PSI-REP-PROFIBUS/12MB

Repeater for PROFIBUS Systems up to 12 Mbps

INTERFACE
Data Sheet
102986_02_en © PHOENIX CONTACT - 03/2007

1 Description The following features of the repeater are particularly


outstanding:
The PSI-REP-PROFIBUS/12MB DIN rail-mountable – Transmission speed of up to 12 Mbps
modular PROFIBUS repeater is designed to meet the high
– Automatic transmit/receive changeover
requirements associated with the use of PROFIBUS
systems. The device is snapped onto standard EN DIN rails – High-quality 4-way isolation
in the control cabinet and supplied with 24 V. The main – Integrated surge protection with transient discharge to
areas of application are: the DIN rail
– Electrical isolation/bus segmentation – 24 V DC control cabinet supply voltage, with
– Increasing system availability user-friendly connection via COMBICON plug-in screw
terminals
– Increasing the range
– Bit retiming
– Increasing transmission speeds
– Bit oversampling
– Extending the number of devices to n x 32
– Modular station structure, even with PSI-MOS-... fiber
– Implementing hybrid/network structures
optic converters
– Modular PROFIBUS hubs

If you have any technical problems, which you cannot resolve with the aid of this documentation, please contact
us during the usual office hours at:
PSI hotline: +49 - 52 35 - 31 98 90
Fax: +49 - 52 35 - 33 09 99
E-mail: interface-service@phoenixcontact.com

Make sure you always use the latest documentation.


It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
PSI-REP-PROFIBUS/12MB

1.1 Bit Retiming 1.2 Bit Oversampling


PROFIBUS signals with a bit distortion of up to 35% can be The bit oversampling function can be used to detect and
reliably detected using the bit retiming function and are filter malfunctions so that they are not transferred to the
converted to their original bit form before being transferred next segment.
to the next segment. This data processing function means
that a virtually unlimited number of repeaters can be
aligned without an impermissible level of bit distortion.

2 Ordering Data
Repeater
Description Type Order No. Pcs./Pck.
Modular PROFIBUS repeater, for electrical isolation and increasing the range PSI-REP-PROFIBUS/12MB 2708863 1
in PROFIBUS systems, 4-way isolation, DIN-rail mountable

Accessories
Description Type Order No. Pcs./Pck.
System power supply unit for supplying a modular star coupler configuration MINI-SYS-PS 100-240AC/24DC/1.5 2866983 1
End bracket CLIPFIX 35 3022218 50
DIN rail connector, power supply and data (2 per device) ME 17,5 TBUS 1,5/ 5-ST-3,81 GN 2709561 10
PROFIBUS cable, Fast Connect type, up to 12 Mbps PSM-CABLE-PROFIB/FC 2744652 1
Small, angled PROFIBUS connector with screw connection SUBCON-PLUS-PROFIB/SC2 2708232 1
Small, angled PROFIBUS connector with screw connection and additional SUBCON-PLUS-PROFIB/PG/SC2 2708245 1
PG connection

3 Technical Data

Interface
Power supply 24 V DC (±20% via COMBICON plug-in screw terminal)
Frequency DC
Nominal current consumption 90 mA (at 24 V DC)
Ready-to-operate indicator "VCC" LED (green)
Maximum star coupler expansion 10
Serial RS-485 Interface PROFIBUS according to IEC 61158, 2-wire
Transmission channels 2 (1/1), TD, RD
Operating mode Half duplex
Data format/encoding UART (11, NRZ)
Data direction changeover Automatic, minimum station response time 2 bits
Transmission speed (manual adjustment) 9.6/19.2/45.45/93.75/187.5/500/1500/3000/6000/12000 kbps; autobaud
Transmission length 1200 m, maximum (depending on transmission speed, bus system, and cable
type)
Transmission medium 2-wire twisted pair, shielded
Connection 9-pos. D-SUB female connector

General Data
Bit distortion input ±35%, maximum
Bit distortion output < 6.25%
Bit delay ≤ 11 bits
Electrical isolation PROFIBUS (A) // PROFIBUS (B) // power supply // DIN rail connector
Test voltage 1.5 kVrms, 50 Hz, 1 min.

