You are on page 1of 4

B238 Technical Data Sheet

Stainless Steel Ball and Stem

Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable flow.

Suitable Actuators
Non-Spring Spring
B238 ARB(X), NRQB(X) AFRB(X)

Dimensions (Inches [mm])

D C

H1 H2
Technical Data 2085
Fluid chilled, hot water, up to 60% glycol
Flow characteristic equal percentage E F B
Controllable flow range 75° A
Valve Size [mm] 1.5” [40]
ARB, ARX
Pipe connection NPT female ends
Housing Nickel-plated brass body
Ball stainless steel A B C D E F H1 H2
11.0” 3.9” 6.4” 5.3” 1.7” [44] 1.2” 0.6” [15]
Stem stainless steel [280] [100] [163] [134] [30]
Stem seal EPDM (lubricated)
Seat PTFE
O-ring EPDM (lubricated) Safety Notes
Characterised disc TEFZEL® WARNING: For Belimo products sold in California: these products do or may
Body Pressure Rating 400 psi
Date created, 09/11/2019 - Subject to change. © Belimo Aircontrols (USA), Inc.

contain chemicals which are known to the State of California to cause cancer
Close-off pressure ∆ps 200 psi and or birth defects or other reproductive harms. For more information see
Cv 19 www.p65warnings.ca.gov.
Weight 1.98 lb [0.90 kg]
Fluid Temp Range (water) 0...250°F [-18...120°C]
Leakage rate 0% for A – AB
Maintenance maintenance-free

Flow/Mounting Details

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


B238 Technical Data Sheet
Stainless Steel Ball and Stem

Dimensions (Inches [mm]) Dimensions (Inches [mm])

D C D C

E F B E F B
A A
ARB N4, ARX N4, NRB N4, NRX N4 AFRB N4, AFRX N4

A B C D E F A B C D E F
11.4” [289] 3.9” [100] 8.5” [217] 7.3” [185] 3.1” [80] 13.0” [330] 3.9” [100] 10.3” [262] 8.5” [216] 3.4” [86]

Dimensions (Inches [mm])

D C

H1 H2

E F B
A

Date created, 09/11/2019 - Subject to change. © Belimo Aircontrols (USA), Inc.


NRQB, NRQX

A B C D E F H1 H2
11.0” 3.9” 7.1” 6.0” 1.7” [44] 1.4” 0.6” [15]
[280] [100] [181] [152] [34]

Dimensions (Inches [mm])

D C

E F B
A
AFRB, AFRX

A B C D E F
10.8” [275] 3.9” [100] 9.0” [229] 7.8” [198] 2.0” [51]

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


ARB24-SR Technical Data Sheet
Modulating, Non-Spring Return, 24 V, for DC 2...10 V or 4...20 mA

Technical Data 2515


Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10%
Power consumption in operation 2.5 W
Power consumption in rest 0.4 W Safety Notes
position WARNING: For Belimo products sold in California: these products do or may
Transformer sizing 5 VA (class 2 power source)
contain chemicals which are known to the State of California to cause cancer
Electrical Connection 18 GA plenum cable, 3 ft [1 m], with 1/2” and or birth defects or other reproductive harms. For more information see
conduit connector www.p65warnings.ca.gov.
Overload Protection electronic thoughout 0...90° rotation
Operating Range DC 2...10 V, 4...20 mA w/ ZG-R01 (500 Ω,
1/4 W resistor)
Input Impedance 100 kΩ for DC 2...10 V (0.1 mA), 500 Ω for
4...20 mA
Position Feedback DC 2...10 V
Angle of rotation 90°
Direction of rotation motor reversible with built-in switch
Position indication Mechanically, pluggable
Manual override external push button
Running Time (Motor) 90 s
Date created, 09/11/2019 - Subject to change. © Belimo Aircontrols (USA), Inc.

Ambient humidity max. 95% r.H., non-condensing


Ambient temperature -22...122°F [-30...50°C]
Storage temperature -40...176°F [-40...80°C]
Degree of Protection IP54, NEMA 2
Agency Listing cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, CE acc. to 2004/108/EC
Noise level, motor 45 dB(A)
Maintenance maintenance-free
Quality Standard ISO 9001
Weight 2.2 lb [1.0 kg]
†Rated Impulse Voltage 800 V, Type action 1, Control Pollution Degree 3.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


ARB24-SR Technical Data Sheet
Modulating, Non-Spring Return, 24 V, for DC 2...10 V or 4...20 mA

Wiring Diagrams
INSTALLATION NOTES 24 VAC Transformer 2 18

Provide overload protection and disconnect as required. Line Blk (1) Common

Actuators may be connected in parallel. Power consumption and input Volts Red (2) Hot +
impedance must be observed. Ω
Only connect common to negative (-) leg of control circuits. Control Signal (–) 500 Ω
VDC/mA (+) Wht (3) Y Input, 2 to 10V
A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2
to 10 VDC.
Actuators with plenum cable do not have numbers; use color codes 2 to 10 VDC (–)
instead. Feedback Signal (+) Org (5) U Output

Meets cULus requirements without the need of an electrical ground


connection. 2 to 10 VDC / 4 to 20 mA Control

! WARNING! LIVE ELECTRICAL COMPONENTS!


During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components.
Have a qualified licensed electrician or other individual who has been
properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to
live electrical components could result in death or serious injury.

Date created, 09/11/2019 - Subject to change. © Belimo Aircontrols (USA), Inc.

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN