1.1 Description
Weishaupt WK-series industrial burners have been Reduced capacity at start up
especially designed for industrial use. The modular design A gas pilot line enables gas-firing burners to start operation at
principle enables these burners to be matched to a reduced ignition load (except vers. LN). Thus only a small
numerous special applications. A large capacity range amount of gas flows into the combustion chamber. After
supports the wide spectrum of applications. ignition the burner moves to partial load.
Modulating regulation
The burner’s output is matched, within its operating range, to
the current heat demand.
1.1 Description
Applications Designation
The burners are suitable for use with heat generators such as
hot-water boilers, steam boilers, air heaters and for certain WKG 70/3 – A / ZMH – NR
process applications. The combustion air must be free of
No suffix = Standard
aggressive substances (halogens, chlorides, fluorides) and NR = NOx reduced
impurities (dust, debris, vapours). Oil and gas installations must LN/1LN = Low-NOx
comply with prevalent standards. 3LN = multiflam
1SF = swirl flame
VSF = variable swirl flame
Permissible ambient conditions
• Ambient temperature -15 to +40 °C (in operation) Preheated air
• Humidity: ≤ 80 % relative humidity, no dew point
• Standard execution is suitable for indoor operation only Sliding two stage
Modulating
• Special measures are required for plant installed outdoors or
in unheated areas (please enquire) Mark
Capacity
Use of the burners in applications or ambient conditions not Size
detailed above must be assessed by Max Weishaupt GmbH.
G = Gas burner
The service intervals may be reduced in accordance with the L = Light-oil burner
GL = Dual-fuel burner (gas/light oil)
more extreme operational conditions. MS = Medium and heavy-oil burnerr
GMS = Dual-fuel burner (gas/heavy oil)
Type approval
Burner sizes 70 and 80 have been tested by an independent Weishaupt WK-series burner
body and conform to the following standards and directives:
Outstanding service
Weishaupt maintains an extensive global sales and service
network. Customer service is available every day around the
clock. In-house training by Weishaupt ensures the high
standard of the service engineers
1LN version
Low-NOx gas and dual-fuel burners with a special
mixing assembly for plant with gas and oil-side
NOx requirements. 1LN means lower NOx figures
compared to NR-version burners. Suitable for
natural gas, LPG, and light oil. Type-approved,
ZM-1LN (ambient-air) version natural-gas, LPG
and light oil burners conform gas-side to NOx
Class 3, and oil-side to NOx Class 2 in
accordance with EN 676 and EN 267.
LN version
Low-NOx gas burners with a special mixing
assembly for plant with gas-side NOx
requirements. LN means lower NOx figures
compared to 1LN-version burners. Suitable for
natural gas. Type-approved, ZM-LN (ambient-air)
version natural-gas burners conform to NOx Class
3 in accordance with EN 676
3LN version
Low-NOx gas and dual-fuel burners with a
multiflam mixing assembly for plant with extremely
low NOx requirements (three-pass and through-
pass boilers only). Fuel distribution results in
ultra-low NOx figures. Suitable for natural gas and
light oil. Type-approved, 3LN (ambient-air) version
natural gas and light oil burners conform to NOx
Class 3 in accordance with EN 676 and EN 267.
WKG 80/3-A ZM-NR
1) Not available with dual-screen Roman and Chinese-script version l Optional (expanded version)
(max. 10 m)
• O2 probe (QGO20)
or
• O2 diffusion probe
(QGO21 for
heavy oil)
Burner with inbuilt digital
combustion manager
T P 0-10 V
4-20 mA
Setpoint input
O2 module CO module
Gas feed
Burner-mounted / panel-mounted
Oil feed ABE control and display unit
Frequency convertor for
variable speed drive
Air feed
Regulating sleeve
(air)
CAN bus (max. 100 m)
PC / touchscreen
visualisation
Modbus
System networking
via PLC / DDC
250
Flue gas
200 Combustion air
Combustion-air preheating ºC
fan
Heat exchanger
150 (air preheater)
tA = 400°C
100
tA = 300°C
50 Heat generator
0 Combustion air,
92 91 90 89 88 87 86 85 84 83 82 81 max. 250 °C Burner
Efficiency %
Example:
Efficiency in % at a flue gas temperature of 300 °C/400 °C as
a function of combustion air temperature with air factor n = 1.1
Combustion efficiency without air preheating Combustion efficiency with air preheating
Hi – VA,f · n · C̄¯ pA · tA Hi – VA,f · n · C̄¯ pA · tA + VL · n · C̄¯ pL · tL
ηF = ·100 % ηF = ·100 %
Hi Hi
1. Technical data
6. Selecting a preheater
When electric and medium preheating are being used, the
electric preheater must cover at least 30 % of the cold-
start capacity. See the electric and medium preheaters
manual (Print No. 83001801) for pressure loss monitoring.
WK burner planning
Project
Customer Project Date
1) Appliance
Make/model Medium Comb. chamber length OK mm
2) Fuel
Oil type heavy oil Type of oil preheating Gas type natural gas
Nett calorific val. [Hi] 11.2 kWh/kg Oil temp. req. at nozzle 155 °C Relative density [d] (Luft = 1)
Viscosity 570 mm2/s Type of regulation Nett calorific val. [Hi] 10.35 kWh/m3
at ref. temperature 50 °C Turndown Gas flow pressure 2 000 mbar
3) General
Ambient temperature 20 °C Control voltage 230 V Max. sound press. level 85 dB(A)
4) Burner
Burner rating 8602 kW Comb. cham. vol. loading MW/m3 Check combustion chamber dimensions,
combustion chamber volume loading, burner
Oil trhoughput 768 kg/h For installation altitudes above 500 m: selection
Gas throughput 831 m3/h Notional burner rating kW Selected burner type
Calculated fan capacity 11612 m3/h Gas flow pressure before double solenoid valve 117 mbar
1) Appliance
Make/model Medium Comb. chamber length mm
2) Fuel
Oil type Type of oil preheating Gas type
Nett calorific val. [Hi] kWh/kg Oil temp. req. at nozzle °C Relative density [d] (air = 1)
3) General
Ambient temperature °C Control voltage V Max. sound press. level dB(A)
4) Burner
Burner rating kW Comb. cham. vol. loading MW/m3 Check combustion chamber dimensions,
combustion chamber volume loading, burner
Oil trhoughput kg/h For installation altitudes above 500 m: selection
3
Gas throughput m /h Notional burner rating kW Selected burner type
Calculated fan capacity m3/h Gas flow pressure before double solenoid valve mbar
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
4.2 NR version
4.2.2 Type WK70
Burner type Version Fuel Capacity range 0 2000 4000 6000 8000 10000 12000 kW
kW kg/h
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
4.4 LN version
4.4.1 Type WK40
Burner type Version Fuel Capacity range 0 500 1000 1500 2000 2500 3000 kW
kW kg/h
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
Note:
The WK 70, 3LN version, is not available as a single-fuel oil burner.
However, a special version dual-fuel burner “without gas valve train and
gas-side accessories” is available.
See price list for applicable price reduction.
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
200 °C combustion air temperatures (ZMH version) one of the full tone areas.
Note:
The WK 70, 3LN version, is not available as a single-fuel oil burner.
However, a special version dual-fuel burner “without gas valve train and
gas-side accessories” is available.
See price list for applicable price reduction.
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
100 °C combustion air temperatures (ZMH version) one of the full tone areas.
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
250 °C 6400
ZMH-1SF Heavy oil 2,490–9,600 222–856
250 °C 6400
ZMH-1SF Natural gas 1,300–9,600 –
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
1)
Capacities up to 32 MW on request (works approval required)
20 °C combustion air temperatures (ZM version) The full-tone and half-tone areas together show the total capacity range.
When sizing burners ensure that the required nominal rating lies within
250 °C combustion air temperatures (ZMH version) one of the full tone areas.
* On application
1)
Burner matchings for water-tube boilers (D-type). These must be verified by the works on an individual basis.
2)
Burner matchings for large-capacity boilers and thermal-fluid heaters. These must be verified by the works on an individual basis.
3)
Ratings up to 32 MW on application.
2,0
Factor
2.0
Burner _________________________ WKGMS70/3 ZMH-NR
1,9
1.9
1,1
1.1
Result 27.5 x 1.6 = 44.0 mbar 1,0
1.0
20 50 100 150 200 250
Combustion air temperature °C
20
Capacity reduction [ % ]
15
10
0
40 100 150 200 250
Question:
What burner rating can still be achieved with a combustion air
temperature of 170 °C?
Example:
Burner ______________________________ WK40/2-A ZMH
Order example for fan No. 696 062: Sound pressure level:
When ordering fans the following points Enveloping surface sound pressure
should be noted: level without sound insulation:
Order No. (50 Hz) _________ 696 062 Enveloping surface sound pressure
level, measured at a distance of
Air quantity at 20 °C. 1 metre from the open suction inlet
ρ = 1.2 kg/m3 _________ 2 500 m3/h with the pressure line connected in
accordance with DIN 45635 under
Static pressure ____________ 30 mbar free-field conditions.
* Sound reduction with complete encapsulation including integrated inlet silencer and grille
(pressure loss approx. 2.5 mbar):
Complete encapsulation will reduce the sound level to 75 dB(A) if the enveloping surface sound pressure level of the fan
without sound insulation is 87–107 dB(A).
Complete encapsulation will reduce the sound level to 80 dB(A) if the enveloping surface sound pressure level of the fan
without sound insulation is 108–112 dB(A).
Complete encapsulation will reduce the sound level to 85 dB(A) if the enveloping surface sound pressure level of the fan
without sound insulation is 113–117 dB(A).
696 036 1750 50 2925 3.7 5.5 0.48 84 94 143 16 207 P4K0 1
696 037 1750 55 2925 4.1 5.5 0.78 85 95 157 17 227 P5K5 1
696 038 1750 60 2925 4.4 5.5 0.78 85 95 157 17 227 P5K5 1
696 039 1750 65 2930 5 7.5 0.86 86 96 178 17 240 P5K5 1
696 040 1750 70 2930 5.3 7.5 0.86 86 96 178 17 240 P5K5 1
696 046 2000 50 2925 4.2 5.5 0.5 84 94 143 16 207 P5K5 1
696 047 2000 55 2925 4.5 5.5 0.81 84 94 157 17 227 P5K5 1
696 048 2000 60 2930 5 7.5 0.81 85 95 162 17 227 P5K5 1
696 049 2000 65 2930 5.7 7.5 1.06 86 96 197 19 259 P7K5 1
696 050 2000 70 2930 6.2 7.5 1.06 86 96 197 19 259 P7K5 1
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 056 2250 50 2925 4.8 5.5 0.68 85 95 164 17 232 P5K5 1
696 057 2250 55 2930 5 7.5 0.79 86 96 186 18 255 P5K5 1
696 058 2250 60 2930 5.7 7.5 0.79 86 96 186 18 255 P7K5 1
696 059 2250 65 2930 6.2 7.5 0.93 97 97 209 20 273 P7K5 1
696 060 2250 70 2940 6.8 11 1.05 87 97 269 20 288 P7K5 1
696 067 2500 55 2930 5.6 7.5 0.68 85 95 169 17 232 P7K5 1
696 068 2500 60 2930 6.1 7.5 0.79 85 95 186 18 255 P7K5 1
696 069 2500 65 2940 6.7 11 0.93 86 96 247 20 275 P7K5 1
696 070 2500 70 2940 7.6 11 1.05 86 96 269 20 288 P11K 1
696 071 2500 75 2940 7.8 11 1.05 87 97 269 20 288 P11K 1
696 072 2500 80 2940 8.5 11 1.05 87 97 269 20 288 P11K 1
696 079 2750 55 2930 5.8 7.5 0.83 85 95 188 18 255 P7K5 1
696 080 2750 60 2940 6.4 11 0.83 86 96 226 18 255 P7K5 1
696 081 2750 65 2940 7 11 0.98 86 96 247 19 272 P7K5 1
696 082 2750 70 2940 7.4 11 1.2 87 97 274 20 288 P7K5 1
696 083 2750 75 2940 8 11 1.2 87 97 274 20 288 P11K 1
696 084 2750 80 2940 8.5 11 1.65 88 98 276 22 326 P11K 1
696 091 3000 55 2930 6.2 7.5 0.83 87 97 226 18 255 P7K5 1
696 092 3000 60 2940 7.1 11 0.83 87 97 226 18 255 P7K5 1
696 093 3000 65 2940 7.6 11 0.98 87 97 247 19 272 P11K 1
696 094 3000 70 2940 8.4 11 1.2 89 99 274 20 288 P11K 1
696 095 3000 75 2940 8.5 11 1.2 89 99 274 20 288 P11K 1
696 096 3000 80 2940 9.8 15 1.65 90 100 285 22 326 P11K 1
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 121 3750 25 2925 3.8 5.5 0.53 83 93 160 15 224 P4K0 1
696 122 3750 30 2925 4.5 5.5 0.53 83 93 160 15 224 P5K5 1
696 123 3750 35 2930 5 7.5 0.53 84 94 165 15 224 P5K5 1
696 124 3750 40 2930 5.7 7.5 1.03 85 95 189 17 261 P7K5 1
696 125 3750 45 2930 6.4 7.5 1.03 86 96 189 17 261 P7K5 1
696 126 3750 50 2940 7.1 11 1.03 87 97 198 17 261 P7K5 1
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 145 4250 25 2925 4.1 5.5 0.55 84 94 179 16 260 P5K5 1
696 146 4250 30 2930 4.9 7.5 0.55 84 94 184 16 260 P5K5 1
696 147 4250 35 2930 5.6 7.5 0.55 85 95 184 16 260 P7K5 1
696 148 4250 40 2930 6.4 7.5 0.55 86 96 184 16 260 P7K5 1
696 149 4250 45 2940 7.2 11 1.08 86 96 227 18 271 P7K5 1
696 150 4250 50 2940 7.9 11 1.19 87 97 247 19 295 P11K 1
696 157 4500 25 2925 4.4 5.5 0.55 84 94 179 16 260 P5K5 1
696 158 4500 30 2930 5.2 7.5 0.55 84 94 184 16 260 P5K5 1
696 159 4500 35 2930 6 7.5 0.55 85 95 184 16 260 P7K5 1
696 160 4500 40 2940 6.8 11 1.08 86 96 227 18 271 P7K5 1
696 161 4500 45 2940 7.6 11 1.08 87 97 227 18 271 P11K 1
696 162 4500 50 2940 8.4 11 1.31 88 98 249 19 294 P11K 1
696 169 4750 25 2925 4.7 5.5 0.55 84 94 179 16 260 P5K5 1
696 170 4750 30 2930 5.5 7.5 0.55 85 95 184 16 260 P7K5 1
696 171 4750 35 2930 6.4 7.5 0.55 86 96 184 16 260 P7K5 1
696 172 4750 40 2940 7.2 11 1.08 87 97 227 18 271 P7K5 1
696 173 4750 45 2940 8.1 11 1.08 87 97 227 18 271 P11K 1
696 174 4750 50 2940 8.9 11 1.31 88 98 249 19 294 P11K 1
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 193 5500 30 2930 6.3 7.5 1.08 86 96 205 16 260 P7K5 1
696 194 5500 35 2940 7.3 11 1.1 86 96 244 18 297 P7K5 1
696 195 5500 40 2940 8.3 11 1.1 87 97 244 18 297 P11K 1
696 196 5500 45 2940 9.3 15 1.21 87 97 258 19 312 P11K 1
696 197 5500 50 2940 10.3 15 1.21 87 97 258 19 312 P11K 1
696 210 6000 60 2940 13.4 15 1.53 90 100 280 19 324 P15K 1
696 211 6000 65 2940 14.8 18.5 1.54 91 101 334 21 350 P15K 1
696 212 6000 70 2940 15.9 18.5 1.54 91 101 334 21 350 P18K 1
696 213 6000 75 2945 17 22 2.08 92 102 396 21 387 P18K 1
696 214 6000 80 2945 18 22 2.86 92 102 420 23 405 P18K 1
696 215 6000 85 2950 19.6 30 2.86 93 103 480 23 405 P22K 1
696 222 6500 60 2940 14.3 18.5 1.56 90 100 322 20 397 P15K 1
696 223 6500 65 2940 15.8 18.5 1.58 91 101 334 22 350 P18K 1
696 224 6500 70 2945 16.9 22 1.58 91 101 364 22 350 P18K 1
696 225 6500 75 2945 18.1 22 2.14 92 102 398 23 387 P18K 1
696 226 6500 80 2945 19.3 22 2.14 92 102 398 23 387 P22K 1
696 227 6500 85 2950 20.4 30 2.96 93 103 489 23 405 P22K 1
696 234 7000 60 2940 15.5 18.5 1.56 90 100 322 20 397 P18K 1
696 235 7000 65 2945 17.1 22 1.58 91 101 364 22 350 P18K 1
696 236 7000 70 2945 18.4 22 1.58 91 101 364 22 350 P18K 1
696 237 7000 75 2950 19.6 30 2.14 92 102 458 23 387 P22K 1
696 238 7000 80 2950 20.9 30 2.14 92 102 458 23 387 P22K 1
696 239 7000 85 2950 22.1 30 2.96 93 103 489 23 405 P22K 1
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 246 7500 60 2940 16.7 18.5 1.56 90 100 322 20 397 P18K 1
696 247 7500 65 2945 18.1 22 1.58 91 101 364 22 350 P18K 1
696 248 7500 70 2950 19.8 30 1.58 92 102 424 22 350 P22K 1
696 249 7500 75 2950 21.2 30 2.14 92 102 458 23 387 P22K 1
696 250 7500 80 2950 22.5 30 2.14 93 103 458 23 387 P22K 1
696 251 7500 85 2950 23.9 30 2.96 93 103 489 23 405 P30K 1
696 270 8500 60 2945 18.8 22 1.6 91 101 352 21 397 P22K 1
696 271 8500 65 2950 20.7 30 1.7 92 102 441 22 415 P22K 1
696 272 8500 70 2950 22.2 30 1.7 93 103 441 22 415 P22K 1
696 273 8500 75 2950 23.7 30 2.32 93 103 478 23 441 P22K 1
696 274 8500 80 2950 25.3 30 2.32 94 104 478 23 441 P30K 1
696 275 8500 85 2955 26.8 37 3.2 95 105 529 23 474 P30K 1
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 294 9500 60 2945 21.2 30 1.6 91 101 412 21 397 P22K 1
696 295 9500 65 2950 23.4 30 1.7 92 102 441 22 415 P22K 1
696 296 9500 70 2950 25.1 30 1.7 93 103 441 22 415 P22K 1
696 297 9500 75 2950 26.8 30 2.32 94 104 478 23 441 P30K 1
696 298 9500 80 2955 28.5 37 2.32 95 105 498 23 441 P30K 1
696 299 9500 85 2955 31 37 3.2 95 105 529 23 474 P37K 1
696 306 10000 60 2945 22.4 30 1.6 92 102 412 21 397 P22K 1
696 307 10000 65 2950 24.2 30 1.76 93 103 441 23 415 P22K 1
696 308 10000 70 2950 26 30 1.76 93 103 441 23 415 P22K 1
696 309 10000 75 2955 27.8 37 2.58 94 104 509 24 441 P30K 1
696 310 10000 80 2955 29.5 37 2.58 95 105 509 24 441 P30K 1
696 311 10000 85 2955 31.3 37 3.45 96 106 537 25 474 P37K 1
696 318 10500 60 2950 23.6 30 1.6 92 102 412 21 397 P22K 1
696 319 10500 65 2950 25.5 30 1.76 93 103 441 23 415 P22K 1
696 320 10500 70 2950 27.4 30 1.76 93 103 441 23 415 P30K 1
696 321 10500 75 2955 29.3 37 2.58 94 104 509 24 441 P30K 1
696 322 10500 80 2955 31.1 37 2.58 95 105 509 24 441 P30K 1
696 323 10500 85 2955 33 37 3.45 96 106 537 25 474 P37K
696 330 11000 60 2950 24.3 30 1.7 92 102 432 22 467 P22K 1
696 331 11000 65 2955 26.8 37 1.87 93 103 461 23 415 P30K 1
696 332 11000 70 2955 28.8 37 1.87 94 104 461 23 415 P30K 1
696 333 11000 75 2955 30.8 37 2.58 96 106 509 24 441 P30K 1
696 334 11000 80 2955 32.7 37 2.58 96 106 509 24 441 P37K 1
696 335 11000 85 2960 34.7 45 3.55 96 106 600 25 474 P37K 1
696 336 11000 90 2960 37.6 45 3.55 96 106 600 25 474 P45K 1
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 337 11500 35 2940 15.3 18.5 1.28 89 99 300 20 363 P15K 1
696 338 11500 40 2945 17.4 22 1.28 89 99 330 20 363 P18K 1
696 339 11500 45 2945 19.4 22 1.28 90 100 343 21 432 P22K 1
696 340 11500 50 2950 21.5 30 1.48 91 101 403 21 432 P22K 1
696 341 11500 55 2950 23.5 30 1.7 92 102 432 22 467 P22K 1
696 342 11500 60 2950 25.6 30 1.7 92 102 432 22 467 P22K 1
696 343 11500 65 2955 28.2 37 1.87 94 104 461 23 415 P30K 1
696 344 11500 70 2955 30.3 37 1.87 94 104 461 23 415 P30K 1
696 345 11500 75 2955 32.3 37 2.58 95 105 509 24 441 P37K 1
696 346 11500 80 2960 34.4 45 2.58 95 105 569 24 441 P37K 1
696 347 11500 85 2960 36.4 45 3.55 96 106 600 25 474 P37K 1
696 348 11500 90 2960 39.5 45 3.55 96 106 600 25 474 P45K 1
696 349 12000 35 2940 16.1 18.5 1.28 90 100 300 20 363 P18K 1
696 350 12000 40 2945 18.2 22 1.28 90 100 330 20 363 P18K 1
696 351 12000 45 2950 20.4 30 1.48 91 101 403 21 432 P22K 1
696 352 12000 50 2950 22.5 30 1.48 91 101 403 21 432 P22K 1
696 353 12000 55 2945 24.6 30 1.7 92 102 432 22 467 P22K 1
696 354 12000 60 2955 26.8 37 1.7 93 103 452 22 467 P30K 1
696 355 12000 65 2955 29.6 37 1.87 94 104 461 23 441 P30K 1
696 356 12000 70 2955 31.7 37 1.87 94 104 461 23 415 P30K 1
696 357 12000 75 2955 33.9 45 2.58 95 105 569 24 441 P37K 1
696 358 12000 80 2960 36 45 2.58 95 105 569 24 441 P37K 1
696 359 12000 85 2960 40.3 55 3.55 96 106 690 25 474 P45K 1
696 360 12000 90 2960 41.3 55 3.55 96 106 690 25 474 P45K 1
696 361 12500 35 2945 16.8 22 1.3 90 100 330 20 363 P18K 1
696 362 12500 40 2945 19.1 22 1.3 90 100 330 20 363 P18K 1
696 363 12500 45 2950 21.3 30 1.5 91 101 403 21 432 P22K 1
696 364 12500 50 2950 23.5 30 1.5 92 102 403 21 432 P22K 1
696 365 12500 55 2950 25.7 30 1.7 92 102 432 22 467 P22K 1
696 366 12500 60 2955 28 37 1.7 93 103 452 22 467 P30K 1
696 367 12500 65 2955 30.2 37 1.97 94 104 489 23 500 P30K 1
696 368 12500 70 2955 32.4 37 1.97 94 104 489 23 500 P30K 1
696 369 12500 75 2960 34.7 45 2.85 95 105 590 26 537 P37K 1
696 370 12500 80 2960 36.9 45 2.85 96 106 590 26 537 P37K 1
696 371 12500 85 2970 41.9 55 3.93 96 106 719 28 570 P45K 1
696 372 12500 90 2970 42.4 55 3.93 97 107 719 28 570 P45K 1
696 373 13000 35 2945 17.6 22 1.3 90 100 330 20 363 P18K 1
696 374 13000 40 2945 19.9 30 1.3 90 100 394 20 363 P22K 1
696 375 13000 45 2945 22.3 30 1.5 91 101 403 21 432 P22K 1
696 376 13000 50 2945 24.6 30 1.5 92 102 403 21 432 P22K 1
696 377 13000 55 2955 26.9 37 1.7 93 103 452 22 467 P30K 1
696 378 13000 60 2955 29.2 37 1.7 93 103 452 22 467 P30K 1
696 379 13000 65 2955 31.5 37 1.97 94 104 489 23 500 P30K 1
696 380 13000 70 2960 33.8 45 1.97 94 104 549 23 500 P37K 1
696 381 13000 75 2960 36.2 45 2.85 96 106 590 26 537 P37K 1
696 382 13000 80 2960 38.5 45 2.85 96 106 590 26 537 P37K 1
696 383 13000 85 2960 40.8 55 3.93 97 107 719 28 570 P45K 1
696 384 13000 90 2970 43.1 55 3.93 97 107 719 28 570 P45K 1
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 385 13500 35 2945 18.4 22 1.3 90 100 330 20 363 P18K 1
696 386 13500 40 2950 20.8 30 1.3 91 101 394 20 363 P22K 1
696 387 13500 45 2950 23.2 30 1.5 91 101 403 21 432 P22K 1
696 388 13500 50 2950 25.6 30 1.5 92 102 403 21 432 P22K 1
696 389 13500 55 2955 28.1 37 1.7 93 103 452 22 467 P30K 1
696 390 13500 60 2955 30.4 37 1.7 93 103 452 22 467 P30K 1
696 391 13500 65 2955 32.9 37 1.97 94 104 489 23 500 P37K 1
696 392 13500 70 2960 35.2 45 1.97 94 104 549 23 500 P37K 1
696 393 13500 75 2960 37.7 45 2.85 96 106 590 26 537 P37K 1
696 394 13500 80 2960 40.1 45 2.85 96 106 590 26 537 P45K 1
696 395 13500 85 2970 42.5 55 3.93 97 107 719 28 570 P45K 1
696 396 13500 90 2970 44.9 55 3.93 97 107 719 28 570 P45K 1
696 397 14000 35 2945 18.6 22 1.38 90 100 336 21 427 P18K 1
696 398 14000 40 2945 21.1 30 1.38 91 101 396 21 427 P22K 1
696 399 14000 45 2945 23.6 30 1.53 92 102 403 22 442 P22K 1
696 400 14000 50 2945 26.1 30 1.53 92 102 403 22 442 P22K 1
696 401 14000 55 2955 28.6 37 1.74 94 104 452 23 467 P30K 1
696 402 14000 60 2955 31.1 37 1.74 94 104 452 23 467 P30K 1
696 403 14000 65 2960 34.2 45 2.24 95 105 549 25 500 P30K 1
696 404 14000 70 2960 36.1 45 2.24 95 105 549 25 500 P30K 1
696 405 14000 75 2960 39.2 45 2.85 96 106 590 26 537 P45K 1
696 406 14000 80 2970 41.7 55 2.85 97 107 680 26 537 P45K 1
696 407 14000 85 2970 44.2 55 4.38 97 107 724 28 570 P45K 1
696 408 14000 90 2970 46.7 55 4.38 97 107 724 28 570 P55K 1
696 415 14500 65 2960 35.6 45 2.24 95 105 549 25 500 P37K 1
696 416 14500 70 2960 38.1 45 2.24 96 106 549 25 500 P37K 1
696 417 14500 75 2970 40.7 55 2.85 96 106 680 26 537 P45K 1
696 418 14500 80 2970 43.3 55 2.85 97 107 680 26 537 P45K 1
696 419 14500 85 2960 45.9 55 4.38 97 107 724 28 570 P55K 1
696 420 14500 90 2970 48.4 55 4.38 98 108 724 28 570 P55K 1
696 421 15000 35 2945 20.1 30 1.38 91 101 396 21 427 P22K 1
696 422 15000 40 2945 22.8 30 1.38 91 101 396 21 427 P22K 1
696 423 15000 45 2945 25.5 30 1.53 92 102 403 22 442 P22K 1
696 424 15000 50 2955 28.2 37 1.53 93 103 423 22 442 P30K 1
696 425 15000 55 2955 30.8 37 1.74 94 104 452 23 467 P30K 1
696 426 15000 60 2960 33.5 45 1.74 94 104 512 23 467 P37K 1
696 427 15000 65 2960 36.9 45 2.24 95 105 549 25 500 P37K 1
696 428 15000 70 2960 39.6 45 2.24 96 106 549 25 500 P37K 1
696 429 15000 75 2970 42.3 55 2.85 96 106 680 26 537 P45K 1
696 430 15000 80 2970 44.9 55 2.85 97 107 680 26 537 P45K 1
696 431 15000 85 2970 48.5 55 4.38 98 108 724 28 570 P55K 1
696 432 15000 90 2975 50.9 75 4.38 98 108 849 28 570 P55K 1
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 433 15500 35 2945 21.4 30 1.38 91 101 396 21 427 P22K 1
696 434 15500 40 2945 24 30 1.38 91 101 396 21 427 P22K 1
696 435 15500 45 2945 26.4 30 1.53 92 102 403 22 442 P22K 1
696 436 15500 50 2955 29.2 37 1.53 93 103 423 22 442 P30K 1
696 437 15500 55 2955 32 37 1.74 94 104 452 23 467 P30K 1
696 438 15500 60 2960 34.7 45 1.74 94 104 512 23 467 P37K 1
696 439 15500 65 2960 38.3 45 2.24 95 105 549 36 500 P37K 1
696 440 15500 70 2970 41.1 55 3.18 96 106 691 36 537 P45K 1
696 441 15500 75 2970 43.8 55 3.18 97 107 691 36 537 P45K 1
696 442 15500 80 2970 46.6 55 3.18 97 107 691 36 537 P45K 1
696 443 15500 85 2970 49.4 55 4.38 98 108 724 38 570 P55K 1
696 444 15500 90 2975 52.1 75 4.38 98 108 849 38 570 P55K 1
696 445 16000 35 2945 21.7 30 1.38 91 101 396 21 427 P22K 1
696 446 16000 40 2945 24.5 30 1.38 91 101 396 21 427 P22K 1
696 447 16000 45 2955 27.4 37 1.53 92 102 423 22 442 P30K 1
696 448 16000 50 2955 30.3 37 1.53 93 103 423 22 442 P30K 1
696 449 16000 55 2955 33.1 45 1.74 94 104 512 23 467 P30K 1
696 450 16000 60 2960 35.9 45 1.74 94 104 512 23 467 P37K 1
696 451 16000 65 2960 39.7 45 2.24 96 106 549 25 500 P37K 1
696 452 16000 70 2970 42.6 55 3.18 97 107 691 36 537 P45K 1
696 453 16000 75 2970 45.4 55 3.18 97 107 691 36 537 P45K 1
696 454 16000 80 2970 48.3 55 3.18 98 108 691 36 537 P55K 1
696 455 16000 85 2975 51.1 75 4.38 98 108 849 38 570 P55K 1
696 456 16000 90 2975 54 75 4.38 98 108 849 38 570 P55K 1
696 457 17000 35 2945 23.9 30 1.38 91 101 396 21 427 P22K 1
696 458 17000 40 2945 25.5 30 1.53 92 102 403 22 442 P22K 1
696 459 17000 45 2955 28.6 37 1.53 92 102 423 22 442 P30K 1
696 460 17000 50 2955 32.4 37 1.53 93 103 423 22 442 P30K 1
696 461 17000 55 2960 34.6 45 1.74 94 104 512 23 467 P37K 1
696 462 17000 60 2960 37.7 45 2.24 95 105 581 61 499 P37K 1
696 463 17000 65 2970 41.5 55 2.24 96 106 671 61 499 P45K 1
696 464 17000 70 2970 44.5 55 3.6 97 107 735 68 551 P45K 1
696 465 17000 75 2970 47.5 55 3.6 97 107 735 68 551 P55K 1
696 466 17000 80 2975 50.5 75 3.6 98 108 860 68 551 P55K
696 467 17000 85 2975 53.6 75 4.9 98 108 885 74 598 P55K 1
696 611 17000 90 2975 56.6 75 4.9 99 109 885 74 598 P75K 2
696 612 17000 95 2975 59.6 75 4.9 99 109 885 74 598 P75K 2
696 613 17000 100 2975 62.6 75 4.9 100 110 885 74 598 P75K 2
696 614 17000 105 2975 65.7 75 6.4 100 110 1005 85 681 P75K 2
696 615 17000 110 2975 68.7 90 6.4 101 111 1045 85 681 P75K 2
696 468 18000 35 2945 24.3 30 1.68 91 101 427 23 499 P30K 1
696 469 18000 40 2955 27.2 37 1.68 92 102 446 23 499 P30K 1
696 470 18000 45 2955 30.4 37 2.1 93 103 489 47 547 P30K 1
696 471 18000 50 2960 33.6 45 2.1 93 103 549 47 547 P37K 1
696 472 18000 55 2960 36.8 45 2.9 94 104 639 67 572 P37K 1
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 479 19000 40 2955 29.3 37 1.68 93 103 446 23 499 P30K 1
696 480 19000 45 2955 32.3 37 2.1 93 103 489 47 547 P30K 1
696 481 19000 50 2960 35.7 45 2.1 94 104 549 47 547 P37K 1
696 482 19000 55 2960 39.1 45 2.9 95 105 639 67 572 P45K 1
696 483 19000 60 2970 42.4 55 2.9 95 105 729 67 572 P45K 1
696 484 19000 65 2970 46.9 55 3.6 96 106 735 68 551 P45K 1
696 485 19000 70 2975 50.3 75 3.6 97 107 860 68 551 P55K 1
696 486 19000 75 2975 53.7 75 3.6 98 108 860 68 551 P55K 1
696 487 19000 80 2975 57.1 75 3.6 98 108 860 68 551 P55K 1
696 488 19000 85 2975 60.5 75 4.9 99 109 885 74 598 P55K 1
696 489 19000 90 2975 63.8 75 4.9 99 109 885 74 598 P55K 1
696 621 19000 95 2975 67.2 75 5.2 100 110 885 74 598 P75K 2
696 622 19000 100 2975 70.6 90 5.2 100 110 925 74 598 P75K 2
696 623 19000 105 2975 74 90 6.4 100 110 1045 85 681 P75K 2
696 624 19000 110 2975 77.4 90 6.4 101 111 1045 85 681 P75K 2
696 490 20000 40 2955 30.7 37 1.68 93 103 446 23 499 P30K 1
696 491 20000 45 2960 34.2 37 2.1 93 103 549 47 547 P37K 1
696 492 20000 50 2960 37.8 45 2.1 94 104 549 47 547 P37K 1
696 493 20000 55 2970 41.3 45 2.9 95 105 729 67 572 P45K 1
696 494 20000 60 2970 44.9 55 2.9 96 106 729 67 572 P45K 1
696 495 20000 65 2970 49.7 55 3.6 97 107 735 68 551 P55K 1
696 496 20000 70 2975 52 75 3.6 97 107 860 68 551 P55K 1
696 497 20000 75 2975 56.9 75 3.6 98 108 860 68 551 P55K 1
696 498 20000 80 2975 60.4 75 3.6 99 109 860 68 551 P55K 1
696 499 20000 85 2975 64 75 4.9 99 109 860 74 598 P55K 1
696 500 20000 90 2975 67.5 75 4.9 99 109 885 74 598 P75K 2
696 625 20000 95 2975 71.1 90 5.2 100 110 925 74 598 P75K 2
696 626 20000 100 2975 74.7 90 5.2 100 110 925 74 598 P75K 2
696 627 20000 105 2975 78.2 90 6.4 101 111 1045 85 681 P75K 2
696 628 20000 110 2982 81.8 90 6.4 101 111 1290 85 751 N90K 2
696 629 20000 115 2982 85.3 110 6.4 102 112 1290 85 751 N90K 2
696 630 20000 120 2982 88.9 110 6.8 102 112 1290 85 751 N90K 2
696 631 20000 125 2982 92.5 110 6.8 102 112 1290 85 751 N90K 2
696 632 20000 130 2982 96 110 6.8 103 113 1290 85 751 N90K 2
696 501 21000 40 2955 33.3 37 1.68 93 103 446 23 499 P30K 1
696 502 21000 45 2960 36.1 45 2.1 94 104 549 47 547 P37K 1
696 503 21000 50 2960 39.9 45 2.1 95 105 549 47 547 P37K 1
696 504 21000 55 2970 43.6 55 2.9 96 106 729 67 572 P45K 1
696 505 21000 60 2970 47.4 55 2.9 97 107 729 67 572 P45K 1
696 506 21000 65 2975 51.1 55 4.1 97 107 898 73 726 P55K 1
696 507 21000 70 2975 54.8 75 4.1 98 108 898 73 726 P55K 1
696 508 21000 75 2975 58.6 75 4.1 98 108 898 73 726 P55K 1
696 509 21000 80 2975 63.8 75 3.6 99 109 860 68 551 P55K 1
696 510 21000 85 2975 67.5 75 4.9 99 109 885 74 598 P75K 2
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 511 21000 90 2975 71.3 90 4.9 100 110 925 74 598 P75K 2
696 633 21000 95 2975 75 90 5.2 100 110 925 74 598 P75K 2
696 634 21000 100 2975 78.8 90 5.2 101 111 925 74 598 P75K 2
696 635 21000 105 2982 82.5 90 6.4 101 111 1290 85 751 N90K 2
696 636 21000 110 2982 86.2 110 6.4 102 112 1290 85 751 N90K 2
696 637 21000 115 2982 90 110 6.4 102 112 1290 85 751 N90K 2
696 638 21000 120 2982 93.7 110 6.8 102 112 1290 85 751 N90K 2
696 639 21000 125 2982 97.5 110 6.8 103 113 1290 85 751 N90K 2
696 640 21000 130 2982 101.2 110 9.4 103 113 1440 94 828 N132K 3
696 512 22000 40 2960 34.3 45 2.1 93 103 549 47 547 P37K 1
696 513 22000 45 2960 38.2 45 2.1 94 104 549 47 547 P37K 1
696 514 22000 50 2970 42.1 55 2.1 95 105 639 47 547 P45K 1
696 515 22000 55 2970 46 55 2.9 96 106 729 67 572 P45K 1
696 516 22000 60 2970 49.9 55 2.9 97 107 729 67 572 P55K 1
696 517 22000 65 2975 53.8 75 4.1 97 107 898 73 726 P55K 1
696 518 22000 70 2975 57.8 75 4.1 98 108 898 73 726 P55K 1
696 519 22000 75 2975 61.7 75 4.1 99 109 898 73 726 P55K 1
696 520 22000 80 2975 65.6 75 4.1 99 109 898 73 726 P55K 1
696 521 22000 85 2975 71.2 90 4.9 100 110 925 74 598 P75K 2
696 522 22000 90 2975 75.1 90 4.9 100 110 925 74 598 P75K 2
696 641 22000 95 2975 79 90 5.2 101 111 925 74 598 P75K 2
696 642 22000 100 2982 82.9 90 5.2 101 111 1160 74 651 N90K 2
696 643 22000 105 2982 86.8 110 6.4 101 111 1290 85 751 N90K 2
696 644 22000 110 2982 90.8 110 6.4 102 112 1290 85 751 N90K 2
696 645 22000 115 2982 94.7 110 6.4 102 112 1290 85 751 N90K 2
696 646 22000 120 2982 98.6 110 6.8 102 112 1345 85 751 N132K 3
696 647 22000 125 2982 102.5 132 6.8 103 113 1345 85 751 N132K 3
696 648 22000 130 2982 106.4 132 9.4 103 113 1440 94 828 N132K 3
696 523 23000 40 2960 36.1 45 2.1 94 104 549 47 547 P37K 1
696 524 23000 45 2960 40.2 45 2.1 95 105 549 47 547 P37K 1
696 525 23000 50 2970 44.2 55 2.9 96 106 729 67 572 P45K 1
696 526 23000 55 2970 48.4 55 2.9 96 106 729 67 572 P45K 1
696 527 23000 60 2975 51.2 75 4.1 97 107 898 73 726 P55K 1
696 528 23000 65 2975 56.6 75 4.1 98 108 898 73 726 P55K 1
696 529 23000 70 2975 60.6 75 4.1 98 108 898 73 726 P55K 1
696 530 23000 75 2975 64.7 75 5.3 99 109 928 73 756 P75K 2
696 531 23000 80 2975 68.8 75 5.3 99 109 928 73 756 P75K 2
696 532 23000 85 2975 74.8 90 4.9 100 110 925 74 598 P75K 2
696 533 23000 90 2975 78.9 90 4.9 101 111 925 74 598 P75K 2
696 649 23000 95 2982 83 90 5.2 101 111 1160 74 651 N90K 2
696 650 23000 100 2982 87.1 110 5.2 101 111 1160 74 651 N90K 2
696 651 23000 105 2982 91.2 110 6.4 102 112 1290 85 751 N90K 2
696 652 23000 110 2982 95.3 110 6.4 102 112 1290 85 751 N90K 2
696 653 23000 115 2982 99.4 110 6.4 102 112 1345 85 751 N132K 3
696 654 23000 120 2982 103.5 132 6.8 103 113 1345 85 751 N132K 3
696 655 23000 125 2982 107.6 132 6.8 103 113 1345 85 751 N132K 3
696 656 23000 130 2982 111.7 132 9.4 103 113 1440 94 828 N132K 3
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 543 24000 85 2975 76.4 90 4.9 100 110 968 76 740 P75K 2
696 544 24000 90 2975 80.7 90 4.9 101 111 968 76 740 N90K 2
696 657 24000 95 2982 85 90 5.8 101 111 1208 76 781 N90K 2
696 658 24000 100 2982 89.2 110 5.8 101 111 1208 76 781 N90K 2
696 659 24000 105 2982 93.5 110 7.4 102 112 1302 88 878 N90K 2
696 660 24000 110 2982 97.8 110 7.4 102 112 1302 88 878 N90K 2
696 661 24000 115 2982 102.1 110 7.4 102 112 1357 88 878 N132K 3
696 662 24000 120 2982 106.3 132 7.4 103 113 1357 88 878 N132K 3
696 663 24000 125 2982 110.6 132 7.9 103 113 1357 88 878 N132K 3
696 664 24000 130 2982 114.9 132 9.4 104 114 1535 102 902 N132K 3
696 551 25000 80 2975 75.6 90 5.2 100 110 968 75 740 P75K 2
696 552 25000 85 2975 80 90 5.2 100 110 968 75 740 N90K 2
696 553 25000 90 2982 84.4 90 5.4 101 111 1218 75 781 N90K 2
696 554 25000 95 2982 88.9 110 6.5 101 111 1302 78 878 N90K 2
696 555 25000 100 2982 93.3 110 6.5 102 112 1302 78 878 N90K 2
696 665 25000 105 2982 97.7 110 7.1 102 112 1302 78 878 N90K 2
696 666 25000 110 2982 102.2 110 7.4 102 112 1357 78 878 N132K 3
696 667 25000 115 2982 106.6 132 7.4 103 113 1357 78 878 N132K 3
696 668 25000 120 2982 111.1 132 7.4 103 113 1357 78 878 N132K 3
696 669 25000 125 2982 115.5 132 7.4 103 113 1357 78 878 N132K 3
696 670 25000 130 2982 120 132 10.5 104 114 1535 102 902 N132K 3
696 556 26000 50 2975 55.4 75 4.2 96 107 898 73 726 P55K 1
696 557 26000 55 2975 55.7 75 3.1 98 108 854 67 632 P55K 1
696 558 26000 60 2975 60.4 75 4.2 98 108 898 73 726 P55K 1
696 559 26000 65 2975 65 75 4.2 98 108 898 73 726 P55K 1
696 560 26000 70 2975 69.6 75 4.5 99 109 938 73 731 P75K 2
696 561 26000 75 2975 74.3 90 5.3 100 110 968 75 740 P75K 2
696 562 26000 80 2975 78.9 90 5.3 100 110 968 75 740 N90K 2
696 563 26000 85 2982 83.5 90 5.4 101 111 1218 75 781 N90K 2
696 564 26000 90 2982 88.1 110 5.6 101 111 1218 75 781 N90K 2
696 565 26000 95 2982 92.8 110 6.7 102 112 1302 78 878 N90K 2
696 566 26000 100 2982 97.4 110 6.7 102 112 1302 78 878 N110K 2
696 671 26000 105 2982 102 110 7.4 102 112 1357 78 878 N132K 3
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 672 26000 110 2982 106.6 132 7.4 102 112 1357 78 878 N132K 3
696 673 26000 115 2982 111.3 132 7.4 103 113 1357 78 878 N132K 3
696 674 26000 120 2982 115.9 132 7.4 103 113 1357 78 878 N132K 3
696 675 26000 125 2982 120.5 132 7.4 104 114 1357 78 878 N132K 3
696 676 26000 130 2982 125.2 160 10.5 104 114 1660 102 902 N132K 3
696 567 27000 50 2975 62.3 75 4.4 97 107 898 73 726 P55K 1
696 568 27000 55 2975 58.3 75 3.3 98 108 854 67 632 P55K 1
696 569 27000 60 2975 63.1 75 4.4 98 108 898 73 726 P55K 1
696 570 27000 65 2975 67.9 75 4.4 99 109 898 73 726 P75K 2
696 571 27000 70 2975 72.7 90 5.5 99 109 968 75 740 P75K 2
696 572 27000 75 2975 77.5 90 5.5 100 110 968 75 740 P75K 2
696 573 27000 80 2982 82.3 90 5.8 100 110 1208 75 781 N90K 2
696 574 27000 85 2982 87.1 110 5.8 101 111 1208 75 781 N90K 2
696 575 27000 90 2982 91.9 110 6.7 101 111 1302 78 878 N90K 2
696 576 27000 95 2982 96.7 110 7.1 102 112 1302 78 878 N110K 2
696 577 27000 100 2982 101.6 110 7.4 102 112 1357 78 878 N110K 2
696 677 27000 105 2982 106.3 132 7.4 102 112 1357 78 878 N132K 3
696 678 27000 110 2982 111.1 132 7.4 103 113 1357 78 878 N132K 3
696 679 27000 115 2982 115.9 132 7.4 103 113 1357 78 878 N132K 3
696 680 27000 120 2982 120.8 132 7.4 103 113 1357 78 878 N132K 3
696 681 27000 125 2982 125.6 160 7.9 103 113 1357 78 878 N132K 3
696 682 27000 130 2982 130.3 160 10.5 104 114 1660 102 902 N132K 3
696 578 28000 50 2975 56.4 75 6.5 96 107 1078 81 872 P55K 1
696 579 28000 55 2975 60.9 90 6.5 97 108 1118 81 872 P75K 2
696 580 28000 60 2975 63.5 75 5.2 98 108 988 79 817 P55K 1
696 581 28000 65 2975 68.5 75 5.2 99 109 1028 79 817 P75K 2
696 582 28000 70 2975 73.5 90 6.5 99 109 1118 81 872 P75K 2
696 583 28000 75 2975 78.5 90 6.5 100 110 1118 81 872 N90K 2
696 584 28000 80 2982 83.5 90 6.7 100 110 1378 81 890 N90K 2
696 585 28000 85 2982 88.4 110 6.7 101 111 1378 81 890 N90K 2
696 586 28000 90 2982 93.4 110 8.4 101 111 1442 87 918 N110K 2
696 587 28000 95 2982 98.4 110 8.4 102 112 1442 87 918 N110K 2
696 588 28000 100 2982 103.4 110 8.4 102 112 1497 87 918 N110K 2
696 683 28000 105 2982 108.4 132 8.9 102 112 1497 87 918 N132K 3
696 684 28000 110 2982 113.4 132 8.9 103 113 1497 87 918 N132K 3
696 685 28000 115 2982 118.4 132 8.9 103 113 1497 87 918 N132K 3
696 686 28000 120 2982 123.4 132 9.2 104 114 1622 87 918 N132K 3
696 687 28000 125 2982 128.4 160 9.2 104 114 1622 87 918 N132K 3
696 688 28000 130 2982 133.4 160 11.3 104 114 1698 113 1002 N132K 3
696 589 29000 50 2975 59.6 90 6.5 96 107 1118 81 872 P55K 1
696 590 29000 55 2975 63.4 90 6.5 97 108 1118 81 872 P75K 2
696 591 29000 60 2975 66.1 75 5.2 98 108 988 75 817 P75K 2
696 592 29000 65 2975 71.3 90 5.2 99 109 1028 75 817 P75K 2
696 593 29000 70 2975 76.4 90 6.5 99 109 1118 81 872 N90K 2
696 594 29000 75 2982 81.6 90 6.7 100 110 1378 81 890 N90K 2
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 595 29000 80 2982 86.8 110 6.7 100 110 1378 81 890 N90K 2
696 596 29000 85 2982 91.9 110 6.7 101 111 1442 81 890 N90K 2
696 597 29000 90 2982 97.1 110 8.4 101 111 1442 87 918 N110K 2
696 598 29000 95 2982 102.2 110 8.4 102 112 1497 87 918 N110K 2
696 599 29000 100 2982 107.4 132 8.4 102 112 1497 87 918 N110K 2
696 689 29000 105 2982 112.6 132 8.9 103 113 1497 87 918 N132K 3
696 690 29000 110 2982 117.7 132 8.9 103 113 1497 87 918 N132K 3
696 691 29000 115 2982 122.9 132 9.2 103 113 1622 87 918 N132K 3
696 692 29000 120 2982 128.1 160 9.2 104 114 1622 87 918 N132K 3
696 693 29000 125 2982 133.2 160 9.2 104 114 1622 87 918 N132K 3
696 694 29000 130 2982 138.4 160 11.3 104 114 1698 113 1002 N132K 3
696 606 30000 80 2982 90 110 6.7 100 110 1378 81 890 N90K 2
696 607 30000 85 2982 95.4 110 6.7 101 111 1378 81 890 N110K 2
696 608 30000 90 2982 100.7 110 8.4 102 112 1497 87 918 N110K 2
