PX-149 Input Terminal Specifications
Inputs per Terminal 16 PX-149
Input Type Sinking
1 9
Input Data Bytes Used 2-bytes Signal LEDs 2 10 Signal LEDs
3 11
Requires external 24VDC power 1...8 4 12
9...16
Input Power Source I/O Bus
source 5 13
6 14
contacts
Current Consumption (from Terminal 7 15
NA Input 1
PX-149 – Sixteen-point
8 16
Power Bus) Input 9
Operating Voltage Rating 24VDC (-15%/+20%) Input 2
24VDC Discrete Input Peak Voltage Rating 30VDC
Input 3
Input 10
Terminal
On Voltage Level 11 to 30 VDC Input 11
Terminal power
Off Voltage Level -3 to +5 VDC bus contact Input 12
Minimum On Current 2mA +24VDC
Input 4
DIN rail
Maximum Off Current 40µA Input 5 release
The PX-149 DC Input Terminal Current Consumption (from I/O Bus) Typ. 20mA Terminal power tab
provides sixteen electrically isolated Electrical Isolation 500Vms (I/O bus/field potential) bus contact
0V
Input 13
24VDC sinking inputs with LED Heat Dissipation 1W max Input 6 Input 14
status. Use with the Protos XTM I/O Off/On Response 3ms
Input 7 Input 15
System. On /Off Response 3ms
Input 8 Input 16
Adjacent Mounting on Bus Terminals
Yes, DC only
with Power Contact
Adjacent Mounting on Bus Terminals
No
without Power Contact
PX-149 Passes Terminal Bus Power Yes
Input LED Input LED
Passes PE Bus No
1 9 1 9
2 10 Status Indicators 16, indicates input is on 2 10
3 11 3 11
4
5
12 4 2 24 VDC
6
13
5 13 Power Supply
7
14
6 14
8
15
7 15
16
8 16 + –
1 9
General Specifications Input 1 Input 9
1 9
2 Operating Temperature 32° to 131°F (0° to 55°C) Input 2 Input 10
2 10
10
Storage Temperature 13° to 185°F (-25° to 85°C)
Input 3 Input 11
3 11
3 11
Relative Humidity 5% to 95%, non-condensing Connect
power supply
Environment Air No corrosive gases permitted Input 4 Input 12 common (–)
4 12 4 12 to same
Mounting/Orientation Input 5 Input 13 common
5 13 Restrictions
35mm DIN rail/None 5 13 as terminal
power bus
Vibration conforms to EN 60068-2-6
Input 6 Input 14
6 14 Shock conforms to EN 60068-2-27, EN 60068-2-29 6 14
Input 7 Input 15
Noise Immunity conforms to EN 61000-6-2/ EN61000-6-4 7 15
Input 8 Input 16
7 15
8 16
Protection Class IP20 8 16
Weight 60g
Dimensions (WxHxD) 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)
Protos XTM is a trademark of [Link] Incorporated Agency Approvals UL File No. E157382, CE
Sales 800-633-0405 [Link] Tech Support 770-844-4200
MOUNTING REMOVAL WARNING
For system assembly, first attach a bus coupler by A locking mechanism prevents individual units from To minimize the risk of potential safety problems, you
snapping onto 35mm DIN rail and securing into posi- being pulled off. For bus terminal removal, pull the should follow all applicable local and national codes
tion using the DIN rail locking wheel (where applicable) orange DIN rail release tab firmly to unlatch the unit that regulate the installation and operation of your
located on the left side of the coupler. To add a bus from the rail. If attached to other terminal units, slide equipment. These codes vary from area to area and it is
terminal, insert unit onto right side of bus coupler using unit forward until released. For bus couplers with your responsibility to determine which codes should be
the tongue and groove at the top and bottom of the locking wheels, release the DIN rail locking wheel, then followed, and to verify that the equipment, installation,
unit, pressing gently until it snaps onto the DIN rail. pull firmly on DIN rail release tab. and operation are in compliance with the latest revision
A proper connection cannot be made by sliding the of these codes.
units together on the DIN rail. When correctly installed, Equipment damage or serious injury to
no significant gap can be seen between the attached personnel can result from the failure to follow all
units. Bus connection is made through the six slide applicable codes and standards. We do not guaran-
contacts located on the upper right side of the units. tee the products described in this publication are
Add up to 64 bus terminals per bus coupler, including a suitable for your particular application, nor do we
bus end terminal. assume any responsibility for your product design,
installation, or operation.
If you have any questions concerning the instal-
lation or operation of this equipment, or if you need
Insert unit using tongue and groove
ntil
molded guide and press gently until additional information, please call Technical Support at
it becomes firmly seated on DIN rail.
ra
ail. 770-844-4200.
Where applicable, rotate Locking
This publication is based on information that was
Where applicable, rotate Locking available at the time it was printed. At AutomationDirect.
Wheel to unlock Bus Coupler
Wheel to lock Bus Coupler com® we constantly strive to improve our products and
services, so we reserve the right to make changes to
the products and/or publications at any time without
notice and without any obligation. This publication may
also discuss features that may not be available in
certain revisions of the product.
WIRING CONNECTION
Wire connection is made through a spring clamp style
terminal. This terminal is designed for a single-conductor
solid or stranded wire. Wire connection is made by firmly
pushing the screwdriver into the screwdriver slot, inserting
Align tab with Firmly pull DIN Rail Release Tab the wire into the wire slot and removing the screwdriver,
molded guide to unlatch unit from rail.
locking the wire into position.
S
Screwdriver
Slot
S
Wire Slot
IMPORTANT HOT SWAP NOT PERMITTED
For complete assembly instructions and compatibility Always remove power from the system before inserting or
between terminals see the PX-USER-M manual available removing bus terminals or couplers as failure to do so could
for free download at [Link]. cause malfunction or damage to the terminals, couplers or
other connected devices. Wiring Specifications
Connection Type Spring Clamp Terminals
Wire Gauge / Wire Cross Section 28-14 AWG / 0.08 - 2.5mm2
2.5mm (0.10) such as our
Document Name Edition/Revision Date Screwdriver Width
TW-SD-MSL-2
PX-149-DS 1st ED. 9/15/2014 Wire Stripping Length 8mm
Copyright 2014, [Link] Incorporated/All Rights Reserved Worldwide.