You are on page 1of 31
ae orrespondence NFe 34-125 October 1992 Aluminium alloy and aluminium steel reinforced , bare conductors for overhead lines Experimental norm published by Technical Union of Electricity The cbservations should be addressed to UTE before the 31°" of October 1994 with a copy to Afnor. Replace the sections 1, 1V, & V of the enregistered norm NF C 34 - 125 September 1976. This norm takes into account the CE! 1089 elaborated by the CE N 7 of the CEI but bring the modifications in accordance with the international publications. Desenpiors Modificsi Corrections This norm specifies the characteristics and the tests to be applied to the Aluminium alloy and aluminium steel alloy conductors for overhead lines As compared.to the edition of September 1976 , creation of three experimental norms — one for the conductors ( C34-125 ) , and the other two for the steel wires ( C34-113 ) covered with zinc and aluminium- magnesium-silicum alloyed wires (C34-112). 6 edited & distibuted by the technical Union on electricity -33. av du General Lecter ~ BP 23 ~ 92262,Fontenay - aux - Roses Cavex — tet 0} 10 93 62.00 equally distnbuted by the French asseciation of standardisation (afnor), tour europa . codex 7 92049 Paris la defense ~ tel 01 42 915555 CONTROLLED The works of harmonisation of the national norms of european countries, being under process in the project group BTTF 67-3 of CENELEC , it could not give the status of approved norm to the present norm. The present norm is published for experimentation , for a period of 2 years , at the issuance of which the competent commission shall examine the opportunity of putting it under the harmonisation procedure and taking in account the results of the works of harmonisation of CENELEC nd. The present norm had been adopted by the Committee of Direction of UTE , on 2 September SUMMARY Foreword 1) Sphere of application 2) Definitions 2.1 Conductor 22 Conductor equistrand Conductor non-equistrand 2.4 Homogeneous Conductor 2.5 Bimetallic Conductor Nominal section of a Conductor Direction of cabling Connection of cabling 29 Spire of cabling 3) Characteristics 3.1 Material 3.2. Dimensions of Conductors 33 External aspect 3.4 Direction of cabling 35 Connection of cabling 3.6 Aptitds at unwinding under mechanical tension 3.7 Disentanglement 3.8 Charge of rupture assigned to a conductor 3.9 Electric resistance of aconductor 3.10Mass of conductor 3.11 .Greasing of conductors 3.12 Length delivered on a reel 3 13Solderings 4) Packing & Marking 4.1 Packing 4.2 Marking Pages SO OeNnNWNvny a: 12 13 5) Tests 5.1 Classifications of Tests 5.2. Tests of qualifications on the conductor 5.3. Tests of qualifications on the wires after cabling 5.4 Tests in the capacity of quality assurance procedure 55. Tests in the capacity of recipe procedure Annex A Table A1 - Recommended characteristics of equistrand Conductors in aluminium — steel alloy Annex B Table B1 - Recommended characteristics of non-equistrand Conductors jin aluminium-stee! alloy Annex C Table C1 - Recommended characteristics of homogeneous Conductors in aluminium alloy Annex D Table D1 - Recommended complementary characteristics for The non-equistrand conductors in aluminium-steel Alloy , figuring in Annex B Table 02 - Recommended complementary characteristics for Homogeneous conductors , figuring in Annex C Annex € Table E1- Coefficient standards resulting from cabling for Homogeneous conductors Table E2- Coefficient standards resulting from cabling for Non-equistrand conductors in aluminium-steet alloy Table E3- Coefficient standards resulting from cabling for Equistrand conductors in aluminium-steel alloy Calculation of the linear resistance Calculation of linear mass 14 14 15 7 19 19 22 23 24 25 25 26 26 27 28 Annex F Determination of the mass of the grease of a conductor Annex G Determination of the module of elasticity of a conductor Table G1 - Homogeneous conductors in aluminium alloy Table G2 - Equistrand conductors in aluminium-steel alloy Table G3 - Non-equistrand conductors in aluminium-steel alloy Annex H Norms to which the reference is made ( normative ) 29 30 30 31 31 32 4, SPHERE OF APPLICATION This norm is applicable to the bare conductors for overhead lines cabled in concentric coats , either with the wires in aluminium alloy in accordance with the norm C 34-112. or with the aluminium alloy wires and the steel wires covered with zinc in accordance with the norm 34-113. However, the norm C34-1254 imposes upon these two norms , the requirement of additional information (5.3.3, 5.3.5, 5.3.6) DEFINITIONS 2.4 Conductor The whole composed of many wires in aluminium alloy, of the same nominal diameter or not, and comprising or not of many steel wires covered with zinc. The wires are cabled in concentric coats, while the conductor consists of steel wires covered with zinc. The central wires are in steel, here where the extemal coats are of aluminium alloy. 