696 609 30000 95 2982 106.1 132 8.4 102 112 1497 87 918 N110K 2
696 610 30000 100 2982 111.4 132 8.4 103 113 1497 87 918 N110K 2
696 695 30000 105 2982 116.7 132 8.9 103 113 1497 87 918 N132K 3
696 696 30000 110 2982 122.1 132 9.2 103 113 1622 87 918 N132K 3
696 697 30000 115 2982 127.4 160 9.2 103 113 1622 87 918 N132K 3
696 698 30000 120 2982 132.8 160 9.2 104 114 1622 87 918 N132K 3
696 699 30000 125 2982 138.1 160 11.3 104 114 1698 113 1002 N132K 3
696 700 30000 130 2982 144 160 11.3 105 115 1698 113 1002 N132K 3
696 927 31000 50 2975 62.7 75 4.2 97 107 921 74 769 P75K 2
696 928 31000 55 2975 65.8 75 4.2 98 107 921 74 769 P75K 2
696 929 31000 60 2975 71.3 90 5.2 98 108 988 79 817 P75K 2
696 930 31000 65 2975 76.8 90 5.2 99 109 988 79 817 P75K 2
696 931 31000 70 2982 82.4 90 6.7 99 109 1378 81 890 N90K 2
696 932 31000 75 2982 87.9 110 6.7 100 110 1378 81 890 N90K 2
696 701 31000 80 2982 93.4 110 7.3 102 112 1378 81 890 N90K 2
696 702 31000 85 2982 98.9 110 7.3 102 112 1378 81 890 N90K 2
696 703 31000 90 2982 104.4 132 8.9 103 113 1497 87 918 N132K 3
696 704 31000 95 2982 110 132 8.9 103 113 1497 87 918 N132K 3
696 705 31000 100 2982 115.5 132 8.9 104 114 1497 87 918 N132K 3
696 706 31000 105 2982 121 132 9.2 104 114 1622 87 918 N132K 3
696 707 31000 110 2982 126.5 160 9.2 105 115 1622 87 918 N132K 3
696 708 31000 115 2982 132 160 9.2 105 115 1622 87 918 N132K 3
696 709 31000 120 2982 137.6 160 9.2 105 115 1622 87 918 N132K 3
696 710 31000 125 2982 143.1 160 11.3 105 115 1698 113 1002 N132K 3
696 711 31000 130 2982 148.6 160 11.3 106 115 2862 113 1224 N160K 3
696 933 32000 50 2975 63.4 75 4.2 97 107 921 74 769 P75K 2
696 934 32000 55 2975 68.3 75 4.2 98 107 921 74 769 P75K 2
696 935 32000 60 2975 74 90 5.2 99 109 988 79 817 P75K 2
696 936 32000 65 2975 79.7 90 5.2 99 109 988 79 817 P75K 2
696 937 32000 70 2982 85.4 90 6.7 100 110 1378 81 890 N90K 2
696 938 32000 75 2982 91.1 110 6.7 100 110 1378 81 890 N90K 2
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 712 32000 80 2982 96.8 110 7.3 102 112 1378 81 890 N90K 2
696 713 32000 85 2982 102.5 132 7.3 102 112 1433 81 890 N132K 3
696 714 32000 90 2982 108.1 132 8.9 103 113 1497 87 918 N132K 3
696 715 32000 95 2982 113.8 132 8.9 103 113 1497 87 918 N132K 3
696 716 32000 100 2982 119.5 132 9.2 104 114 1622 87 918 N132K 3
696 717 32000 105 2982 125.2 160 9.2 104 114 1622 87 918 N132K 3
696 718 32000 110 2982 130.9 160 9.2 105 115 1622 87 918 N132K 3
696 719 32000 115 2982 136.6 160 9.2 105 115 1622 87 918 N132K 3
696 720 32000 120 2982 142.3 160 9.2 105 115 1622 87 918 N132K 3
696 721 32000 125 2982 148 160 11.3 105 115 2862 113 1224 N160K 3
696 722 32000 130 2982 153.7 200 11.3 106 115 2862 113 1224 N160K 3
696 939 33000 50 2975 64.9 75 4.3 97 107 921 74 769 P75K 2
696 940 33000 55 2975 70.7 90 4.3 98 107 961 74 769 P75K 2
696 941 33000 60 2975 76.6 90 5.4 99 109 988 79 817 P75K 2
696 942 33000 65 2982 82.5 90 5.4 99 109 1248 79 851 N90K 2
696 943 33000 70 2982 88.4 110 6.7 100 110 1378 81 890 N90K 2
696 944 33000 75 2982 94.3 110 6.7 100 110 1378 81 890 N90K 2
696 945 33000 80 2982 100.1 110 6.9 101 111 1433 81 890 N110K 2
696 946 33000 85 2982 106 132 6.9 102 112 1433 81 890 N110K 2
696 723 33000 90 2982 111.9 132 8.9 103 113 1497 87 918 N132K 3
696 724 33000 95 2982 117.8 132 8.9 104 114 1497 87 918 N132K 3
696 725 33000 100 2982 123.6 160 9.2 104 114 1622 87 918 N132K 3
696 726 33000 105 2982 129.5 160 9.2 104 114 1622 87 918 N132K 3
696 727 33000 110 2982 135.4 160 9.2 105 115 1622 87 918 N132K 3
696 728 33000 115 2982 141.3 160 9.2 105 115 1622 87 918 N132K 3
696 729 33000 120 2982 147.1 160 9.4 105 114 2510 87 1097 N160K 3
696 730 33000 125 2982 153 200 11.3 106 115 2865 113 1224 N160K 3
696 731 33000 130 2982 158.9 200 11.3 106 115 2865 113 1224 N160K 3
696 732 33000 135 2982 164.8 200 11.3 106 115 2865 113 1224 N160K 3
696 733 33000 140 2982 170.6 200 11.8 107 115 2865 113 1224 N160K 3
696 947 34000 50 2975 67.2 75 4.4 97 107 921 74 769 P75K 2
696 948 34000 55 2975 73.3 90 4.4 98 107 961 74 769 P75K 2
696 949 34000 60 2975 79.3 90 5.4 99 109 988 79 817 P75K 2
696 950 34000 65 2982 85.4 110 6.9 99 109 1378 81 890 N90K 2
696 951 34000 70 2982 91.4 110 6.9 100 110 1378 81 890 N90K 2
696 952 34000 75 2982 97.5 110 6.9 101 111 1378 81 890 N90K 2
696 953 34000 80 2982 103.5 132 6.9 101 111 1433 81 890 N110K 2
696 954 34000 85 2982 109.6 132 6.9 102 112 1433 81 890 N110K 2
696 734 34000 90 2982 115.6 132 8.9 103 113 1497 87 918 N132K 3
696 735 34000 95 2982 121.7 132 9.2 104 114 1622 87 918 N132K 3
696 736 34000 100 2982 127.7 160 9.2 104 114 1622 87 918 N132K 3
696 737 34000 105 2982 133.8 160 9.2 104 114 1622 87 918 N132K 3
696 738 34000 110 2982 139.9 160 9.2 105 115 1622 87 918 N132K 3
696 739 34000 115 2982 145.9 160 9.4 105 114 2510 87 1097 N160K 3
696 740 34000 120 2982 152 200 9.4 105 114 2510 87 1097 N160K 3
696 741 34000 125 2982 158 200 11.3 106 115 2865 113 1224 N160K 3
696 742 34000 130 2982 164.1 200 11.3 106 115 2865 113 1224 N160K 3
696 743 34000 135 2982 170.1 200 11.3 106 115 2865 113 1224 N160K 3
696 744 34000 140 2982 176.2 200 11.8 107 115 2865 113 1224 N160K 3
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 955 35000 50 2975 69.7 90 4.4 97 107 961 74 769 P75K 2
696 956 35000 55 2975 75.9 90 4.4 98 107 961 74 769 P75K 2
696 957 35000 60 2982 82.1 90 5.4 99 109 1248 79 851 N90K 2
696 958 35000 65 2982 88.4 110 6.9 100 110 1378 81 890 N90K 2
696 959 35000 70 2982 94.6 110 6.9 100 110 1378 81 890 N90K 2
696 960 35000 75 2982 100.8 110 7.1 101 111 1433 81 890 N110K 2
696 961 35000 80 2982 107.1 132 7.1 101 111 1433 81 890 N110K 2
696 962 35000 85 2982 113.3 132 7.1 102 112 1433 81 890 N110K 2
696 745 35000 90 2982 119.5 132 9.2 103 113 1622 87 918 N132K 3
696 746 35000 95 2982 125.8 160 9.2 104 114 1622 87 918 N132K 3
696 747 35000 100 2982 132 160 9.2 104 114 1622 87 918 N132K 3
696 748 35000 105 2982 138.2 160 9.2 104 114 1622 87 918 N132K 3
696 749 35000 110 2982 144.5 160 9.4 105 114 2510 87 1097 N160K 3
696 750 35000 115 2982 150.7 200 9.4 105 114 2510 87 1097 N160K 3
696 751 35000 120 2982 156.9 200 9.4 105 114 2510 87 1097 N160K 3
696 752 35000 125 2982 163.2 200 11.3 106 115 2865 113 1224 N160K 3
696 753 35000 130 2982 169.4 200 11.3 106 115 2865 113 1224 N160K 3
696 754 35000 135 2982 175.6 200 11.3 107 115 2865 113 1224 N160K 3
696 755 35000 140 2982 181.9 200 11.8 107 116 3150 113 1289 N200K 4
696 756 36000 50 2975 72.1 90 4.4 98 107 961 74 769 P75K 2
696 757 36000 55 2975 78.5 90 4.4 98 107 961 74 769 P75K 2
696 758 36000 60 2982 84.9 110 5.4 99 109 1248 79 851 N90K 2
696 759 36000 65 2982 91.3 110 6.9 100 110 1378 81 890 N90K 2
696 760 36000 70 2982 97.7 110 6.9 100 110 1378 81 890 N90K 2
696 761 36000 75 2982 104.1 132 7.1 101 111 1433 81 890 N110K 2
696 762 36000 80 2982 110.5 132 7.1 101 111 1433 81 890 N132K 3
696 763 36000 85 2982 116.9 132 7.1 102 112 1433 81 890 N132K 3
696 764 36000 90 2982 123.3 160 9.2 102 112 1622 87 918 N132K 3
696 765 36000 95 2982 129.7 160 9.2 103 113 1622 87 918 N132K 3
696 766 36000 100 2982 136.2 160 9.2 103 113 1622 87 918 N132K 3
696 767 36000 105 2982 142.6 160 9.4 104 114 1622 87 918 N132K 3
696 768 36000 110 2982 149 200 9.6 104 114 1737 87 918 N132K 3
696 769 36000 115 2982 155.4 200 11.3 104 114 1963 113 1060 N160K 3
696 770 36000 120 2982 161.8 200 11.3 105 115 1963 113 1060 N160K 3
696 771 36000 125 2982 168.2 200 11.3 105 115 1963 113 1060 N160K 3
696 772 36000 130 2982 174.6 200 11.3 105 115 1963 113 1060 N160K 3
696 773 36000 135 2982 181 200 11.8 106 116 1963 113 1060 N160K 3
696 774 36000 140 2982 187.4 250 11.8 106 116 3150 113 1289 N200K 4
696 775 37000 50 2975 74.6 90 5.2 97 107 988 79 817 P75K 2
696 776 37000 55 2982 81.2 90 5.4 98 108 1248 79 851 N90K 2
696 777 37000 60 2982 87.8 110 6.7 99 109 1378 81 890 N90K 2
696 778 37000 65 2982 94.3 110 6.7 100 110 1378 81 890 N90K 2
696 779 37000 70 2982 97.9 110 6.7 100 110 1378 81 890 N90K 2
696 780 37000 75 2982 104.5 132 6.9 101 111 1433 81 890 N110K 2
696 781 37000 80 2982 111.1 132 6.9 101 111 1433 81 890 N110K 2
696 782 37000 85 2982 117.7 132 6.9 102 112 1433 81 890 N110K 2
696 783 37000 90 2982 124.3 160 9.2 102 112 1622 87 918 N132K 3
696 784 37000 95 2982 130.8 160 9.2 103 113 1622 87 918 N132K 3
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 785 37000 100 2982 137.4 160 9.2 103 113 1622 87 918 N132K 3
696 786 37000 105 2982 144 160 9.2 103 113 1622 87 918 N132K 3
696 787 37000 110 2982 150.6 200 9.6 104 114 1737 87 918 N132K 3
696 788 37000 115 2982 157.2 200 11.3 104 114 1963 113 1060 N160K 3
696 789 37000 120 2982 163.8 200 11.3 105 115 1963 113 1060 N160K 3
696 790 37000 125 2982 170.4 200 11.3 105 115 1963 113 1060 N160K 3
696 791 37000 130 2982 177 200 11.3 105 115 1963 113 1060 N160K 3
696 792 37000 135 2982 183.6 200 11.8 106 116 3150 113 1289 N200K 4
696 793 37000 140 2982 190.1 250 11.8 106 116 3150 113 1289 N200K 4
696 799 38000 75 2982 110.8 132 6.9 101 111 1433 81 890 N110K 2
696 800 38000 80 2982 117.6 132 6.9 102 112 1433 81 890 N110K 2
696 801 38000 85 2982 124.4 160 9.2 102 112 1622 87 918 N132K 3
696 802 38000 90 2982 131.1 160 9.2 103 113 1622 87 918 N132K 3
696 803 38000 95 2982 137.9 160 9.2 103 113 1622 87 918 N132K 3
696 804 38000 100 2982 144.7 160 9.2 103 113 1622 87 918 N132K 3
696 805 38000 105 2982 151.4 200 9.6 104 114 1737 87 918 N132K 3
696 806 38000 110 2982 158.2 200 9.6 104 114 1737 87 918 N160K 3
696 807 38000 115 2982 164.9 200 11.3 105 115 1963 113 1060 N160K 3
696 808 38000 120 2982 171.7 200 11.3 105 115 1963 113 1060 N160K 3
696 809 38000 125 2982 178.5 200 11.3 105 115 1963 113 1060 N160K 3
696 810 38000 130 2982 185.3 250 11.8 106 116 3150 113 1289 N200K 4
696 811 38000 135 2982 192 250 11.8 106 116 3150 113 1289 N200K 4
696 812 38000 140 2982 198.8 250 11.8 106 116 3150 113 1289 N200K 4
696 813 39000 50 2975 79.6 90 5.2 98 108 988 79 817 N90K 2
696 814 39000 55 2982 86.5 110 5.4 99 109 1248 79 851 N90K 2
696 815 39000 60 2982 93.5 110 6.7 99 109 1248 81 890 N90K 2
696 816 39000 65 2982 100.4 110 6.9 100 110 1433 81 890 N110K 2
696 817 39000 70 2982 107.4 132 6.9 101 111 1433 81 890 N110K 2
696 818 39000 75 2982 114.3 132 6.9 101 111 1433 81 890 N110K 2
696 819 39000 80 2982 121.3 132 7.1 102 112 1558 81 890 N132K 3
696 820 39000 85 2982 128.2 160 9.2 102 112 1622 87 918 N132K 3
696 821 39000 90 2982 135.1 160 9.2 103 113 1622 87 918 N132K 3
696 822 39000 95 2982 142.1 160 9.2 103 113 1622 87 918 N132K 3
696 823 39000 100 2982 149 200 9.4 104 114 1737 87 918 N132K 3
696 824 39000 105 2982 156 200 9.6 104 114 1737 87 918 N160K 3
696 825 39000 110 2982 162.9 200 9.6 104 114 1737 87 918 N160K 3
696 826 39000 115 2982 169.9 200 11.3 105 115 1963 113 1060 N160K 3
696 827 39000 120 2982 176.8 200 11.3 105 115 1963 113 1060 N160K 3
696 828 39000 125 2982 183.8 200 11.8 105 115 3150 113 1289 N200K 4
696 829 39000 130 2982 190.7 250 11.8 106 116 3150 113 1289 N200K 4
696 830 39000 135 2982 197.6 250 11.8 106 116 3150 113 1289 N200K 4
696 831 39000 140 2982 204.6 250 11.8 106 116 3150 113 1289 N200K 4
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 832 40000 50 1486 75.4 90 31.5 94 104 1381 189 1122 P75K 3
696 833 40000 55 1490 82.5 90 39.7 95 104 1543 236 1201 N90K 3
696 834 40000 60 1490 89.6 110 39.7 95 105 1693 236 1201 N90K 3
696 835 40000 65 1490 96.7 110 39.7 96 106 1693 236 1201 N90K 3
696 836 40000 70 1488 103.8 132 45.2 96 106 1935 282 1280 N110K 4
696 837 40000 75 1488 111 132 56.9 97 107 2268 314 1302 N132K 4
696 838 40000 80 1488 118.1 132 56.9 98 108 2268 314 1302 N132K 4
696 839 40000 85 1488 125.2 160 73.6 98 108 2687 not available 1466 N132K 4
696 840 40000 90 1488 132.3 160 73.6 99 109 2687 not available 1466 N132K 4
696 841 40000 95 1488 142 160 82.9 99 109 2812 not available 1383 N160K 5
696 842 40000 100 1490 149.1 200 89.5 100 110 3112 not available 1402 N160K 5
696 843 40000 105 1490 156.3 200 96.7 100 110 3357 not available 1557 N160K 5
696 844 40000 110 1490 163.4 200 109.3 100 110 3706 not available 1730 N160K 6
696 845 40000 115 1490 170.5 200 130.3 101 111 4071 not available 1792 N160K 8
696 846 40000 120 1490 177.6 200 132.3 101 111 4071 not available 1792 N160K 8
696 847 40000 125 1488 184.8 200 141.4 101 111 5108 not available 2689 N200K 6
696 848 40000 130 1488 191.9 250 150.9 102 112 5714 not available 2735 N200K 12
696 849 40000 135 1488 199 250 160.9 102 112 6093 not available 2810 N200K 16
696 850 40000 140 1488 206.1 250 171.1 102 112 6093 not available 2810 N250K 16
696 851 41000 50 1486 77.5 90 31.5 94 104 1381 189 1122 P75K 3
696 852 41000 55 1490 84.8 110 39.7 95 105 1693 236 1201 N90K 4
696 853 41000 60 1490 92.1 110 39.7 95 105 1693 236 1201 N90K 4
696 854 41000 65 1488 99.4 110 39.7 96 106 1693 236 1201 N110K 4
696 855 41000 70 1488 106.7 132 45.2 97 107 1935 282 1280 N110K 4
696 856 41000 75 1488 114 132 56.9 97 107 2268 314 1302 N132K 4
696 857 41000 80 1488 121.3 132 56.9 98 108 2268 314 1302 N132K 4
696 858 41000 85 1488 128.6 160 73.6 98 108 2687 not available 1466 N132K 4
696 859 41000 90 1488 135.9 160 73.6 99 109 2687 not available 1466 N132K 4
696 860 41000 95 1490 146 160 82.9 99 109 2812 not available 1383 N160K 8
696 861 41000 100 1490 153.3 200 89.5 100 110 3112 not available 1402 N160K 8
696 862 41000 105 1490 160.6 200 96.7 100 110 3357 not available 1557 N160K 8
696 863 41000 110 1490 167.9 200 109.3 101 111 3706 not available 1730 N160K 8
696 864 41000 115 1490 175.2 200 130.3 101 111 4071 not available 1792 N200K 10
696 865 41000 120 1488 182.5 200 132.3 101 111 4071 not available 2660 N200K 12
696 866 41000 125 1488 189.8 250 141.4 102 112 5348 not available 2689 N200K 12
696 867 41000 130 1488 197.1 250 150.9 102 112 5714 not available 2735 N200K 16
696 868 41000 135 1488 204.4 250 160.9 102 112 6093 not available 2810 N200K 16
696 869 41000 140 1488 211.7 250 171.1 102 112 6093 not available 2810 N250K 16
696 870 42000 50 1486 79.1 90 39.7 94 104 1543 236 1201 P75K 4
696 871 42000 55 1490 87.1 110 39.7 95 105 1693 236 1201 N90K 4
696 872 42000 60 1490 94.5 110 39.7 95 105 1693 236 1201 N90K 4
696 873 42000 65 1488 102 132 39.7 96 106 1773 236 1201 N110K 4
696 874 42000 70 1488 109.5 132 45.2 97 107 1935 282 1280 N110K 4
696 875 42000 75 1488 117 132 56.9 97 107 2268 314 1302 N132K 4
696 876 42000 80 1488 124.4 160 56.9 98 108 2413 314 1302 N132K 4
696 877 42000 85 1488 131.9 160 73.6 98 108 2687 not available 1466 N132K 4
696 878 42000 90 1488 139.4 160 73.6 99 109 2687 not available 1466 N132K 4
696 879 42000 95 1490 149.8 200 82.9 99 109 2917 not available 1383 N160K 8
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
696 880 42000 100 1490 157.4 200 89.5 100 110 3112 not available 1402 N160K 8
696 881 42000 105 1490 165.3 200 96.7 100 110 3357 not available 1557 N160K 8
696 882 42000 110 1490 172.3 200 109.3 101 111 3706 not available 1730 N160K 8
696 883 42000 115 1490 179.8 200 130.3 101 111 4071 not available 1792 N160K 10
696 884 42000 120 1488 187.3 250 132.3 101 111 4993 not available 2660 N200K 12
696 885 42000 125 1488 194.7 250 141.4 102 112 5348 not available 2689 N200K 12
696 886 42000 130 1488 202.2 250 150.9 102 112 5714 not available 2735 N200K 16
696 887 42000 135 1488 209.7 250 160.9 102 112 6093 not available 2810 N200K 16
696 888 42000 140 1488 217.2 250 171.1 103 113 6093 not available 2810 N200K 16
696 889 43000 50 1486 79.8 90.0 38.5 94 104 1588 195 1198 N110K 4
696 890 43000 55 1490 87.4 110 50.7 95 105 1864 254 1274 N110K 4
696 891 43000 60 1490 95.1 110 50.7 95 105 1864 254 1274 N110K 4
696 892 43000 65 1488 102.8 132 57.8 96 106 2097 298 1416 N132K 6
696 893 43000 70 1488 112.4 132 66.4 97 107 2268 314 1302 N132K 6
696 894 43000 75 1488 120.1 132 66.4 98 108 2268 314 1302 N132K 6
696 895 43000 80 1488 127.7 160 78.2 98 108 2687 not available 1466 N132K 6
696 896 43000 85 1488 135.4 160 78.2 98 108 2687 not available 1466 N132K 6
696 897 43000 90 1490 146.2 160 86.9 99 109 2812 not available 1383 N160K 8
696 898 43000 95 1490 153.9 200 86.9 99 109 2917 not available 1383 N160K 8
696 899 43000 100 1490 161.6 200 95.4 100 110 3112 not available 1402 N160K 8
696 900 43000 105 1490 169.2 200 100.3 100 110 3357 not available 1557 N160K 8
696 901 43000 110 1490 176.9 200 113.2 101 111 3706 not available 1730 N160K 8
696 902 43000 115 1488 184.5 200 137.1 101 111 4071 not available 2660 N200K 12
696 903 43000 120 1488 192.2 250 137.1 101 111 4993 not available 2660 N200K 12
696 904 43000 125 1488 199.8 250 146.2 102 112 5348 not available 2689 N200K 12
696 905 43000 130 1488 207.5 250 157.1 102 112 5714 not available 2735 N200K 16
696 906 43000 135 1488 215.1 250 174.2 102 112 6093 not available 2810 N200K 16
696 907 43000 140 1488 222.8 250 174.2 103 113 6093 not available 2810 N200K 16
696 908 44000 50 1490 81.8 90 38.5 94 104 1633 195 1236 N110K 4
696 909 44000 55 1490 89.6 110 50.7 95 105 1864 254 1274 N110K 4
696 910 44000 60 1490 97.5 110 50.7 95 105 1864 254 1274 N110K 4
696 911 44000 65 1488 105.3 132 60.1 96 106 2097 298 1416 N132K 6
696 912 44000 70 1488 115.3 132 69.3 97 107 2268 314 1302 N132K 6
696 913 44000 75 1488 123.2 160 69.3 98 108 2413 314 1302 N132K 6
696 914 44000 80 1488 131 160 81.3 98 108 2687 not available 1466 N132K 6
696 915 44000 85 1488 138.8 160 81.3 99 109 2687 not available 1466 N132K 6
696 916 44000 90 1490 150 200 89.9 99 109 2917 not available 1383 N160K 8
696 917 44000 95 1490 157.8 200 89.9 100 110 2917 not available 1383 N160K 8
696 918 44000 100 1490 165.6 200 99.6 100 110 3112 not available 1402 N160K 8
696 919 44000 105 1490 173.5 200 106.8 101 111 3357 not available 1557 N160K 8
696 920 44000 110 1488 181.3 200 118.2 101 111 3706 not available 2564 N200K 8
696 921 44000 115 1488 189.1 250 142.5 101 111 4993 not available 2660 N200K 12
696 922 44000 120 1488 197 250 142.5 102 112 4993 not available 2660 N200K 12
696 923 44000 125 1488 204.8 250 151.2 102 112 5348 not available 2689 N200K 16
696 924 44000 130 1488 212.6 250 160.3 102 112 5714 not available 2735 N200K 16
696 925 44000 135 1488 220.5 250 182.9 103 113 6093 not available 2810 N200K 16
696 926 44000 140 1488 228.3 250 182.9 103 113 6093 not available 2810 N250K 16
* Voltage 400 V, frequency 50 Hz. IE2 high-efficiency motor. For other voltages and/or frequencies, or for installation altitudes above 500 m, please enquire.
