ NOT YET PROGRAMMED 22-Feb-21
Fire Alarm Integration with FFS

System Ready
Device as per

Description /
Device label

Accepted
3rd Party
Loop No.

Location
Address

Lay-out
System
Panel

Type
Description / Location Remarks Date Verify

3 4 426 CT2 ZCV DMM/STA/B2A1/D0304426‐SHAFT‐A05 ZCV ✖ ✖ ✖ ✖ NOT YET PROGRAMMED 22-Feb-21


3 5 161 CT2 DMM/STA/B2A2/D0305161‐GALLERY‐715 FHR Location: B2A2 / BEAM CONTROLLER 18-Feb-21
3 5 162 CT2 DMM/STA/B2A2/D0305162‐GALLERY‐715 ZCV Location: B2A2 / BEAM CONTROLLER 18-Feb-21
4 2 390 CT2 DMM/STA/L2A2/D0402390‐KIT‐261 WFS ✔ ✔ ✖ ✔ Location: L2A2 / SPARE 18-Feb-21
4 2 391 CT2 DMM/STA/L2A2/D0402391‐KIT‐261 ZCV ✔ ✔ ✖ ✔ Location: L2A2 / SPARE 18-Feb-21
4 5 132 CT1 FHC SMM/STA/L3A1/D0405132‐CONC NR LTA605 FHR NOT YET PROGRAMMED 18-Feb-21
4 5 133 CT2 ZCV SMM/STA/L3A1/D0405133‐CONC NR LTA605 ZCV NOT YET PROGRAMMED 18-Feb-21

5 1 158 CT2 ACV DMM/STA/LB3B/D0501158‐ICV 667 B3 ✖ ✔ ✖ ✔ Location: B3B - ICV 667 / ACV-PS 3 (Pressure Switch) 21-Feb-21

5 1 159 CT2 ACV DMM/STA/LB3B/D0501159‐ICV 667 B3 ✖ ✔ ✖ ✔ Location: B3B - ICV 667 / ACV-TS 3 (Tamper Switch) 21-Feb-21

5 1 160 CT2 ACV DMM/STA/LB3B/D0501160‐ICV 667 B1 ✖ ✔ ✖ ✔ Location: B3B - ICV 667 / ACV-PS 2 (Pressure Switch) 21-Feb-21

5 1 161 CT2 ACV DMM/STA/LB3B/D0501161‐ICV 667 B1 ✖ ✔ ✖ ✔ Location: B3B - ICV 667 / ACV-TS 2 (Tamper Switch) 21-Feb-21

5 1 162 CT2 ACV DMM/STA/LB3B/D0501162‐ICV 667 B2 ✖ ✔ ✖ ✔ Location: B3B - ICV 667 / ACV-PS 1 (Pressure Switch) 17-Feb-21