2.2 Conductor equistrand Conductors in which the wires have the same nominal diameter. To realise certain conductors . the central wire can have an increased diameter with the consent of the client 2.3 Conductor non-equistrand Conductor in which the wires of different coats have different nominal diameters. 2.4 Homogeneous conductor Conductor in which the wires are solely wires of aluminium alloy 2.5 Bimetallic conductor Conductors made of aluminium alloy wires and steel wires covered with zine. 2.6 Nominal section of a conductor Sum of nominal straight sections of aluminium alloy wires and the steel wires that composes the conductor , rounded to 0.1 mm2 for the conductors of Section inferior to 228 mm2 and to square millimeter for the conductors of section superior or equal to 228 mm2. 2.7 Direction of cabling While the conductor is held vertically , the wires can wind themselves either following the central part of the letter Z , or following the central part of the letter S. In the first case, the direction of cabling is called “to the right’ , and in the second case , it is called “to the left". 2.7 Connection of cabling Connection between the axial length of a complete tour of a spiral formed by an individual wire in the cabled conductor and the external diameter of this spiral. 2.8 Spire of cabling Axial length of a complete tour of a spiral formed by a wire in the conductor. CHARACTERISTICS 3.1 Material The cabled conductor is comprised of aluminium-magnesium-silicum alloy wires of circular straight section , and if need be , of steel wires of circular straight section covered with zinc, The aluminium alloy wires are defined in the norm C 34-112 and the steel wires covered with zinc in the norm C 34-113. For the class and the nuances chosen, all the wires should have the properties prescribed in the norms C 34-112 and C34-113 , before cabling 3.2 Dimensions of conductors The recommended dimensions of the conductors are given in the tables of Annexes ABC. The dimensions and cablings not figuring in these tables , can be studied and the appropriate given after an agreement between the manufacturer and the buyer preseriptions of this norm should then be applied. 3.3 The external aspect The surface of the conductor should be smooth , and should not have any rough patches, irfegular protuberance (burr) or inclusions ction of cabling Two successive coats should always be cabled in reverse sense. The directions of cabling for the conductors described in Annexes A, B, & C are given in their tables. “ 3.5 Connection of cabling The connection of cabling of different coats should be within the limits fixed by Table | & TABLE -1 Value of cabling connection of the conductors | CABLING CONNECTION | NATURE OF WIRES ey Raa Steel wires. + Coat 3 wires ~ 6 wires 16 26 + Coat 12 wires ~ 18 wires 14 22 {res in aluminium alloy © External coats 10 ed + Directly under lying coat a i In 8 steel core, the connection of cabling of one coat should not be superior to the cabling ‘onnection of the steel coat immediately lying under. Also . in 2 conductor having many coats of aluminium alloy , the cabling connection of one coat should not be superior to the cabling connection of the coat immediately lying under. In the two ses. the distance between the connection of two neighbouring coats should not be inferior to as. For the conductors in Annexes B & C, the complementary characteristics on the value of cabling connection of diverse coats, are indicated in the tables of Annex D. : 3.6 Aptitude at unwinding under mechanical tension 4 conductor should be apt in unwinding under mechanical tension. A method of control is under study. - 3.7 Disentanglement The wires of a conductor should remain in place or can just slightly move while we take” away the fret placed at the extremity of the conductor (conductor unwound on the ground) In case where the wires might move , they should be able to be replaced with hands. 3.8 Charge of rupture assigned to a conductor Charge of rupture assigned to a homogeneous conductor in aluminium alloy is taken as equal to the sum of resistance at minimum traction of each of the wires multiplied by their section. The charge of rupture assigned to the bimetallic conductors is the sum of resistance at minimum traction of each of the alloyed wires multiplied by their section, this sum being increased by the sum of charge of the steel wires corresponding to a length compatible with the one of aluminium alloy, at the time of its rupture. To allow a specification and for the convenience , this charge of steel wires is taken , by default , as equal to the charge corresponding to a lengthening of 1 % on a test-tube of 250 mm length. 