102986_02_en PHOENIX CONTACT 2


PSI-REP-PROFIBUS/12MB

General Data (Continued)


Alarm output 60 V DC/42 V AC, 1 A, maximum
Status and diagnostic indicators Power supply (VCC), transmit/receive data (port A)
Housing material PA V0, green
Conductor cross section 0.2 mm2 ... 2.5 mm2
Ambient temperature
Operation -20°C ... +60°C
Storage/transport -40°C ... +85°C
Humidity 10% ... 95%, no condensation
Dimensions (W x H x D) 35 mm x 99 mm x 105 mm
Degree of protection IP20
Weight 200 g, approximately
MTBF according to Telcordia standard
Ambient temperature 25°C 878,000 h
Ambient temperature 40°C 489,000 h
Chloroform test Free from substances which would hinder coating with paint or varnish
(according to VW/Audi/Seat specification)
Vibration resistance 5g according to IEC 60068-2-6, 2.5 h each in x, y, and z direction, criterion A
Shock resistance 15g according to IEC 60068-2-27 with 11 ms pulse length, criterion C
Free fall 1 m without packaging according to IEC 60068-2-32
Air and creepage distances DIN EN 50178, DIN EN 60950

Tests/Approvals
CE c
UL In preparation
Ex X II 3G Ex nAC IIC T4 X

Conformance With EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC
Noise Immunity Test According to EN 61000-6-21
Electrostatic discharge (ESD) EN 61000-4-2 Criterion B2 8 kV air discharge
6 kV contact discharge
Electromagnetic HF field EN 61000-4-3 Criterion A3
Amplitude modulation 10 V/m
Pulse modulation 10 V/m
Fast transients (burst) EN 61000-4-4 Criterion B2
Signal 2 kV/5 kHz
Power supply 2 kV/5 kHz
Surge current load (surge) EN 61000-4-5 Criterion B2
Signal 1 kV/12 Ω
Power supply 0.5 kV/2 Ω
Conducted interference EN 61000-4-6 Criterion A3
Amplitude modulation 10 V 80% AM 1 kHz
Noise Emission Test According to EN 61000-6-4
Noise emission of housing EN 550114 Class A5
1
EN 61000 corresponds to IEC 61000
2
Criterion B: Temporary adverse effects on the operating behavior, which the device corrects automatically.
3
Criterion A: Normal operating behavior within the specified limits.
4 EN 55011 corresponds to CISPR11
5
Class A: Industrial application, without special installation measures.

102986_02_en PHOENIX CONTACT 3


PSI-REP-PROFIBUS/12MB

Block Diagram

DC
24V (1)
DC DC
0V (2)
DC gn
Port A DIN rail connector
DATA Port B
DIN rail bus RATE
VP 6 6 VP
GND 5 Bus 5 GND
management
DATA (P) 3 3 DATA (P)
DATA (N) 8 8 DATA (N)
Retiming Retiming
gn ye Retiming

24V 0V GND D(P) D(N)


DIN railrail
DIN connector
bus
Figure 1 Block diagram

Housing Dimensions

105 35

PSI-REP-PROFIB/12MB
Ord.-No. 27 08 863

VCC
TD
99

RD

ERR A

Port A

ERR B
PORT B

102986A001

Figure 2 Housing dimensions (in mm)

102986_02_en PHOENIX CONTACT 4


PSI-REP-PROFIBUS/12MB

4 Safety Instructions

Installation, operation, and maintenance may only be carried out by qualified electricians. When
installing and operating the device, the applicable safety directives (including national safety
directives), accident prevention regulations, as well as general technical regulations, must be
observed.

Notes on Explosion Protection

The device is a category 3 item of electrical equipment. Follow the instructions provided here during
installation.
The device must be installed in housing with IP54 protection according to EN 60529. The specified
limits for mechanical strain or thermal loads for the device must not be exceeded.
Temporary malfunctions (transients) must not exceed the rated voltage by more than 40%.
Repairs must not be carried out by the user.
Cables may only be snapped on and connected in potentially explosive areas when the power is
disconnected.