m³/min mbar kW A kg
ATTENTION
0,17
0,2
0,3
450...500 mm
A=1
Approx. burner Pump technical data Nominal connection diameter Version with 1 pump
rating range Capacity Speed Motor Pump inlet Burner supply Pump return Pump type Part No.
kg/h l/h rpm kW
up to 101 240 1400 0.75 DN15 / Ø21.3 DN15 / Ø21.3 DN15 / Ø21.3 MOG 5305-So-Wh EL 27000854
101–164 390 1400 1.10 DN15 / Ø21.3 DN15 / Ø21.3 DN15 / Ø21.3 MOG 5306-So-Wh EL 27000855
164–227 540 1400 1.50 DN15 / Ø21.3 DN15 / Ø21.3 DN15 / Ø21.3 MOG 5307-So-Wh EL 27000856
227–294 700 1400 2.20 DN25 / Ø33.7 DN25 / Ø33.7 DN25 / Ø33.7 MOG 5308-So-Wh EL 27000857
294–504 1200 1400 3.00 DN25 / Ø33.7 DN25 / Ø33.7 DN25 / Ø33.7 MOG 5309-So-Wh EL 27000858
504–600 1428 2900 2.20 DN32 / Ø42.4 DN25 / Ø33.7 DN25 / Ø33.7 LFW-15-EL 27000801
600–789 1878 2900 3.00 DN32 / Ø42.4 DN25 / Ø33.7 DN25 / Ø33.7 LFW-20-EL 27000802
789–1011 2406 2900 3.00 DN32 / Ø42.4 DN32 / Ø42.4 DN32 / Ø42.4 LFW-26-EL 27000803
1011–1338 3186 2900 4.00 DN32 / Ø42.4 DN32 / Ø42.4 DN32 / Ø42.4 LFW-32-EL 27000804
1338–1784 4248 2900 5.50 DN40 / Ø48.3 DN40 / Ø48.3 DN40 / Ø48.3 LFW-42-EL 27000805
1784–2379 5664 2900 7.50 DN50 / Ø60.3 DN50 / Ø60.3 DN40 / Ø48.3 LFW-54-EL 27000806
up to 122 290 1680 0.86 DN15 / Ø21.3 DN15 / Ø21.3 DN15 / Ø21.3 MOG 5305-So-Wh EL 27000854
122–197 470 1680 1.3 DN15 / Ø21.3 DN15 / Ø21.3 DN15 / Ø21.3 MOG 5306-So-Wh EL 27000855
197–273 650 1680 1.75 DN15 / Ø21.3 DN15 / Ø21.3 DN15 / Ø21.3 MOG 5307-So-Wh EL 27000856
273–353 840 1680 2.55 DN25 / Ø33.7 DN25 / Ø33.7 DN25 / Ø33.7 MOG 5308-So-Wh EL 27000857
Approx. burner Pump technical data Nominal connection diameter Version with 1 pump
rating range Capacity Speed Motor Pump inlet Burner supply Pump return Pump type Part No.
kg/h l/h rpm kW
up to 223 456 2900 1.10 DN25 / Ø33.7 DN20/Ø26.9 DN20/Ø26.9 LFW-5-S 27000848
up to 282 576 3450 1.3 DN25 / Ø33.7 DN20/Ø26.9 DN20/Ø26.9 LFW-5-S 27000859
Approx. burner Pump technical data Nominal connection diameter Version with 2 pumps
rating range Capacity Speed Motor Pump inlet Burner supply Pump return Pump type Part No.
kg/h l/h rpm kW
Light oil 6 mm²s. ℓ=0.84 kg/l. 50 Hz frequency* (with 0.25 mm mesh strainer)
Light oil 6 mm²s. ℓ=0.84 kg/l. 60 Hz frequency* (with 0.25 mm mesh strainer)
Approx. burner Pump technical data Nominal connection diameter Version with 2 pumps
rating range Capacity Speed Motor Pump inlet Burner supply Pump return Pump type Part No.
kg/h l/h rpm kW
Heavy oil. 12 mm²s. ℓ= 0.98 kg/l. 50 Hz frequency* (with 0.5 mm mesh strainer)
up to 223 456 2900 1.10 DN25 / Ø33.7 DN20/Ø26.9 DN20/Ø26.9 DLC-600-S 27000851
Heavy oil. 12 mm²s. ℓ= 0.98 kg/l. 60 Hz frequency* (with 0.5 mm mesh strainer)
up to 282 576 3450 1.30 DN25 / Ø33.7 DN20/Ø26.9 DN20/Ø26.9 DLC-600-S 27000853
Approx. burner Pump technical data Nominal connection diameter Version with 1 pump
rating range Capacity Speed Motor Pump inlet Burner supply Pump return Pump type Part No.
kg/h l/h rpm kW
up to 235 700 1400 2.20 DN25 / Ø33.7 DN25 / Ø33.7 DN25 / Ø33.7 MOG 5308-So-Wh 27000857
235–403 1200 1400 3.00 DN25 / Ø33.7 DN25 / Ø33.7 DN25 / Ø33.7 MOG 5309-So-Wh 27000858
403–480 1428 2900 2.20 DN32 / Ø42.4 DN25 / Ø33.7 DN25 / Ø33.7 LFW-15-EL 27000801
480–631 1878 2900 3.00 DN32 / Ø42.4 DN25 / Ø33.7 DN25 / Ø33.7 LFW-20-EL 27000802
631–808 2406 2900 3.00 DN32 / Ø42.4 DN32 / Ø42.4 DN32 / Ø42.4 LFW-26-EL 27000803
808–1070 3186 2900 4.00 DN32 / Ø42.4 DN32 / Ø42.4 DN32 / Ø42.4 LFW-32-EL 27000804
1070–1427 4248 2900 5.50 DN40 / Ø48.3 DN40 / Ø48.3 DN40 / Ø48.3 LFW-42-EL 27000805
up to 282 840 1680 2.55 DN25 / Ø33.7 DN25 / Ø33.7 DN25 / Ø33.7 MOG 5308-So-Wh 27000857
282–379 1128 3450 1.80 DN20 / Ø26.9 DN20 / Ø26.9 DN20 / Ø26.9 LFW-10-EL 27000860
379–599 1782 3450 2.64 DN32 / Ø42.4 DN25 / Ø33.7 DN25 / Ø33.7 LFW-15-EL 27000807
599–786 2340 3450 3.60 DN32 / Ø42.4 DN35 / Ø33.7 DN35 / Ø33.7 LFW-20-EL 27000808
786–1008 3000 3450 3.60 DN32 / Ø42.4 DN32 / Ø42.4 DN32 / Ø42.4 LFW-26-EL 27000809
1008–1316 3918 3450 4.80 DN32 / Ø42.4 DN32 / Ø42.4 DN32 / Ø42.4 LFW-32-EL 27000810
1316–1754 5220 3450 6.60 DN40 / Ø48.3 DN50 / Ø60.3 DN40 / Ø48.3 LFW-42-EL 27000811
Approx. burner Pump technical data Nominal connection diameter Version with 2 pumps
rating range Capacity Speed Motor Pump inlet Burner supply Pump return Pump type Part No.
kg/h l/h rpm kW
Light oil 6 mm²s. ℓ=0.84 kg/l. 50 Hz frequency* (with 0.25 mm mesh strainer)
up to 480 1428 2900 2.20 DN32 / Ø42.4 DN25 / Ø33.7 DN25 / Ø33.7 DLC-1800-EL 27000812
480–631 1878 2900 3.00 DN32 / Ø42.4 DN25 / Ø33.7 DN25 / Ø33.7 DLC-2400-EL 27000813
631–808 2406 2900 3.00 DN50 / Ø60.3 DN32 / Ø42.4 DN32 / Ø42.4 DLC-2600-EL 27000814
808–1070 3186 2900 4.00 DN50 / Ø60.3 DN32 / Ø42.4 DN32 / Ø42.4 DLC-3300-EL 27000815
1070–1427 4248 2900 5.50 DN50 / Ø60.3 DN40 / Ø48.3 DN40 / Ø48.3 DLC-5000-EL 27000816
Light oil 6 mm²s. ℓ=0.84 kg/l. 60 Hz frequency* (with 0.25 mm mesh strainer)
up to 379 1128 3450 1.80 DN32 / Ø42.4 DN20 / Ø26.9 DN20 / Ø26.9 DLC-1200-EL 27000818
379–599 1782 3450 2.64 DN32 / Ø42.4 DN25 / Ø33.7 DN25 / Ø33.7 DLC-1800-EL 27000819
599–786 2340 3450 3.60 DN32 / Ø42.4 DN32 / Ø42.4 DN32 / Ø42.4 DLC-2400-EL 27000820
786–1008 3000 3450 3.60 DN50 / Ø60.3 DN32 / Ø42.4 DN32 / Ø42.4 DLC-2600-EL 27000821
1008–1316 3918 3450 4.80 DN50 / Ø60.3 DN32 / Ø42.4 DN32 / Ø42.4 DLC-3300-EL 27000822
1316–1754 5220 3450 6.60 DN50 / Ø60.3 DN50 / Ø60.3 DN40 / Ø48.3 DLC-5000-EL 27000823
Technical data, DLC versions EL and S, 2 pumps Scope of delivery, duplex pump station
Operating pressure _________________________ max. 30 bar 2 screw pumps
Max. supply pressure _____________________________ 6 bar 1 pressure regulating valve
Max. negative pressure __________________________ 0.4 bar 2 non-return valves
Max. supply temperature _________________________ 180 ºC 1 pressure gauge
Motor voltage up to 2.99 kW _________________ 230/400 V 2 vacuum gauges
Motor voltage from 3 kW _____________________ 400/690 V 1 oil drip tray
Frequency ____________________________ 50 Hz (or 60 Hz)
Protection ______________________________________ IP 55 Supplied assembled.
Example
Known:
Viscosity of the oil: 300 mm²/s at 50 °C
Sought:
Preheat temperature in °C to achieve the recommended nozzle
viscosity
Method:
Go vertically upwards from the 50 °C reference temperature
point to where it intersects the 300 mm2/s viscosity line. From
there, go down parallel to the next oil curve until you reach the
“recommended nozzle viscosity” line. Finally go vertically
downwards to the temperature axis, from where the preheat
temperature of 147 °C can be read off.
Recommended
Depending on nozzle size, the following maximum viscosities
should be observed:
Temperature [°F]
40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340
2000
Viscosity [mm²/s]
Viscosity [E]
200
150
1000 120
Max. pump viscosity
600
60
400
300 40
30
200
20
5 1,4
M
ax
4 . li 1,3
gh
Av t-o
era il v
3 ge al
lig ue 1,2
ht sp
Av -o er
e il v DI
ra al N
ge ue 51
2 Ke s 60
ro 3
s 1,1
en
e/
pe
1,5 tro
le
um
va
lu
es
1 1,0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180
Temperature [°C]
Description On point 1
WEV electric preheater
Medium and heavy-oil preheater stations are supplied fully The electrically generated heat energy is conducted via a
piped up on a base plate. The preheater station regulates the copper plate to the oil pipe coil. The oil preheater has a large
preheat temperature and thus the viscosity of the oil. The heat exchange surface for a relatively small oil volume, making
compact, space-saving preheaters are high-capacity heat it possible to heat the oil up to the necessary atomising
exchangers with forced circulation. temperature within a short period of time. Rapid heat
distribution prevents localised overheating so the oil will not
Weishaupt’s versatile oil preheaters guarantee substantially carbonise. The maximum oil temperature achievable at the
stable oil temperatures and thus good combustion figures. nozzle is approx. 150 ºC, depending on the oil throughput and
the temperature of the oil at the inlet – see the following WEV
There are the following preheater options: capacity chart. Several electric preheaters are brought together
1. Preheating using a WEV type electric preheater as a parallel switched assembly. Weishaupt electric preheaters
2. Preheating using an MV type medium preheater are equipped as standard with a temperature regulator, two
(with temperature regulator) thermostats in series for burner release, and a temperature
3. Preheating using a combination of medium preheater limiter.
(without temperature regulator) and WEV type electric
preheater
1600
Oil throughput as
1500 a function of ∆t at
1400 maximum capacity
1300
W
EV
3/
1200
01
Oil throughput [kg/h]
1100
1000 W
EV
3.1
900 /0
WE 1
800 V2
.2/
700 01
600
500
400
300
200
100
20 30 40 50 60 70 80 90 100
Temperature change Δt [K]
3.0
3,0
2.5
2,5
Pressure loss [bar]
2.0
2,0
1.5
1,5
01
/0
1 V3/ 01
.2 WE V3.1/
E V2 WE
1.0
1,0 W
0.5
0,5
00
0 100 200 300 400 500 600 700 800 900 1000
The values for types WEV2.2/01 to WEV3/01 were Note Due to the different oil throughputs and the varying inlet
determined using heavy oil (viscosity 450 mm²/s at 50 °C) viscosities, the data given relating to the pressure losses
Oil inlet temperature: _____________________________ 60 °C of the preheaters should be used as guide values.
Oil outlet temperature: ___________________________ 150 °C
Pressure loss for the preheater must not exceed 1.5 bar.
For values above the oil preheater’s nominal rating the oil inlet
temperature was increased accordingly.
Capacity chart (maximum achievable oil temperature with hot water and steam)
1500$C
$C
170 $C
°C
0.5 bar
1.0 bar
2.5 bar
5.0 bar
°C
°C
7.5 bar
bar
10 bar
110 °C
15 bar
Saturated steam
110
0,5
1,0
2,5
5,0
7,5
15
13
15
700
The hot water temperatures/
600 steam pressures must be
available at the preheater inlet.
Oil throughput [kg/h]
500
400
300
200
100
80 90 100 110 120 130 140 150 160
On point 3.
The most commonplace method of oil preheating is the When the required medium temperature has been reached,
combination of a medium preheater (without temperature changeover to the medium preheater takes place thus saving
regulator) and an electric preheater connected in series. They electrical energy. The electric preheater then just provides
are used when light oil or gas are not available for start-up supplemental heating and regulates the temperature.
and/or when the medium temperature is not sufficient to
adequately heat the heavy oil. The electric preheater heats the
heavy oil for plant start-up (the capacity of the electric
preheater should cover at least 30 % of the appliance rating).
15 0$C
$C
bar
bar
bar
bar
°C
0,5 bar
1,0 bar
2,5 bar
5,0 bar
°C
bar
170 °C
bar
bar
7,5 bar
10 bar
15 bar
Saturated steam
130
150
170
0.5
1.0
2.5
5.0
7.5
10
1000
The hot water temperatures/
900 steam pressures must be
110 $C
800
700
600
500
400
80 90 100 110 120 130 140 150 160
2.5
2,5
The values were determined
using heavy oil (max. viscosity
2.0
2,0 150 mm2/s at 50 °C with an
Pressure loss [bar]
1.0
1,0
0.5
0,5
00
100 200 300 400 500 600 700 800 900 1000
q 1
i u
3 1
5
0 z
Medium preheater station (MV10) Electric preheater station (2 x WEV3) Pump station (LFW-26-EL)
Vent
Ring main valve
Ring main
connection
Shut-off device
with limit switch
Oil gases/air Differential pressure
overflow valve Heating
element
MV9C medium preheater fittings (with thermostatic valve, without electric preheater)
– flanged for high-temperature hot water from 180 ºC up to 200 ºC 120 001 81
– flanged for high-pressure steam from 7.5 bar up to 13 bar 170 003 63
– flanged for high-pressure steam from 13 bar up to 20 bar 170 003 64
– flanged for high-pressure steam from 20 bar up to 25 bar 170 003 65
– flanged for thermal fluid from 200 ºC up to 250 ºC 120 001 84
– flanged for thermal fluid from 250 ºC up to 300 ºC 120 001 85
MV10A medium preheater fittings (with thermostatic valve, without electric preheater)
– flanged for high-temperature hot water from 180 ºC up to 200 ºC 170 001 68 170 001 69
– flanged for high-pressure steam from 7.5 bar up to 13 bar 170 001 71 170 001 72
– flanged for high-pressure steam from 13 bar up to 20 bar 170 001 74 170 001 75
– flanged for high-pressure steam from 20 bar up to 25 bar 170 001 85 170 001 86
– flanged for thermal fluid from 200 ºC up to 250 ºC 170 001 77 170 001 78
– flanged for thermal fluid from 250 ºC up to 300 ºC 170 001 80 170 001 81
Description
The connection fittings are selected according to medium type.
HW inlet
HTHW inlet
Thermal-fluid inlet
Thermal-fluid inlet
5. Low-pressure steam up to 0.5 bar Ball valve MV9C, screwed 170 003 59
High-pressure steam up to 1.5 bar Condensate controller MV9C, flanged 170 003 61
Condensate outlet Steam trap MV10A, screwed 170 001 47
MV10A, flanged 170 001 50
6
8 9
1 1
Steam inlet
6. High-pressure steam 1.5–15 bar Ball valve MV9C, screwed 170 003 60
Condensate outlet
Strainer MV9C, flanged 170 003 62
Pressure regulator MV10A, screwed 170 001 53
5
6
Pressure gauge MV10A, flanged 170 001 56
1
4 3 8 9
1 Condensate controller
Steam trap
HPS inlet
7. High-pressure steam 15–25 bar Ball valve MV9C, flanged 170 003 67
Strainer MV10A, flanged 170 002 00
Condensate outlet Pressure regulator
5
6 Pressure gauge
4 3 8 9 Condensate controller
1 1
Steam trap
HPS inlet
HTHW inlet
Thermal-fluid inlet
3. Thermal fluid 250 °C–300 °C Bellow valve MV9C, flanged 120 001 85
Thermal-fluid outlet Strainer MV10A, flanged 170 001 80
Control valve with thermostat
6
2 4 7 2
Thermal-fluid inlet
4. High-pressure steam 7.5–13 bar Ball valve MV9C, flanged 170 003 63
Strainer MV10A, flanged 170 001 71
Condensate outlet
5
6
Control valve with thermostat
4 8 9 Pressure gauge
1 7 1
Condensate controller
Steam trap
HPS inlet
5. High-pressure steam 13–20 bar Ball valve MV9C, flanged 170 003 64
Condensate outlet
Strainer MV10A, flanged 170 001 74
5 Control valve with thermostat
6 8 9
1 4 7 1 Pressure gauge
Condensate controller
Steam trap
HPS inlet
6. High-pressure steam 20–25 bar Ball valve MV9C, flanged 170 003 65
Condensate outlet Strainer MV10A, flanged 170 001 85
5 Pressure regulator
4 3
6 8 9 Control valve with thermostat
1 7 1
Pressure gauge
Condensate controller
Steam trap
HPS inlet
Legend:
1 Ball valve 4 Strainer 8 Condensate controller (sight glass)
2 Bellow valve 5 Pressure gauge 9 Steam trap
3 Water/ thermal-fluid/steam pressure 6 Oil preheater
regulator 7 Control valve with thermostat
1 1
HW inlet 6
1 3 1
HTHW inlet 6
1 3 1
Thermal-fluid inlet 6
2 3 2
Thermal-fluid inlet 6
5. Low-pressure steam up to 0.5 bar Ball valve MV10A, screwed 170 001 48
High-pressure steam up to 1.5 bar Condensate controller MV10A, flanged 170 001 51
Condensate outlet Steam trap
6 8 9
1 1
8 9
Steam inlet 6
6. High-pressure steam 1.5–15 bar Ball valve MV10A, screwed 170 001 54
Condensate outlet
Strainer MV10A, flanged 170 001 57
6
Pressure regulator
8 9
4 3
5
Manometer
1 1
Condensate controller
Steam trap
6 8 9
HPS inlet
7. High pressure steam 15–25 bar Ball valve MV10A, flanged 170 002 01
Strainer
Condensate outlet Pressure regulator
6 8 9
5
1
4 3 1
Manometer
Condensate controller
Steam trap
6 8 9
HPS inlet
6
HTHW inlet
Thermal-fluid inlet
Thermal-fluid inlet
4. High-pressure steam 7.5–13 bar Ball valve MV10A, flanged 170 001 72
Strainer
Condensate outlet
5
6 8 9 Control valve with thermostat
1 4 7 1
Pressure gauge
Condensate controller
Steam trap
8 9
6
HPS inlet
5. High-pressure steam 13–20 bar Ball valve MV10A, flanged 170 001 75
Condensate outlet
Strainer
5
6 8 9 Control valve with thermostat
1 4 7 1 Pressure gauge
Condensate controller
Steam trap
8 9
6
HPS inlet
6. High-pressure steam 20–25 bar Ball valve MV10A, flanged 170 001 86
Condensate outlet Strainer
5
6 8 9
Pressure regulator
1 4 3 7 1
Control valve with thermostat
Pressure gauge
Condensate controller
6
8 9
Steam trap
HPS inlet
Legend:
1 Ball valve 4 Strainer 8 Condensate controller (sight glass)
2 Bellow valve 5 Pressure gauge 9 Steam trap
3 Water/ thermal fluid/steam pressure 6 Oil preheater
regulator 7 Control valve with thermostat
Burner Low pressure supply (with FRS) High pressure supply (with high P. Burner Low pressure supply (with FRS) High pressure supply (with high P.