3.9 Electrical resistance of a conductor 3.10 31 The theoretical electrical resistance of the conductors designated in the Annexes A, B, C 's given in these tables For the other conductors, the evaluation of the theoretical electric resistance is done by taking into account for each wire composing the conductor, of a coefficient of increase of resistance due at the cabling, established on the average cabling connection , according to the article 3.5 and indicated in the tables of Annex E Mass of conductor The theoretic mass of non-greased conductors designated in the Annexes A,B & C are given in their tables . As compared to these theoretic masses, it is accorded a tolerance of + 2%. For other conductors , the evaluation of the mass is done by taking into account for each wite composing the conductor of @ coefficient of increase of mass due at the cabling , established on the average cabling connections , according to the article 3.5 and indicated in the tables of Annex & Greasing of conductors The internal coats of conductors should be greased with a neutral grease vis-a-vis the aluminium alloy and of zinc and chemically stable Its dropping point should be atleast equal to 65 °C for the homogeneous conductors of nominal section inferior to 228 mm2 and to 95°C for the other conductors 5 Unless specified otherwise in the order, the external coat of conductors of 7 wires is gteased and of the conductors of more than 7 wires is not greased. “The mass of grease for each conductor designated in Annexes A,B & C is indicated in their tables , of one part with the external coat greased . and the other with external coat non-greased The tolerance on the mass of grease is of # 30% The calculation of the mass of grease of a conductor is given in Annex F., 3.43 3.13.1 Stee! w 3.12 Length delivered on a reel Atthe time of manufacture of a conductor , the measure of the length of conductors during the winding on the reel, should be assured with a device giving a precision of £1°% As far as the tolerance on the length delivered on the reels is concerned , as compared to the ones ordered, the ordered ones should be agreed between the client and the manufacturer. In absence of contractual documents between the client and the manufacturer , and while notably, for certain lengths of conductors, the technical reasons ( crossing a iver, long range on mountain, average range of 450 m ) impose, that the tolerance should be less raised, the value and the meaning of these should be made precise in the order, the tolerance applied is as follows The lenath delivered on a reel is equal to the length indicated in the Order , with a tolerance of 5% , with a minimum of + 50m For the 5% of the total length of the Ordered conductor , it can deliver reels of inferior length 2s compared to the one decided through the order. The smallest length Gelivered here should not be less than 400m. At the outside , for the conductors of nominal section more equal to 228mm’, this smallest length should not be less than 20% of the length decided per reel Unless decided otherwise between the parties, each reel should consist of only one length of conductor. Soldering 3s ng should be done on the steel wires covered with zinc: + 3.13.2 Aluminium alloy wires a) Number of solderings : with the excéption of the cases given hereafter, the presence of soldering on individual wires of aluminium alloy, done after the final reducing of diameter , is tolerated. in any case , no soldering should be done except during the risky breakage of wires occuring at the time of cabling. In case where the mode of manufacturing consists of systematic assembling of wires between the reels by temporary soldering, the section of conductor consisting of soldering should be eliminated No soldering should be done on the external coat of the homogeneous conductors for sections superior or equal to 228 mm2 and on the external coat of bimetallic conductors. Moreover, on the external coat of wires of homogeneous conductors of the section inferior to 228mm2 , the number of solderings should not exceed , one by section of length of 1500 m per reel In any case , the no. of solderings should verify the table hereunder NUMBER OF COATS MAXIMUN NUMBER OF F ALUMINIUM ALLOY | SOLDERINGS ALLOWED BY oe |_ SECTION OF 1500 METERS _| 2 A minimum distance of 50m should be respected between 2 solderings. b) Soldering procedure : The solderings should be done by heating effect of Joule, or by cold pressure; in the later case , the wire should be reheated on a minimum length of 25mm on both sides of the soldering On the length of the reheated wire , the mechanical characteristics of a full wire are not required . At all times, the resistance at the traction of a wire should be Mpa and 208 Mpa ; @ ©) Signaiting of soldering : For the wires of external coat, there should be a mark on both sides and a few between 139 centimeters from the solderings, this mark is done by for e.g. a ring of bright red celluloid paint or a rubber band of red-brown colour. 