5 Function Elements
1 24 V DC supply voltage connection
1 2 2 0 V DC supply voltage connection
3 4
3 Switch contact connection 1
4 Switch contact connection 2
5 "VCC" LED: Ready-to-operate
6 "TD" LED: Transmit data dynamic port A (yellow)
7 "RD" LED: Receive data dynamic port A (green)
PSI-REP-PROFIB/12MB

5 Ord.-No. 27 08 863
8 9-pos. D-SUB: PROFIBUS interface port A
6 VCC 9 "ERR A" LED: Transmission error port A
TD 10 "ERR B" LED: Transmission error port B
7 8
RD 11 9-pos. D-SUB: PROFIBUS interface port B
9 ERR A

Port A

ERR B
10
Port B

11
102964A002

Figure 3 Function elements

102986_02_en PHOENIX CONTACT 5


PSI-REP-PROFIBUS/12MB

6 Applications
Stub line PROFIBUS 12 MBit/s
The PSI-REP-PROFIBUS/12MB repeater can be used to
create network topologies that are ideally adapted to the 100m
relevant application.
The limits set by the PROFIBUS standard, which specifies
the electrical properties of PROFIBUS, are thus extended.
This standard defines the following basic specifications:
1. Maximum of 32 devices per potential segment 100m

2. Only (linear) bus structure permitted


Max. 31 devices
3. Maximum bus cable length 1200 m
4. Maximum branch line length of 5 m without termination
= Switch on bus termination resistor
resistor (depending on the transmission speed)
5. Bus cable termination at the start and end of the bus Linear structure
cable

Example Applications for Repeaters


A segment can be created as an active branch, which can
comprise the full bus cable length and a maximum of 31
devices.
Electrical isolation and bus segmentation using repeaters Max. 30 devices Max. 30 devices
enables the permissible bus cable length to be multiplied
and the number of devices to be extended to n x 32, since
the total number of devices of the PROFIBUS specification
applies in each potential segment. = Switch on bus termination resistor

The repeater supports higher transmission speeds by


Star structure
subdividing into shorter segment lengths. For example, a
200 m PROFIBUS system can only be operated at a
transmission speed of 1.5 Mbps. The use of a repeater after
100 m means that 8 times the performance can be
achieved, i.e., 12 Mbps.
Hybrid/network structures, star, and tree structures can be
created using the PSI-REP-PROFIBUS/12MB modular
repeater. A freely selectable installation concept,
independent of the restrictive linear structure, is thus
possible. The repeaters can be extended using
PSI-MOS-PROFIB/FO... fiber optic converters for
PROFIBUS systems. = Switch on bus termination resistor

In addition, the repeaters can be combined and thus Tree structure


configured to form a modular PROFIBUS hub.

= Switch on bus termination resistor

102986_02_en PHOENIX CONTACT 6


PSI-REP-PROFIBUS/12MB

7 DIP Switches
The DIP switches (1) are located under the cap (2) on the
TD
port B interface (see Figure 4). B
R
ER
• Insert a small screwdriver into the slot on the bottom of Po
rt A

the cap and lever it off. 6


5 A
4 R
2
3 ER
1
Setting the Transmission Speed ON

Set the transmission speed using DIP switches 1 to 4. ON

1
2
S1...S6

3
4
5
Transmission DIP Switch

6
Speed (kbps) 1 2 3 4
AUTO (default) OFF OFF OFF OFF
12000 OFF OFF OFF ON
6000 OFF OFF ON OFF

B
T
3000 OFF OFF ON ON

R
O
P
1500 OFF ON OFF OFF
500 OFF ON OFF ON
187.5 OFF ON ON OFF 102986B003
93.75 OFF ON ON ON
Figure 4 DIP switches (default upon delivery: all DIP
45.45 ON OFF OFF OFF
switches set to OFF)
19.2 ON OFF OFF ON
9.6 ON OFF ON OFF

DIP switches 5 and 6 are reserved and have no


function.

102986_02_en PHOENIX CONTACT 7


PSI-REP-PROFIBUS/12MB

8 Connection Notes 8.1 Combined Assembly With a System Power


Supply (Modular Star Coupler)
Only mount and remove devices when the 1. Connect together the required number of DIN rail
power supply is disconnected. connectors for the connection station. Two DIN rail
Warning connectors are required for each device (see A in
Figure 5). A maximum of ten devices are permitted in a
Disregarding this warning may result in connection station.
damage to equipment and/or serious personal
2. Push the connected DIN rail connectors onto the DIN
injury. Only qualified personnel may start up
rail (B and C).
and operate this device. According to the
safety instructions in this text, qualified 3. Place the device onto the DIN rail from above. The
personnel are persons who are authorized to upper holding keyway of the device must be hooked
start up, to ground, and to mark devices, onto the top edge of the DIN rail (see Figure 6 on
systems, and equipment according to the page 9). Make sure that it is aligned correctly with the
standards of safety technology. In addition, DIN rail connectors.
these persons must be familiar with all warning 4. Once the device has been snapped on properly, check
instructions and maintenance measures in this that it is fixed securely on the DIN rail.
text.

