fieldbus technologies
supported by Danfoss
VLT® frequency
converters
www.danfoss.com/drives
Efficient communica-
tion – reduced costs
Fieldbus solutions for
any PLC network
Real time information is becoming increasingly im-
portant in industrial automation and control systems.
Immediate access to data increases transparency in
production facilities, while making it possible to opti-
mize system performance, carry out error analysis and
provide remote support around the clock from any-
where in the world.
2
3
Traditional wiring. No fieldbus.
In this type of network, communication
between the drive and PLC requires
one cable for each parameter that
needs to be controlled. The advantage
of such a system is that the individual
PLC
components themselves are rela-
tively cheap, and the system itself is not
among the most complex.
5 5 5 5 5
This, however, come at a price, as such
systems are relatively expensive both
to install and extend, as each addi-
Status Quick Ext. Alarm Status Quick Ext. Alarm Status Quick Ext. Alarm Status Quick Ext. Alarm Status Quick Ext. Alarm
Menus Menu log Menus Menu log Menus Menu log Menus Menu log Menus Menu log
k Ca k Ca k Ca k Ca k Ca
ac ac ac ac ac
nc
nc
nc
nc
nc
B
B
el
el
el
el
el
tional parameter or drive requires new
Inf o
Inf o
Inf o
Inf o
Inf o
On OK On OK On OK On OK On OK
Warn. Warn. Warn. Warn. Warn.
Hand Off Auto Reset Hand Off Auto Reset Hand Off Auto Reset Hand Off Auto Reset Hand Off Auto Reset
on on on on on on on on on on
Fieldbus wiring
A typical fieldbus system only uses
twisted pair cables to connect the drive
to the PLC. Despite the higher cost of PLC
components, fieldbus systems offer Serial
several advantages over older, hard- communication
wired systems: fewer cables, faster com-
missioning and a reduced risk of faults.
ac
k
Quick
Menus
Ext.
Menu
Ca
Alarm
log
Status
ac
k
Quick
Menus
Ext.
Menu
Ca
Alarm
log
Status
ac
k
Quick
Menus
Ext.
Menu
Ca
Alarm
log
Status
ac
k
Quick
Menus
Ext.
Menu
Ca
Alarm
log
Status
ac
k
Quick
Menus
Ext.
Menu
Ca
Alarm
log
Status
ac
k
Quick
Menus
Ext.
Menu
Ca
Alarm
log
nc
nc
nc
nc
nc
B
B
el
el
el
el
el
el
Inf o
Inf o
Inf o
Inf o
Inf o
Inf o
On OK On OK On OK On OK On OK On OK
Warn. Warn. Warn. Warn. Warn. Warn.
Hand Auto Hand Auto Hand Auto Hand Auto Hand Auto Hand Auto
ac
k
Quick
Menus
Ext.
Menu
Ca
Alarm
log
Status
ac
k
Quick
Menus
Ext.
Menu
Ca
Alarm
log
Status
ac
k
Quick
Menus
Ext.
Menu
Ca
Alarm
log
Status
ac
k
Quick
Menus
Ext.
Menu
Ca
Alarm
log
Status
ac
k
Quick
Menus
Ext.
Menu
Ca
Alarm
log
nc
nc
nc
nc
nc
B
B
el
el
el
el
el
Inf o
Inf o
Inf o
Inf o
On OK On OK On OK On OK On OK
Warn. Warn. Warn. Warn. Warn.
Hand Off Auto Reset Hand Off Auto Reset Hand Off Auto Reset Hand Off Auto Reset Hand Off Auto Reset
on on on on on on on on on on
5
Easy engineering and setup
VLT® Motion Control Tool software can be configured to link VLT® Motion Control
MCT 10 to the system’s electrical diagrams or Tool MCT 10 supports:
In addition to operating the drive via operating manuals. This helps to reduce VLT® PROFIBUS DP-V1
LCP (local control panel), VLT® drives the risk of incorrect configuration while MCA 101
can also be configured and monitored offering fast access to troubleshooting. VLT® PROFIBUS Converter
with Danfoss own PC software. This MCA 114
provides plant managers with a Easy communication VLT® PROFINET MCA 120
comprehensive overview over the Besides a single point to point VLT® EtherNet/IP MCA 121
system at any point in time, adding a connection via standard USB cable, VLT® Modbus TCP MCA 122
new level of flexibility in configuration, the tool offers the possibility to VLT® POWERLINK MCA 123
monitoring and troubleshooting. connect via an RS 485 interface, FC RS484 Protocol
allowing connecting to several drives USB port on FC 102/FC 103/
MCT 10 is a windows based engineering in an easy and simple network, up FC 202/ FC 301/FC 302/
tool with a clearly structured interface to communication through existing FCD 302
that provides an instant overview of all fieldbus networks like PROFIBUS.
the drives in a system of any size. Furthermore also connection through
Ethernet based technology, in point to
Parameter configuration is possible point or through existing networks, is
both online on a connected drive available and providing a simple access
and offline in the tool itself, and the to all the given functionality.