Location: B3B - ICV 667 / ACV-TS 1 (Tamper Switch) /


5 1 163 CT2 ACV DMM/STA/LB3B/D0501163‐ICV 667 B2 ✖ ✔ ✖ ✖ 17-Feb-21
LEAKAGE & NOT ALIGNED
Module not shown in the FA Drawing / Location to be
5 2 440 CT1 SMM/STA/LB3B/D050240‐CORRIDOR‐059 FHR ✖ ✖ ✖ ✖ 17-Feb-21
verify
5 4 390 CT2 WFS DMM/STA/LGFB/D0504390‐SHAFT‐B01 WFS ✔ ✔ ✖ ✔ Location: GFB / (WFS-1) 16-Feb-21
5 4 391 CT2 ZCV DMM/STA/LGFB/D0504391‐SHAFT‐B01 ZCV ✔ ✔ ✖ ✔ Location: GFB / (ZCV-1) 16-Feb-21
5 4 433 CT2 WFS DMM/STA/LGFB/D0504433‐F&B KITCHEN107 WFS ✔ ✔ ✖ ✔ Location: GFB / No Pressure Gauge / (WFS-3) 20-Feb-21
5 4 434 CT2 ZCV DMM/STA/LGFB/D0504434‐F&B KITCHEN107 ZCV ✔ ✔ ✖ ✔ Location: GFB / No Pressure Gauge / (ZCV-3) 20-Feb-21
5 4 435 CT2 WFS DMM/STA/LGFB/D0504435‐F&B KITCHEN106 WFS ✔ ✔ ✖ ✔ Location: GFB / (WFS-2) 20-Feb-21
5 4 436 CT2 ZCV DMM/STA/LGFB/D0504436‐F&B KITCHEN106 ZCV ✔ ✔ ✖ ✔ Location: GFB / (ZCV-2) 20-Feb-21
5 8 383 CT2 WFS DMM/STA/L1B/D0508383‐SHAFT‐687‐104F‐B WFS ✔ ✔ ✖ ✔ Location: L1B - Shaft B01 / (WFS-1) 20-Feb-21
5 8 384 CT2 ZCV DMM/STA/L1B/D0508384‐SHAFT‐687‐104F‐B ZCV ✔ ✔ ✖ ✔ Location: L1B - Shaft B01 / (ZCV-1) 20-Feb-21
5 8 393 CT2 WFS DMM/STA/L1B/D0508393‐F&B CON‐061‐104F WFS ✖ ✖ ✖ ✖ Need Scaffolding / Double height area 22-Feb-21
5 8 394 CT2 ZCV DMM/STA/L1B/D0508394‐F&B CON‐061‐104F ZCV ✖ ✖ ✖ ✖ Need Scaffolding / Double height area 22-Feb-21
5 8 395 CT2 WFS DMM/STA/L1B/D0508395‐F&B CON‐F07‐104F WFS ✖ ✖ ✖ ✖ Need Scaffolding / Double height area 22-Feb-21
5 8 396 CT2 ZCV DMM/STA/L1B/D0508396‐F&B CON‐F07‐104F ZCV ✖ ✖ ✖ ✖ Need Scaffolding / Double height area 22-Feb-21
5 8 397 CT2 WFS DMM/STA/L1B/D0508397‐F&B CON‐060‐104F WFS ✖ ✖ ✖ ✖ Need Scaffolding / Double height area 21-Feb-21
5 8 398 CT2 ZCV DMM/STA/L1B/D0508398‐F&B CON‐060‐104F ZCV ✖ ✖ ✖ ✖ Need Scaffolding / Double height area 21-Feb-21

6 1 132 CT2 ACV DMM/STA/LB3D/D0601132‐I.C.V‐692 ZCV ✖ ✔ ✖ ✔ Location: B3D - ICV 692 / ACV-PS 6 (Pressure Switch) 17-Feb-21

Location: B3D - ICV 692 / ACV-TS 6 (Tamper Switch) /


6 1 133 CT2 ACV DMM/STA/LB3D/D0601133‐I.C.V‐692 ZCV ✖ ✔ ✖ ✖ 17-Feb-21
NOT ALIGNED

6 1 134 CT2 ACV DMM/STA/LB3D/D0601134‐I.C.V‐692 ZCV ✖ ✔ ✖ ✔ Location: B3D - ICV 692 / ACV-PS 5 (Pressure Switch) 17-Feb-21

6 1 135 CT2 ACV DMM/STA/LB3D/D0601135‐I.C.V‐692 ZCV ✖ ✔ ✖ ✔ Location: B3D - ICV 692 / ACV-TS 5 (Tamper Switch) 17-Feb-21

Location: B3D - ICV 692 / Leakage in FS & Alarm found


6 1 136 CT2 WFS DMM/STA/LB3D/D0601136‐I.C.V‐692 ZCV ✖ ✔ ✖ ✖ 17-Feb-21
in Supervisory / (WFS-2)

6 1 137 CT2 ZCV DMM/STA/LB3D/D0601137‐I.C.V‐692 ZCV ✖ ✔ ✖ ✔ Location: B3D - ICV 692 / (ZCV-2) 17-Feb-21

6 1 151 CT2 ACV DMM/STA/LB3C/D0601151‐ICV 691 ZCV ✖ ✔ ✖ ✔ Location: B3C1 - ICV 691 / ACV-PS 2 (Pressure Switch) 18-Feb-21

