You are on page 1of 4

How can you update the hardware catalog without direct internet access? - ID: 223748...

Page 1 of 4

(http://www.siemens.com)
Industry Online Support
Product Support

 Home (start)  Product Support

Entry type: FAQ, Entry ID: 22374877, Entry date: 04/27/2011 
 Rate

How can you update the hardware catalog without direct internet access?
Entry Associated product(s)

Instructions
As from STEP 7 version V5.2 you have the option of updating your hardware catalog via the Internet.

If the PC on which STEP 7 is installed does not have direct Internet access, the download "STEP 7_HSPs.zip" is
available in Entry ID  23183356 (/cs/document/23183356/step-7-v5.x-hardware-support-packages-(hsps-as-at-11-
2016)-for-installing-hardware-updates-in-the-hardware-configuration?lc=en-ww) for updating the hardware catalog
of your STEP 7 installation. The download contains the packaged software components (Hardware Support
Packages) needed for the modules and can be transferred to the PC with the STEP 7 installation, for example with
a memory stick.

Please go to Entry ID for downloading the Hardware Support Packages.

The following table shows you how you can use the download of the Hardware Support Packages (HSPs) to update
your STEP 7 hardware catalog.

No. Procedure
1 Preparation
In the entry mentioned above you right-click the link "STEP7_HSP" and in the pop-up menu that opens you
open the "Save target as..." dialog. Save the "STEP7_HSPs.zip" file in a separate directory on your hard disk.
Then transfer the "STEP7_HSPs.zip" file (using a memory stick for example) into a separate directory on the
PC on which STEP 7 is installed and open the zip file. Extract the software components from the archive via
"Actions > Extract". The Hardware Support Packages are then unpacked in the directory selected.
2 In the SIMATIC Manager you open the hardware configuration and then open the dialog "Install hardware
updates" via "Options > Install hardware updates...".
Note
Before installing the software components we recommend closing all STEP 7 applications (LAD/STL/FBD
editor, symbol table, ...). Also close the station in your hardware configuration via "Station > Close".
3 In the "Install Hardware Updates" dialog you select the "Copy from disk" option and then click on the
"Execute..." button.

Fig. 01

© Siemens AG 2009-2016 - Imprint (http://www.siemens.com/corporate_info) Data protection regulations (http://www.siemens.com/privacy) Cookie policy (http://www.siemens.com/cookie-policy-en)

https://support.industry.siemens.com/cs/document/22374877/how-can-you-update-the... 2016-12-07
How can you update the hardware catalog without direct internet access? - ID: 223748... Page 2 of 4

4 In the "Copy hardware updates" dialog that opens (Fig. 02), in "Search in:" you enter the path in which you
unpacked the "STEP7_HSPs.zip" file. When unpacking the "STEP7_HSPs.zip" file the "hspcontents.xml" file
was stored on the drive of your choice. Open the "hspcontents.xml" file.

Fig. 02
Note
When extracting (as described under No. 1), the "HWUpdates" directory with the software components is
inserted in the path you selected. You can choose the directory from the drop-down list.
5 In the "Copy hardware updates" dialog that opens you see the updates that are available. You can deselect
updates which you do not require in this window. Only those updates with a check mark are downloaded. Via
this dialog you copy the hardware updates into the storage folder. After copying there is still no new module in
your hardware catalog. For this you must first install the updates concerned. As from STEP 7 version V5.3 you
can also select or deselect all the updates offered using the "Select All" or "Deselect All" buttons respectively.
The "yes" and "no" designations in the "Copies" column indicate the following:
Yes: the hardware update is already in the storage folder for hardware updates.
No: the hardware update is not yet in the storage folder for hardware updates.
Click on the "Copy" button and close the "Copy hardware updates" dialog.

Fig. 03

© Siemens AG 2009-2016 - Imprint (http://www.siemens.com/corporate_info) Data protection regulations (http://www.siemens.com/privacy) Cookie policy (http://www.siemens.com/cookie-policy-en)

https://support.industry.siemens.com/cs/document/22374877/how-can-you-update-the... 2016-12-07
How can you update the hardware catalog without direct internet access? - ID: 223748... Page 3 of 4

6 After "Copy hardware updates" you must select the hardware updates required in the storage folder and then
click on the "Install" button. Now the hardware updates are installed.

Fig. 04
Note
During installation you receive the message that you must close all STEP 7 applications, here you click on the
"Yes" button. The hardware configuration and the SIMATIC Manager are then closed automatically.
It might happen that a copied HSP (Hardware Support Package) is not displayed in the "Install hardware
updates" list although the HSP is in the previous "Copy hardware updates" list. In this case you should check
which version of STEP 7 is required for this HSP and if necessary, upgrade your version of STEP 7 so that this
hardware function can be used.
7 After successful installation you receive the message "The selected hardware updates were installed
successfully". Confirm with OK. You can then close the "Install Hardware Updates" dialog.

Fig. 05
Now when you reopen the hardware configuration you will find an updated hardware catalog.

Also available in the following languages:


 German
 French
 Italian
 Spanish
 Chinese

Entry belongs to product tree folder(s):


 Automation Technology  Automation Systems  Industrial Automation Systems SIMATIC  Software for SIMATIC Controller  STEP 7 V5.x  STEP7 basic software and editors  STEP 7 (products?pnid=14342)
 Automation Technology  Automation Systems  Industrial Automation Systems SIMATIC  Software for SIMATIC Controller  STEP 7 V5.x  STEP7 basic software and editors  STEP 7 Professional (products?
pnid=14349)

Rate entry
© Siemens AG 2009-2016 - Imprint (http://www.siemens.com/corporate_info) Data protection regulations (http://www.siemens.com/privacy) Cookie policy (http://www.siemens.com/cookie-policy-en)

https://support.industry.siemens.com/cs/document/22374877/how-can-you-update-the... 2016-12-07
How can you update the hardware catalog without direct internet access? - ID: 223748... Page 4 of 4

     no rating Submit rating

Feedback *)

Name
Ashish Wandhare

Phone number
+46 (122) 81149

email
ashish.wandhare.ext@siemens.com
Comment Number of characters: 0 (max. 500)

Send copy of comment to sender Send

*) Note: Do not use this feedback functionality for technical requests. Please use the Support Request (/my/ww/en/requests/#createRequest) instead.

© Siemens AG 2009-2016 - Imprint (http://www.siemens.com/corporate_info) Data protection regulations (http://www.siemens.com/privacy) Cookie policy (http://www.siemens.com/cookie-policy-en)

https://support.industry.siemens.com/cs/document/22374877/how-can-you-update-the... 2016-12-07

You might also like