rating (flow pressure in mbar before regulator) (flow rate in mbar rating (flow pressure in mbar before regulator) (flow rate in mbar
kW ball valve. pe. max. = 300 mbar) into gas valve assembly) kW ball valve. pe. max. = 300 mbar) into gas valve assembly)
Nom. dia. of the valve train Nom. dia. of the valve train Nom. dia. of the valve train Nom. dia. of the valve train
1 1⁄2 2 65 80 100 125 1 1⁄2 2 65 80 100 125 1 1⁄2 2 65 80 100 125 1 1⁄2 2 65 80 100 125
Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly
65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65
Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³ Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³
1200 64 29 21 17 15 15 37 18 14 13 12 12 1800 134 57 37 30 26 24 76 35 26 23 22 21
1400 85 38 27 22 19 19 49 24 19 17 16 16 2000 164 68 44 35 30 28 93 41 31 27 25 25
1600 109 48 33 27 24 22 63 30 23 21 20 19 2200 196 81 51 40 34 32 111 48 36 32 29 28
1800 136 59 39 32 28 26 78 37 28 25 24 23 2400 231 94 59 45 38 36 130 56 41 36 33 32
1900 151 65 43 34 30 28 87 40 30 27 25 25 2600 – 108 67 51 42 40 – 64 46 40 37 36
2000 166 71 46 37 32 30 95 43 33 30 27 27 2800 – 123 75 57 47 44 – 72 51 45 40 39
2100 182 77 50 40 34 32 104 47 35 32 29 29 2900 – 130 79 60 49 46 – 76 54 47 42 41
2200 198 83 54 42 36 34 113 51 38 34 31 31 3000 – 138 84 63 51 48 – 80 57 49 44 43
Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³ Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³
1200 88 38 25 20 18 17 49 22 17 15 14 14 1800 188 76 47 36 30 28 105 44 32 28 25 25
1400 118 50 33 26 22 21 67 30 22 20 18 18 2000 230 92 56 43 35 33 128 53 38 33 30 29
1600 152 63 41 32 27 26 86 38 28 25 23 22 2200 – 109 66 50 41 38 – 63 44 39 35 34
1800 190 78 49 38 32 31 107 46 34 30 28 27 2400 – 127 76 57 46 43 – 73 51 44 39 38
1900 211 86 54 42 35 33 119 51 37 33 30 29 2600 – 147 87 64 52 48 – 84 58 50 44 43
2000 232 94 59 45 38 35 131 56 40 35 32 31 2800 – 168 99 72 58 53 – 95 65 56 49 48
2100 – 102 63 48 40 38 – 60 43 38 34 34 2900 – 179 105 76 60 56 – 101 68 58 52 50
2200 – 111 68 52 43 40 – 65 46 41 37 36 3000 – 190 111 80 63 58 – 107 72 61 54 52
LPG * LHV = 25.89 kWh/mn³; d = 1.555; Wi = 20.762 kWh/mn³ LPG * LHV = 25.89 kWh/mn³; d = 1.555; Wi = 20.762 kWh/mn³
1200 30 16 13 11 11 10 18 10 9 8 8 8 1800 62 31 23 19 18 17 37 20 16 15 15 14
1400 40 21 16 14 13 13 24 13 11 11 10 10 2000 76 37 27 23 21 20 45 24 20 18 17 17
1600 51 26 19 17 15 15 30 17 14 13 12 12 2200 90 43 31 26 24 23 54 28 23 21 20 20
1800 62 31 23 20 18 17 37 20 17 15 15 15 2400 106 50 35 30 27 26 63 33 26 24 23 23
1900 69 33 25 21 19 19 41 22 18 17 16 16 2600 123 57 40 33 30 29 73 37 30 28 26 26
2000 75 36 26 22 20 20 45 24 19 18 17 17 2800 141 64 45 37 33 32 83 42 33 31 29 28
2100 82 39 28 24 22 21 49 26 21 19 18 18 2900 150 68 47 39 35 33 89 44 35 32 30 30
2200 89 42 30 25 23 22 53 27 22 21 19 19 3000 160 72 49 41 36 35 94 47 37 34 32 31
Screwed Flanged
WK50/1-B, standard version
R 1½ W-MF 512 DN 65 DMV 5065/12
Burner Low pressure supply (with FRS) High pressure supply (with high P. R2 DMV 525/12 DN 80 DMV 5080/12
rating (flow pressure in mbar before regulator) (flow rate in mbar DN 100 DMV 5100/12
kW ball valve. pe. max. = 300 mbar) into gas valve assembly) DN 125 VGD 40.125
Nom. dia. of the valve train Nom. dia. of the valve train DN 150 VGD 40.150
2 65 80 100 125 150 2 65 80 100 125 150
Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly
80 80 80 80 80 80 80 80 80 80 80 80
Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³ * The valve train table for LPG is based on propane, but is also
2500 82 45 30 22 20 18 41 25 20 16 15 15 suitable for sizing butane valve trains.
2700 96 52 35 25 22 21 48 29 23 19 18 18
2900 110 59 39 29 25 24 56 33 27 22 21 20
3100 125 67 45 32 28 27 64 38 30 25 23 23 Note:
3300 141 76 50 36 32 30 72 43 34 28 27 26 • The combustion chamber resistance (mbar) must be added to the
3500 159 85 56 41 36 33 81 48 39 32 30 29 minimum gas pressure calculated.
3700 177 94 62 45 39 37 91 54 43 36 33 33
4000 206 110 72 52 45 42 105 63 50 41 39 38 • Preheated air: The difference between the burner resistance
(mbar) with preheated air and the burner resistance (mbar) with
Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³ ambient air must be added to the minimum gas pressure and
2500 117 62 40 29 25 24 58 34 27 22 20 20 combustion chamber resistance (see section 5.2.2).
2700 136 72 47 34 29 27 68 40 31 26 24 23
2900 156 82 54 38 33 31 79 46 36 30 28 27
3100 178 94 61 43 37 35 90 52 41 33 31 31 Gas valve train sizing for other gas types on application.
3300 201 105 68 48 42 39 101 59 46 38 35 34
3500 226 119 77 54 47 44 114 67 52 43 40 39 Low pressure supplies use pressure regulators with safety membranes
3700 253 132 85 60 52 49 128 75 59 48 45 44
4000 – 154 99 70 60 56 – 87 68 55 52 50 in accordance with EN 88-1. Maximum permissible connection
pressure at the valve train inlet is 300 mbar.
LPG * LHV = 25.89 kWh/mn³; d = 1.555; Wi = 20.762 kWh/mn³
2500 38 23 17 14 13 12 20 13 11 10 9 9 High pressure supplies use high pressure regulators in accordance
2700 44 26 19 16 14 14 24 16 13 12 11 11
2900 51 30 22 18 16 15 27 18 15 13 13 13 with EN 334. These can be selected from the relevant technical
3100 58 34 25 20 18 17 31 20 17 15 14 14 brochure.
3300 65 38 27 22 20 19 35 23 19 17 16 16
3500 73 42 30 24 22 21 39 26 22 19 18 18
3700 81 47 34 27 24 23 44 29 24 21 20 20
4000 94 54 39 30 28 27 51 34 28 25 24 23
Screwed Flanged
R2 DMV 525/12 DN 65 DMV 5065/12
DN 80 DMV 5080/12
DN 100 DMV 5100/12
DN 125 VGD 40.125
DN 150 VGD 40.150
* The valve train table for LPG is based on propane, but is also
suitable for sizing butane valve trains.
Note:
• The combustion chamber resistance (mbar) must be added to the
minimum gas pressure calculated.
• Preheated air: The difference between the burner resistance
(mbar) with preheated air and the burner resistance (mbar) with
ambient air must be added to the minimum gas pressure and
combustion chamber resistance (see section 5.2.2).
Screwed Flanged
WK70/1-B, ZM(H)-NR version R2 DMV 525/12 DN 65 DMV 5065/12
Burner Low pressure supply (with FRS) High pressure supply (with high P. DN 80 DMV 5080/12
rating (flow pressure in mbar before regulator) (flow rate in mbar DN 100 DMV 5100/12
kW ball valve. pe. max. = 300 mbar) into gas valve assembly) DN 125 VGD 40.125
Nom. dia. of the valve train Nom. dia. of the valve train DN 150 VGD 40.150
65 80 100 125 150 65 80 100 125 150
Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly
100 100 100 100 100 100 100 100 100 100
Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³ * The valve train table for LPG is based on propane, but is also
5000 149 90 58 48 43 77 57 43 39 38 suitable for sizing butane valve trains.
5400 172 104 67 55 50 89 66 49 45 44
5800 197 118 76 62 56 102 75 56 51 49
6200 225 135 86 71 63 116 85 64 58 56 Note:
6600 255 153 98 81 72 133 97 73 67 64 • The combustion chamber resistance (mbar) must be added to the
7000 287 172 110 90 81 149 110 83 75 73 minimum gas pressure calculated.
7400 – 192 123 100 90 167 122 92 84 81 • Preheated air: The difference between the burner resistance
7700 – 207 132 108 97 180 132 99 90 87
(mbar) with preheated air and the burner resistance (mbar) with
Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³ ambient air must be added to the minimum gas pressure and
5000 212 127 81 66 59 109 80 60 54 52 combustion chamber resistance (see section 5.2.2).
5400 245 146 92 75 67 126 92 68 62 59
5800 281 166 104 85 75 143 104 77 69 67
6200 – 187 117 94 84 162 117 86 77 74 Gas valve train sizing for other gas types on application.
6600 – 210 129 104 92 181 130 95 85 82
7000 – 233 143 114 100 – 143 104 93 89 Low pressure supplies use pressure regulators with safety membranes
7400 – 257 156 124 109 – 157 113 101 97 in accordance with EN 88-1. Maximum permissible connection
7700 – 276 166 132 116 – 168 120 107 103
pressure at the valve train inlet is 300 mbar.
LPG * LHV = 25.89 kWh/mn³; d = 1.555; Wi = 20.762 kWh/mn³
5000 78 54 41 37 35 48 39 34 32 31 High pressure supplies use high pressure regulators in accordance
5400 90 62 47 42 40 54 45 38 36 36
5800 102 70 52 47 44 61 50 43 40 40 with EN 334. These can be selected from the relevant technical
6200 115 78 58 51 48 69 56 47 45 44 brochure.
6600 128 86 63 56 53 76 62 52 49 48
7000 142 95 69 61 57 84 68 56 53 52
7400 156 104 75 66 62 92 74 61 58 57
7700 167 110 80 70 65 98 78 65 61 60
Burner Low pressure supply (with FRS) High pressure supply (with high P. Burner Low pressure supply (with FRS) High pressure supply (with high P.
rating (flow pressure in mbar before regulator) (flow rate in mbar rating (flow pressure in mbar before regulator) (flow rate in mbar
kW ball valve. pe. max. = 300 mbar) into gas valve assembly) kW ball valve. pe. max. = 300 mbar) into gas valve assembly)
Nom. dia. of the valve train Nom. dia. of the valve train Nom. dia. of the valve train Nom. dia. of the valve train
65 80 100 125 150 65 80 100 125 150 100 125 150 100 125 150
Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly
100 100 100 100 100 100 100 100 100 100 150 150 150 150 150 150
Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³ Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³
5600 165 92 65 56 51 76 51 46 45 45 9600 152 115 98 102 89 84
6400 214 118 68 57 51 99 66 45 44 44 10000 159 119 100 105 90 85
7200 270 148 83 62 52 124 82 54 46 43 11000 177 129 106 113 95 88
8000 – 182 101 75 63 153 101 66 56 53 12000 197 139 112 121 100 92
9000 – 229 126 94 79 193 127 83 70 66 13000 219 151 119 130 105 96
10000 – 282 155 115 96 – 157 101 87 81 14000 242 163 126 139 110 100
11000 – – 187 138 115 – 189 122 104 98 15000 267 176 134 149 116 104
12000 – – 221 164 136 – – 145 124 116 16000 293 190 142 160 122 108
17000 – 205 150 171 128 112
Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³ 18000 – 240 178 202 153 136
5600 239 132 75 62 56 111 74 49 48 48 19000 – 266 198 224 170 151
6400 – 172 96 72 61 144 96 63 54 51 20000 – 294 218 248 188 167
7200 – 216 120 90 76 182 121 79 68 64 21000 – – 240 273 207 183
8000 – 265 147 110 92 – 149 97 83 78 22000 – – 263 299 226 200
9000 – – 185 137 115 – 187 122 105 98
10000 – – 227 168 141 – – 150 128 121 Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³
11000 – – 273 202 169 – – 181 155 145 9600 215 161 135 144 124 116
12000 – – – 240 200 – – – 183 172 10000 224 166 138 147 126 118
11000 250 179 146 158 132 122
LPG * LHV = 25.89 kWh/mn³; d = 1.555; Wi = 20.762 kWh/mn³ 12000 278 194 155 169 138 127
5600 83 61 51 47 45 45 43 42 41 41 13000 – 210 164 181 144 131
6400 101 66 53 48 46 52 43 42 42 41 14000 – 228 174 194 152 136
7200 124 74 55 49 46 63 46 41 41 41 15000 – 246 184 208 159 142
8000 151 89 56 49 46 76 55 40 40 40 16000 – 266 195 223 167 147
9000 189 111 69 56 50 95 68 50 45 43 17000 – 286 207 238 175 153
10000 233 137 85 69 61 118 85 62 56 53 18000 – – 245 280 210 185
11000 283 167 104 84 74 144 103 76 69 66 19000 – – 272 311 233 205
12000 – 200 125 101 90 173 125 92 83 80 20000 – – 300 344 257 226
21000 – – 1) – 282 248
22000 – – 1) – 309 271
LPG * LHV = 25.89 kWh/mn³; d = 1.555; Wi = 20.762 kWh/mn³
Flanged 9600 136 121 114 114 109 107
DN 65 DMV 5065/12 10000 139 123 115 116 109 107
DN 80 DMV 5080/12 11000 147 127 118 119 112 109
DN 100 DMV 5100/12 12000 156 132 121 123 114 111
13000 165 137 124 127 117 113
DN 125 VGD 40.125 14000 175 143 128 132 120 115
DN 150 VGD 40.150 15000 186 149 132 136 123 118
16000 197 155 135 141 126 120
17000 210 162 140 146 129 122
18000 230 177 152 160 140 133
* The valve train table for LPG is based on propane, but is also 19000 254 194 166 176 154 146
20000 279 214 183 193 169 160
suitable for sizing butane valve trains. 21000 – 235 200 212 185 176
22000 – 257 220 233 204 193
Note:
• The combustion chamber resistance (mbar) must be added to the 1) Please enquire regarding valve train
minimum gas pressure calculated.
• Preheated air: The difference between the burner resistance
(mbar) with preheated air and the burner resistance (mbar) with
ambient air must be added to the minimum gas pressure and
combustion chamber resistance (see section 5.2.2).
* The valve train table for LPG is based on propane, but is also
suitable for sizing butane valve trains.
Note:
• The combustion chamber resistance (mbar) must be added to the
minimum gas pressure calculated.
• Preheated air: The difference between the burner resistance
(mbar) with preheated air and the burner resistance (mbar) with
ambient air must be added to the minimum gas pressure and
combustion chamber resistance (see section 5.2.2).
Burner Low pressure supply (with FRS) High pressure supply (with high P. Burner Low pressure supply (with FRS) High pressure supply (with high P.
rating (flow pressure in mbar before regulator) (flow rate in mbar rating (flow pressure in mbar before regulator) (flow rate in mbar
kW ball valve. pe. max. = 300 mbar) into gas valve assembly) kW ball valve. pe. max. = 300 mbar) into gas valve assembly)
Nom. dia. of the valve train Nom. dia. of the valve train Nom. dia. of the valve train Nom. dia. of the valve train
65 80 100 125 150 65 80 100 125 150 65 80 100 125 150 65 80 100 125 150
Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³ Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³
4800 145 91 62 53 48 79 60 48 44 43 5500 164 93 55 42 37 78 53 37 32 30
5000 156 97 66 56 51 85 64 51 47 45 6000 194 109 64 49 43 92 63 43 38 36
5400 180 111 75 63 57 97 73 57 53 51 7000 262 147 85 65 56 124 85 57 50 48
5800 206 127 84 71 64 111 83 65 60 58 8000 – 191 110 84 72 162 110 74 65 61
6200 234 144 95 80 73 126 94 73 67 65 9000 – 240 137 105 90 – 138 94 82 77
6600 265 163 107 90 82 142 107 83 76 74 10000 – 296 169 129 110 – 171 115 100 95
7000 298 183 121 101 92 160 120 93 86 83 11000 – – 203 155 132 – – 139 121 115
12000 – – 242 184 157 – – 165 144 136
Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³
4800 203 125 82 69 62 108 81 62 57 56 Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³
5000 219 134 88 73 66 116 87 66 61 59 5500 231 128 73 55 47 108 72 48 41 39
5400 253 153 100 83 75 133 99 76 69 67 6000 275 153 86 65 56 128 86 57 49 47
5800 290 175 113 94 84 152 113 86 79 76 7000 – 207 117 88 75 175 118 78 68 64
6200 – 199 128 106 96 174 128 97 89 86 8000 – 270 152 114 97 – 153 102 88 83
6600 – 225 145 120 108 197 145 110 101 98 9000 – – 191 143 121 – 193 128 110 104
7000 – 254 163 135 121 – 164 125 114 110 10000 – – 233 175 147 – – 157 135 127
11000 – – 280 209 176 – – 188 161 152
LPG * LHV = 25.89 kWh/mn³; d = 1.555; Wi = 20.762 kWh/mn³ 12000 – – – 247 207 – – – 190 179
4800 91 69 57 53 51 62 55 49 48 47
5000 97 73 60 56 54 66 58 52 51 50 LPG * LHV = 25.89 kWh/mn³; d = 1.555; Wi = 20.762 kWh/mn³
5400 111 83 68 63 61 76 66 59 58 57 5500 81 51 36 31 28 44 34 27 25 24
5800 127 94 77 71 69 86 75 67 65 64 6000 95 61 42 36 33 52 40 32 30 29
6200 144 107 87 80 77 98 85 76 74 73 7000 129 82 56 48 44 71 54 43 40 39
6600 162 120 97 90 87 110 96 86 83 82 8000 167 105 72 61 56 92 71 56 52 51
7000 182 135 109 101 97 124 108 96 93 92 9000 210 132 90 76 70 115 89 70 65 63
10000 257 161 109 93 85 142 109 86 80 78
11000 – 194 131 111 102 171 130 103 96 93
12000 – 229 154 130 119 – 154 122 113 110
Flanged
DN 65 DMV 5065/12
DN 80 DMV 5080/12
DN 100 DMV 5100/12
DN 125 VGD 40.125
DN 150 VGD 40.150
* The valve train table for LPG is based on propane, but is also
suitable for sizing butane valve trains.
Note:
• The combustion chamber resistance (mbar) must be added to the
minimum gas pressure calculated.
• Preheated air: The difference between the burner resistance
(mbar) with preheated air and the burner resistance (mbar) with
ambient air must be added to the minimum gas pressure and
combustion chamber resistance (see section 5.2.2).
100 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
8.4 Gas valve train sizing
LN version gas burners
WK40/2-A, ZM(H)-LN version WK70/1-B, ZM(H)-1LN version
Burner Low pressure supply (with FRS) High pressure supply (with high P. Burner Low pressure supply (with FRS) High pressure supply (with high P.
rating (flow pressure in mbar before regulator) (flow rate in mbar rating (flow pressure in mbar before regulator) (flow rate in mbar
kW ball valve. pe. max. = 300 mbar) into gas valve assembly) kW ball valve. pe. max. = 300 mbar) into gas valve assembly)
Nom. dia. of the valve train Nom. dia. of the valve train Nom. dia. of the valve train Nom. dia. of the valve train
1 1⁄2 2 65 80 100 125 1 1⁄2 2 65 80 100 125 65 80 100 125 150 65 80 100 125 150
Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly
65 65 65 65 65 65 65 65 65 65 65 65 100 100 100 100 100 100 100 100 100 100
Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³ Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³
1800 138 61 42 34 30 29 81 39 30 27 26 25 4000 97 60 39 33 30 50 38 29 26 25
2000 166 70 46 37 32 30 95 43 33 29 27 26 4600 130 81 54 45 41 69 52 41 37 36
2200 195 80 51 40 33 31 110 48 35 31 28 28 5000 154 96 64 54 49 83 63 49 45 44
2400 228 91 56 43 35 33 127 53 38 33 30 29 5400 180 111 74 63 57 97 73 57 53 51
2600 – 103 62 46 37 35 – 59 41 35 31 30 5800 206 128 85 71 65 111 84 65 60 58
2800 – 115 68 49 39 36 – 64 44 37 33 32 6200 235 145 96 81 74 126 95 74 68 66
3000 – 129 74 53 42 38 – 71 47 39 35 33 6600 266 164 109 91 83 143 108 84 77 75
7000 298 184 121 102 92 161 121 94 87 84
Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³
1800 196 84 55 44 38 36 113 52 40 36 33 33 Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³
2000 235 96 61 47 40 38 133 58 43 38 35 34 4000 136 82 52 43 38 69 51 38 34 33
2200 – 110 68 51 42 39 – 64 46 40 36 35 4600 182 110 71 59 53 95 70 53 48 47
2400 – 125 75 55 44 41 – 71 49 42 38 36 5000 215 130 84 70 63 113 83 63 58 56
2600 – 142 82 59 47 43 – 79 53 45 39 38 5400 251 151 98 81 73 131 97 74 67 65
2800 – 159 90 64 49 45 – 87 56 47 41 39 5800 288 174 112 92 83 151 111 84 77 74
3000 – 178 99 68 52 46 – 95 60 50 42 41 6200 – 198 127 105 94 172 127 96 88 85
6600 – 224 143 118 106 195 144 109 99 96
7000 – 251 160 132 118 – 161 121 111 107
Screwed Flanged
WK70/2-A, ZM(H)-1LN version
R 1½ W-MF 512 DN 65 DMV 5065/12
Burner Low pressure supply (with FRS) High pressure supply (with high P. R2 DMV 525/12 DN 80 DMV 5080/12
rating (flow pressure in mbar before regulator) (flow rate in mbar DN 100 DMV 5100/12
kW ball valve. pe. max. = 300 mbar) into gas valve assembly) DN 125 VGD 40.125
Nom. dia. of the valve train Nom. dia. of the valve train DN 150 VGD 40.150
65 80 100 125 150 65 80 100 125 150
Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly
100 100 100 100 100 100 100 100 100 100
Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³ Note:
5500 190 119 81 69 63 104 80 63 59 57 • The combustion chamber resistance (mbar) must be added to the
6000 217 133 87 73 66 116 86 66 61 59
6500 247 148 94 77 69 128 93 70 64 61 minimum gas pressure calculated.
7000 278 163 101 81 72 140 101 74 66 64 • Preheated air: The difference between the burner resistance
8000 – 198 117 91 79 169 117 82 72 69 (mbar) with preheated air and the burner resistance (mbar) with
9000 – 249 147 114 99 – 148 103 91 86 ambient air must be added to the minimum gas pressure and
10000 – – 178 138 119 – 180 125 110 104
11000 – – 211 163 140 – – 147 129 122 combustion chamber resistance (see section 5.2.2).
Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³ Gas valve train sizing for other gas types on application.
5500 261 158 102 85 76 137 102 77 71 68
6000 300 177 111 90 80 153 110 81 74 71
6500 – 198 120 95 83 169 120 86 77 73 Low pressure supplies use pressure regulators with safety membranes
7000 – 220 129 101 87 187 130 90 80 76 in accordance with EN 88-1. Maximum permissible connection
8000 – 276 158 121 103 – 160 108 94 89 pressure at the valve train inlet is 300 mbar.
9000 – – 197 150 128 – 200 134 117 111
10000 – – 240 182 155 – – 164 142 134
11000 – – 286 216 182 – – 194 168 158 High pressure supplies use high pressure regulators in accordance
with EN 334. These can be selected from the relevant technical
brochure.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 101
8. Gas valve train sizing
Flanged
DN 65 DMV 5065/12
DN 80 DMV 5080/12
DN 100 DMV 5100/12
DN 125 VGD 40.125
DN 150 VGD 40.150
* The valve train table for LPG is based on propane, but is also
suitable for sizing butane valve trains.
Note:
• The combustion chamber resistance (mbar) must be added to the
minimum gas pressure calculated.
• Preheated air: The difference between the burner resistance
(mbar) with preheated air and the burner resistance (mbar) with
ambient air must be added to the minimum gas pressure and
combustion chamber resistance (see section 5.2.2).