6 1 152 CT2 ACV DMM/STA/LB3C/D0601152‐ICV 691 ZCV ✖ ✔ ✖ ✔ Location: B3C1 - ICV 691 / ACV-TS 2 (Tamper Switch) 18-Feb-21

6 1 153 CT2 ACV DMM/STA/LB3C/D0601153‐ICV 691 ZCV ✖ ✔ ✖ ✔ Location: B3C1 - ICV 691 / ACV-PS 1 (Pressure Switch) 18-Feb-21

6 1 154 CT2 ACV DMM/STA/LB3C/D0601154‐ICV 691 ZCV ✖ ✔ ✖ ✔ Location: B3C1 - ICV 691 / ACV-TS 1 (Tamper Switch) 18-Feb-21

6 1 238 CT2 DMM/STA/LB3C/D0601238‐MEDIA STO‐069 FHR Location: B3C / SPARE 17-Feb-21


6 1 239 CT2 DMM/STA/LB3C/D0601238‐MEDIA STO‐069 ZCV Location: B3C / SPARE 17-Feb-21

6 4 384 CT2 WFS DMM/STA/LB1C/D0604384‐SHAFT‐C09 WFS ✖ ✖ ✖ ✖ No Access / Need to open the steel grating for access 21-Feb-21

6 4 385 CT2 ZCV DMM/STA/LB1C/D0604385‐SHAFT‐C09 ZCV ✖ ✖ ✖ ✖ No Access / Need to open the steel grating for access 21-Feb-21

7 3 178 CT2 FHC DMM/STA/LB1D/D0703178‐CORRIDOR‐207 FHR ✔ ✔ ✖ ✔ Location: B1D / SPARE 20-Feb-21


Fire Alarm Integration with FFS

System Ready
Device as per

Description /
Device label

Accepted
3rd Party
Loop No.

Location
Address

Lay-out
System
Panel

Type
Description / Location Remarks Date Verify

7 3 179 CT2 ZCV DMM/STA/LB1D/D0703179‐CORRIDOR‐207 ZCV ✔ ✔ ✖ ✔ Location: B1D / SPARE 20-Feb-21


7 4 432 CT1 SMM/STA/LGFD/D0704432‐F&B‐085 FHR ✔ ✔ ✖ ✔ Location: GFD / SPARE 20-Feb-21
7 5 126 CT1 SMM/STA/LGFD/D0705126‐LOBBY‐230 FHR ✔ ✔ ✖ ✔ Location: GFD - IDF 243 / APS-02 20-Feb-21
8 1 234 CT2 DMM/STA/B3E3/D0801234‐PLAYER TUNNEL‐ WFS Location: B3E3 - Waster Room 004 / MFSD 21-Feb-21
8 1 235 CT2 DMM/STA/B3E3/D0801235‐PLAYER TUNNEL‐ZCV Location: B3E3 - Waster Room 004 / MFSD 21-Feb-21

8 3 131 CT1 SMM/STA/B3E3/D0803131‐MASSAGE TM C‐ WFS ✖ ✖ ✖ ✖ Location: B3E3 - Massage RM 140 / SPARE 17-Feb-21