4, PACKING & MARKING : 4 4.1 Packing The manufacturer should inform his client . immediately after receiving each lot , or, if'it has not gone through the expected tests in the procedure of recipe, during the delivery @ number of reels that comprises the delivery - the length of each one of them - if there has been a number of solderings existing on the external coat of each reel as well as the distance of each one of them from the free end of conductor Unless decided otherwise between the client and the manufacturer, the conductors are delivered on wooden reels, according to the norm NFB 55007. The cheeks of the reels should have sufficient diameter to prevent any risk of contact of the conductor with the floor/ground , during the handling and transportation. The diameter of the drum should be equal to atleast 30 times the diameter of a wound conductor. The reels should be able to support, without damage, the normal operation of handling & transportation ( loading, unloading , trucking ) and allow a convenient unwinding of the conductor under a maximum constraint of 15 Mpa. To this effect, the conductor should be wound in spires as close as possible, without overlapping of the spires of the same coat with a sufficient tension permitting a good unwinding. For the conductors of section inferior to 228mm®, the overlapping of the spires of the last coat can be tolerated , on a condition that it does not affect the aptitude of unwinding of the conductor Moreover, the free end of the conductor should be fixed on the cheek of the reel with @ sufficient tension, to avoid any displacement of the final spires during their handling & transportation. The manufacturer has the power to use his usual type of reel, by choosing the one that permits to observe the above mentioned conditions , following the section of conductor and the length to be delivered. If an order necessitates the utilisation of the reels having cheeks of a diameter superior to 1.60m or a total largeness superior to 1.06m, the manufacturer should demand confirmation of the client before executing the order. The concucior should be protected according to the conditions of its transportitiendling - for e.g. with planks , with the lattice, held against tiie conductor by an appropriate fretting 4.2 Marking Each reel should have on each cheek, a permanent label , with sufficient resistance to bad weather, having the following information - Name of manufacturer - Number of reel - Name of the client & - Number of the order - Length of conductor - Raw mass - Type of conductor -Mass of the reel (tare) -Month and the year of manufacture & TESTS 5.1 Classification of tests The tests are classified as - tests of qualification done on prototype or head of the series in accordance with the dispositions of the paragraphs 5.2 & 5.3 -tests of series recommended in the frame of procedure of quality assurance , in accordance with the dispositions of the paragraph 5.4 tests of acceptation done within the frame of procedure of recipe at the time of delivery of conductors in accordance with the dispositions of paragraph 5.5. The tables 2 & 3 give the list of tests to be done. Table 2 Enumeration of the tests to be done on the conductor Tests of Proceaure Tess Quattication | Ofrecice | References /neaton 61°88 compastion ofthe conductor xa) |x go2t Verfication of the section of the | conaustor x x 5522 \arteaton of he ctomator of tne conductor x 5523 ‘euifeaton of direction of eabing a x x s524 \enfcaton of connection of cabling x x §525 Venfcation of the charge o | ‘of conductor x $526 ————————— Veuteaton ofthe mess of conductor 7 x x 5527 Convo! of greasing of conductor | x 1 x §528 Venicaton of procedure | Of scidering of wires in aluminium x x 9529 alloy a [ Ventication of dietentanglement of | the conductor x | $5210 Note During this verification , it is necessary to do ( if they were already not done) all the tests of qualification related to the wires in aluminium alloy and in steel wires, before cabling ,specified in the norms that are in power. Table 3 Enumeration of the tests to be done after cabling | Tests of Procedure | Tests qualification of References _ Recive Verification of continuity of covering | ee x § 5.2.10 cenfication of the external aspect of | wipes 9 aluminium alloy or in steel x x § 53.4 verification of diameter of AX tires in aiuminium alloy or x x § 5.3.2 est 1 & lengthening | | Of sees in aluminium alloy % x | gs533 st of winding the aluminium alloy | wies x |_& § 5.34 Test of resistivity of aluminium atloy wires x _x § 535 Verification of the resistance at the “traction of steel wites x x § 5.36 Test y of steal wires x x § 5.37 n of mass of zinc of ste! | wires _ x x § 53.8 Ventication of adherence of the _ covering of steel wires x x § 53.9 om 5.2 Test of qualification on the conductor The manufacturer , who has referred himself to the present norm, in order to sell his product, |s obliged to proove that the tests of qualifications had been done for the proposed conductor. ‘The sections of conductor utilised for the diverse tests of qualification are taken from the same , reel, The list of tests to be done is given in table 2 5.2.1 Verification of the composition of the conductor The composition announced of a conductor is controlled by verifying the characteristics specified in the paragraphs 3.1, 3.2, 3.33.4. As far as the paragraph 3.1 is concemed, it is necessary to verify the conformity to the tests of qualification prescribed in the corresponding norms of wires before cabling ( that is to say, do if they are not done , all the tests of qualification on the wires before cabling , in accordance with the norms in power ). 