6
PROFINET stars
in PLC setup
The electronic control system for the main line at the Ulanhot PROFINET on
cigarette factory in China includes over 130 VLT® Automation- AIDA cruise ships
Drive FC 302 equipped with PROFINET cards. The stability and AIDA Cruise’s two cruise ships of a new
reliability of the PROFINET system is a significant improvement generation of energy efficient and en-
compared with the original system. vironmentally friendly ocean liners will
be equipped with more than 100 VLT®
Star-structure automation system AutomationDrive FC 302 on each ship
Using Danfoss VLT® PROFINET, the Siemens PLC and SCALANCE – ranging from 2.2 to 400kW - all with a
switch form a star network with the frequency converters, each PROFINET interface.
drive working independently without affecting other nodes’
communication. The star or tree topology ensures that all nodes VLT® AutomationDrive FC 302 drives
are independent and free from the influence of other bus seg- have been specified as standard for all
ments, the whole prime line automation network being divided electric motors in the engine room,
into management and equipment levels. utilities, deck machinery and hotel/
HVAC systems which will be delivered
The Benefits by leading suppliers of marine equip-
This has produced a number of benefits. The VLT® drive’s proven ment from all over the world.
reliability ensures its continuous operation in a variety of indus-
trial invironments throughout the factory. The system creates a “With PROFINET installed throughout
star-structure automation system of greater reliability and func- the vessel, the engineers on board have
tionality than is possible with PROFIBUS. If one sub-station fails, the complete overview of the many
the other stations remain operational to ensure that each node systems at any given time. Warnings,
within the network is independent of each other. malfunctions or alarms can be spot-
ted and handled immediately. This
The system’s data processing capabilities have been strength- is good for safety and not least the
ened, simplifying overall operation and also making the opera- passenger experience of comfort”, says
tors’ tasks easy and convenient. In addition, managers are able Ulf Hirsekorn, Senior Superintendent
to access much more data, thereby increasing the prime line Electric, AIDA.
efficiency.
7
Fieldbus overview
An overview of available fieldbuses for
VLT® HVAC Drive, VLT® Refrigeration Drive, VLT® AQUA Drive,
VLT® AutomationDrive and VLT® Decentral Drive.
VLT® HVAC VLT® Refrigeration VLT® AQUA VLT® Automation VLT® Decentral
Fieldbus Drive Drive Drive Drive Drive
FC 102 FC 103 FC 202 FC 301 FC 302 FCD 300 FCD 302
VLT® PROFIBUS DP-V1 MCA 101 n n n n n n n
VLT® PROFINET MCA 120 n n n n n n
VLT® PROFIBUS Converter MCA 113 n
VLT® PROFIBUS Converter MCA 114 n
VLT® DeviceNet MCA 104 n n n n
VLT® EtherNet/IP MCA 121 n n n n n
VLT® DeviceNet Converter MCA 194 n
Modbus RTU (integrated) n n n n n n n
VLT® Modbus TCP MCA 122 n n n n
VLT® CANopen MCA 105 n n
VLT® EtherCAT MCA 124 n n
VLT® POWERLINK MCA 123 n n n
VLT® BACnet MCA 109 n
VLT® LonWorks MCA 108 n
VLT® AK-LonWorks MCA 107 n
Metasys N2 (integrated) n
ASi Bus (integrated) n
VLT® Interbus MCA 110 n
8
VLT® PROFIBUS DP-V1 ASi Bus (integrated) VLT® EtherNet/IP MCA 121
MCA 101 The ASi Bus connects the VLT® Ethernet will become the future
Operating the frequency converter Decentral Drive FCD 300 to the standard for communication on
via a fieldbus lets you reduce the ASi bus network. ASi Bus is a cost the factory floor. The EtherNet/
cost of your system, communicate effective fieldbus choice, where IP Option is based on the new-
faster and more efficiently, and the application demands only est technology available for the
benefit from an easier user inter- few predefined speed values and Industrial use and handles even the
face. where a detailed drive status is not most demanding requirements.