8 4 394 CT1 DMM/STA/B3E1/D0804394‐DRIVEWAY‐645 WFS Module for MFSD 17-Feb-21


8 4 429 CT2 DMM/STA/B3E2/D0804429‐DRIVEWAY FHR Location: B3E2 - Player Tunnel 1 / APS 02 17-Feb-21
8 4 430 CT2 DMM/STA/B3E2/D0804430‐DRIVEWAY ZCV Location: B3E2 - Player Tunnel 1 / APS 02 17-Feb-21
Location: B3G2 - DWAY 645 ICV700 (as per mimic) /
9 2 402 CT2 WFS DMM/STA/LB3F/D0902402‐DWAY‐645 ICV700 WFS ✖ ✔ ✖ ✔ 18-Feb-21
(WFS-3)
Location: B3G2 - DWAY 645 ICV700 (as per mimic) /
9 2 403 CT2 ZCV DMM/STA/LB3F/D0902403‐DWAY‐645 ICV700 ZCV ✖ ✔ ✖ ✔ 18-Feb-21
(ZCV-3)
Location: B3G2 - DWAY 645 ICV700 (as per mimic) /
9 2 404 CT2 WFS DMM/STA/LB3F/D0902404‐DWAY‐645 ICV700 WFS ✖ ✔ ✖ ✖ 18-Feb-21
Leakage in FS / (WFS-2)
Location: B3G2 - DWAY 645 ICV700 (as per mimic) /
9 2 405 CT2 ZCV DMM/STA/LB3F/D0902405‐DWAY‐645 ICV700 ZCV ✖ ✔ ✖ ✔ 18-Feb-21
(ZCV-2)
9 5 146 CT2 WFS DMM/STA/LGFF/D0905146‐F&B KIT‐027 WFS ✔ ✔ ✖ ✔ Location: GFF - Storage 245 / (WFS-3) 20-Feb-21
9 5 147 CT2 ZCV DMM/STA/LGFF/D0905147‐F&B KIT‐027 ZCV ✔ ✔ ✖ ✔ Location: GFF - Storage 245 / (ZCV-3) 20-Feb-21
10 7 188 CT2 DMM/STA/L4E/D1007188‐COMM CTRL RM080 WFS ✔ ✔ ✖ ✔ Location: L4E2 / SPARE 18-Feb-21
10 7 189 CT2 DMM/STA/L4E/D1007189‐COMM CTRL RM080 ZCV ✔ ✔ ✖ ✔ Location: L4E2 / SPARE 18-Feb-21
11 4 388 CT1 SMM/STA/L3G1/D1104388‐CONCOURSE‐10 FHR ✔ ✔ ✖ ✔ Location: L3G1 / SPARE 18-Feb-21

12 1 154 CT2 FHC DMM/STA/LGFE/D1201154‐SHAFT‐E06 FHR ✖ ✖ ✖ ✖ No Access / Need to provide Steel grating plate in shaft 21-Feb-21

12 1 155 CT2 ZCV DMM/STA/LGFE/D1201155‐SHAFT‐E06 ZCV ✖ ✖ ✖ ✖ No Access / Need to provide Steel grating plate in shaft 21-Feb-21

12 4 446 CT2 WFS DMM/STA/LGFE/D1204446‐SHAFT‐E06 WFS ✖ ✖ ✖ ✖ No Access / Need to provide Steel grating plate in shaft 21-Feb-21

12 4 447 CT2 ZCV DMM/STA/LGFE/D1204447‐SHAFT‐E06 ZCV ✖ ✖ ✖ ✖ No Access / Need to provide Steel grating plate in shaft 21-Feb-21

12 5 178 CT2 ACV DMM/STA/LGFE/D1205178‐F‐PRO‐364 ICV‐ZCV ✔ ✔ ✖ ✔ Location: GF07 - F. Pro 765 / ACV-PS 3 (Pressure Switch) 16-Feb-21

Location: GF07 - F. Pro 765 / ACV-TS 3 (Tamper Switch)


12 5 179 CT2 ACV DMM/STA/LGFE/D1205179‐F‐PRO‐364 ICV‐ZCV ✔ ✔ ✖ ✖ 16-Feb-21
/ NOT ALIGNED

12 5 180 CT2 ACV DMM/STA/LGFE/D1205180‐F‐PRO‐364 ICV‐ZCV ✔ ✔ ✖ ✔ Location: GF07 - F. Pro 765 / ACV-PS 4 (Pressure Switch) 16-Feb-21

Location: GF07 - F. Pro 765 / ACV-TS 4 (Tamper Switch)