5.2.2 Verification of the section of conductor The verification of the section of conductor is realised by measuring the diameter of wires composing the conductor ( see article 5.3.2 ) It is accorded a tolerance of +2% for each measure and +1.5% for the average of 4 measures . wherein the positions are selected at random with the spacing of mimimum 20 om. 5.2.3 Verification of the diameter of conductor The diameter of conductor should be measured , following 2 perpendicular directions situated approximately in the same straight section. The diameter is measured by means of a device permitting to have a precision of atleast 0.01 mm The tolerance accorded as compared to the nominal diameter of conductor is of #1% for the diameters either superior or equal to 10mm and 40.1% for the diameters less than 10mm 52.4 Verification of the direction of cabling The directions of cabling should be according to the specifications of article 3.4 5.2.5 Verification of the connection of cabling The connection of cabling of diverse coats should be measured The values rounded to the 10 should be according to the specifications of article 3.5. 5.2.8 Verification of charge of rupture of the conductor The control is done by s:eans of an appropriate testing machine having a precisicn of atleast 1% — It consists of a test of rupture on a free length of conductor of atleast 400 times the external diameter without being inferior to 10m. We use the joints of ends accepted by the buyer, for e.g. the joints pressed, stretched, the joints of epoxy type or the preformed type. Thevconductor is held tight for one hour , between 60% and 65% of its C.R A after which the charge of traction is increased progressively till the rupture. No rupture or slipping of wires should take place before having had attained a charge of traction atleast equal to the charge of rupture assigned to the conductor multiplied by a” coefficient of 0.95. ~ A new test ( upto a total of 3 test ) should be done , if the first rupture of wire is situated at less than 1 om. of a joint , as well as while the effort has not attained the charge of rupture prescribed in the paragraph above & 5.3 5.2.7 Verification of the mass of conductor The mass of non-greased conductor is measured and the results should be according to the tolerances indicated in article 3.10 This verification is done on a length of 1m of conductor 5.2.8. Control of greasing of conductor The point of the drop of the grease is controlled according to article 3.11 and the norm NF 34-200, The mass of grease is measured by determining the difference between the mass of conductor greased with the mass of non-greased conductor The result should be according to the tolerances indicated in article 3.11 5.2.9. Verification of procedure of soldering of aluminium alloy wires On the three test-tubes of aluminium alloy wires of diameter equal to that of wires entering in the composition of conductor, there is some soldering done through procedure utilised by the manufacturer, The test-tubes become the object of tests for notably verifying , that the constraint of rupture is comprised between 130 MPa and 205 Mpa. 5.210 Verification of disentanglement of the conductor Atleast 10 meters of conductor are unwound on the ground, the end of the conductor having being maintained / held by a fret. This fret is removed ; the wires should stay in place or can be displaced slightly, just enough, whereby they can be replaced by hands Tests of qualification.on the wires after cabling apy The tests of qualification are done as per table 3 5.3.1 Verification of &xternal aspect of wires We verify that the surface of the wires taken are according to the prescription of paragraph 3.3 after examining with naked eyes or corrected. 5.3.2 Verification of diameter of wires + We verity the diameter of each wire taken and straightened following 2 directions perpendicular situated approximately in the same straight section. The diameter is measured by means of a device permitting to have a precision of atleast 0.01mm. The tolerances accorded are the ones specified in the norms C34-112 and C34-113. 5.3.3 Test of Traction and lengthening of wires in aluminium alloy The resistance at the traction and lengthening after the rupture are determined on each wire taken away and straightened after uncabling. The average value of the resistance at the traction should be superior by 5% to the minimum. value prescribed for the individual wires before cabling , is to be 342 Mpa for the wires of nominal diameter inferior or equal to 3.5 mm and 330 Mpa for the other wires. Moreover, the resistance at the traction measured after uncabling can be inferior to the minimum value prescribed before cabling ( is to be 325 Mpa or 315 Mpa , that is if the nominal diameters of the wires before cabling are inferior or equal , or superior to 3.5 mm ) ‘on more than 5% of number of wires ( number rounded up at immediately superior unit ) The lengthening after rupture , measured on a length of 250 mm of each wire taken , should not in any case be inferior to 3%. 