102 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
8.5 Gas valve train sizing
3LN version gas and dual-fuel burners
WKG80/1-A, 3LN version WKGL80/1-A, 3LN version
Burner Low pressure supply (with FRS) High pressure supply (with high P. Burner Low pressure supply (with FRS) High pressure supply (with high P.
rating (flow pressure in mbar before regulator) (flow rate in mbar rating (flow pressure in mbar before regulator) (flow rate in mbar
kW ball valve. pe. max. = 300 mbar) into gas valve assembly) kW ball valve. pe. max. = 300 mbar) into gas valve assembly)
Nom. dia. of the valve train Nom. dia. of the valve train Nom. dia. of the valve train Nom. dia. of the valve train
100 125 150 100 125 150 100 125 150 100 125 150
Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly
150 150 150 150 150 150 150 150 150 150 150 150
Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³ Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³
13000 220 152 120 131 106 97 13000 224 156 124 135 110 100
14000 255 177 140 153 124 113 14000 259 181 144 157 128 117
15000 292 202 159 175 141 129 15000 297 207 164 180 146 134
16000 – 228 180 198 159 146 16000 – 233 185 203 165 151
17000 – 255 200 221 178 162 17000 – 261 206 227 184 168
Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³ Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³
13000 – 206 160 177 140 127 13000 – 212 166 183 146 133
14000 – 240 186 206 164 149 14000 – 246 192 213 170 155
15000 – 275 213 236 188 170 15000 – 281 220 243 194 177
16000 – – 240 267 212 192 16000 – – 248 275 219 200
17000 – – 268 – 237 214 17000 – – 277 – 245 222
LPG * LHV = 25.89 kWh/mn³; d = 1.555; Wi = 20.762 kWh/mn³ LPG * LHV = 25.89 kWh/mn³; d = 1.555; Wi = 20.762 kWh/mn³
13000 148 120 107 110 100 96 13000 148 120 107 110 100 96
14000 170 138 123 127 115 111 14000 170 138 123 127 115 111
15000 193 156 139 144 130 125 15000 193 156 139 144 130 125
16000 217 175 155 161 145 140 16000 217 175 155 161 145 140
17000 242 194 172 178 161 154 17000 242 194 172 178 161 154
Flanged
DN 100 DMV 5100/12
DN 125 VGD 40.125
DN 150 VGD 40.150
* The valve train table for LPG is based on propane, but is also
suitable for sizing butane valve trains.
Note:
• The combustion chamber resistance (mbar) must be added to the
minimum gas pressure calculated.
• Preheated air: The difference between the burner resistance
(mbar) with preheated air and the burner resistance (mbar) with
ambient air must be added to the minimum gas pressure and
combustion chamber resistance (see section 5.2.2).
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 103
8. Gas valve train sizing
Burner Low pressure supply (with FRS) High pressure supply (with high P. Burner Low pressure supply (with FRS) High pressure supply (with high P.
rating (flow pressure in mbar before regulator) (flow rate in mbar rating (flow pressure in mbar before regulator) (flow rate in mbar
kW ball valve. pe. max. = 300 mbar) into gas valve assembly) kW ball valve. pe. max. = 300 mbar) into gas valve assembly)
Nom. dia. of the valve train Nom. dia. of the valve train § Nom. dia. of the valve train Nom. dia. of the valve train
65 80 100 125 150 65 80 100 125 150 100 125 150 100 125 150
Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly
100 100 100 100 100 100 100 100 100 100 150 150 150 150 150 150
Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³ Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³
5600 175 101 62 49 43 86 60 43 38 37 9600 107 70 52 57 44 39
6400 221 125 73 57 49 106 73 50 44 42 11000 146 97 74 82 64 57
7200 278 157 91 70 60 133 91 62 54 51 12000 176 118 91 100 78 70
8000 – 192 111 85 73 163 111 75 66 62 13000 207 139 107 118 93 84
9000 – 239 137 104 89 – 138 93 81 76 14000 240 162 125 138 108 98
10000 – 294 167 127 108 – 169 114 99 94 15000 275 185 142 158 124 112
11000 – – 202 153 130 – – 137 119 113 16000 – 208 160 178 140 126
12000 – – 237 179 152 – – 161 140 132 17000 – 233 179 199 156 141
18000 – 261 200 223 175 158
Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³ 19000 – 290 222 248 194 175
5600 244 137 79 61 53 116 79 54 47 44
6400 – 172 96 72 61 145 96 63 55 51 Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³
7200 – 217 122 91 77 183 122 81 69 65 9600 154 100 75 83 63 56
8000 – 267 149 112 94 – 151 99 85 80 11000 210 140 107 118 92 82
9000 – – 186 139 116 – 188 123 106 99 12000 254 169 130 144 113 102
10000 – – 228 169 142 – – 151 129 121 13000 299 200 154 171 134 121
11000 – – 272 201 168 – – 180 154 144 14000 – 233 179 199 156 141
12000 – – – 235 195 – – – 178 167 15000 – 266 204 228 179 161
16000 – – 230 257 202 182
17000 – – – – 225 203
18000 – – – – 252 227
Screwed Flanged 19000 – – – – – 252
R2 DMV525/12 DN 65 DMV5065/12
DN 80 DMV5080/12
DN 100 DMV5100/12
DN 125 VGD40.125
DN 150 VGD40.150
Note:
• The combustion chamber resistance (mbar) must be added to the Low pressure supplies use pressure regulators with safety membranes
minimum gas pressure calculated. in accordance with EN 88-1. Maximum permissible connection
• Preheated air: The difference between the burner resistance pressure at the valve train inlet is 300 mbar.
(mbar) with preheated air and the burner resistance (mbar) with
ambient air must be added to the minimum gas pressure and High pressure supplies use high pressure regulators in accordance
combustion chamber resistance (see section 5.2.2). with EN 334. These can be selected from the relevant technical
brochure.
Gas valve train sizing for other gas types on application.
104 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
8.6 Gas valve train sizing
VSF version gas and dual-fuel burners
WKG80/5-A, ZM(H)–VSF version WKG80/4-A, ZM(H)–VSF version
Burner Low pressure supply (with FRS) High pressure supply (with high P. Burner Low pressure supply (with FRS) High pressure supply (with high P.
rating (flow pressure in mbar before regulator) (flow rate in mbar rating (flow pressure in mbar before regulator) (flow rate in mbar
kW ball valve. pe. max. = 300 mbar) into gas valve assembly) kW ball valve. pe. max. = 300 mbar) into gas valve assembly)
Nom. dia. of the valve train Nom. dia. of the valve train Nom. dia. of the valve train Nom. dia. of the valve train
100 125 150 100 125 150 100 125 150 100 125 150
Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly Nom. dia. of the gas butterfly
150 150 150 150 150 150 150 150 150 150 150 150
Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³ Natural gas E (N) LHV = 10.35 kWh/mn³; d = 0.606; Wi = 13.295 kWh/mn³
17500 – 222 165 187 141 124 9600 52 115 98 102 89 84
18000 – 231 169 193 144 127 10000 59 119 100 105 90 85
19000 – 247 179 206 152 132 11000 177 129 106 113 95 88
20000 – 265 189 219 159 138 12000 197 139 112 121 100 92
21000 – 291 208 240 175 151 13000 219 151 119 130 105 96
22000 – – 228 264 191 166 14000 242 163 126 139 110 100
23000 – – 248 288 209 180 15000 267 176 134 149 116 104
24000 – – 269 312 226 195 16000 293 190 142 160 122 108
25000 – – 290 337 244 210 18000 – 240 178 202 153 136
26000 – – – – 262 226 20000 – 294 218 248 188 167
27000 – – – – 280 241 22000 – – 263 299 226 200
Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³ Natural gas LL (N) LHV = 8.83 kWh/mn³; d = 0.641; Wi = 11.029 kWh/mn³
17500 – – 228 261 194 170 9600 215 161 135 144 124 116
18000 – – 234 269 199 174 10000 224 166 138 147 126 118
19000 – – 249 288 210 181 11000 250 179 146 158 132 122
20000 – – 263 307 220 189 12000 278 194 155 169 138 127
21000 – – 287 336 240 206 13000 – 210 164 181 144 131
22000 – – – – 263 225 14000 – 228 174 194 152 136
23000 – – – – 286 245 15000 – 246 184 208 159 142
24000 – – – – 310 265 16000 – 266 195 223 167 147
25000 – – – – 334 286 18000 – – 245 280 210 185
26000 – – – – – 302 20000 – – 300 344 257 226
27000 – – – – – 315 22000 – – – – 309 271
Note:
• The combustion chamber resistance (mbar) must be added to the
minimum gas pressure calculated.
• Preheated air: The difference between the burner resistance
(mbar) with preheated air and the burner resistance (mbar) with
ambient air must be added to the minimum gas pressure and
combustion chamber resistance (see section 5.2.2).
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 105
106 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
9. Order numbers
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 107
9. Order numbers
WK70 burners without preheated combustion air WK40 burners with preheated combustion air
Oil burners Oil burners
Burner type Version Order No. Burner type Version Order No.
WK80 burners without preheated combustion air WK80 burners with preheated combustion air
Oil burners Oil burners
Burner type Version Order No. Burner type Version Order No.
108 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
9.2 Order numbers, NR version
WK50 burners without preheated combustion air WK50 burners with preheated combustion air
Gas burners Gas burners
Burner type Version Order No. Burner type Version Order No.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 109
9. Order numbers
110 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
9.2 Order numbers, NR version
WK80 burners without preheated combustion air WK80 burners with preheated combustion air
Gas burners Gas burners
Burner type Version Order No. Burner type Version Order No.
WKG80/3-A ZM-NR DN 100 277 814 16 WKG80/3-A ZMH-NR DN 100 277 816 16
ZM-NR DN 125 277 814 17 ZMH-NR DN 125 277 816 17
ZM-NR DN 150 277 814 18 ZMH-NR DN 150 277 816 18
WKGL80/3-A ZM-NR DN 100 278 814 16 WKGL80/3-A ZMH-NR DN 100 278 816 16
ZM-NR DN 125 278 814 17 ZMH-NR DN 125 278 816 17
ZM-NR DN 150 278 814 18 ZMH-NR DN 150 278 816 18
WKGMS80/3-A ZM-NR DN 100 279 814 16 WKGMS80/3-A ZMH-NR DN 100 279 816 16
ZM-NR DN 125 279 814 17 ZMH-NR DN 125 279 816 17
ZM-NR DN 150 279 814 18 ZMH-NR DN 150 279 816 18
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 111
9. Order numbers
112 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
9.3 Order numbers, 1LN version
WK70 burners without preheated combustion air WK70 burners with preheated combustion air
Gas burners Gas burners
Burner type Version Order No. Burner type Version Order No.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 113
9. Order numbers
WK70 burners without preheated combustion air WK70 burners with preheated combustion air
Gas burners Gas burners
Burner type Version Order No. Burner type Version Order No.
114 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
9.5 Order numbers, 3LN multiflam® version
WK70 burners without preheated combustion air WK70 burners with preheated combustion air
Max. combustion air temperature100 °C
Gas burners
Gas burners
Burner type Version Order No.
Burner type Version Order No.
WKG70/1-B 3LN DN 80 277 737 15
3LN DN 100 277 737 16 WKG70/1-B ZMH-3LN DN 80 277 738 15
3LN DN 125 277 737 17 ZMH-3LN DN 100 277 738 16
3LN DN 150 277 737 18 ZMH-3LN DN 125 277 738 17
ZMH-3LN DN 150 277 738 18
WKG70/2-A 3LN DN 80 277 747 15
3LN DN 100 277 747 16 WKG70/2-A ZMH-3LN DN 80 277 748 15
3LN DN 125 277 747 17 ZMH-3LN DN 100 277 748 16
3LN DN 150 277 747 18 ZMH-3LN DN 125 277 748 17
ZMH-3LN DN 150 277 748 18
WKG70/3-A 3LN DN 65 277 724 14
3LN DN 80 277 724 15 WKG70/3-A ZMH-3LN DN 65 277 726 14
3LN DN 100 277 724 16 ZMH-3LN DN 80 277 726 15
3LN DN 125 277 724 17 ZMH-3LN DN 100 277 726 16
3LN DN 150 277 724 18 ZMH-3LN DN 125 277 726 17
ZMH-3LN DN 150 277 726 18
Dual-fuel burners
WK80 burners with preheated combustion air
Burner type Version Order No. Max. combustion air temperature100 °C
Dual-fuel burners
Burner type Version Order No.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 115
9. Order numbers
116 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
9.6 Order numbers, 1SF version
WK70 burners without preheated combustion air WK70 burners with preheated combustion air
Oil burners Oil burners
Burner type Version Order No. Burner type Version Order No.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 117
9. Order numbers
WKGL80/3-A ZM-1SF DN 100 278 815 16 WKGL80/3-A ZM-1SF DN 100 278 817 16
ZM-1SF DN 125 278 815 17 ZM-1SF DN 125 278 817 17
ZM-1SF DN 150 278 815 18 ZM-1SF DN 150 278 817 18
WKGMS80/3-A ZM-1SF DN 100 279 815 16 WKGMS80/3-A ZM-1SF DN 100 279 817 16
ZM-1SF DN 125 279 815 17 ZM-1SF DN 125 279 817 17
ZM-1SF DN 150 279 815 18 ZM-1SF DN 150 279 817 18
118 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
9.7 Order numbers, VSF version
WK80 burners without preheated combustion air WK80 burners with preheated combustion air
Gas burners Gas burners
Burner type Version Order No. Burner type Version Order No.
WKG80/4-A ZM-VSF DN 100 277 835 16 WKG80/4-A ZM-VSF DN 100 277 837 16
ZM-VSF DN 125 277 835 17 ZM-VSF DN 125 277 837 17
ZM-VSF DN 150 277 835 18 ZM-VSF DN 150 277 837 18
WKG80/5-A ZM-VSF DN 100 277 855 16 WKG80/5-A ZM-VSF DN 100 277 857 16
ZM-VSF DN 125 277 855 17 ZM-VSF DN 125 277 857 17
ZM-VSF DN 150 277 855 18 ZM-VSF DN 150 277 857 18
WKG80/6-A ZM-VSF DN 100 on request WKG80/6-A ZMH-VSF DN 100 on request
ZM-VSF DN 125 on request ZMH-VSF DN 125 on request
ZM-VSF DN 150 on request ZMH-VSF DN 150 on request
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 119
9. Order numbers
Cast aluminium burner housing and housing cover frame plate, cover, mixing assembly, ignition unit,
flame monitoring, flange gasket,, fixing screws l l l l l l
Heavy-oil execution (cooling for air actuator, oil actuator, controls assembly and flame sensor;
without cooling air fan) l l
Oil strainer in flow l l l l
Solenoid-activated nozzle shut-off assembly, regulating nozzle l l l l
Min. and max. oil pressure switches l l l l
Burner-mounted motorised oil pump l l l l
Burner-mounted oil preheater l l
Double gas solenoid valve, Class A l l l l
Ignition gas solenoid valve, Class A l l l
Min. and max. gas pressure switches l l l l
Gas butterfly valve, double-flanged bend/double-flanged reducing bend l l l l
Mixing assembly with regulating sleeve l l l l l
Mixing assembly with adjustable flame tube l
Controls assembly cover with ventilation slits l l
Variable mounting position
(Except with standard mounted pump) l l l l l l
Vertical firing (flame downwards) l l l l l l
Vertical firing (flame upwards)
(Except with standard mounted pump) l l
W-FM 100 digital combustion manager and ABE control and display unit in a burner-mounted
terminal enclosure l l l l l l
Air regulator actuator l l l l l l
Gas butterfly valve actuator l l l l
Oil regulator actuator l l l l
Regulating mixing sleeve actuator l l l l l
Flame-sensing ionisation probes l
QRI flame sensor (infrared and flicker detector) l l l l l
Air pressure switch for combustion air monitoring l l l l l l
Air pressure switch for cooling air monitoring l l
Suitable for unsupervised operation (72 h self-checking) l l l l l l
IP54 protection l l l l l l
Burners for preheated combustion air have the following standard features:
– Preheated air execution (cooling for air actuator, oil actuator, controls assembly and flame sensor)
– Internal sound-attenuating insulation
– Controls assembly cover with ventilation slits
– W-FM 100 digital combustion manager and ABE control and display loose for inclusion in a control panel
– Air pressure switch for cooling air monitoring
120 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
9.8 Scope of delivery, WK50
Details WKL WKMS WKG WKGL WKGMS
ZM ZM ZM ZM-NR 1LN ZM ZM-NR 1LN ZM ZM-NR
Cast aluminium burner housing and housing cover frame plate, cover,
mixing assembly, ignition unit, flame monitoring, flange gasket, fixing-
screws l l l l l l l l l l
Heavy-oil execution (cooling for air actuator, oil actuator, controls
assembly and flame sensor; without cooling air fan) l l l
Oil strainer in flow l l l l l l
Solenoid-activated nozzle shut-off assembly, regulating nozzle l l l l l l l
Min. and max. oil pressure switches l l l l l l l
Burner release thermostat in flow;
Bypass solenoid valve in flow l l l
Double gas solenoid valve, Class A l l l l l l l l
Ignition gas solenoid valve, Class A l l l l l l l l
Min. and max. gas pressure switches l l l l l l l l
Gass butterfly valve, double-flanged bend/double-flanged reducing bend l l l l l l l l
Mixing assembly with regulating sleeve l l l l l l l l
Mixing assembly with adjustable flame tube l l
Controls assembly cover with ventilation slits l l l
Variable mounting position l l l l l l l l l l
Vertical firing (flame downwards) l l l l l l l l l l
Vertical firing (flame upwards) l l l l l l l l l l
W-FM 100 digital combustion manager and ABE control and display unit
in a burner-mounted terminal enclosure l l l l l l l l l l
Air regulator actuator l l l l l l l l l l
Gas butterfly valve actuator l l l l l l l l
Oil regulator actuator l l l l l l l
Regulating mixing sleeve actuator l l l l l l l l
QRI flame sensor (infrared and flicker detector) l l l l l l l l l l
Air pressure switch for combustion air monitoring l l l l l l l l l l
Air pressure switch for cooling air monitoring l l l
Suitable for unsupervised operation (72 h self-checking) l l l l l l l l l l
IP54 protection l l l l l l l l l l
Burners for preheated combustion air have the following standard features:
– Preheated air execution (cooling for air actuator, oil actuator, controls assembly and flame sensor)
– Internal sound-attenuating insulation
– Controls assembly cover with ventilation slits
– W-FM 100 digital combustion manager and ABE control and display loose for inclusion in a control panel
– Air pressure switch for cooling air monitoring
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 121
9. Order numbers
122 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
9.8 Scope of delivery, WK80
Details WKL WKMS WKG WKGL WKGMS
ZM ZM ZM-NR 3LN ZM-NR 3LN ZM-NR
Cast aluminium burner housing and housing cover frame plate, cover, mixing assembly, ignition
flame monitoring, flange gasket,, fixing screws l l l l l l l
Heavy-oil execution (cooling for air actuator, oil actuator, controls assembly and flame
sensor; without cooling air fan) l l
Internal sound-attenuating sound insulation l l l l l l l
Oil strainer in flow l l l l l
Two shut-off solenoid valves in flow and return l
Solenoid-activated nozzle shut-off assembly, regulating nozzle l l l l
Min. and max. oil pressure switches l l l l l
Burner release thermostat in flow; bypasss solenoid valve in flow l l
Double gas solenoid valve, Class A l l l l l
Ignition gas solenoid valve, Class A l l l l l
LPG ignition device (ball valve, double solenoid valve with integral filter and
pressure regulator) and combustion manager W-FM 200, >17.5MW l l
Min. and max. gas pressure switches l l l l l
Gas butterfly valve, double-flanged bend/double-flanged reducing bend l l l l l
Mixing assembly with regulating sleeve l l l l l
Mixing assembly with modulating diffuser disc l l
Rail-mounted mixing assembly for easy removal during servicing l l l l l
Controls assembly cover with ventilation slits l l
Variable mounting position l l l l l
Vertical firing (flame downwards) l l
W-FM 100 digital combustion manager and ABE control and display unit in a burner-mounted
terminal enclosure l l l l l l l
Air regulator actuator l l l l l l l
Gas butterfly valve actuator l l l l l
Oil regulator actuator l l l l l
Regulating mixing sleeve actuator l l l l l
Stepping motor for fully adjustable mixing head l l
QRI flame sensor (infrared and flicker detector) l l l l l
QRA 73 flame sensor (UV, self-checking) l l
Air pressure switch for combustion air monitoring l l l l l l l
Air pressure switch for cooling air monitoring l l
suitable for unsupervised operation (72 h self-checking) l l l l l l l
IP54 protection l l l l l l l
Direct ignition l ❍ l l l l ❍
l Standard ❍ Optional
Burners for preheated combustion air have the following standard features:
– Preheated air execution (cooling for air actuator, oil actuator, controls assembly and flame sensor)
– Controls assembly cover with ventilation slits
– W-FM 100 digital combustion manager and ABE control and display loose for inclusion in a control panel
– Air pressure switch for cooling air monitoring
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 123
124 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10. Special equipment
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 on application 270 005 01
Variable speed drive with W-FM 200 LGW10 in lieu of LGW50 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim on application –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 270 000 15 270 000 15
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 005 06
a) W-FC 4.0 For parallel firing into a combustion chamber on request on request
from the same direction
b) W-FC 5.0 1) For burners firing into a combustion chamber from opposing directions, on request on request
individual/staged firing of multiple burners, and for plant with various flame sources
(e.g. waste and biomass incineration)
c) W-FC 6.0 1) For control of a separate FGR damper on plant with on request on request
extreme NOx requirements (USA)
See accessories list for optical alignment tool (1 required per site)
See accessories list for Service Packet software (incl. connection cable for CFC and VLoad)
1)
W-FM 200 required.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 125
10. Special equipment
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), WKL on application 270 005 01
loose, in lieu of W-FM100
WKMS on application 270 005 01
Variable speed drive with W-FM 200 LGW10 in lieu of LGW50 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim on application –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 270 000 15 270 000 15
0–40 bar pressure gauge with ball valve fitted in flow 270 000 09 270 000 09
0–40 bar pressure gauge with ball valve fitted in return 270 000 62 270 000 62
-1 +9 bar vacuum-pressure gauge with ball valve 120 000 62 120 000 62
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
126 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.1 Standard version
10.1.3 Special equipment for WKGL/WKGMS40/1 and /2
Special equipment WK40 ZM WK40 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), WKGL on application 270 005 01
loose, in lieu of W-FM100
WKGMS on application 270 005 01
Variable speed drive with W-FM 200 LGW10 in lieu of LGW50 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim on application –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 270 000 15 270 000 15
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 005 06
0–40 bar pressure gauge with ball valve fitted in flow 270 000 09 270 000 09
0–40 bar pressure gauge with ball valve fitted in return 270 000 62 270 000 62
-1+9 bar vacuum-pressure gauge with ball valve 120 000 62 120 000 62
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 127
10. Special equipment
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 270 007 65 270 005 01
Variable speed drive with W-FM 200 LGW10 in lieu of LGW50 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 270 000 15 270 000 15
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 006 92
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
128 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.1 Standard version
10.1.5 Special equipment for WKL/WKMS50/1 and /2
Special equipment WK50 ZM WK50 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module) WKL on application 270 005 01
loose, in lieu of W-FM100
WKMS 270 007 26 270 005 01
Variable speed drive with W-FM 200 LGW10 in lieu of LGW50 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 270 000 15 270 000 15
0–40 bar pressure gauge with ball valve fitted in flow 270 000 09 270 000 09
0–40 bar pressure gauge with ball valve fitted in return 270 000 62 270 000 62
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 129
10. Special equipment
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), WKGL on application 270 005 01
loose, in lieu of W-FM100
WKGMS 270 007 41 270 005 01
Variable speed drive with W-FM 200 LGW10 in lieu of LGW50 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 270 000 15 270 000 15
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 006 92
0–40 bar pressure gauge with ball valve fitted in flow 270 000 09 270 000 09
0–40 bar pressure gauge with ball valve fitted in return 270 000 62 270 000 62
-1+9 bar vacuum-pressure gauge with ball valve 120 000 62 120 000 62
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
130 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.1 Standard version
10.1.7 Special equipment for WKG70/1
Special equipment WK70 ZM WK70 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 270 007 66 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 005 29
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 131
10. Special equipment
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module) WKL on application 270 005 01
loose, in lieu of W-FM100
WKMS 270 007 68 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
0–40 bar pressure gauge with ball valve fitted in flow 270 000 09 270 000 09
0–40 bar pressure gauge with ball valve fitted in return 170 005 51 170 005 51
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
132 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.1 Standard version
10.1.9 Special equipment for WKGL/WKGMS70/1
Special equipment WK70 ZM WK70 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module) WKGL 270 006 44 270 005 01
loose, in lieu of W-FM100
WKGMS on application 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 005 29
0–40 bar pressure gauge with ball valve fitted in flow 270 000 09 270 000 09
0–40 bar pressure gauge with ball valve fitted in return 170 005 51 170 005 51
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 133
10. Special equipment
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), WKL 270 007 69 270 005 01
loose, in lieu of W-FM100
WKMS on application 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
0–40 bar pressure gauge with ball valve fitted in flow 170 006 09 170 006 09
0–40 bar pressure gauge with ball valve fitted in return 170 005 51 170 005 51
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
On application
134 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.2 NR version
10.2.1 Special equipment for WKG50/1 and /2
Special equipment WK50 ZM WK50 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 270 007 65 270 005 01
Variable speed drive with W-FM 200 LGW10 in lieu of LGW50 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 270 000 15 270 000 15
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 006 92
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 135
10. Special equipment
10.2 NR version
10.2.2 Special equipment for WKGL/WKGMS50/1 and /2
Special equipment WK50 ZM WK50 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), WKGL on application 270 005 01
loose, in lieu of W-FM100
WKGMS 270 007 41 270 005 01
Variable speed drive with W-FM 200 LGW10 in lieu of LGW50 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 270 000 15 270 000 15
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 006 92
0–40 bar pressure gauge with ball valve fitted in flow 270 000 09 270 000 09
0–40 bar pressure gauge with ball valve fitted in return 270 000 62 270 000 62
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
136 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.2 NR version
10.2.3 Special equipment for WKG70/1 and /3
Special equipment WK70 ZM WK70 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 270 007 66 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 005 29
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
WKG70/1 NR combustion head extension, not W-FM 300 mm 270 003 51 270 003 51
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 137
10. Special equipment
10.2 NR version
10.2.4 Special equipment for WKGL/WKGMS70/1 and /3
Special equipment WK70 ZM WK70 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), WKGL 270 006 44 270 005 01
loose, in lieu of W-FM100
WKGMS on application 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 005 29
0–40 bar pressure gauge with ball valve fitted in flow 270 000 09 270 000 09
0–40 bar pressure gauge with ball valve fitted in return 170 005 51 170 005 51
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
138 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.2 NR version
10.2.5 Special equipment for WKG80/3
Special equipment WK80 ZM WK80 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module, fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 270 006 68 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 006 19
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 139
10. Special equipment
10.2 NR version
10.2.6 Special equipment for WKGL/WKGMS80/3
Special equipment WK80 ZM WK80 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module) WKGL 270 007 70 270 005 01
loose, in lieu of W-FM100
WKGMS 270 007 71 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 006 19
0-40 bar pressure gauge with ball valve fitted in flow 170 006 09 170 006 09
0-40 bar pressure gauge with ball valve fitted in return 170 005 51 170 005 51
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
140 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.3 1LN version
10.3.1 Special equipment for WKG50/1 and /2
Special equipment WK50 ZM WK50 ZMH
Order No. Order No.