12 5 181 CT2 ACV DMM/STA/LGFE/D1205181‐F‐PRO‐364 ICV‐ZCV ✔ ✔ ✖ ✖ 16-Feb-21
/ NOT ALIGNED
12 5 232 CT2 DMM/STA/LGFE/D1205232‐CORRIDOR‐734 FHR ✔ ✔ ✖ ✔ Location: GF08 / AEROSOL 20-Feb-21
12 5 233 CT2 DMM/STA/LGFE/D1205233‐CORRIDOR‐734 ZCV ✔ ✔ ✖ ✔ Location: GF08 / AEROSOL 20-Feb-21
13 1 132 CT2 WFS DMM/STA/LGFA/D1301132‐F&B‐101 WFS ✔ ✔ ✖ ✔ Location: GFA2 / (WFS-1) 20-Feb-21
13 1 133 CT2 ZCV DMM/STA/LGFA/D1301133‐F&B‐101 ZCV ✔ ✔ ✖ ✔ Location: GFA2 / (ZCV-1) 20-Feb-21
13 1 140 CT2 WFS DMM/STA/LGFA/D1301140‐F&B‐040 WFS ✔ ✔ ✖ ✔ Location: GFA1 / (WFS-2) 20-Feb-21
13 1 141 CT2 ZCV DMM/STA/LGFA/D1301141‐F&B ‐040 ZCV ✔ ✔ ✖ ✔ Location: GFA1 / (ZCV-2) 20-Feb-21
13 3 165 CT2 WFS DMM/STA/LGFA/D1303165‐TICKETING‐140 WFS ✔ ✔ ✖ ✔ Location: GFA1 / (WFS-3) 16-Feb-21
13 3 166 CT2 ZCV DMM/STA/LGFA/D1303166‐TICKETING‐140 ZCV ✔ ✔ ✖ ✔ Location: GFA1 / (ZCV-3) 16-Feb-21
13 3 167 CT2 WFS DMM/STA/LGFA/D1303167‐TICKETING‐140 WFS ✔ ✔ ✖ ✔ Location: GFA1 / (WFS-4) 16-Feb-21
13 3 168 CT2 ZCV DMM/STA/LGFA/D1303168‐TICKETING‐140 ZCV ✔ ✔ ✖ ✔ Location: GFA1 / (ZCV-4) 16-Feb-21
13 3 169 CT2 WFS DMM/STA/LGFA/D1303169‐TICKETING‐140 WFS ✔ ✔ ✖ ✔ Location: GFA1 / (WFS-5) 16-Feb-21
13 3 170 CT2 ZCV DMM/STA/LGFA/D1303170‐TICKETING‐140 ZCV ✔ ✔ ✖ ✔ Location: GFA1 / (ZCV-5) 16-Feb-21
13 3 171 CT2 WFS DMM/STA/LGFA/D1303171‐TICKETING‐140 WFS ✔ ✔ ✖ ✔ Location: GFA1 / (WFS-6) 16-Feb-21
13 3 172 CT2 ZCV DMM/STA/LGFA/D1303172‐TICKETING‐140 ZCV ✔ ✔ ✖ ✔ Location: GFA1 / (ZCV-6) 16-Feb-21
Location: GF15 - F. PRO 037 / ACV-PS 4 (Pressure
13 5 206 CT2 ACV DMM/STA/LGFA/D1305206‐F‐PRO‐037 ICV‐ZCV ✖ ✔ ✖ ✔ 16-Feb-21
Switch)
Location: GF15 - F. PRO 037 / ACV-TS 4 (Tamper Switch)
13 5 207 CT2 ACV DMM/STA/LGFA/D1305207‐F‐PRO‐037 ICV‐ZCV ✖ ✔ ✖ ✖ 16-Feb-21
/ LEAKAGE & NOT ALIGNED
Location: GF15 - F. PRO 037 / ACV-PS 3 (Pressure
13 5 208 CT2 ACV DMM/STA/LGFA/D1305208‐F‐PRO‐037 ICV‐ZCV ✖ ✔ ✖ ✔ 16-Feb-21
Switch)

13 5 209 CT2 ACV DMM/STA/LGFA/D1305209‐F‐PRO‐037 ICV‐ZCV ✖ ✔ ✖ ✔ Location: GF15 - F. PRO 037 / ACV-TS 3 (Tamper Switch) 16-Feb-21
Fire Alarm Integration with FFS

System Ready
Device as per

Description /
Device label

Accepted
3rd Party
Loop No.