5.34 Test of winding of aluminium alloy wires A test of winding is done on the wires taken according to the prescribed test on the wires before cabling ( norm C34-112 ) 5.3.5 Test of resistivity of aluminium alloy wires The resistivity is measured at 20 °C on each wire taken and straightened , after un-cabling 8 The average value of measures, hereby done should be at the most equal to 3,26.10 Qm. he meantime the individual value of resistivity can exceed the maximum value of 3,29.10 8 © m on at the most 5% of number of wires , these being rounded up to an immediately superior unit 5.3.6 Test of traction ana lengthening of steel wires The determination of resistance at the traction and the lengthening after rupture is done on each steel wire takervand straightened , after uncabling. The average value of resistance at the traction should be superior by 5% to the minimum value prescribed for the individual wires before cabling , for the nuance chosen. Moreover, the value of the resistance at the traction measured after uncabling can be inieriér to the minimum value of the resistance at the traction prescribed before uncabling on at the most 5% of number of wires ( numbers rounded up to an immediately superior unit ) The lengthening after rupture , measured on a length of 250 mm of each wire taken, should not be inferior to the values of tables 2 & 3 of the norm C34-113 5.3.7 Verification of ductility of steel wires 5.3.3 Test of Traction and lengthening of wires in aluminium alloy The resistance at the traction and lengthening after the rupture are determined on each wire taken away and straightened after uncabling. The average value of the resistance at the traction should be superior by 5% to the minimum value prescribed for the individual wires before cabling , is to be 342 Mpa for the wires of nominal diameter inferior or equal to 3.5 mm and 330 Mpa for the other wires. Moreover, the resistance at the traction measured after uncabling can be inferior to the minimum value prescribed before cabling ( is to be 325 Mpa or 315 Mpa , that is if the nominal diameters of the wires before cabling are inferior or equal , or superior to 3.5 mm ) on more than 5% of number of wires ( number rounded up at immediately superior unit ) The lengthening after rupture , measured on a length of 250 mm of each wire taken , should not in any case be inferior to 3%. 5.3.4 Test of winding of aluminium alloy wires 4 test of winding is done on the wires taken according to the prescribed test on the wires before cabling ( norm C34-112 ). 5.35 Test of resistivity of aluminium alloy wires The resistivity is measured at 20 °C on each wire taken and straightened , after un-cabling . 8 average value of measures, hereby done should be at the most equal to 3,28.10 Om. the meantime the individual value of resistivity can exceed the maximum value of 3,29.10 8 {2 m on at the most 5% of number of wires , these being rounded up to an immediately superior unit 536 Test of traction and lengthening of steel wires The determination of resistance at the traction and the lengthening after rupture is done on each steel wire taken and straightened , after uncabling. The average value of resistance at the traction should be superior by 5% to the minimum value prescribed for the individual wires before cabling , for the nuance chosen. 6 Moreover, the value of the resistance at the traction measured after uncabling can be inferior to the minimum value of the resistance at the traction prescribed before uriéabling on at the" most 5% of number of wires ( numbers rounded up to an immediately superior unit ) The lengthening after rupture , measured on a length of 250 mm of each wire taken, should not be inferior to the values of tables 2 & 3 of the norm C34-113. The torsion test of steel wires covered with zinc is done on 3 wires chosen at random and it is admissible that the minimum number of tours specified on the wires before cabling . can be reduced by 2 units. The test of winding is done on 3 wires chosen at random according to the specifications of the norm on the steel wires covered with zinc (C34-113 ). 53.8 Verification of the mass of zinc of the steel wires The test is done on 3 wires chosen at random . This verification is done according to the norm on steel wires covered with zinc (C34-113 ) 53.9 Verification of adherence of covering of steel wires This test is done on 3 wires chosen at random. This verification is done according the norm on the steel wires covered with zinc - C34-113 5310 Venfication of the continuity of covering of steel wires [his test is done on 3 wires chosen at random. This verification is done according to the norm on the stee! wires covered with zinc - C34-113. 