Analogue module / capacity controller for W-FM100 270 004 35 270 004 35
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 on application 270 005 01
Variable speed drive with W-FM 200 LGW10 in lieu of LGW50 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 270 000 15 270 000 15
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 006 92
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
On application
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 141
10. Special equipment
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 on application 270 005 01
Variable speed drive with W-FM 200 LGW10 in lieu of LGW50 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim on application –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 270 000 15 270 000 15
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 006 92
0–40 bar pressure gauge with ball valve fitted in flow 270 000 09 270 000 09
0–40 bar pressure gauge with ball valve fitted in return 270 000 62 270 000 62
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
On application
142 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.3 1LN version
10.3.3 Special equipment for WKG70/1 and /2
Special equipment WK70 ZM WK70 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 270 007 67 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 005 29
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
On application
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 143
10. Special equipment
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 on application 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 005 29
0–40 bar pressure gauge with ball valve fitted in flow 270 000 09 270 000 09
0–40 bar pressure gauge with ball valve fitted in return 170 005 51 170 005 51
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
On application
144 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.4 LN version
10.4.1 Special equipment for WKG40/2
Special equipment WK40 ZMH
Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) 270 005 29
On application
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 145
10. Special equipment
10.4 LN version
10.4.2 Special equipment for WKG70/1 and /2
Special equipment WK70 ZM WK70 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 on application 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 005 29
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
146 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.5 3LN version
10.5.1 Special equipment for WKG70/1, /2 and /3
Special equipment WK70 ZM WK70 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 on application 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 005 29
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
On application
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 147
10. Special equipment
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 on application 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 005 29
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
On application
148 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.5 3LN version
10.5.3 Special equipment for WKG80/1
Special equipment WK80 ZM WK80 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 270 006 68 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 006 19
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
On application
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 149
10. Special equipment
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 on application
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71
up to 250 °C –
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) –
0-40 bar pressure gauge with ball valve fitted in flow 170 006 09
0-40 bar pressure gauge with ball valve fitted in return 170 005 51
On application
150 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.6 1SF version
10.6.1 Special equipment for WKG50/2
Special equipment WK50 ZM WK50 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 270 007 65 270 005 01
Variable speed drive with W-FM 200 LGW10 in lieu of LGW50 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 270 000 15 270 000 15
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 006 92
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
On application
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 151
10. Special equipment
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), WKGL on application 270 005 01
loose, in lieu of W-FM100
WKGMS 270 007 41 270 005 01
Variable speed drive with W-FM 200 LGW10 in lieu of LGW50 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 270 000 15 270 000 15
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 006 92
0-40 bar pressure gauge with ball valve fitted in flow 270 000 09 270 000 09
0-40 bar pressure gauge with ball valve fitted in return 270 000 62 270 000 62
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
On application
152 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.6 1SF version
10.6.3 Special equipment for WKG70/1 and /2
Special equipment WK70 ZM WK70 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 270 007 66 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 005 29
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
On application
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 153
10. Special equipment
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), WKGL 270 006 44 270 005 01
loose, in lieu of W-FM100
WKGMS on application 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 005 29
0-40 bar pressure gauge with ball valve fitted in flow 270 000 09 270 000 09
0-40 bar pressure gauge with ball valve fitted in return 170 005 51 170 005 51
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
On application
154 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
10.6 1SF and VSF versions
10.6.5 Special equipment for WKG80/3, /4 and /5
Special equipment WK80 ZM WK80 ZMH
Order No. Order No.
W-FM 200 (incl. analogue module/capacity controller and VSD module), fitted, in lieu of W-FM100 270 005 00 –
W-FM 200 (incl. analogue module/capacity controller and VSD module), loose, in lieu of W-FM100 270 006 68 270 005 01
Variable speed drive with W-FM 200 LGW50 in lieu of LGW150 270 004 98 270 004 98
PT1000 air temperature sensor for efficiency display with W-FM 200 and O2 trim 270 005 12 –
Solenoid valve for air pressure switch test for continuous run fan or post-purge 170 002 71 170 002 71
Gas butterfly valve actuator cooling, offset gas butterfly valve (vertical burner mounting) – 270 006 19
110 V control voltage for W-FM 100/200 270 007 40 270 007 40
On application
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 155
156 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
11. Technical data
11.1 WK40
Standard and LN versions
Special equipment WK40/1 WK40/2
/3 – –
Oil pressure switch 0–10 bar type DSA46 F001 type DSA46 F001
Air pressure switch without VSD type LGW50 A2P type LGW50 A2P
3 solenoid valves 3 x 22 W 3 x 22 W
1 oil regulator 1 x 22 W 1 x 22 W
Oil solenoid valves 115 V (flow) type 321 H 2322 G 3/8 type 321 H 2322 G 3/8
115 V (return) type 121 G 2320 G 3/8 type 121 G 2320 G 3/8
230 V (bypass, normally open) on MS type 322 H 7306 G 3/8 type 322 H 7306 G 3/8
Actuator Air regulator type SQM 45.291 A9 (3 Nm) type SQM 45.291 A9 (3 Nm)
Mixing assembly type SQM 45.291 A9 (3 Nm) type SQM 45.291 A9 (3 Nm)
Gas butterfly valve type SQM 45.291 A9 (3 Nm) type SQM 45.291 A9 (3 Nm)
Oil regulator EL: type SQM 45.291 A9 (3 Nm) EL: type SQM 45.291 A9 (3 Nm)
MS: type SQM48.497 A9 (20 Nm) MS: SQM48.497 A9 (20 Nm)
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 157
11. Technical data
11.2 WK50
Standard, NR, 1LN and 1SF versions
Special equipment WK50/1
WK50/2
/3 –
3 solenoid valves 3 x 22 W
1 oil regulator 1 x 22 W
Protection IP54
158 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
11.3 WK70
Standard, NR, 1LN, LN, 3LN and 1SF versions
Special equipment WK70/1 WK70/1 version 3LN
WK70/2 WK70/2 version 3LN
WK70/3 WK70/3 version 3LN
Oil pressure switch 0–10 bar type DSA46 F001 type DSA46 F001
Air pressure switch without VSD type LGW150 A2P type LGW150 A2P
3 solenoid valves 3 x 22 W –
1 oil regulator 1 x 22 W –
Oil solenoid valves 115 V (flow) type 321 H 2522 G 1/2 2 x type 321 H 2522 G 1/2
115 V ( return) type 121 G 2520 G 1/2 2 x type 121 G 2520 G 1/2
Actuator Air regulator type SQM 48.497 A9 (20 Nm) type SQM 48.497 A9 (20 Nm)
Mixing assembly type SQM 48.497 A9 (20 Nm) type SQM 48.697 A9 (35 Nm)
Gas butterfly valve type SQM 45.291 A9 (3 Nm) type SQM 45.291 A9 (3 Nm)
Oil regulator EL: type SQM 48.297 A9 (3Nm) EL: type SQM 45.291 A9 (3Nm)
MS: type SQM48.497 A9 (20Nm)
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 159
11. Technical data
11.4 WK80
Standard, NR, 3LN, 1SF and VSF versions
Special equipment WK80 WK80 version 3LN
/3 type MDK80/1828 –
Oil pressure switch 0–10 bar type DSA46 F001 type DSA46 F001
Air pressure switch without VSD type LGW150 A2P type LGW150 A2P
3 solenoid valves 3 x 22 W –
1 oil regulator 1 x 22 W –
Oil solenoid valves 115 V (flow) type 5406A20 G 3/4 2 x type 5406A20 G 3/4
Actuator Air regulator type SQM 48.497 A9 (20 Nm) type SQM 48.497 A9 (20 Nm)
Mixing assembly type SQM 48.697 A9 (35 Nm) type SQM 48.697 A9 (35 Nm)
Gas butterfly valve type SQM 45.291 A9 (3 Nm) type SQM 45.291 A9 (3 Nm)
Oil regulator type SQM 48.497 A9 (20 Nm) type SQM 48.497 A9 (20 Nm)
Gas ingnition for heavy oil operation standard when QBR > 17.5 MW –
optional when QBR < 17.5 MW –
160 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
11.5 Weights
WK40, WK50, WK70, WK80
Approx. weight Approx. weight
Burner type kg Burner type kg
WKL50 160
WKMS50 165
WKGL50 165
WKGMS50 170
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 161
11. Technical data
P P
115V
115V
230V
115V 115V
P M P M
M 9 7 12 11 M 9 7 12 5 11
1 1
P P
115V
115V
230V
115V 115V
P M P M
M 9 7 12 11 M 9 7 12 5 11
13 1a 13 1a
1 Oil pump
1a External pump station with pressure maintenance
2 Oil preheater
3 Strainer
4 Oil flow temperature sensor
5 Oil return temperature sensor
6 Min. pressure switch
7 Max. pressure switch
8 Solenoid valve - flow (fitted in the direction of flow)
9 Solenoid valve - return (fitted against the direction of flow)
10 Bypass solenoid valve (normally open)
11 Nozzle assembly solenoid
12 Oil regulator
13 Filter
162 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
WKL multiflam® version oil burners
10 9 8 2 2 4
115V 115V
115V 115V
P M
1a 3 3 7 6 5
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 163
11. Technical data
Standard: Oil and gas operation with gas pilot ignition (Gas ignition
Oil = Direct ignition unit) with optional change-over Natural Gas/LPG
Gas = Ignition gas between V1 and V2 ). (Standard: Oil = LPG ignition, Gas = Natural gas ignition
With double gas valve and valve proving into V1)
9 9a 10 11 15 12 13 1 9 4 5 14 14 11
P P
LPG
P P P V1 V2
1 2 3 4 5 6 7 8
P P P
1 9 2 3 4 5 6 7 8
164 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
Gas valve train handing
Where an appliance has a hinged door, the valve train should
be installed on the opposite side of the appliance to its door
hinges.
Compensator
The use of a compensator is recommended in order to ensure
the tension-free installation of the valve train.
Gas meter
A gas meter must be installed in order to enable gas
consumption to be measured during commissioning.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 165
11. Technical data
Ignition variant A Ignition variant B with ignition pilot Ignition variant C with ignition pilot
A B C
V1 V2
LPG
Main gas line
Gas valve train with ignition variant B Gas valve train with ignition variant C
G
Light-oil ignition burner
P
166 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
Variants D to F
Optimal ignition for high-viscosity Flame monitoring is via a separate
liquid fuels on WK(G)MS80, using a ionisation probe, which necessitates the
high-quality ignition burner use of a W-FM 200 combustion
This variant facilitates reliable ignition manager.
at a considerably reduced rating. Ignition electrode
This reliable solution was developed
An ignition electrode is used to ignite especially for heavy and special fuel
Ionisation electrode
the pilot burner’s gas mixture. The oils with widely varying characteristics.
pilot burner is then used to ignite the It is also suitable for extreme ignitions, Front view
main flame upon fuel release. such as cold-starting plant that utilises Ignition electrode
pre-heated combustion air.
A typical LPG bottle (11/33 kg) is
adequate for ensuring reliable ignition.
For example, an 11 kg LPG bottle is
sufficient for well over 300 ignitions. Ignition variants D to F with ignition burner
D P P
W-MF
E P P
W-MF
F W-MF
LPG LPG
V1 V2 V1 V2
Main gas line Main gas line
Gas valve train with ignition variant D Gas valve train with ignition variant E Gas valve train with ignition variant F
WK…40–70 WK…80
WKL WKG / WKGL WKL WKMS WKMS WKG WKGMS WKGMS
WKMS WKGMS < 17.5 MW WKGL < 17.5 MW
A ● ● ● 2)
B ● ● ● 2)
C ● (WKMS)
D ● 1) ● 1)
E ● 1) ● 1)
F ● 1)
● 1)
G ● ●
Accessories for variants C to E 1 Complete set (Part No. 271 805 2601 2) comprising:
2 1 Pressure regulator for 11/33 kg LPG bottle
3
2 Hose-rupture protection
3 3 m hose
● Standard ● Optional 1)
W-FM 200 combustion manager required 2)
1SF version excluded
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 167
11. Technical data
30
200°C
250°C
150°C
100°C
DIN-CERTCO Reg. No.
Combustion chamber resistance [mbar]
25 5G846/12M
-5
35
150°C
100°C
30 5G846/12M
25 Full load range, vers. ZMH
10
Full load range, vers. ZM
5
-5
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000
168 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
11.7 Capacity graphs
11.7.2 NR version
Burner type WKG(L,MS)70/1-B ZM-NR
Rating, kW Natural gas 1100–7700
LPG 1100–7700
Light oil 1100–7700
Heavy oil 1800–7700
30
200°C
250°C
150°C
100°C
CE Product ID No.
Combustion chamber resistance [mbar]
25 CE-0085 AS 0410
10
Full load range, Capacity graph with reference to
5
vers. ZM EN 267 and/or EN 676.
-5
35
150°C
100°C
CE Product ID No.
Combustion chamber resistance [mbar]
30 CE-0085 AS 0410
25 Full load range, vers. ZMH
DIN-CERTCO Reg. No.
20 5G846/07M
15
-5
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 169
11. Technical data
35 200°C
250°C
150°C
100°C
CE Product ID No.
Combustion chamber resistance [mbar]
30 CE-0085 CL 0065
25 Full load range, vers. ZMH
DIN-CERTCO Reg. No.
20 5G1048/M
15
-5
0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000 22000 24000
170 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
11.7 Capacity graphs
11.7.3 1LN version
Burner type WKG(L) 70/1-B ZM-1LN
Rating, kW Natural gas 900–7000
LPG 1000–7000
Light oil 1370–7000
35
200°C
250°C
150°C
100°C
CE Product ID No.
Combustion chamber resistance [mbar]
30 CE-0085 AS 0410
25 Full load range, vers. ZMH
DIN-CERTCO Reg. No.
20 5G846/12M
15
-5
35
150°C
100°C
CE Product ID No.
Combustion chamber resistance [mbar]
30 CE-0085 AS 0410
25 Full load range, vers. ZMH
DIN-CERTCO Reg. No.
20 5G846/12M
15
-5
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 171
11. Technical data
30
200°C
250°C
150°C
100°C
CE Product ID No.
Combustion chamber resistance [mbar]
25 CE-0085 AS 0410
-5
35
150°C
100°C
CE Product ID No.
Combustion chamber resistance [mbar]
30 CE-0085 AS 0410
25 Full load range, vers. ZMH
10
Full load range, vers. ZM
5
-5
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000
172 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
11.7 Capacity graphs
11.7.5 3LN version
Burner type WKG(L)70/1-B ZM-3LN
Rating, kW Natural gas 1000–10000
LPG 1550–10000
Light oil 1550–10000
35
CE Product ID No.
Combustion chamber resistance [mbar]
30 CE-0085 AS 0410
25
DIN-CERTCO Reg. No.
20 5G846/12M
15 Full load range, vers. ZM
-5
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 173
11. Technical data
35
CE Product ID No.
Combustion chamber resistance [mbar]
30 CE-0085 AS 0410
25
DIN-CERTCO Reg. No.
20 5G846/12M
15
Full load range,
10 vers. ZM Capacity graph with reference to
EN 267 and/or EN 676.
5
-5
35
CE Product ID No.
Combustion chamber resistance [mbar]
30 CE-0085 CL 0065
25
DIN-CERTCO Reg. No.
20 5G1048/M
15 Full load range, vers. ZM
-5
174 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12. Dimensions
d3
30°
60°
d4
d5
d6
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 175
176 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12. Dimensions
400
280
250
356,5
444
Oil
578*
inlet Cooling air connection
not fitted to WKL40
221
Ø30
180
200
400
M12
Ø290
240
220
310
80
ø8
258
368
261
400
280
356,5
444
Oil
578*
400
M12
Ø290
240
220
310
80
368
Dimensions are approximate. We reserve the right to
make changes as a result of technical developments.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 177
12. Dimensions
400
280
250
356,5
444
Oil
578
inlet
221
Ø30
180
200
400
M12
Ø290
240
220
310
80
ø8
258
368
261
400
280
356,5
444
Oil
578
inlet
221
Ø30
400
M12
Ø290
240
220
310
80
ø8
258
368
Dimensions are approximate. We reserve the right to
make changes as a result of technical developments.
178 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.2 Standard version
12.2.3 WKG40 gas burner, version ZM
WKG40/1 version ZM
313 338
Ø280
Ø250
400
384
444
DN65 140
116 260
388 Drilling dimensions
1046
360
180
200
400
M12
Ø290
240
220
310
80
ø8
258
368
WKG40/2 version ZM
313 338
261
400
280
384
444
DN65 140
116 260
388 Drilling dimensions
1046 360
180
200
400
M12
Ø290
240
220
310
80
ø8
258
368
Dimensions are approximate. We reserve the right to
make changes as a result of technical developments.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 179
12. Dimensions
Ø280
Ø250
400
384
444
578
DN65 140
180
200
400
M12
Ø290
240
220
310
80
ø8
258
368
578
DN65
140
116 260 Ø90
230 388 255 Drilling dimensions
1046 360
Cooling air connection
180
200
400
M12
Ø290
240
220
310
80
ø8
258
368
Dimensions are approximate. We reserve the right to
make changes as a result of technical developments.
180 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.2 Standard version
12.2.5 WKGL/WKGMS40 dual-fuel burner, version ZM
WKGL/WKGMS40 /1 version ZM Preheater not
fitted to 438* 338
WKGL40
186*
190*
400
280
250
356,5
384
444
Oil
578*
inlet Cooling air connection
not fitted to WKL40
221
Ø30
DN65
140
230 116 260 Ø30 Ø90*
297 388 342 255* Drilling dimensions
1046 Oil Cooling air connection* 360
outlet
469
180
200
400
M12
Ø290
240
220
310
80
ø8
258
368
261
400
280
356,5
384
444
Oil
578*
inlet
Cooling air connection
not fitted to WKL40
221
Ø30
DN65
140
230 116 260 Ø30 Ø90*
297 388 342 255* Drilling dimensions
1046 Oil 360
outlet Cooling air connection*
469
180
200
400
M12
Ø290
240
220
310
80
368
Dimensions are approximate. We reserve the right to
make changes as a result of technical developments.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 181
12. Dimensions
400
280
250
356,5
384
444
Oil
578
inlet
221
Ø30
DN65
140
230 116 260 Ø30 Ø90
297 388 342 255 Drilling dimensions
1046 Oil Cooling air connection 360
outlet
469
180
200
400
M12
Ø290
240
220
310
80
ø8
258
368
261
400
280
356,5
384
444
Oil
578
inlet
221
Ø30
DN65
140
230 116 260 Ø30 Ø90
297 388 342 255 Drilling dimensions
1046 Oil Cooling air connection* 360
outlet
469
180
200
400
M12
Ø290
240
220
310
80
182 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.2 Standard version
12.2.7 WKL/WKMS50 oil burner, version ZM
WKL/WKMS50/1 version ZM 402
540
380
290
518
650*
Cooling air connection
not fitted to WKL50
97
Ø30
17
245
270
M12
Ø390
365
403
270
100
370
465
495
* Not applicable to WKL 50
650*
17
392 Ø30
258 528 Ø30
Ø90*
165 426 125 311*
Drilling dimensions
490 Oil Oil
1212 Cooling air connection* outlet inlet
540
245
270
M12
Ø390
365
403
270
100
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 183
12. Dimensions
Ø380
Ø290
540
518
650
97
17
Ø30
258 Ø90 Ø30
165 426 528 337
125 311 Drilling dimensions Oil Oil
490
1212
Cooling air connection outlet inlet
540
245
270
M12
Ø390
365
403
270
100
370
465
495
650
97
17
Ø30
Ø30
258 Ø90 Drilling dimensions
165 426 528 392 125 311 490 Oil Oil
Cooling air-connection outlet inlet
1212
540
245
270
M12
Ø390
365
403
270
100
370
465
495
Dimensions are approximate. We reserve the right to
make changes as a result of technical developments.
184 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.2 Standard version
12.2.9 WKG50 gas burner, version ZM
WKG50/1 version ZM 373 402
Ø380
Ø290
540
518
464
DN80 165
158 337
528
Drilling dimensions
1212 490
540
245
270
M12
Ø390
365
403
100
270
370
465
495
DN80 165
158 Drilling dimensions
528 490
1212 392 540
245
270
M12
Ø390
365
403
270
100
370
465
495
Dimensions are approximate. We reserve the right to
make changes as a result of technical developments.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 185
12. Dimensions
Ø380
Ø290
540
464
518
DN80 165
158 337 Ø90
258 528 311 Drilling dimensions
1212 Cooling air connection 490
540
245
270
M12
Ø390
365
403
270
100
370
465
495
650
DN80 165
Ø90
158 392 Drilling dimensions
311
258 528 490
Cooling air connection
1212 540
245
270
M12
Ø390
365
403
270
100
370
Dimensions are approximate. We reserve the right to 465
495
make changes as a result of technical developments.
186 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.2 Standard version
12.2.11 WKGL/WKGMS50 dual-fuel burner, version ZM
WKGL/WKGMS50/1 version ZM 373 402
540
380
290
518
464
650*
Cooling air connection
not fitted to WKGL50
97
DN80
Ø30
17
165
258 158 337 Ø90* Ø30
165 426 528 125 311* Drilling dimensions
1212 490 Oil Oil
Cooling air connection* outlet inlet
540
245
270
M12
Ø390
365
403
270
100
370
465
495
* Not applicable to WKGL50
650*
DN80
17
165 Ø30
258 158 392 Ø30
Ø90*
165 426 528 125 311* Drilling dimensions Oil Oil
1212 490 outlet inlet
Cooling air connection*
540
245
270
M12
Ø390
365
403
270
100
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 187
12. Dimensions
Ø380
Ø290
540
518
464
650
97
DN80 165
17
Ø30
258 158 337 Ø90 Ø30
125 311
Drilling dimensions
165 426 528 Oil Oil
490
Cooling air connection outlet inlet
1212
540
245
270
M12
Ø390
365
403
270
100
370
465
495
444
650
97
DN80
17
165 Ø30
Ø30
258 158 392 Ø90
125 311
165 426 528 Drilling dimensions Oil Oil
1212 Cooling air connection 490 outlet inlet
540
245
270
M12
Ø390
365
403
270
100
370
Dimensions are approximate. We reserve the right to 465
495
make changes as a result of technical developments.