necessary. EtherNet/IP extends commercial
n PROFIBUS DP-V1 gives you wide off-the-shelf Ethernet to the Com-
compatibility, a high level of n Configurable I/O mon Industrial Protocol (CIP™) –
availability, support for all major n ASi protocol ver. 2.11 profile 7.F the same upper-layer protocol and
PLC vendors, and compatibility n Up to 31 drives pr. ASi bus line object model found in DeviceNet.
with future versions n 150µSec update time pr. drive
n Fast, efficient communication, n FCD300 monitored ASi bus The MCA 121 offers advanced
transparent installation, advan- with selectable action on loss of features:
ced diagnosis and parameterisa- communication n Built-in high performance switch
tion and auto-configuration of enabling line-topology, and
process data via GSD-file Ordering number: eliminating the need for external
n A-cyclic parameterisation using 175N2324 uncoated switches
PROFIBUS DP-V1, PROFIdrive or n Advanced switch and diagnosis
Danfoss FC profile state machi- functions
nes, PROFIBUS DP-V1, Master n Built-in web server
Class 1 and 2 VLT® Interbus MCA 110 n E-mail client for service
(DIN Rail option) notification
Ordering number: The VLT® Interbus MCA 110 con- n Unicast and Multicast communi-
130B1100 uncoated nects the AutomationDrive to the cation
130B1200 coated Interbus network. The gateway not n AOI available for easy program-
only provides connection to the ming
Interbus network, it also has local
digital I/O’s, that can be monitored/ Ordering number:
VLT® PROFINET MCA 120 controlled from the PLC. 130B1119 uncoated
The MCA120 gives the user access 130B1219 coated
to the power of Ethernet, and the n Variable I/O size
options is designed, so that many n Support of Drivecom 21statema-
of the features from the PROFIBUS chine
MCA 101 can be reused, giving n Four digital inputs 24V VLT® Modbus TCP MCA 122
the user lowest effort to migrate n Two digital outputs 24V/25mA Modbus TCP is the first industrial
PROFINET, securing the investment n PCP communication for parame- Ethernet based protocol for auto-
in PLC program. ter access mation. The MCA 122 Modbus TCP
option connects to Modbus TCP
Other features: Ordering number: based networks. It is able to handle
n Built-in web server for remote di- 130B1211 uncoated connection intervals down to 5
agnosis and reading out of basic ms in both directions, positioning
drive parameters. it among the fastest performing
n Support of DP-V1 Diagnostic, Modbus TCP devices in the market.
allows a easy, fast and standard- VLT® DeviceNet MCA 104 For master redundancy the option
ized handling of warning and DeviceNet offers robust, efficient features hot swapping between
fault information into the PLC, data handling thanks to advanced two masters.
which improve bandwidth in the Producer/Consumer technology.
system. Other features:
n This modern communications n Built-in web-server for remote
PROFINET encompasses a suite of model offers key capabilities that diagnosis and reading out basic
messages and services for a variety let you effectively determine drive parameters
of manufacturing automation what information is needed and n An e-mail notificator can be
applications, including control, when. configured for sending an e-mail
configuration and information. n You will also benefit from ODVA’s message to one or several receiv-
strong conformance t esting poli- ers, if certain warnings or alarms
Ordering number: cies, which ensure that products occurs, or has cleared again
130B1135 uncoated are interoperable.
130B1235 coated Ordering number:
Ordering number: 130B1196 uncoated
130B1102 uncoated 130B1296 coated
130B1202 coated 9
Modbus RTU (integrated) VLT® LonWorks for Metasys N2 (integrated)
Modbus RTU is one of the most ADAP-KOOL® MCA 107 Within HVAC the Metasys N2 pro-
widespread fieldbus protocols. ADAP-KOOL® is a complete elec- tocol has gained a loyal customer
It runs on standard RS485 and tronic refrigeration and control sys- base. Metasys N2 works seamlessly
provides a cost effective system tem for monitoring and controlling with most BMS controllers making
without sacrificing speed. The refrigeration plants. Connecting it easy to handle with low commis-
Danfoss Modbus RTU is flexible this drive to an ADAP-KOOL® Lon sioning costs.
and can be configured for optimal network is simple. After entering a
performance in most applications. network address, pressing a service n Easy control of the drive via
Modbus RTU is well suited for ap- pin starts the automatic configura- Metasys Objects
plications in oil & gas, water and tion procedure. n Set basic drives parameters via
HVAC. internal floating point and inter-
Ordering number: nal integer point
n User definable register blocks for 130B1169 uncoated, n 15 different commands and
fast access to control & status of 130B1269 coated subcommands supported for full
the drive (128 read/write regi- control of the drive
sters) n Diagnostic counters for fast fault
n Access to drive parameters via detection
holding registers VLT® LonWorks MCA 108 n Supervise communication with
n 10 different Modbus function LonWorks is a fieldbus system user definable action if commu-
codes for support of major developed for building automation. nication is lost.