54 Tests in the frame of quality assurance procedure The manufacturer of conductor establishes a system of management of quality described in the quality manual. The consistency of the quality is assured according to the modalities of the norm NF EN 29002 in the capacity of a quality plan accepted by the client. 5 Tests in the capacity of recipe procedure The manufacturer does not establish a system of management of quality he list of tests to be done in this case is given in tables 2 & 3. 5.5.1 Sampling The tables 4.5. & 6 give , accara'sg to the number N of reels of conductors presented by the manufacturer, the number of reels of conductors on which the test prescribed in table 2 , aie done As far as the test on the wires are concerned , the tests are done on all the wires of a section of conductor taken from each reel retained Number of reels to be taken acco Table 4 Homogeneous conductors presented in the control of recipe ig to the number N of the reels - NUMBER COMPOSITION OF THE CONDUCTOR (NUMBER OF WIRES) 7 I 19 a7 61 91 427, z ep. [stats é Pe ee 10d ai 2 2 2 sl 3) 2 | 2 20 7 6 4 | 3 3 Wohwina | ee] sx | aw | aw | ae > 100 min. of 20 | ) “Ns plevor to the number of takings indicated, each ree! composing the lot should Become the object of taking, Tables Bimetallic conductors (equistrand) Number of reels to be taken according to the number N of the reels Presented in the recipe control NUMBER COMPOSITION OF THE CONDUCTOR oF (NUMBER OF WIRES) REELS N [oa [rar | asia | 20a7 0-7 a8 ite 10 a [a * 1 1 1 ito 15 [4 le iF 2 2 161030 2 3 2 2110 50 8 5 4 ‘ 3 51 t0 100 z 7 5 5 4 = >100 Jrow | aw | 5% 5% 4% NN surfer to he number of takings inccatea, each reel composing the lt sould become the object of taking Table 6 Bimetallic cbnductors (non-equistrand) Number of reels to be taken according to the number N of the reels presented in the recipe control NUMBER | COMPOSITION OF THE CONDUCTOR oF (NUMBER OF WIRES) REELS N ~ | iseg | 32ea | _sst9 120037 te. 1 1 : 1 {eis | ® 2 2 1 | s6t030 3 2 2 2 311060 4 2 2 2 [5110 100 5 4 3 3 [>t00 ow 5% 3% a 5.52 Place of execution of the tests Unless decided otherwise by the manufacturer and the buyer at the time of placing order , all the tests should be done in the manufacturer's factory. 5.5.3. Sanetion of tests The results of all the tests should be factory. If one or more characteristics measure on the sample are not according to the specification, another sample of the same effect is taken , on which the relative tests for the litigious characteristics are redone. if the results obtained on the second sample are satisfactory, the lot is accepted and the litigious reels are eliminated. The lot is refused in case of contrary results. ‘2ua}1691 UBRy Kok Jo 2oUENU 4) Jo 6omMA JIE JO 9109 € WI FOEHEe) JoFINPUED © 19} OTERAIED ID ‘voqeputJ0 ani au s9pUn Kuo veniB axe sarvea aSouL, 189) ayo Suiewainbar se parapsve> aq 194 Prous UE UoNUNOUI 0 apN iq pun LONG 210 Kay, 9 xOUUE UL PaIEDPUI LORR\NE!D 10 BPOU By O BuDIODDN PoBUNDIEP O:OMEONION sEOM) s'el | o000€1 fol | 00996 ost | —d00r8 tet | o0orer vat | — coore zt | o0orZ: vat] coors zbL | odovet vet] — coore zpt | ooorey zt | oooret e’st | oaonot e's} | og0g0: ot | c00¢6 #001 (ein) 30.04) | s0yanpuog, . umers sopnpu0g yan uayae> aang | qwaryja09 9 £9 ooze geo] cesse ese ez ue ve} esvez| adept | 922 XOTHd le er over zo oseer see sz 6 zr| ues} 902} 662 TaLs¥d sz or oz0L zrvo| — oetst so'zz sve Z ce} ss'vs| ov'eez | ez 1alsva sz 9 oss sez] ossre, sozz| sre 6 aL | 2o'abL sziovt | 982 XOTHa Wz se eva ogozt 6 ee Z ce} over} — zz'van| azz Talsvd ze se seat one’ | oor0z ot ez 6 | 66°91 822 XOIHd a 1s wg sezo| 0896 gu sz L oe} seve ez'Let | 918 TaLSva a] le sus seo | azo9r ss sz ot al) eves 9688 | 9'18t XOTHd +) sz Lys elzo| —orez sus sez é oc| cove] ezett | Vert taisva vt Ed 062 zero] oazet suse sez 6 ai] poise age | Verb xOTHe o 81 veg oss'o| —a6roL + z et ai} 69's 9g'99 | Z'9LL XOTHE s cy ave 4690] sess sce sez Z a) cove leer | ¢'s2 xOTHd ® oO sue zag) — sive on z Z za} 662 oxiue | L's xOTHd € 8 eh 9u1 gaze ee z | 6| zs ue) L'Le XxOTHe 1209 any : eur soil ‘uy seuit jo : Jojre wo uae | pausaey’| ances | Sue semi | uiseum| say | winununye BES ese | a.0z1v | omidny JeuRLoN | j22I8}90N | JON | 1999840 | UL Samm JO 10 sso | Jo 96seuD — uoneubisog » N "P= woasodiwos voines jeuKON 2 ps oyDeseY> popUOUHOIy by ange vxNNY € usuaunbss ge paopaues ‘29 }0u pinout pue voneunoy yo ‘oueys801 uBiy 0a Jo 2ouend a4 jo 894m fA 70 109 eu pas Lone2»pu oan au J9pUN MLO LAN are SaATeA UL ‘1 /9pun vanB ave uy 9 x2UUe u pate oNeo}e9)o Bpou a4 oF Bupr0D.e pa:NU.SP a1DM SaNIEA SEOUL ee) sais 8 ver cosse | om 964 sure sro oize9 rer | oveue| ovens | zovze | oo'e6 | wanoostod s se oosez | on pute s9v0'0 coer vac srewi | zvews| soar | cess | so vinniad 8 ge onset 95 6 sree 4900 sete vee so'exsr | ev'exeo | ez'v01 | e8'z0s | zig viINniad s et on0ze se ou e664 sor