188 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.2 Standard version
12.2.13 WKL/WKMS70 oil burner, version ZM
WKL/WKMS70/1 version ZM 466
Ø400
Ø518
700
547*
628
145 55 Ø90*
300 730 417 360*
1689 Oil Drilling dimensions
outlet Oil
inlet Cooling air connection* M16
700
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
* Not applicable to WKL
145 55
300 730 462 360*
1689 Oil Oil
outlet Cooling air connection*
inlet Drilling dimensions
700
M16
30
°
Ø530
Ø735
60°
°
30
556
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 189
12. Dimensions
Ø400
Ø518
Ø700
547
628
145 55 Ø90
300 730 417
360
1689 Oil Oil Cooling air connection Drilling dimensions
outlet inlet M16
700
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
60°
°
30
556
518
414
190 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.2 Standard version
12.2.15 WKG70 gas burner, versions ZM and ZMH
454 466
WKG70/1 version ZM
Ø400
Ø518
700
589
628
DN100 205
188
730
700
Drilling dimensions
1689 417 M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
454
Ø90
205
DN100
360
188 Cooling air connection
300 730
1689 417
700 Drilling dimensions
M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 191
12. Dimensions
Ø400
Ø518
700
589
628
145 55
DN100
188 Oil 205
730 outlet Oil inlet Drilling dimensions
700
1689 417 M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
454 466
WKGMS70/1 version ZM
Ø400
Ø518
700
547
628
145 55 Ø90
DN100 205
188 360
300 730 Oil Oil
1689 417
Cooling air connection Drilling dimensions
outlet inlet
M16
700
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
639
make changes as a result of technical developments.
192 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.2 Standard version
12.2.17 WKGL/WKGMS70 dual-fuel burner, version ZMH
454
WKGL/WKGMS70/1 version ZMH
Ø400
Ø518
Ø700
547
628
145 55 Ø90
DN100 205
360
188
300 730 Cooling air connection Drilling dimensions
700 M16
1689 417
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
make changes as a result of technical developments. 639
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 193
12. Dimensions
Ø590
850
708
1023 500
2123 205 40
Oil Oil
outlet inlet
Drilling dimensions
M16
850
Ø7
70
0
Ø6 4
Ø87
5
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
194 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.2 Standard version
12.2.18 WKMS80 oil burner, version ZM
WKMS80/3 version ZM 524
Ø590
850
610
708
Ø90
393 1023 500
205 40
2123
410
Ø7
70
0
Ø64
Ø87
5
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 195
12. Dimensions
Ø590
850
610
708
Ø90
393 1023 500
205 40
2123
410
Ø7
70
0
Ø64
Ø8
30 75
°
30
°
30° 30°
300
500
644
670
100
556
644
670
196 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.3 NR version
12.3.1 WKG50 gas burner, version ZM-NR
WKG50/1 version ZM-NR 373 402
Ø380
Ø290
540
518
464
DN80 165
158 307
Drilling dimensions
490
528
1212
245
540
270
M12
Ø390
365
403
270
100
370
465
495
DN80 165
M12
Ø390
365
403
270
100
370
465
Dimensions are approximate. We reserve the right to 495
make changes as a result of technical developments.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 197
12. Dimensions
12.3 NR version
12.3.2 WKG50 gas burner, version ZMH-NR
WKG50/1 version ZMH-NR
Ø380
Ø290
540
464
518
650
DN80 165
158 307 Ø90
258 528 373 311 Drilling dimensions
1212 490
Cooling air connection
540
245
270
M12
Ø390
365
403
270
100
370
465
495
650
DN80 165
Ø90
158 337
311
Drilling dimensions
258 528 490
Cooling air connection
1212 540
245
270
M12
Ø390
365
403
270
100
370
465
Dimensions are approximate. We reserve the right to 495
make changes as a result of technical developments.
198 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.3 NR version
12.3.3 WKGL/WKGMS50 dual-fuel burner, version ZM-NR
WKGL/WKGMS50 /1 version ZM-NR 373 402
Ø380
Ø290
540
518
464
650*
Cooling air connection
not fitted to WKL40
97
DN80
17
125 165
258 Ø90* Ø30
158 307
311* Ø30
165 426 528 Drilling dimensions
1212 Cooling air connection* 490 Oil Oil
outlet inlet
540
245
270
M12
Ø390
365
403
270
100
370
465
495
* Not applicable to WKGL50
650*
DN80
17
M12
Ø390
365
403
270
100
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 199
12. Dimensions
12.3 NR version
12.3.4 WKGL/WKGMS50 dual-fuel burner, version ZMH-NR
WKGL/WKGMS50 /1 version ZMH-NR 373
Ø380
Ø290
540
464
518
650
97
DN80
17
125 165
158 307 Ø90 Ø30
258 528 Ø30
311
165 426
Drilling dimensions
Cooling air connection 490
Oil Oil
1212 outlet inlet
540
245
270
M12
Ø390
365
403
270
100
370
465
495
650
97
DN80
17
125 165
Ø30
Ø90
258 158 337 Ø30
311 Drilling dimensions
165 426 528 490 Oil Oil
Cooling air connection
1212 540 outlet inlet
245
270
M12
Ø390
365
403
270
100
370
465
Dimensions are approximate. We reserve the right to 495
make changes as a result of technical developments.
200 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.3 NR version
12.3.5 WKG70 gas burner, version ZM-NR
454 466
Ø400
Ø518
700
589
628
DN100 205
188
730
700
1689 347 Drilling dimensions
M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
DN100 205
188
730
Drilling dimensions
700 M16
1689 462
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
639
make changes as a result of technical developments.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 201
12. Dimensions
12.3 NR version
12.3.6 WKG70 gas burner, version ZMH-NR
454
Ø400
Ø518
700
547
589
628
Ø90
DN100 205
188 360
300 730
Cooling air connection
1689 347 700
Drilling dimensions
M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
454
WKG70/3 version ZMH-NR
Ø480
Ø518
700
547
589
628
Ø90
DN100 205
360*
188
Cooling air connection
300 730 Drilling dimensions
1689 462 700 M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
639
make changes as a result of technical developments.
202 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.3 NR version
12.3.7 WKGL/WKGMS70 dual-fuel burner, version ZM-NR
WKGL/WKGMS70/1 version ZM-NR 454 466
Ø400
Ø518
700
547*
589
628
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
454 466
WKGL/WKGMS70/3 version ZM-NR
Ø480
Ø518
700
547*
589
628
145 55
DN100 205
Oil
188 outlet Oil 360* Drilling dimensions
300* 730 Cooling air connection* M16
inlet
1689 462 700
30
°
Ø530
Ø735
60°
°
30
556
518
414
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 203
12. Dimensions
12.3 NR version
12.3.8 WKGL/WKGMS70 dual-fuel burner, version ZMH-NR
WKGL/WKGMS70/1 version ZMH-NR 454
Ø400
Ø518
700
547
589
628
145 55 Ø90
DN100 Oil 205
188 outlet 360 Drilling dimensions
300 730 Oil Cooling air connection M16
1689 347 inlet
30
°
700
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
204 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.3 NR version
12.3.8 WKGL/WKGMS70 dual-fuel burner, version ZMH-NR
WKGL/WKGMS70/3 version ZMH-NR 454
Ø480
Ø518
700
547
589
628
145 55
Ø90
DN100 Oil 205
188 outlet Oil 360
300 730
inlet
Cooling air connection Drilling dimensions
1689 462
M16
700
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 205
12. Dimensions
12.3 NR version
12.3.9 WKG80 gas burner, versions ZM-NR
WKG80/3 version ZM-NR 486 524
Ø590
850
708
741
DN150 283
368 500
Ø7
70
0
Ø64
Ø87
5
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
206 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.3 NR version
12.3.9 WKG80 gas burner, versions ZMH-NR
WKG80/3 version ZMH-NR 486
Ø590
850
610
708
741
Ø90
DN150 283
368 500 410
Ø7
70
0
Ø6 4
Ø87
5
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 207
12. Dimensions
12.3 NR version
12.3.10 WKGL80 dual-fuel burner, version ZM-NR
WKGL80/3 version ZM-NR 486 524
Ø590
850
708
741
205 40
DN150 283
368 500 Oil Oil
1023 outlet inlet Drilling dimensions
2123 M16
850
Ø7
70
0
Ø6 4
Ø87
5
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
208 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.3 NR version
12.3.10 WKGMS80 dual-fuel burner, version ZM-NR
WKGMS80/3 version ZM-NR 486 524
Ø590
850
610
708
741
Ø90
205 40
DN150 283
368 500 410
Cooling air connection
393 1023 Oil Oil Drilling dimensions
2123
outlet inlet M16
850
Ø7
70
0
Ø6 4
Ø87
5
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 209
12. Dimensions
12.3 NR version
12.3.11 WKGL80 version ZMH-NR
WKGL80/3 version ZMH-NR 486
Ø590
850
610
708
741
Ø90
205 40
DN150 283
368 500 410
Ø7
70
0
Ø6 4
Ø87
5
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
210 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.3 NR version
12.3.11 WKGMS80 version ZMH-NR
WKGMS80/3 version ZMH-NR 486
Ø590
850
610
708
741
Ø90
205 40
DN150 283
368 500 410
Cooling air connection
393 1023 Oil Oil Drilling dimensions
2123 outlet inlet M16
850
770
640
875
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 211
12. Dimensions
Ø380
Ø290
540
518
464
DN80 165
540
245
270
M12
Ø390
365
403
270
100
370
465
495
DN80 165
158 452
528
Drilling dimensions
1212 540 490
245
270
M12
Ø390
365
403
270
100
370
Dimensions are approximate. We reserve the right to 465
make changes as a result of technical developments. 495
212 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.4 1LN version
12.4.2 WKG50 gas burner, version ZMH-1LN
WKG50/1 version ZMH-1LN 373
Ø380
Ø290
540
464
518
650
DN80 165
158 307 Ø90
258 528 311
1212
Cooling air connection
Drilling dimensions
490
540
245
270
M12
Ø390
365
403
270
100
370
465
495
650
DN80 165
Ø90
158 452
311 Drilling dimensions
258 528 490
540 Cooling air connection
1212
245
270
M12
Ø390
365
403
270
100
370
Dimensions are approximate. We reserve the right to 465
495
make changes as a result of technical developments.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 213
12. Dimensions
Ø380
Ø290
540
518
464
Ø30
97
DN80
17
540
245
270
M12
Ø390
365
403
270
100
370
465
495
Ø30
97
DN80
17
M12
Ø390
365
403
270
100
370
Dimensions are approximate. We reserve the right to 465
make changes as a result of technical developments. 495
214 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.4 1LN version
12.4.4 WKGL50 dual-fuel burner, version ZMH-1LN
WKGL50/1 version ZMH-1LN 373
Ø380
Ø290
540
464
518
650
97
DN80
17
125 165
158 307 Ø90 Ø30
258 528 Ø30
311 Drilling dimensions Oil
165 426 Cooling air connection 490 outlet Oil
1212 inlet
540
245
270
M12
Ø390
365
403
270
100
370
465
495
650
97
DN80
17
125 165
Ø30
Ø90
258 158 452 Ø30
311 Oil
165 426 528
Drilling dimensions outlet
540 Cooling air connection Oil
490
1212 inlet
245
270
M12
Ø390
365
403
270
100
370
465
Dimensions are approximate. We reserve the right to 495
make changes as a result of technical developments.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 215
12. Dimensions
Ø406
Ø518
700
589
628
DN100 205
188
300 730
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
Dimensions are approximate. We reserve the right to 639
216 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.4 1LN version
12.4.5 WKG70 gas burner, version ZM-1LN
WKG70/2 version ZM-1LN
454 466
Ø480
Ø518
700
589
628
DN100 205
188
300 730
Drilling dimensions
1689 477 700 M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 217
12. Dimensions
Ø406
Ø518
700
547
589
628
Ø90
DN100 205
188 360
300 730 Cooling air connection
1689 439 700 Drilling dimensions
M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
454
WKG70/2 version ZMH-1LN
Ø480
Ø518
700
547
589
628
Ø90
DN100 205
360
188
Cooling air connection
300 730 Drilling dimensions
1689 477 700 M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
639
make changes as a result of technical developments.
218 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.4 1LN version
12.4.7 WKGL70 dual-fuel burner, version ZM-1LN
454 466
Ø406
Ø518
700
589
628
145 55
DN100 Oil 205
188 outlet Oil
300 730 inlet
1689 439 700 Drilling dimensions
M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
454 466
WKGL70/2 version ZM-1LN
Ø480
Ø518
700
589
628
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
639
make changes as a result of technical developments.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 219
12. Dimensions
Ø406
Ø518
700
547
589
628
145 55 Ø90
DN100 205
Oil
188 360
outlet Oil
300 730 inlet Cooling air connection
1689 439 700
Drilling dimensions
M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
454
WKGL70/2 version ZMH-1LN
Ø480
Ø518
700
547
589
628
145 55 Ø90
DN100 205
188
Oil 360
outlet Oil Cooling air connection Drilling dimensions
300 730 inlet
1689 477 700 M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
639
make changes as a result of technical developments.
220 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.5 LN version
12.5.1 WKG40 gas burner, version ZMH-LN
WKG40/2 version ZMH-LN
313
Ø296
400
384
444
578
DN65 140
180
200
M12
Ø320
240
220
310
80
ø8
258
368
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 221
12. Dimensions
12.5 LN version
12.5.2 WKG70 gas burner, version ZM-LN
454 466
Ø406
Ø518
700
589
628
DN100 205
188
300 730
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
454 466
WKG70/2 version ZM-LN
Ø480
Ø518
700
589
628
DN100 205
188
300 730 Drilling dimensions
1689 477 700 M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
639
make changes as a result of technical developments.
222 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.5 LN version
12.5.3 WKG70 gas burner, version ZMH-LN
454
Ø406
Ø518
700
547
589
628
Ø90
DN100 205
188 360
300 730 Cooling air connection
1689 439 700 Drilling dimensions
M16
30
°
Ø530
Ø735
60°
°
30
556
518
496 414
602
639
454
WKG70/2 version ZMH-LN
Ø480
Ø518
700
547
589
628
Ø90
DN100 205
360
188
300 730
Cooling air connection Drilling dimensions
1689 477 700 M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
639
make changes as a result of technical developments.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 223
12. Dimensions
Ø444
Ø518
700
589
628
DN100 205
188
730 700
1689 474
Drilling dimensions
M16
30
°
Ø530
Ø735
60°
°
30
556
518
496 414
602
639
454 466
WKG70/2 version 3LN
Ø480
Ø518
700
589
628
DN100 205
188
730 Drilling dimensions
1689 475 700 M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
639
make changes as a result of technical developments.
224 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.6 3LN version
12.6.2 WKG70 gas burner, version ZMH-3LN
454
WKG70/1 version ZMH-3LN
Ø444
Ø518
700
547
589
628
Ø90
DN100 205
188 360
300 730
Cooling air connection
1689 474 700 Drilling dimensions
M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
454
WKG70/3 version ZMH-3LN
Ø480
Ø518
700
547
589
628
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
make changes as a result of technical developments. 639
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 225
12. Dimensions
Ø444
Ø518
700
589
628
145 55
DN100
205
188 Oil
outlet Oil
730
inlet Drilling dimensions
1689 474 700
M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
454 466
WKG70/2 version 3LN
Ø480
Ø518
700
589
628
145 55
DN100
205
188 Oil Oil
730 outlet inlet Drilling dimensions
1689 475 700 M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
639
make changes as a result of technical developments.
226 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.6 3LN version
12.6.4 WKGL70 dual-fuel burner, version ZMH-3LN
454
WKGL70/1 version ZMH-3LN
Ø444
Ø518
700
547*
589
628
DN100 145 55
188 205
Oil 360*
300* 730
outlet Oil Cooling air connection *
1689 474 inlet Drilling dimensions
700 M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
* Not applicable to WKGL 639
454
WKGL70/3 version ZMH-3LN
Ø480
Ø518
700
547*
589
628
DN100 145 55
188 205
Oil 360*
300* 730
outlet Oil Cooling air connection *
1689 475,03 inlet Drilling dimensions
700 M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 227
12. Dimensions
Ø540
Ø558
850
708
741
DN150 283
368 510
Ø7
70
0
Ø64
Ø8
75
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
486 524
WKGL80/1 version 3LN
Ø540
Ø558
850
708
741
205 40
DN150 283
368 510
1023
Oil Oil Drilling dimensions
outlet inlet
2123
850
M16
Ø7
70
0
Ø64
Ø8
75
30
°
30
°
30° 30°
300
500
644
670
100
556
Dimensions are approximate. We reserve the right to 644
670
make changes as a result of technical developments.
228 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.6 3LN version
12.6.6 WK/WKGL80 gas and dual-fuel burners, vers. ZMH-3LN
486
WKG80/1 version ZMH-3LN
Ø540
Ø558
850
610
708
741
Ø90
DN150 283
368 510 410
Ø7
70
0
Ø64
Ø8
75
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 229
12. Dimensions
540
380
350
518
464
DN80 165
158 337
Drilling dimensions
490
528
1212
540
245
270
M12
Ø390
365
403
270
100
370
465
495
650
DN80 165
Ø90
158 337
311 Drilling dimensions
258 528 490
Cooling air connection
1212 540
245
270
M12
Ø390
365
403
270
100
370
Dimensions are approximate. We reserve the right to 465
495
make changes as a result of technical developments.
230 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.7 1SF version
12.7.2 WKG70 gas burner, version ZM-1SF
454 466
Ø400
Ø518
700
589
628
DN100 205
188
730
700
1689 347 Drilling dimensions
M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
DN100 205
188
730
700 Drilling dimensions
1689 362
M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 231
12. Dimensions
Ø400
Ø518
700
547
589
628
Ø90
DN100 205
188 360
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
454
WKG70/2 version ZMH-1SF
Ø480
Ø518
700
547
589
628
Ø90
DN100 205
360*
188
300 730
Cooling air Drilling dimensions
1689 362 700 connection M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
639
make changes as a result of technical developments.
232 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.7 1SF version
12.7.4 WKL/WKMS70 oil burners, versions ZM-1SF/ZMH-1SF
WKL/WKMS70/2 version ZM-1SF
466
Ø480
Ø518
700
547*
628
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
* Not applicable to WKL 639
145 55 Ø90
300 730 362
360
1689
Oil Oil Cooling air
Drilling dimensions
outlet inlet connection M16
700
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
Dimensions are approximate. We reserve the right to 602
639
make changes as a result of technical developments.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 233
12. Dimensions
Ø600
850
708
1023 480
2123 205 40
Oil Oil
Drilling dimensions
outlet inlet
M16
850
Ø7
70 0
Ø6 4
Ø8
75
°
30
30
°
3 0° 30°
300
500
644
670
100
556
644
670
524
WKMS80/3 version ZM-1SF
Ø600
850
610
708
Ø90
393 1023 480
205 40
2123
410
Oil Oil Cooling air
outlet inlet connection
Drilling dimensions
M16
850
Ø7
70 0
Ø64
Ø8
75
°
30
30
°
30° 30°
300
500
644
670
100
556
644
670
Dimensions are approximate. We reserve the right to
make changes as a result of technical developments.
234 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.7 1SF version
12.7.6 WKL/WKMS80/3 oil burners, version ZMH-1SF
WKL/WKMS80/3 version ZMH-1SF
Ø600
850
610
708
Ø90
393 1023 480
205 40
2123
410
Oil Oil Cooling air
Drilling dimensions
M16
outlet inlet connection
850
Ø7
70 0
Ø64
Ø8
75
°
30
30
°
3 0° 30°
300
500
644
670
100
556
644
670
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 235
12. Dimensions
Ø400
Ø518
700
547*
589
628
Cooling air
connection
not fitted to WKGL70
145 55
DN100 205
188 Oil Oil 360*
300* 730 outlet inlet Cooling air connection * Drilling dimensions
1689 347 700 M16
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
* Not applicable to WKGL 602
639
Cooling air
connection
not fitted to WKGL70
145 55
DN100 205
188 Oil Oil 360*
Drilling dimensions
300* 730 outlet inlet Cooling air connection * M16
60°
°
30
556
518
414
236 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.7 1SF version
12.7.8 WKGL/WKGMS70 dual-fuel burners, version ZMH-1SF
454
WKGL/WKGMS70/1 version ZMH-1SF
Ø400
Ø518
700
547
589
628
145 55 Ø90
DN100 205
188 Oil Oil 360 Drilling dimensions
300 730 outlet inlet M16
Cooling air connection
1689 347
30
700
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
639
145 55
Ø90
DN100 205
188 Oil Oil 360 Drilling dimensions
300 730
outlet inlet Cooling air connection
1689 362
M16
700
30
°
Ø530
Ø735
60°
°
30
556
518
414
496
602
Dimensions are approximate. We reserve the right to 639
make changes as a result of technical developments.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 237
12. Dimensions
Ø600
850
708
741
205 40
DN150 283
368 480
1023
Oil Oil Drilling dimensions
outlet inlet
2123 M16
850
Ø7
70 0
Ø64
Ø8
75
°
30
30
°
30° 30°
300
500
644
670
100
556
644
670
486 524
WKGMS80/3 version ZM-1SF
Ø600
850
610
708
741
Ø90
205 40
DN150 283
368 480 Oil Oil 410 Drilling dimensions
393 1023 outlet inlet Cooling air
2123 connection M16
850
Ø7
70 0
Ø6 4
Ø8
75
°
30
30
°
3 0° 3 0°
300
500
644
670
100
556
644
670
Dimensions are approximate. We reserve the right to
make changes as a result of technical developments.
238 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.7 1SF version
12.7.10 WKGL/WKGMS80/3 dual-fuel burners, version ZMH-1SF
WKGL80/3 version ZMH-1SF 486
Ø600
850
610
708
741
Ø90
205 40
DN150 283
368 472
Oil Oil 410 Drilling dimensions
393 1023 outlet inlet Cooling air
2123 connection M16
850
Ø7
70 0
Ø6 4
Ø8
75
°
30
30
°
3 0° 30°
300
500
644
670
100
556
644
670
741
Ø90
205 40
DN150 283
368 480
Oil Oil 410 Drilling dimensions
393 1023 outlet inlet Cooling air
2123 connection M16
850
Ø7
70 0
Ø64
Ø8
75
°
30
30
°
30° 30°
300
500
644
670
100
556
644
670
Dimensions are approximate. We reserve the right to
make changes as a result of technical developments.
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 239
12. Dimensions
Ø590
850
708
741
DN150 283
368 500
1023
Drilling dimensions
2123 M16
850
Ø7
70
0
Ø6 4
Ø87
5
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
240 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.8 VSF version
12.8.1 WKG80 gas burner, version ZMH-VSF
WKG80/4, /5 version ZMH-VSF 486
Ø590
850
610
708
741
Ø90
DN150 283
368 500 410 Drilling dimensions
393 1023 Cooling air
2123
connection M16
850
Ø7
70
0
Ø6 4
Ø87
5
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 241
12. Dimensions
Ø625
850
708
741
DN150 283
368 502
Ø7
70
0
Ø64
Ø87
5
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
242 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
12.8 VSF version
12.8.2 WKG80 gas burner, version ZMH-VSF
WKG80/6 version ZMH-VSF 486
Ø625
850
610
708
741
Ø90
DN150 283
368 502 410
Ø7
70
0
Ø64
Ø87
5
30
°
30
°
30° 30°
300
500
644
670
100
556
644
670
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 243
Notes
244 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
Notes
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 245
Notes
246 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
Notes
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 247
Notes
248 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
Notes
© Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014 249
Notes
250 © Copyright Max Weishaupt GmbH · Print No. 83112402, July 2014
Max Weishaupt GmbH
88475 Schwendi
Tel +49 7353 830
Fax +49 7353 83358
www.weishaupt.de