PSI-REP-PROFIBUS/12MB devices are


designed exclusively for SELV operation
A
according to IEC 60950/EN 60950/
VDE 0805.

• Install the device on a 35 mm DIN rail according to


DIN EN 60715. To avoid contact resistance only use
clean, corrosion-free DIN rails. End brackets should be B C
mounted on both sides of the device to stop the
devices from slipping on the DIN rail (for ordering data
see page 2).

101973A003

Figure 5 Combined assembly

102986_02_en PHOENIX CONTACT 8


PSI-REP-PROFIBUS/12MB

8.2 Assembly as an Individual Device in the Control 9 Cabling Notes


Cabinet (Stand-Alone)
1. Place the device onto the DIN rail from above. The 9.1 Connecting the Supply Voltage
upper holding keyway of the device must be hooked
The device is operated with a +24 V DC SELV.
onto the top edge of the DIN rail (see Figure 6).
2. Push the device from the front towards the mounting
surface.
Operation as an Individual Device
3. Once the device has been snapped on properly, check
that it is fixed securely on the DIN rail. Supply the supply voltage to the module via terminal
blocks 1 (24 V) and 2 (0 V).

Individual Redundant
supply supply

24 V 0V 24 V 0 V 24 V 0V

102964A006

Figure 7 Individual/redundant supply

Operation in a Star Coupler Configuration


When the devices are operated in a star coupler
configuration, the supply voltage must only be supplied to
102964B005
the first device in the station. The remaining devices are
Figure 6 Assembly in the control cabinet supplied via the DIN rail connector. A redundant supply
concept can be created by connecting a second power
8.3 Removal supply unit to another device in the configuration.

1. Pull the locking latch down using a screwdriver, Using the MINI-SYS-PS-... System Power Supply Unit
needle-nose pliers or similar.
2. Pull the bottom edge of the module away from the As an alternative, the star coupler configuration can also be
mounting surface. supplied using the MINI-SYS-PS 100-240AC/24DC/1.5
3. Pull the module diagonally upwards away from the DIN power supply unit (Order No. 2866983). It is connected via
rail. two DIN rail connectors.
4. If removing a complete star distributor, remove the DIN
Usually the system power supply unit is mounted as the first
rail connectors from the DIN rail as well.
device in a configuration. A second power supply unit can
be used to create a redundant supply concept.

102986_02_en PHOENIX CONTACT 9


PSI-REP-PROFIBUS/12MB

9.2 Wiring the Switch Contact


PSI-REP-PROFIBUS/12MB repeaters are equipped with a 24 V DC
floating switch contact for error diagnostics (connection
terminal blocks 3 and 4 in Figure 3 on page 5). This contact
opens on the relevant device in the event of a transmission
error at port A or port B.
The switch contact is an N/C contact and can be linked to a
local digital input, e.g., on the PLC, to support error
detection.
If devices are combined (in a modular star coupler
configuration), the individual contacts can be linked to
separate input points (Figure 8) or the individual contacts
can be looped to generate a group message (Figure 9).

The maximum load capacity of the relay 101973A006


contact is 60 V DC/42 V AC, 1 A.
Figure 8 Individual message

24 V DC

Group message

101973A007

Figure 9 Group message

102986_02_en PHOENIX CONTACT 10


PSI-REP-PROFIBUS/12MB

9.3 Connecting the Data Cables

Attention
Use shielded twisted pair data cables.
Connect the cable shielding at both ends of IB/1
OF 63
2M
B

-PR 8 8

the transmission path. EP 7 0


I-R . 2
PS .-No
O rd

1. Use a suitable connector (e.g., SUBCON-PLUS- VC


C

PROFIB..., see page 2) to connect the bus cable to the RD


TD Port A
D-SUB connection on the repeater. R
A
ER r tA
2. If the repeater is located at the start or end of an Po

electrical PROFIBUS segment, activate termination in ER


R
B
Port B
the connector.

B
T
Pin Signal Meaning

R
O
P
3 RxD/TxD-P Receive/transmit data, positive
B cable
5 DGND Data transmission potential/
(reference potential to VP)
6 VP Supply voltage, positive (P5V) 102986A004
(50 mA, maximum)