ovezz vez | ovexs| ovexe| sese | ee'see | zip taisve s an oer L st ter zo sou oz, | soir] ovexsr | aver sors | se xOTs (om) eon) 109 e090 oi ewara | jeusorxo (60 oe (neo) . Fone enweo ayy | s0renpucg wou um wed ) fo | sonny | unuwinyy toy Buns 10 roronpuog o.02ty | paubissy vas | wnuwny | asic | W209 3814 uonerera 10 wy seg | eoueisisay | amdng sau JO ‘ug yo Bunge 40 Ayousers (w6) ssen oupag | joaBieuy | jewsanra Tap jemion x ouy quay soponpuog waryjeco | Jo ampony aseei6 jo ssew wousodwo | — vonpeg yeuon | jo uoneubisaq © | une papusuuios94 & le aiavi X3NNY e sai- reo 100 fous igo Buoei8 04 LA pamouad heme ae aH LHDE J6FOIONPUED EOL we \one9pu jo a 9 epur Kuo VaR ae Seren 95AUL. 191 2j@eiouoHNDD 8 poxpreues 8g jOU ney Pue VoNEWHORH JO ORY ey sePUN VON We FOUL. © HBULE U PIEDPH LOREFLIE JO BPOW CL UIGICITE POURLIOTEPBIOMETIEN SHELL. 2 tz cosos rs - suv soz00 oLzos oozs cov zt es'cest | 0091 wasy wz ‘ooszs we eat vote 26200 ozose © oor ov 16 iserit | yeti waisy = tz ooszs a6 Ov ‘Sez 16c0'0 osoue see owe 6 s9'098 ise UaLSV ez coors 6 36 vist £9800 orsat cove see 9 zos| oswasy 6% 004s e og 6001 $0600 sestt Sere Sse “& woos ‘9of NaISY te 000s 4 w v6L SiFO 046 soe se “ee ve REZ 882 NSLS wz coos iz oe 129 oro sore over coe “ cou] see waisy *z coos a te 005 cero 006s ova ose “ zois| eter uausy ez ‘00009 8 se ov azo ole ses sue fe tom | sri waisy wz co009 ‘ wz we e8z0 oes cori cee 6 soot} zit wasy ez 0009 nt 802 aero save se sce ot wise] ssc waisy wz ooze 8 eel £090 sus sre sue ‘ srs] ovswaisy| ez coves 8 %6 asso sut o's ose 2 seve| wrewmsy) f 8 coos * z09 ost si 00'9 oz L esiz zwasv| Ff co) = - I : i yeoo wy Jeg, ep} (wu) (eww) g vene ceo 409 reo s.ozy| —pautissy | ovsnpuog,| (ts) sax som | sewngueg | sernpueo) aye siojenpuog | jeweng | jewerxg souelsisay, aimidny jovaraweg | J s918WeIG jo saquuony 10. 10 1200 yoAonsers | anowwm wm | wy iad suarg | yo abve49 jeuiayey jeuwon, vores vowjeubiseq, og pompon | (wibjsseaBje sey | ssew ——enisoau0g AojJo winununye ur sijonpuEs snosUaBoweY aYp jo s9!:sHeIDeIeYD PopUEWUoI0y bo FavL 2 xaNNY ® macreo e@ @ Tre erarcaa wen 228 ANNEX D Table 04 Complementary characteristics recommanded for the conductors non-equistrand in aluminium stee! alloy figuring in Annex B veneer Sieeies ies nA Alby seston | czatinne cabing onnesion | Coot moa Cebing Connection in | otwees) [atrium —— | Maxum | ates) | ana eshte \ 2 las | PASTEL 8 [a7 ho im 4242 18 [16 10 13 PE 16 Ts | 16 12 15 2 mt 16 2 n 2 | 2 0 a TUNIA 6 | 16 18 16 12, 15, 2 a ‘8 2 " “ _ | __| 20 10 13 pouvso 8 lie 8 2 ‘9 4 wus “ i 30 nes 8 a 8 x ° 4 ; a x ” in tae o2 _Complimentary chasers commended for tha omogoneous conduttors turing i Annex G s Cabling Comeston of Coat 6 wires | Coat 12 wires Coat 18 wires | Coat 24 wires | Coat 30wires | Coat 36 wires ons he [Man | atm | wax | tin | Max | aim [mtx | in | wax | on] Max |r ota | | | Be ow lo fu : | . | ; | | yp ow fis fio |e fo fits | " | sw fw fio ji foo fas fio fue oe be tee fan~ [oe [oor das [a0 foes re foes Py me Calculation of the linear resistance of a conductor, a) Homogeneous conductor in aluminium alloy The linear resistance of a homogeneous conductor composed of n coats of wires is given through the formula (1) 10° p RN expressed in ohms per kilometer p the average resistivity of the alloy defined § 53.5 ( ing. m) the section of central wire in mm? 5 s the section of coat ; of wires in mm? Ki » the coefficient related to the coat j re-obtained in the table E1 b) Bimetallic conductor in aluminium-steel wire ‘The linear resistance of a bimetallic conductor of n coats composed of a coats of steel wires and of (n-a) coats of lloyes wires 18 given through the formula (2). 10? p - XY sue : Si is the section of coat ; of alloyed wires in mm? Ki is the coefficient related to the coat ; of the alloy re-obtained in the tables £2 and £3 2 2. yet Calculation of the linear mass of a conductor a) Homogeneous conductor in aluminium alloy The linear mass of a homogeneous conductor made of n coats of wires is given through the formula (3) M, (° + y Ki Si ) vt ™ _ eb kg per km. tion in mm? of the central wire s jon in mm? of the coat; of the wires Kj coetficient related to the coat j given in table E1 b) Simetallic conductor in aluminium - steel alloy the linear mass of a bimetallic conductor is made of n coats composed of a coats of steel wires and of (n-a) coats of alloyed wires is given through the formula (4) Me +41 EY sw jeer sw) eit M linear mass in.kg ber km s section in mm? of the central steel wire si section in mm? of the coat | of the wires Ki coefficient related to the coat given in tables €2 & €3 & ANNEX F Determination of the mass of grease of a conductor The empty area between the 2 wires ( see figure ) is more or less equal to o no? A=2 wees) 2 8 the value of 0.87 gicm? for the volumic mass of the grease and by taking the level of By takin minimurs filing of 0.7, the mass of grease in g/m is or stil iber of the coat, the first one finding itself around the central wire

You might also like