controllers. It enables communication between n Monitors the inputs and controls
n Diagnostic counters for fast fault individual units in the same system the outputs utilizing them as
detection (peer-to-peer) and thus supports remote I/Os
n Supervise communication with decentralising of control. n Synchronizes the drives and the
user definable action if commu- BMS clocks, eliminating the need
nication is lost. n No need for main station for batteries inside the drive
n Monitor the drives inputs and (master-follower)
controls the outputs utilizing n Units receive signals directly
them as remote I/O’s n Supports Echelon free-topology
interface (flexible cabling and
installation) VLT® CANopen MCA 105
n Supports embedded I/Os and I/O High flexibility and low cost
VLT® BACnet MCA 109 options (easy implementation of are two of the cornerstones for
The open communications proto- de-central I/Os) CANopen. The CANopen option for
col for worldwide building automa- n Sensor signals can quickly be the VLT® AutomationDrive is fully
tion use. The BACnet protocol is an moved to another controller via equipped with both high priority
international protocol that effi- bus cables access to control and status of the
ciently integrates all parts of build- n Certified as compliant with Lon- Drive (PDO Communication) and
ing automation equipment from Mark ver. 3.4 specifications access to all Parameters through
the actuator level to the building acyclic data (SDO Communication).
management system. Ordering number: For interoperability the option has
130B1106 uncoated, implemented the DSP402 AC drive
n BACnet is the world standard for 130B1206 coated Profile. This all guarantees stan-
building automation dardised handling, interoperability
n International standard and low cost.
ISO 16484-5
n With no license fees, the protocol n Supports Danfoss FC profile and
can be used in building automa- CANopen DS 402 Profile
tion systems of all sizes n Access to all drive parameters via
n The BACnet option lets the drive SDO communication.
communicate with building
management systems running Ordering number:
the BACnet protocol 130B1103 uncoated,
n BACnet is typically used for 130B1205 coated
heating, ventilation, cooling and
climate equipment control
n The BACnet protocol is easily
integrated into existing control
equipment networks
Ordering number:
130B1144 uncoated,
10 130B1244 coated
VLT® EtherCAT MCA 124 VLT® DeviceNet Converter VLT® PROFIBUS Converter
The VLT® EtherCAT Option offers MCA 194 MCA 114
connectivity to EtherCAT based The VLT® DeviceNet Converter MCA The VLT® PROFIBUS Converter MCA
networks via the EtherCAT Protocol. 194 turns the FC 302 into a VLT® 114 turns the FC 302 into a VLT®
The option handles the EtherCAT 5000 on a DeviceNet network. This 5000 on a Profibus network. This
line communication at full speed will eliminate the need for rewrit- will eliminate the need for rewrit-
and connection towards the drive ing the PLC program, and lower the ing the PLC program, and lower the
down to 4 ms intervals in both cost exchanging a VLT 5000 with a cost exchanging a VLT 5000 with a
directions. This allows the MCA 124 FC 302. Machines can be updated FC 302. Machines can be updated
to participate in networks from low to new standards and support new to new standards and support new
performance up to servo applica- motor technology and be updated motor technology and be updated
tions. to new safety standards, via the FC to new safety standards, via the FC
302 build in STO function. 302 build in STO function.
n CoE CAN over EtherCAT Support
n EoE Ethernet over EtherCAT sup- n Support VLT 5000 I/O Instances n Support VLT 5000 PPO’s
port n No change to the PLC program n No change to the PLC program
n HTTP (Hypertext Transfer Proto- n No need for VLT 5000 spare parts n No need for VLT 5000 spare parts
col) for diagnosis via built-in web n Converts access of VLT 5000 n Converts access from Profibus of
server parameters from DeviceNet into VLT 5000 parameters into FC 302
n SMTP (Simple Mail Transfer Proto- FC302 parameters parameters
col) for e-mail notification n Reduces the spare parts stock to n Reduces the spare parts stock to
n TCP/IP for easy access to drive FC 302 only. FC 302 only.
configuration data from MCT 10
Ordering number: Ordering number:
Ordering number: NA uncoated, 130B5601 coated NA uncoated, 130B1246 coated
130B5546 uncoated
130B5646 coated
11
What VLT® is all about