Data sheet
3449_en_A © PHOENIX CONTACT 2016-11-17
1 Description
The GW PL DP/MODBUS is a DIN rail-mounted gateway
module for interfacing Modbus® slave devices to a
PROFIBUS DP network. The gateway enables an existing
Modbus field device to become a PROFIBUS DP-compliant
device.
The GW PL DP/MODBUS is a Modbus master that
communicates with slave devices, typically measurement
instruments, that use Modbus. The gateway reads variables
from the instrument and converts them to dynamic variables
on PROFIBUS. Four analog input function blocks are
supported. The location of the Modbus registers and data
type of the Modbus variable can be configured.
The Primary Variable is read continuously and updated. Any
Modbus communication problem is reported in the
PROFIBUS diagnostics message. The physical interface is
RS-485.
GW PL DP/MODBUS supports alarm flagging in the
module. Four alarm levels are supported along with low-
pass filtering. Users can configure the GW PL DP/MODBUS
using standard configuration tools.
This data sheet is valid for all products listed on the following page:
GW PL DP/MODBUS
2 Ordering data
3 Technical data
General data
Ambient temperature (operation) -40°C ... 85°C
Ambient temperature (storage/transport) -40°C ... 85°C
Permissible humidity (operation) 95% (non-condensing)
Degree of protection IP20
Mounting On horizontal DIN rail NS 35 in acc. with EN 60715
Width 22.5 mm
Height 114.5 mm
Depth 99 mm
Vibration (operation) 5g, 10-150 Hz
Shock 30g, 18 ms
Connection data
Connection method D-SUB 9, COMBICON
Conductor cross section 2.5 - 0.02 mm² (AWG 12 - 24)
Wire-clamp screw torque 0.5 ... 0.6 Nm
Electrical data
Supply voltage 18 V DC ... 30 V DC
Max. current consumption 60 mA
Approvals
ATEX PRESAFE 16ATEX7686X, II 3G, Ex nA IIC T4 Gc
IECEx IECEx PRE 16.0001X, Ex nA IIC T4 Gc
UL, USA/Canada Class I, Div. 2, Groups A, B, C, D
Class I, Zone 2, AEx nA IIC T4, Ex nA IIC T4 GcX
4 Dimensional drawing
PWR
DP
DP TRM
MOD
ON
1 2
MOD TRM
112,24
7 8
99
5 Block diagram
Block diagram
DP
+ 1+
- 1-
NC 2+
NC 2-
3+
3-
4+
4-
+ -
2. Ensure that the DIN rail is connected to ground. Power connector (Item 1)
3. Place the module on the DIN rail from above. The upper
keyway must be hooked on the top edge of the DIN rail. Pos. Label Function
Rotate the module toward the rail, making sure it aligns 1 24 V
with the ME 22,5 TBUS connector, until it snaps in 2 0V
place. 3 NC Not connected
6.2 Removal 4 NC Not connected
Label Function
B B (positive)
A A (negative)
B B (positive)
A A (negative)
3449_en_A PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany 5/5