Location
Address

Lay-out
System
Panel

Type
Description / Location Remarks Date Verify

13 6 406 CT2 WFS DMM/STA/L1A/D1306406‐F&B CON‐021‐104F WFS Need Scaffolding / Double Height Area 20-Feb-21
13 6 407 CT2 ZCV DMM/STA/L1A/D1306407‐F&B CON‐021‐104F ZCV Need Scaffolding / Double Height Area 20-Feb-21
13 6 408 CT2 WFS DMM/STA/L1A/D1306408‐F&B CON‐102‐104F WFS Need Scaffolding / Double Height Area 20-Feb-21
13 6 409 CT2 ZCV DMM/STA/L1A/D1306409‐F&B CON‐102‐104F ZCV Need Scaffolding / Double Height Area 20-Feb-21
14 2 419 CT2 DMM/STA/L2B/D1402419‐AHU RM 690 FHR ✔ ✔ ✖ ✔ SPARE 16-Feb-21
14 2 420 CT2 DMM/STA/L2B/D1402420‐AHU RM 690 ZCV ✔ ✔ ✖ ✔ SPARE 16-Feb-21
Module not shown in FA drawing / Location to be verify
15 1 145 CT1 SMM/STA/L2C2/D1501145‐AIR HANDLING 138 FHR 18-Feb-21
/ SPARE
17 4 398 CT2 FHC DMM/STA/L3F/D1704398‐CORRIDOR 031 FHR ✖ ✔ ✖ ✔ Location: L3F - Concourse 10 / (FHC-1) 18-Feb-21
17 4 399 CT2 ZCV DMM/STA/L3F/D1704399‐CORRIDOR 031 ZCV ✖ ✔ ✖ ✔ Location: L3F - Concourse 10 / (ZCV-1) 18-Feb-21
Location: L3H - Corridor 47 / No Pressure Gauge / (FHC-
18 3 146 CT2 FHC DMM/STA/L3H/D1803146‐CORRIDOR‐047 FHR ✔ ✔ ✖ ✔ 20-Feb-21
3)
Location: L3H - Corridor 47 / No Pressure Gauge / (ZCV-
18 3 147 CT2 ZCV DMM/STA/L3H/D1803147‐CORRIDOR‐047 ZCV ✔ ✔ ✖ ✔ 20-Feb-21
3)
19 1 132 CT2 ACV DMM/AUX/LGFA/D1901132‐SHAFTZCV ✔ ✔ ✖ ✔ Location: GFWA / ACV-PS 6 (Pressure Switch) 16-Feb-21
19 1 133 CT2 ACV DMM/AUX/LGFA/D1901133‐SHAFTZCV ✔ ✔ ✖ ✔ Location: GFWA / ACV-TS 6 (Tamper Switch) 16-Feb-21
19 1 134 CT2 ACV DMM/AUX/LGFA/D1901134‐SHAFTZCV ✔ ✔ ✖ ✔ Location: GFWA / ACV-PS 5 (Pressure Switch) 16-Feb-21
19 1 135 CT2 ACV DMM/AUX/LGFA/D1901135‐SHAFTZCV ✔ ✔ ✖ ✔ Location: GFWA / ACV-TS 5 (Tamper Switch) 16-Feb-21

19 2 384 CT1 SMM/AUX/LGFWA/D1902384‐OPEN/OFC‐074 FHR ✖ ✖ ✖ ✖ Location to be verify / Need to check in Mapping 21-Feb-21

19 2 408 CT2 FHC DMM/AUX/LGFA/D1902408‐STORAGE‐37 WFS ✔ ✔ ✖ ✔ Location: GFWA / (FHC-13) 22-Feb-21


19 2 409 CT2 ZCV DMM/AUX/LGFA/D1902409‐STORAGE‐37 WFS ✔ ✔ ✖ ✔ Location: GFWA / (ZCV-13) 22-Feb-21

You might also like